Escolar Documentos
Profissional Documentos
Cultura Documentos
siemens.com/transformers
Reactors enhance
grid stability and
economic efficiency
A secure power supply system requires a Reactors can be used for a wide range of
well-built supply grid. State-of-the-art tech- applications:
nology, high quality, and reliability are fun-
Series reactors are deployed for short-circuit
damental prerequisites. Reactors offer grid
current limitation and load flow changes.
operators benefits at various levels for
achieving this goal: Shunt reactors provide voltage control and
reactive power compensation, and can also
Technical: Better voltage control, lower
be designed as variable shunt reactors with
reactive power load through optimized
tap changers. They serve to:
reactive power compensation, compliance
with contractual requirements (shunt compensate for capacitive reactive power
reactors), short-circuit current limitation, of transmission lines particularly on
and impedance adjustment of line sec- grids operating at low- or no-load
tions (series reactors). condition
Shunt reactor from Siemens
Economical: Most cost-efficient solution reduce network-frequency overvoltage
for reactive power compensation and in case of load variation, shedding, or
short-circuit current limitation, lower reac- network operating at no load
tive power demand, lower losses, higher
improve the stability and economic effi-
grid capacity, balanced load flows and line
ciency of power transmission
loads.
Expertise combined with customer
Entrepreneurial: Flexibility and indepen-
proximity
dence from other connected grid
operators. For over 100 years weve partnered up
with notable energy providers and grid
Every one of our products is an individual,
operators. We have developed our own
custom-tailored fabrication that always
design tools for reactors, implementing
meets all product requirements governing
decades of experience. Our network of
voltage, rating, mode of operation, noise
Before delivery, every unit is tested at manufacturing plants spread around the
and losses, connection technology, and
a high-voltage test bay world enables us to combine the advan-
cooling type as well as transport and
tages of a large company while still main-
installation.
taining close proximity to our customers. In
this way, we support our customers daily
and help them on their way to success. No
matter where you are, our experts are
always on hand to offer support.
2
Systematic quality
For us, quality is a thorough, consistent philosophy pervading advise them in advance on desired, necessary, and possible
all our company locations, and one that is reflected in all our additional design features. At all our company locations, proj-
processes. Each of our manufacturing plants has been indi- ect management and order execution are entrusted to ser-
vidually certified to ISO 9001 and holds other, local certifica- vice-focused employees on whom our customers can rely.
tions which are available for viewing. The products manufac- And Siemens after-sales service is, of course, also there for
tured meet all required standards, from IEC to ANSI and IEEE. you once our reactors have been delivered.
As leaders in quality on the transformer market, we define Measurable reliability
quality as an interplay of know-how, top-quality materials,
The validity of our design rules are confirmed by the high
and qualified personnel throughout our work procedures.
number of units in service (over 800 just in the last ten
Every manufacturing step is accompanied by quality controls;
years). We work to the highest possible precision and always
final inspection and acceptance testing are performed in our
use high-quality materials. Our qualification system for con-
high-voltage test bays in the manufacturing facility. We can
tracting suppliers worldwide is based on the same standards
also conduct special tests upon request. We regularly invite
we hold ourselves to. The result is a failure rate that is noth-
customers to attend such tests and inspections so they can
ing short of impressive and well gladly provide you with
be sure of the quality of their product.
our latest mean time between failures (MTBF) figures.
With quality assurance in mind, we go even one step further
in the service we provide for our customers: We already
3
Grid troubleshooter
Possible application areas Fixed or variable?
Reactors are real all-rounders. In conven- Fixed reactors are the most suitable eco-
tional electricity transmission grids, they are nomical solution for constant loads and grid
used for voltage control, reactive power conditions. However, variable reactors are
compensation, load flow changes, and for the best solution for accommodating wide
short-circuit current limitation. load fluctuations on the line and changing
grid conditions in future (for example due
In todays new energy landscape that fea-
to grid expansion or changes in the power
tures growing numbers of distributed power
generation structure), as well as for use as
generation and higher fluctuation in power
flexible spare units. A fixed reactor would
feed-in, the scopes of application particu-
overcompensate under rising load, which
larly for variable reactors have expanded
would lead to unwanted further drop in
significantly, for example:
voltage and to additional inductive reactive
Typical application area for reactors: grid-connection of large wind and solar power transport through the line. Variable
the power transmission grid power farms reactors can be adapted to the given load
situation and thereby always offer the
compensation of voltage fluctuations due
precise compensation needed.
to distributed power generation or the
wide load fluctuations of private
households
connection of future large energy storage
systems which, during charging and use,
cause higher loads and, during storage
time, lead to no-load conditions on lines
accommodation of topological changes
such as grid extensions or changeover
from overhead power lines to cables
Furthermore, owing to the steadily growing
Hydro energy storage can lead to range of voltage/power combinations, vari-
increased load as well as no-load able reactors offer the option of flexible
conditions on power lines spare units for multiple power classes simul-
taneously, minimizing the number of
replacement units that have to be kept for a
spares plan.
4
Reactors can compensate for voltage fluctuations when renewable energy sources feed the grid
U1 U2 U1 U2 U1 U2 U1 U2
5
Precision in every work step
Our oil-filled reactors are manufactured in two design types: In our shunt reactors, Siemens uses an iron core divided by
air gaps, achieving a compact design with low noise, vibra-
without an iron core, with a magnetic-flux return circuit
tion, and losses. Another benefit of the iron core with air
(series reactors up to 800 kV / 1,500 MVAr)
gaps is a dampening effect (knee-point voltage) that limits
with the iron core divided by air gaps (shunt reactors up to voltage under extreme overcurrent conditions. The core is
800 kV / 300 MVAr) made from radially laminated iron packages, while ceramic
spacers ensure precise compliance with the specific air gap
Achieving low vibration, noise, and losses that remain con-
requirements. The core is clamped together by tie rods made
stant over the entire operating period requires precision. We
of steel and/or limbs, and held in place together with the iron
accomplish this not only by drawing on our decades of expe-
yoke and return circuit in a clamping frame. Siemens has two
rience, but also by using exact and tested design analysis
concepts to offer and adapts the design as needed: With
programs and the highest possible precision in every stage
inner clamping, the tie rods are inserted through holes in the
of the manufacturing process.
core, which in particular at high voltages results in a compact
For windings, insulation, tank, monitoring devices, connec- design and, due to the optimized force transmission, in mini-
tion equipment, and the tap changer, Siemens uses proven mum noise. With outer clamping, the tie rods are located out-
technology known in transformer design and manufacturing. side the core and winding which, at low voltages or in single-
phase reactors, reduces the unit weight (in particular of core
The centerpiece of a reactor, however, is the core, which is
and winding). Siemens unique spring technology between
very different to the cores used in power transformers.
the tie rod and crossbeam ensures constant core pressing.
Series reactors are generally designed and manufactured as
In this way, Siemens design constantly maintains low vibra-
single-phase units without an iron core (air core), and with
tion and noise levels over the entire service life of these units.
only a magnetic-flux return circuit.
6
The design process for reactors also differs quite radically Measurement is better than calculation
from that of transformers. Most notably the mechanical
Not every test bay designed for transformers can also per-
design, owing to its special core, can be much more complex
form the tests required for reactors. In the test bays at our
and therefore demand particular attention to control certain
Siemens locations that manufacture reactors, tests can be
physically determined characteristics. This is why it is so
conducted under real operating conditions right up to the
important to be able to rely on the manufacturer and its
highest voltage levels and power ratings. This means, for
expertise, especially for these products. Siemens uses soft-
example, that the manufacturing plants that produce the
ware and simulation tools developed in house to ensure in
three-phase reactors can also test them under three-phase
subsequent testing that the guaranteed performance values
conditions. Guarantee values do not need to be extrapolated:
are indeed met.
with Siemens, you can rely on the real measured data.
Close-up view of core with air gaps Wooden bracing on the return circuit leg of a reactor core
7
Five production locations
one design concept
Siemens Transformers organization has a large manufactur- This ensures that you as a customer enjoy the following
ing network at its disposal. Reactors are manufactured at five benefits:
production facilities located on three continents. Every reac-
prompt preparation of proposals and quotations
tor is a customized product, tailored to meet the customers
needs. Our manufacturing network, working to uniform, optimized, thorough, and consistent project management
standardized internal guidelines governing the design and
highly reliable on-time delivery
manufacturing of reactors, ensures that all our customers
worldwide have access to the same extensive know-how and flexibility, security, and reliability thanks to backup
quality, irrespective of location. At the same time, our manu- manufacturing plants
facturing plants adhere to all local standards and conditions
uniform documentation
of the countries to where our products are delivered.
punctual delivery
Nuremberg, Germany
Linz, Austria
Weiz, Austria
Mumbai, India
Jundia, Brazil
8
In 2014, Siemens delivered the largest series reactor in the world for use at the 400-kV level at 408 MVAr rated power
and 2,770 MVAr throughput power.
Increased reliability
thanks to series reactors
Series reactors are used to control current and increase Arc-furnace series reactors provide an additional reactance
impedance. As their name suggests, these reactors are to stabilize the arc and increase efficiency.
arranged in series with the existing line and serve, for
In motor start-up reactors, the starting current is limited
example, as:
where appropriate in combination with a speed controller.
short-circuit current limitation reactors
Grounding reactors are a special application where they
load flow change reactors serve to increase the impedance at the neutral point of
transformers. In case of a fault, the reactor limits the fault
arc-furnace reactors
current at the neutral point, ideally precisely compensating
(motor) start-up reactors to limit starting current the capacitive grounding current and supporting restoration
of the line.
The main application area is current limitation. The series
reactor constitutes an impedance in the grid and thereby Another application area is for one-time impedance adjust-
increases the resistance of the arrangement. ment of a subsystem in order to change the load flows. For
such one-time adjustment, a series reactor is usually the
With short-circuit current limitation reactors, the possible
most economical solution. If load flow control needs to be
short-circuit current is limited in the event of a fault. The
permanently flexible, it is recommended that a phase shift
reactance of these reactors is designed to achieve effective
oscillator is used.
short-circuit current limitation while the voltage drop across
the reactor is still acceptable during normal operation. Siemens Transformers manufactures series reactors up to
Because short-circuit current limitation reactors cause volt- 800 kV and 1,500 MVAr, usually as oil-filled units with an air
age to drop and also impact the transient behavior within core. Depending on customer needs and wishes, however,
the grid, the site of installation and the reactor dimensions they can also be designed with an iron core (particularly
must be chosen carefully. Our colleagues at Siemens Trans- neutral-point grounding reactors).
mission Solutions will gladly assist you in this regard and
can perform the necessary network studies.
9
Reactors at site of installation Reactors ensure efficiency in particular on long high-voltage lines
Increasing efficiency
by reactive power compensation
and voltage control
Contrary to series reactors, shunt reactors are arranged The advantages of fixed shunt reactors from Siemens are
between line voltage and ground. Their place of installation is obvious:
usually located at the start or end of a long overhead power
Fixed reactors are simple devices that can be easily switched
line or cable connection, or in central substations. While over-
into operation when needed. The compact design combined
head power lines are of comparably low capacitance and
with low maintenance needs make reactors a perfect solution
therefore only require compensation at high voltages and/or
to increase efficiency. Our unique spring technology, paired
along very long power lines, cables have a significantly
with high-quality materials and precise design and manufac-
higher conductor-to-ground capacitance (by a factor of 20).
turing by our highly trained, expert personnel, guarantees
Therefore, compensation should be provided already for
a consistently high-performance product that has been deliv-
lower voltages and shorter cable lengths.
ering added value to our customers for decades.
Shunt reactors fulfill three main functions:
They protect high-voltage equipment by reducing local
overvoltages.
They reduce unnecessary reactive power transport through
compensation of capacitive reactive power (for example
from high-voltage cables and overhead transmission lines,
connected power producers, or industries), thereby reduc-
ing line losses and increasing the possible active power
transport through the line.
They compensate for the Ferranti effect.
Under no-load/low-load conditions voltage increases steeply
along line capacitance above voltage levels given by the
grid code. Reactors adjust the voltage to the rated value.
10
Variable reactors with tap changer The tap changer enables full flexibility and higher efficiency
11
Economic efficiency
and sample calculations
While procurement of fixed reactors in particular is driven by Sample calculation: fixed or variable reactor?
technical needs, these units also always increase efficiency.
Particularly in cases where operators incur expenses for
Compared to power operations without reactors, there is less reactive power, procurement of a (variable) reactor is almost
need for reactive power sourcing from a third party, which always economically worthwhile. The sample presents a case
might not be free of charge. Reactive power transport can of combined feed-in from wind and solar power sources into
also be minimized, which reduces power losses and increases the 380-kV grid via a 380/110-kV grid transformer and a
the active power capacity of the lines. 110-kV cable connection. The active power feed-in at the
380-kV grid transformer is shown in green. The reactive
Procuring a variable shunt reactor can in many cases lower
power demand is marked in dark red. A fixed reactor is
costs for operators even further. Various benefits lead to
designed for the maximum reactive power demand. With
quick amortization of the higher procurement price:
increasing power feed-in, the fixed reactor is overcompensat-
reactive power purchase is reduced even further ing and additional capacitive reactive power has to be pur-
chased from the grid (light red line). What is more, the capac-
reduced losses from transmission lines and connected
itive reactive power transport over the 400-kV grid causes
equipment
additional losses. A variable reactor on the other hand
lower average losses of variable shunt reactor compared to enables continuous adjustment of reactive power in such a
fixed reactor way that no additional reactive power costs are incurred
(orange line).
possibility to respond flexibly to changing grid conditions
250
50 km 50 km 270.0 MW
200
115.0 MW
150
50
50
0 2 4 6 8 10 12 14 16 18 20 22 24
Reference day [h]
12
Sample calculation for fixed reactor:
Calculating the cost-effectiveness of the case study described, reducing losses in the connected grid transformer and high-
the cost column includes the purchase price of the reactor voltage line are so high that procurement of the fixed reactor
as well as the units power losses and operating costs. The pays off within five months.
savings gained by reducing the reactive power required
If reactive power has to be purchased, investment in a
shunt reactor is definitely worthwhile.
Total savings per month +221,000 (per month) Discount factor for calculating the discounted cash flow (DCF): 9% p.a.
Total savings per month +94,600 (per month) Discount factor for calculating the DCF: 9% p.a.
13
References
1. Variable reactors for Cyprus
Two variable, three-phase reactor units, each 132 kV/2775 MVAr (in 18 taps),
intended to adjust reactive power to the varying load cycles of the Cypriot grid. The
noise level is extremely low, at 60 dB. With these units, the customer is preparing to
accommodate further expansion into renewable energy sources, which involves an
increase in volatility.
14
Published by
Siemens AG 2016
Energy Management
Freyeslebenstrasse 1
91058 Erlangen, Germany
For more information, please contact
our Customer Support Center.
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com
Article-No. EMTR-B10016-00-7600
Printed in Germany
Dispo 19200
fb 6965 WS 02161.0
Printed on elementary chlorine-free
bleached paper.
Subject to change without prior notice.
The information in this document contains
general descriptions of the technical options
available, which may not apply in all cases.
The required technical options should therefore
be specified in the contract.