Escolar Documentos
Profissional Documentos
Cultura Documentos
Additional REB500sys combines the well-proven numer- Main 2 / back-up bay protection
ical busbar and breaker failure protection Definite and inverse time over- and under-
main features
REB500 of ABB with Main 2 or back-up pro- current protection
tection for line or transformer feeders. The Directional overcurrent definite and inverse
Main 2 / Group 1 or back-up protection is time protection
based on the well-proven protection function Inverse time earth fault overcurrent protec-
library of ABB line and transformer protection tion
for 50, 60 and 16.7 Hz.
Definite time over- and undervoltage pro-
tection
Page 2
Substation Automation Products
Three-phase current and three-phase volt- - checks for dead line, dead bus, dead
age plausibility line and bus
The numerical busbar protection REB500 The protection operates selectively for all
detects all phase and earth faults in solidly faults inside the zone of protection and
grounded and resistive-grounded power sys- remains reliably stable for all faults outside the
tems and phase faults in ungrounded systems zone of protection.
and systems with Petersen coils.
REB500sys is perfectly suited for retrofit con-
The main CTs supplying the currents to the cepts and stepwise upgrades. The bay unit is
busbar protection have to fulfil only modest used as a stand-alone unit for bay protection
performance requirements (see page 18). The functions (e.g. line protection, autoreclosure
protection operates discriminatively for all and synchrocheck or 2- and 3 winding trans-
faults inside the zone of protection and former protection or autonomous T-zone pro-
remains reliably stable for all faults outside the tection). The central unit can be added at a
zone of protection. later stage for full busbar and breaker failure
protection functionality.
Page 3
Substation Automation Products
Application (contd) Depending on the network voltage level and - Line variant 5 (L-V5)
the protection philosophy the following protec- as line variant L-V1 plus autoreclosure and
tion concepts are generally applied: synchrocheck.
Two main protection schemes per bay - Line variant 6 (L-V6) for 16.7 Hz
and one busbar protection. non-directional overcurrent, distance protec-
With REB500sys the protection concept tion, autoreclosure.
can be simplified. Due to the higher inte- - Line variant 7 (L-V7) for 16.7 Hz
gration of functionality one of the main pro- as line variant L-V6 plus directional earth
tection equipment can be eliminated. fault protection for grounded systems
One main protection and one back-up
protection scheme per bay, no busbar Transformer protection
protection. - Transformer variant 1 (T-V1)
With REB500sys a higher availability of the 2- or 3 winding transformer differential pro-
energy delivery can be reached, due to the tection, thermal overload, current functions;
implementation of busbar and breaker fail- applicable also as autonomous T-zone pro-
ure protection schemes where it hasn't tection.
been possible in the past because of eco-
- Transformer variant 2 (T-V2)
nomical reasons.
2-winding transformer differential protec-
tion, thermal overload, current functions,
Nine standard options are defined for Main 2/
overfluxing protection, neutral overcurrent
Group 1 or back-up bay level functions:
(EF).
Line protection - Transformer variant 3 (T-V3)
- Line variant 1 (L-V1) Distance protection for transformer back-up
directional, non-directional overcurrent and or 2-winding transformer differential protec-
directional earth fault protection tion, thermal overload, current functions,
- Line variant 2 (L-V2) voltage functions, frequency functions,
as line variant L-V1 plus distance prot. power function, overfluxing protection.
Fig. 1
Page 4
Substation Automation Products
IEC61850
Standard
Option
IEEE
Main functionality
Busbar protection 87B BBP PDIF z
Busbar protection with neutral current 87BN I0 PDIF z
Breaker failure protection inlcluding neutral current detection 50BF BFP RBRF z
End-fault protection 51/62EF EFP PTOC z
Breaker pole discrepancy 51/62PD PDF PTOC z
Overcurrent check feature 51 PTOC z
Voltage check feature 59/27 PTOV/PTUV z
Check zone 87CZ BBP CZ PDIF z
Current plausibility check - - - z
Overcurrent protection (def. time) 51 OCDT PTOC z
Trip command re-direction 94RD - z
Software matrix for inputs / outputs / trip matrix - - z
Event recording up to 1000 events - ER - z
Disturbance recorder (4 x I) 95DR DR RDRE z
Disturbance recorder (4 x I, 5 x U) up to 10 s at 2400 Hz 95DR DR RDRE z
Communication interface IEC 61850-8-1/
- Com - z
LON / IEC 60870-5-103
Time synchronization - - z
Redundant power supply for central- and/or bay units - - z
Isolator supervision - - z
Differential current supervision - - z
Comprehensive self-supervision - - z
Dynamic Busbar replica with display of currents - - z
WEB - Server - - z
Testgenerator for commissioning & maintenance - - z
Remote-HMI - - z
Delay / Integrator function - - z
Binary logic and Flip-Flop functions - - z
Definite time over- and undercurrent protection 51 OCDT PTOC z z z z z z z z z z z
Inverse time overcurrent protection 51 OCINV PTOC z z z z z z z z z
Definite time over- and undervoltage protection 59/27 OVDT PTUV/PTOV z z z z z z z z z
Inverse time earth fault overcurrent protection 51N I0INV PTOC z z z z z z z z z
Directional overcurrent definite time protection 67 DIROCDT PTOC z z z z z z z
Directional overcurrent inverse time protection 67 DIROCINV PTOC z z z z z z z
Three phase current plausibility 46 CHKI3PH PTOC z z z z z z z z z
Three phase voltage plausibility 47 CHKU3PH PTUV z z z z z z z
Test sequenzer - - z z z z z z z z z z z
Direct. sensitive EF prot. for grounded systems 67N DIREFGND PDEF z z z z z z z z
Direct. sensitive EF prot. for ungrounded or compensated
32N DIREFISOL PSDE z z z z z
systems
Distance protection 21 DIST PDIS z z z z z z
Autoreclosure 79 AR RREC z z z z z
Synchrocheck 25 SYNC RSYN z z
Transformer differential protection 2 winding 87T DIFTRA PDIF z z z
Transformer differential protection 3 winding 87T DIFTRA PDIF z
Thermal overload 49 TH PTTR z z z z z z z z z
Peak value over- and undercurrent protection 50 OCINST PTUC/PTOC z z z z
Peak value over- and undervoltage protection 59 OVINST PTUV/PTOV z z z z z z z
Definite time overfluxing protection 24 U/fDT PVPH z z z
Inverse time overfluxing protection 24 U/fINV PVPH z z z
Rate-of-change frequency protection 81 df/dt PVRC z z
Frequency protection 81 Freq PTOF/PTUF z z
Power protection 32 P PDUP/PDOP z z
Page 5
Substation Automation Products
Mode of There are three versions of installing the numerical busbar protection REB500 and the numeri-
installation cal station protection REB500sys:
Page 6
Substation Automation Products
System design Bay unit (500BU03) cess data are transferred at regular intervals
The bay unit (see Fig. 4) is the interface from the bay units to the central processing
between the protection and the primary sys- unit via the process bus.
tem process comprising the main CTs, isola-
tors and circuit-breaker and performs the Every bay unit has 20 binary inputs and 16
associated data acquisition, pre-processing, relay outputs. The binary I/O module detects
control functions and bay level protection and processes the positions of isolators and
functions. It also provides the electrical insula- couplers, blocking signals, starting signals,
tion between the primary system and the external resetting signals, etc. The binary
internal electronics of the protection. input channels operate according to a pat-
ented pulse modulation principle in a nominal
The input transformer module contains four range of 48 to 250 V DC. The PC-based HMI
input CTs for measuring phase and neutral program provides settings for the threshold
currents with terminals for 1 A and 5 A. Addi- voltage of the binary inputs. All the binary out-
tional interposing CTs are not required, put channels are equipped with fast operating
because any differences between the CT relays and can be used for either signaling or
ratios are compensated by appropriately con- tripping purposes (see contact data in Table
figuring the software of the respective bay 8).
units.
A software logic enables the input and output
Optional input transformer module also con- channels to be assigned to the various func-
tains five input voltage transformers for the tions. A time stamp is attached to all the data
measurement of the three-phase voltages and such as currents, voltages, binary inputs,
two busbar voltages and recording of voltage events and diagnostic information acquired by
disturbances or 6 current transformers for a bay unit.
transformer differential protection. (see
Fig. 12). Where more binary and analog inputs are
needed, several bay units can be combined to
In the analog input and processing module, form a feeder/bus coupler bay (e.g. a bus cou-
the analog current and voltage signals are pler bay with CTs on both sides of the bus-tie
converted to numerical signals at a sampling breaker requires two bay units).
rate of 48 samples per period and then
numerically preprocessed and filtered accord- The bay unit is provided with local intelligence
ingly. Zero-sequence voltage and zero-current and performs local protection (e.g. breaker
signals are also calculated internally. The Pro- failure, end fault, breaker pole discrepancy),
bay protection (Main 2 or back-up bay protec-
tions) as well as the event and disturbance
recording.
DC
DC Real-time SAS/SMS RS 232
Optical Interface Interface
Clock
Interface DC
DC
Local HMI
Process-bus
Local HMI
CPU
Uhr I nte rf ace I nte rf ace
M odul
M odul
M odul Mod ul
CPU
Kopp ler E/ A Ko pp ler E/ A
Module
CIM
DSP
DC
Re a l -ti m e S A S/ SM S RS 23 2
Cl o c k In t e rfa c e I n te rf a c e
DC
c es s- bu s
Local HMI
CP U
M o d u le
C IM
tp u t
CP U CP U
M odule M odule
Mem St a r-
c o u p le r
Bi n a ry
I/ O
St ar
c o u p le r
Binary in/output
registers
A/D
CPU CPU
Module Module
Filter Filter
Electrical
insulation
Page 7
Substation Automation Products
System design (contd) In the event that the central unit is out of oper- Central unit (500CU03)
ation or the optical fiber communication is dis- The hardware structure is based on standard
rupted an alarm is generated, the bay unit will racks and only a few different module types
continue to operate, and all local and bay pro- for the central unit (see Fig. 4).
tection as well as the recorders (event and
disturbance) will remain fully functional The modules actually installed in a particular
(stand-alone operation). protection scheme depend on the size, com-
plexity and functionality of the busbar system.
The hardware structure is based on a closed,
monolithic casing and presented in two A parallel bus on a front-plate motherboard
mounting solutions: establishes the interconnections between the
modules in a rack. The modules are inserted
Without local HMI: ideal solution if conve- from the rear.
nient access to all information via the cen-
tral unit or by an existing substation The central unit is the system manager, i.e. it
automation system is sufficient. configures the system, contains the busbar
replica, assigns bays within the system, man-
With local HMI and 20 programmable LEDs ages the sets of operating parameters, acts as
(Fig. 5): ideal solution for distributed and process bus controller, assures synchroniza-
kiosk mounting (AIS), since all information tion of the system and controls communica-
is available in the bay. tion with the station control system.
For the latter option it is possible to have the The variables for the busbar protection func-
HMI either built in or connected via a flexible tion are derived dynamically from the process
cable to a fixed mounting position (see data provided by the bay units.
Fig. 28).
The process data are transferred to the cen-
In the event of a failure, a bay unit can be eas- tral processor via a star coupler module. Up to
ily replaced. The replacement of a bay unit 10 bay units can be connected to the first cen-
can be handled in a simple way. During sys- tral processor and 10 to the others. Central
tem start-up the new bay unit requests its processors and star coupler modules are
address, this can be entered directly via its added for protection systems that include
local HMI. The necessary setting values and more than 10 bay units. In the case of more
configuration data are then downloaded auto- than 30 bay units, additional casings are
matically. required for accommodating the additional
central processors and star coupler modules
Additional plug-and-play functionality required.
Bay units can be added to an existing
REB500 system in a simple way. All modules of the central unit have a plug-
and-play functionality in order to minimize
module configuration.
Page 8
Substation Automation Products
0
0 Restraint current
ImI
(||)
n arctan Ln (5)
Fig. 7 Tripping characteristic of the stabilized ReILn
differential current algorithm.
N
IRest ILn (2)
n1
Page 9
Substation Automation Products
I2
This first timer operates in a stand-alone
I1 Re mode in the bay unit.
Tripping area I2
A remote tripping signal can be configured in
0 = 36 the software to be transmitted after the first or
Case 1 2
second timer.
Fig. 8 Characteristic of the phase comparator for Phase-segregated measurements in each bay
determining energy direction
unit cope with evolving faults.
Page 10
Substation Automation Products
is only possible if the voltage falls short of A disturbance record can be triggered by
(U<) or exceeds (U0>) the set value. either the leading or lagging edges of all
binary signals or by events generated by the
Additionally this release criterion can be con- internal protection algorithms. Up to 10 gen-
figured for each feeder (voltage transformers eral-purpose binary inputs may be configured
must be installed). For details see Table 22. to enable external signals to trigger a distur-
bance record. In addition, there is a binary
Check zone criterion input in the central and the bay unit for starting
The check zone algorithm can be used as a the disturbance recorders of all bay units.
release criterion for the zone-discriminating
low-impedance busbar protection system. It is The number of analog channels that can be
based on a stabilized differential current mea- recorded, the sampling rate and the recording
surement, which only acquires the feeder cur- period are given in Table 14. A lower sampling
rents of the complete busbar. The isolator / rate enables a longer period to be recorded.
breaker positions are not relevant for this cri-
terion. The total recording period can be divided into
a maximum of 15 recording intervals per bay
Neutral current detection I0 unit.
Earth fault currents in impedance-grounded
systems may be too low for the stabilized dif- Each bay unit can record a maximum of 32
ferential current and phase comparison func- binary signals, 12 of which can be configured
tions to detect. A function for detecting the as trigger signals.
neutral current is therefore also available, but
The function can be configured to record the
only for single phase-to-earth faults.
pre-disturbance and post-disturbance states
of the signals.
Pole discrepancy
A pole discrepancy protection algorithm The user can also determine whether the re-
supervises that all three poles of a circuit- corded data is retained or overwritten by the
breakers open within a given time. next disturbance (FIFO = First In, First Out).
This function monitors the discrepancy bet- This function is performed in a stand-alone
ween the three-phase currents of the circuit- mode in the bay unit (see page 7).
breaker.
Note:
When it picks up, the function does not send Stored disturbance data can be transferred via
an intertripping signal to the central unit, but, if the central unit to other computer systems for
configured, it starts the local breaker failure evaluation by programs such as PSM505 [3].
protection (BFP logic 3). Files are transferred in the COMTRADE for-
mat.
This function is also performed in a stand-
alone mode in the bay unit. After retrieving the disturbance recorder data,
it is possible to display them graphically with
Event recording PSM505 directly.
The events are recorded in each bay unit. A
time stamp with a resolution of 1ms is attach-
Communication interface
ed to every binary event. Events are divided Where the busbar protection has to communi-
into the three following groups: cate with a station automation system (SAS),
system events a communication module is added to the cen-
tral unit. The module supports the interbay
protection events
bus protocols IEC 61850-8-1, IEC 60870-5-
test events 103 and LON.
The events are stored locally in the bay unit or The IEC 61850-8-1 interbay bus transfers via
in the central unit. either optical or electrical connection:
Page 11
Substation Automation Products
Functionality (contd) disturbance recording data (via MMS file (protection zones). The system monitors any
transfer protocol) inconsistencies of the binary input circuits
time synchronization with Simple Network connected to the isolator auxiliary contacts
Time Protocol (SNTP) and generates an alarm after a set time delay.
two independent time servers are sup- In the event of an isolator alarm, it is possible
ported. Server 2 as backup time to select the behavior of the busbar protec-
tion:
The LON interbay bus transfers via optical
connection: blocked
Page 12
Substation Automation Products
in addition 20 freely programmable LEDs The HMI runs under MS WINDOWS NT, WIN-
for user-specific displays on the bay unit DOWS 98, WINDOWS 2000 and WINDOWS
500BU03 and central unit 500CU03. XP. The HMI500 is equipped with a comfort-
able on-line help function. A data base com-
The following information can be displayed: parison function enables a detailed
measured input currents and voltages comparison between two configuration files
(e.g. between the PC and the central unit or
measured differential currents (for the bus-
between two files on the PC).
bar protection)
system status, alarms Remote HMI
switchgear and isolator positions (within A second serial interface at the rear of the
the busbar protection function) central unit provides facility for connecting a
PC remotely via either an optical fiber, TCP/IP
starting and tripping signals of protection or modem link. The operation and function of
functions HMI500 is the same whether the PC is con-
nected locally or remotely.
Additional Bay level functions The line protection functions (L-V1 - L-V7) are
functionalities These functions are based on the well estab- used as Main 2 or back-up for lines as well as
lished and well-proven functions built in the for transformer bays. The transformer protec-
ABB line and transformer protection. The bay tion functions (T-V1 - T-V4) are used as Group
level functions contain all the relevant addi- 2 or back-up bay protection for transformer
tional functions, which are normally requested bays or as an independent T-Zone protection.
of a line and transformer protection scheme.
Page 13
Substation Automation Products
Voltage transformer circuit supervision High stability for external faults and current
transformer saturation
Power swing blocking function
No auxiliary transformers necessary
HF teleprotection. The carrier-aided because of vector group and CT ratio com-
schemes include: pensation
- permissive underreaching transfer trip- Inrush restraint using 2nd harmonic
ping
- permissive overreaching transfer trip- The transformer differential protection function
ping can also be used as an autonomous T-zone
protection in a 1 breaker scheme.
- blocking scheme with echo and tran-
sient blocking functions Thermal overload
Load-compensated measurement This function protects the insulation against
thermal stress. This protection function is nor-
- fixed reactance slope mally equipped with two independently set
- reactance slope dependent on load levels and is used when oil overtemperature
value and direction (ZHV<) detectors are not installed.
When the autoreclosure function is realized Rate of change frequency protection df/dt
This function is used for the static, dynamic
outside of REB500sys, all input and output
and adaptive load-shedding in power utilities
signals required by the external autoreclosure
and industrial distribution systems. The func-
equipment are available in order to guarantee
tion supervises the rate-of-change df/dt of one
correct functionality.
voltage input channel. Several stages of the
rate-of-change frequency protection are often
Page 14
Substation Automation Products
needed. This can be achieved by configuring forwards or reverse measurement. The char-
the rate-of-change frequency function several acteristic angle is set to 90
times. (U0 I0 sin ) in ungrounded systems and to
0 or 180 (U0 I0 cos ) for systems with
Definite time overfluxing protection Petersen coils. The neutral current is always
This function is primarily intended to protect used for measurement in the case of systems
the iron cores of transformers against exces- with Petersen coils, but in ungrounded sys-
sive flux. The function works with a definite tems its use is determined by the value of the
time delay. The magnetic flux is not measured capacitive current and measurement is per-
directly. Instead the voltage/frequency-ratio, formed by a measuring CT to achieve the
which is proportional to the flux is monitored. required sensitivity. To perform this function
the BU03 with 3I, 1MT and 5U is required.
Inverse time overfluxing protection
This function is primarily intended to protect Definite time over- and undercurrent pro-
the iron cores of transformer against exces- tection
sive flux. The function works with an inverse This function is used as Main 2 or as back-up
time delay. The inverse curve ca be set by a function respectively for line, transformer or
table of 10 values and the times t-min and t- bus-tie bays. This function can be activated in
max. The magnetic flux is not measured di- the phase- and/or the neutral current circuit.
rectly. Instead the voltage/frequency-ratio,
which is proportional to the flux is monitored. Inverse time overcurrent protection
The operating time of the inverse time over-
Power function current function reduces as the fault current
This function provides single, or three phase increases and it can therefore achieve shorter
measurement of the real or apparent power. operating times for fault locations closer to the
The function can be configured for monitoring source. Four different characteristics accord-
reverse, active or reactive power (power ing to British Standard 142 designated normal
direction setting). Phase angle errors of the inverse, very inverse, extremely inverse and
CT/VT inputs can be compensated by setting. long time inverse but with an extended setting
The operating mode can be configured either range are provided. The function can be con-
to underpower or to overpower protection. figured for single phase measurement or a
combined three-phase measurement with
Logics and delay/integrator detection of the highest phase current.
These functions allow the user the engineer-
ing of some easily programmable logical func- Inverse time earth fault overcurrent protec-
tions and are available as standard also in the tion
REB500 functionality. The inverse time earth fault overcurrent func-
tion monitors the neutral current of the sys-
Directional sensitive earth fault protection tem. Four different characteristics according
for grounded systems to British Standard 142 designated normal
A sensitive directional ground fault function inverse, very inverse, extremely inverse and
based on the measurement of neutral current long time inverse but with an extended setting
and voltage is provided for the detection of range are provided.
high-resistance ground faults in solidly or low-
resistance grounded systems. The scheme Directional overcurrent definite / inverse
operates either in a permissive or blocking time protection
mode and can be used in conjunction with an The directional overcurrent definite time func-
inverse time earth fault overcurrent function. tion is available either with inverse time or def-
In both cases the neutral current and voltage inite time overcurrent characteristic. This
can be derived either externally or internally. function comprises a voltage memory for
This function works either with the same com- faults close to the relay location. The function
munication channel as the distance protection response after the memory time has elapsed
scheme or with an independent channel. can be selected (trip or block).
Directional sensitive earth fault protection Definite time over- and undervoltage pro-
for ungrounded or compensated systems tection
The sensitive earth fault protection function for This function works with a definite time delay
ungrounded systems and compensated sys- with either single or three-phase measure-
tems with Petersen coils can be set for either ment.
Page 15
Substation Automation Products
Page 16
Substation Automation Products
FST-connector FST-connector
dB
Fig. 9 Attenuation
Isolator auxiliary contact must close before the isolator main contact
Auxiliary contacts on the isolators are con- gap reaches its flashover point.
nected to binary inputs on the bay units and
control the status of the busbar replica in the Conversely, during the opening movement,
numerical busbar protection. the N/O contact must not open before the iso-
lator main contact gap exceeds its flashover
One potentially-free N/O and N/C contact are point.
required on each isolator. The N/O contact
signals that the isolator is CLOSED and the If this is not the case, i.e. the contact signals
N/C contact that the isolator is OPEN. Dur- no longer closed beforehand, then the N/C
ing the closing movement, the N/O contact contact may not signal OPEN before the
flashover point has been exceeded.
Open Close
end position end position
Close isolator
Open isolator
Isolator
Auxiliary contacts:
Flashover gap
CLOSED
normally open
OPEN
normally closed
must be closed
may be closed
must be open
Fig. 10 Switching sequence of the auxiliary contacts that control the busbar replica
Page 17
Substation Automation Products
Current transformer requirements for sta- Applying relationships (1) and (2):
bility during external faults (Busbar protec-
tion) 30000
(1) n ---------------- = 6
The minimum CT requirements for 3-phase 5000
systems are determined by the maximum fault
current. (2) n' 10
The effective accuracy limit factor (n') must be Selected: n' 10
checked to ensure the stability of the busbar
protection during external faults. The current transformer requirements for
REB500sys for Line and Transformer protec-
The rated accuracy limit factor is given by the tion are described in a separate publication
CT manufacturer. Taking account of the bur- [1].
den and the CT losses, the effective accuracy
limit factor n' becomes: Pick-up for internal faults
In the case of internal busbar faults, CT sa-
turation is less likely, because each CT only
PN PE
n' n conducts the current of its own feeder.
PB PE
Should nevertheless CT saturation be possi-
where: ble, it is important to check that the minimum
n = rated accuracy limit factor fault current exceeds the setting for Ikmin.
PN = rated CT power
PE = CT losses Note:
PB = burden at rated current For systems that measure I0, the REB500
questionnaire 1MRB520371-Ken should be
In the case of schemes with phase-by-phase filled in and submitted to ABB, so that the CT
measurement, n' must satisfy the following requirements can be checked in order to
two relationships: ensure proper I0 measurement.
1 I Kmax
(1) n ------------------
-
5 I 1N
Page 18
Substation Automation Products
Page 19
Substation Automation Products
Hardware modules
Page 20
Substation Automation Products
Page 21
Substation Automation Products
Recording facilities
Table 13 Event recorder
Event recorder Bay unit Central unit
System events
Protection events 100 total 1000 total
Test events
Page 22
Substation Automation Products
Page 23
Substation Automation Products
Page 24
Substation Automation Products
Table 24 Delay/integrator
For delaying pick-up or reset or for integrating 1 binary signal
Provision for inverting the input
4 independent parameter sets
Settings:
Pick-up or reset time 0 to 300 s in steps of 0.01 s
Integration yes/no
Page 25
Substation Automation Products
Page 26
Substation Automation Products
Page 27
Substation Automation Products
Page 28
Substation Automation Products
Table 34 Directional sensitive earth fault protection for grounded systems (67N)
Detection of high-resistance earth faults
Current enabling setting 3I0
Direction determined on basis of neutral variables (derived externally or internally)
Permissive or blocking directional comparison scheme
Echo logic for weak infeeds
Logic for change of energy direction
4 independent parameter sets
Settings:
Current pick-up setting 0.1 to 1.0 IN in steps of 0.01 IN
Voltage pick-up setting 0.003 to 1 UN in steps of 0.001 UN
Characteristic angle -90 to +90 in steps of 5
Delay 0 to 1 s in steps of 0.001 s
Accuracy of the current pick-up setting 10% of setting
Page 29
Substation Automation Products
Page 30
Substation Automation Products
Isochrones
0.6 0.6
ZF/ZL
ZF/ZL
0.4 0.4
18ms 29ms
0.2 0.2
17ms
18ms
0 0
0.1 1 10 100 1000 0.1 1 10 100 1000
SIR (ZS/ZL) SIR (ZS/ZL)
0.6 0.6
ZF/ZL
ZF/ZL
0.4 0.4
0.2 0.2
17ms
18ms 29ms
0 0
0.1 1 10 100 1000 0.1 1 10 100 1000
SIR (ZS/ZL) SIR (ZS/ZL)
0.6 0.6
ZF/ZL
ZF/ZL
0.4 0.4
0.2 0.2
17ms 18ms 29ms
0 0
0.1 1 10 100 1000 0.1 1 10 100 1000
SIR (ZS/ZL) SIR (ZS/ZL)
Page 31
Substation Automation Products
Page 32
Substation Automation Products
I
I = I1+ I2 + I3
IN
Protected I2
I1 unit
I3 HEST 965 007 C
Page 33
Substation Automation Products
Technical data (contd) Table 40 Peak value over- and undercurrent protection (50)
Maximum or minimum function (over- and undercurrent)
Single or three-phase measurements
Wide frequency range (0.04 to 1.2 fN)
Peak value evaluation
Settings:
Current 0.1 to 20 IN in steps of 0.1 IN
Delay 0 to 60 s in steps of 0.01s
Accuracy of pick-up value (at 0.08 to 1.1 fN) 5% or 0.02 IN
Reset ratio >90% (for max. function)
<110% (for min. function)
Max. trip time with no delay (at fN) 30ms (for max. function)
60ms (for min. function)
Page 34
Substation Automation Products
Page 35
Substation Automation Products
Page 36
Substation Automation Products
500BIO01 500BIO01
1 1
Alarm 2 Alarm 2
1 3 1
aux aux 3
2 2
4 4
Warning 5 Warning 5
6 6
500PSM03 500PSM03
Fig. 11 Central unit module; Connection of power supply, binary inputs and outputs
Page 37
Substation Automation Products
Connection diagrams
(contd)
Bay unit types Available inputs/outputs
500BU03_4 (4 I, 20/16 I/O, stand-alone) z z z
500BU03_2 (4 I, 5 U, 20/16 I/O, stand-alone) z z z z
500BU03_6 (3 I, 1MT, 5 U, 20/16 I/O, stand-alone) z z z z
500BU03_1 (4 I, 5 U, 20/16 I/O, stand-alone) red. power supply z z z z z
500BU03_5 (3 I, 1MT, 5 U, 20/16 I/O, stand-alone)red. power supply z z z z z
500BU03_4 (4 I, 20/16 I/O, classic-mounting) z z z
500BU03_2 (4 I, 5 U, 20/16 I/O, classic-mounting) z z z z
500BU03_6 (3 I, 1MT, 5 U, 20/16 I/O, classic-mounting) z z z z
500BU03_1 (4 I, 5 U, 20/16 I/O, classic-mounting) red. power supply z z z z z
500BU03_5 (3 I, 1MT, 5 U, 20/16 I/O, classic-mounting) red. power supply z z z z z
500BU03_8 (9 I, 20/16 I/O, stand-alone) z z z
500BU03_7 (9 I, 20/16 I/O, stand-alone) red. power supply z z z z
500BU03_8 (9 I, 20/16 I/O, classic-mounting) z z z
500BU03_7 (9 I, 20/16 I/O, classic-mounting) red. power supply z z z z
E
Tx 1
J
I4[1] 1
I
I1[1]
E
Tx
U
1
I
I1[1]
I1[1]
A 2 I4[5] 2 I1[5] A U1 2 I1[5]
I1[5]
Rx Tx Rx Tx U1[0]
Terminal block/ Function Wire gauge/ 3 I4[0] 3 I1[0]
U2
3 I1[0]
I1[0]
4 I5[1] 4 I2[1] 4 I2[1]
terminals Type Rx
5 I5[5] 5 I2[5]
Rx U2[0]
5
I2[1]
I2[5]
I2[5]
A, B Binary inputs 1.5 mm2 C
6 I5[0] 6 I2[0]
C U3
U3[0] 6 I2[0]
I2[0]
C, D Binary outputs 1.5 mm2 7 I6[1] 7 I3[1]
U4
7 I3[1]
I3[1]
17 I9[5]
H H
D D
18 I9[0]
HMI HMI
Abbreviations Explanation DC DC
OCxx Opto-coupler
CRxx Tripping relay I I I I
0 0 0 0
OLxx Optical link
R P R P
+ + + +
- - - -
500BU03 500BU03
Binary Inputs Processbus Current Transformer Current Transformer U Voltage Transformer I Current Transformer
J I
A 1
OC01
1 1 1
Tx E 1 1 1 1
2
5 5 5
OC02 OL01 U1 I1
3 2 I4 2 I1 2
Rx
0 0 0 0
4
3 3 2 3
5
OC03 Binary Outputs
6 1 C 1 1
4
1
OC04 4 4 4
7 CR01 2
5 5 5
5 I5 5 I2 U2 5 I2
8 3
0 0 0 0
9 4 6 6 5 6
OC05
10 CR02 5
OC06 1 1 1
11 6
7 7 7 7
12 7 5
5 5
8 I6 8 I3 U3 8 I3
13 CR03 8
OC07 0 0 0 0
14 9 9 9 8 9
OC08
15 10
CR04 1 1
16 11 10 10
10
CR05
12 5
17
18
OC09
13
11
5
I7
0
U4 11
0
I4 *)
CR06 0
B 1
OC10
14 12 11 12
CR07
15
2
OC11 1
3 13 13
4
OC12
1 D 5
14 I8 U5
5 2
0 0
CR08 3 15 14
6
OC13
CR09
4
7 1
OC14 CR10
5 16 H HMI Interface H HMI Interface
8
OC15 5
9 6
17 I9
10 7
0
CR11
8
18
11
OC16
CR12
12 9
OC17
CR13 10
13 Redundant Power Supply Power Supply Redundant Power Supply Power Supply
OC18
11
R P
14
15 12
R P
+ + 1 + 1 +
16
1 1 _ _
CR14 13 _ _
OC19
CR15 2 2 2 2
17 14
OC20
18 CR16 15
Page 38
Substation Automation Products
E J I E J I
Terminal block/ Function Wire gauge/
Tx 1 I4[1] 1 I1[1] Tx 1 I4[1] 1 I1[1]
terminals Type A 2 I4[5] 2 I1[5] A 2 I4[5] 2 I1[5]
Rx Tx Rx Tx
2 3 I4[0] 3 I1[0] 3 I4[0] 3 I1[0]
A, B Binary inputs 1.5 mm
2 4 I5[1] 4 I2[1] 4 I5[1] 4 I2[1]
C, D Binary outputs 1.5 mm Rx Rx
5 I5[5] 5 I2[5] 5 I5[5] 5 I2[5]
E Optical connection C
6 I5[0] 6 I2[0]
C
6 I5[0] 6 I2[0]
Rx Receive FST plug 7 I6[1] 7 I3[1] 7 I6[1] 7 I3[1]
Tx Transmit FST plug 8 I6[5] 8 I3[5] 8 I6[5] 8 I3[5]
2
I Currents 2.5 mm 9 I6[0] 9 I3[0] 9 I6[0] 9 I3[0]
14 U2[0] 14 I8[5]
15 15 I8[0]
B 16 U3 B 16 U1
17 U3[0] 17 U1[0]
H H
Abbreviations Explanation D 18 D
18
OCxx Opto-coupler HMI HMI
I I I I
0 0 0 0
R P R P
+ + + +
- - - -
500BU03 500BU03
Binary Inputs Processbus Current Transformer Current Transformer J Current Transformer I Current Transformer
J I
1
A 1
OC01
1 1 1
1
Tx E 1 1 1
2 5
OC02 OL01 5 5 5
I4 I1 I4 2 I1
3 2 2 2
Rx 0
4 0 0 0
3 3 3 3
5
OC03 Binary Outputs 1
6 1 C 1 1 1
4
OC04 4 4 4
7 CR01 2 5
5 5 5
5 I5 5 I2 5 I5 5 I2
8 3
0
0 0 0
9 4 6 6 6 6
OC05
10 CR02 5
OC06 1
1 1 1
11 6 7
7 7 7
12 7 5
5 5 5
8 8 8 8 I3
CR03 8
I6 I3 I6
13
OC07 0
0 0 0
9 9 9 9 9
14
OC08
15 10
Voltage Transformer
CR04 1
16 11
10 10
CR05
12
17 5
OC09 U1 11 I7
18 13
CR06 0 0
B 1 14 11 12
OC10
CR07
15
2
OC11 1
3
13 13
OC12
4 1 D 5
U2 14 I8
5 2
0
0
CR08 3 14 15
6
OC13
CR09
4
7
OC14 CR10
16 H HMI Interface Voltage Transformer H HMI Interface
5
8 16
OC15
9 6
U3
10 7 0
U1
CR11 17 0
11 8 17
OC16
CR12
12 9
OC17
CR13 10 Redundant Power Supply Power Supply
13 Redundant Power Supply Power Supply
OC18
11
14
R P R P
15 12 + +
+ + 1 1
1 1 _ _
16 CR14 13 _ _
OC19 2 2
CR15 14 2 2
17
OC20
18 CR16 15
Page 39
Substation Automation Products
Disturbance recorder
End fault protection
Distance protection
Busbar protection
Analog inputs
Synchrocheck
Voltage check
Currents
1
1
2 5 Phase current L1
I1 zzzz zzzz z (Line)
3 0
4 1
5 5 Phase current L2
I2 zzzz zzzz z (Line)
6 0
7 1
8 5 Phase current L3
I3 zzzz zzzz z (Line)
9 0
10 1
11 5 Neutral current Lo (Y)
I4 z (Line)
12 0
Voltages
1
Phase voltage L1
U1 zzz z (Line)
2 0
4
Phase voltage L2
U2 zzz z (Line)
5 0
7
Phase voltage L3
U3 zzz z (Line)
8 0
10
Phase voltage L2
U4 z (Bus 1)
11 0
1ph -> L2-E
13
Phase voltage L2
U5 z (Bus 2)
14 0
1ph -> L2-E
Page 40
Substation Automation Products
Disturbance recorder
End-fault protection
Busbar protection
Thermal overload
Analog inputs
Currents
1 1
I
2 5 Phase current L1
I1 z z z z z A-side
3 0
4 1
5 5 Phase current L2
I2 z z z z z A-side
6 0
7 1
8 5 Phase current L3
I3 z z z z z A-side
9 0
Currents
1 1
J
2 5 Phase current L1
I4 z B-side
3 0
4 1
5 5 Phase current L2
I5 z B-side
6 0
7 1
8 5 Phase current L3
I6 z B-side
9 0
Currents
10 1
J
11 5 Phase current L1
I7 z C-side (if existing)
12 0
13 1
14 5 Phase current L2
I8 z C-side (if existing)
15 0
16 1
17 5 Phase current L3
I9 z C-side (if existing)
18 0
Page 41
Substation Automation Products
Connection diagrams
(contd) Bay Unit Protection functions
Disturbance recorder
End fault protection
Distance protection
Busbar protection
Thermal overload
Analog inputs
Frequency
Power
Currents
1 1
I
2 5 Phase current L1
I1 z z z z z A-side
3 0
4 1
5 5 Phase current L2
I2 z z z z z A-side
6 0
7 1
8 5 Phase current L3
I3 z z z z z A-side
9 0
Currents
1 1
J
2 5 Phase current L1
I4 z z z z z B-side
3 0
4 1
5 5 Phase current L2
I5 z z z z z B-side
6 0
7 1
8 5 Phase current L3
I6 z z z z z B-side
9 0
Voltages
10
J
Phase voltage L1
U1 z z z z z A-side or B-side
11 0
13
Phase voltage L2
U2 z z z z z A-side or B-side
14 0
16
Phase voltage L3
U3 z z z z z A-side or B-side
17 0
Page 42
Substation Automation Products
Disturbance recorder
End fault protection
Busbar protection
Thermal overload
Analog inputs
Currents
1 1
I
2 5 Phase current L1
I1 z z z z z A-side
3 0
4 1
5 5 Phase current L2
I2 z z z z z A-side
6 0
7 1
8 5 Phase current L3
I3 z z z z z A-side
9 0
Currents
1 1
J
2 5 Phase current L1
I4 z B-side
3 0
4 1
5 5 Phase current L2
I5 z B-side
6 0
7 1
8 5 Phase current L3
I6 z B-side
9 0
Currents
10 1
J
11 5 Current Lx
I7 z (e.g. Lo)
12 0
13 1
14 5 Current Lx
I8 z (e.g.Lo)
15 0
Voltages
16
J Voltage Lx
U1 z z z (e.g. Phase L1-L2 ->
17 0
Overfluxing protection )
Page 43
Substation Automation Products
OC01 1
External reset 2 2
OC02
6
5
OC05
8
8
Block breaker failure protection OC06
CR05 9
9
10 System alarm
OC07
11
10
11
OC08
CR06 12 In service
12
13
13
14
OC09
15
14
OC11
CR08
16
CR09 18 Breaker failure protection tripped
OC12
17
18
Fig. 18 REB500: Typical assignment of the in/outputs of a central unit for busbar and breaker failure pro-
tection
17
OC09 1
18 D
2
1
OC10 B CR08 3
2 CR09
OC11 4
3 CR10
OC12 5
4
5 6
7
6
Bus 1 Isolator Q1 off OC13 CR11 Trip Phase L1, trip coil 1
8
7
Bus 1 Isolator Q1 on OC14 CR12 9 Trip Phase L2, trip coil 1
8 Trip Phase L3, trip coil 1
Bus 2 Isolator Q2 off OC15 CR13 10
9
10 11
12
11
OC16
Bus 2 Isolator Q2 on CR14 13 Trip Phase L1, trip coil 2
12
OC17 CR15 14 Trip Phase L2, trip coil 2
13
OC18 CR16 15 Trip Phase L3, trip coil 2
14
15
16
OC19
17
OC20
18
Fig. 19 REB500: Typical assignment of the in/outputs for a double busbar with busbar and breaker failure
protection of a bay unit
Page 44
Substation Automation Products
9
CR03 8 AR Close Command
Carrier Receive, Distance Prot. OC05
9
10
Carrier Receive, DEF Prot. OC06
10
11
CR04
12 11 Remote Trip, channel 1
CR05
13 12 Carrier Send, Distance Prot.
Bus 1 VT MCB Fail OC07
14 13
Bus 2 VT MCB Fail 15
OC08 CR06
14 Remote Trip, channel 2
CR07
16 15 Carrier Send, DEF Prot.
17
Breaker Q0 Close Command OC09
18
1
1
D
Line VT MCB Fail OC10 B 2
2 CR08 3
CB All Poles Closed for DEF Prot. OC11 Start L1L2L3 to AR in Main 1
3 CR09
OCO Ready for AR Release OC12 4 Trip CB 3-Pole to AR in Main 1
4 CR10
5 Trip CB to AR in Main 1
5
6
6
OC13
Bus 1 Isolator Q1 off 7
7
Bus 1 Isolator Q1 on OC14 CR11 8 Trip Phase L1, trip coil 1
8
Bus 2 Isolator Q2 off OC15 CR12 9 Trip Phase L2, trip coil 1
9
10 CR13 10 Trip Phase L3, trip coil 1
11 11
OC16
Bus 2 Isolator Q2 on 12
12
Breaker Q0 off OC17
13
CR14 13 Trip Phase L1, trip coil 2
Breaker Q0 on OC18
14 CR15 14 Trip Phase L2, trip coil 2
15 CR16 15 Trip Phase L3, trip coil 2
16
OC19
Prepare 3 Pole Trip,from Main1
17
Main 1 Healthy/In Service Mode (Blk. AR) 18
OC20
Fig. 20 REB500sys: Typical assignment of the in-/outputs of line variant L-V4 for 500BU03
(See [2] Application description)
Page 45
Substation Automation Products
Connection diagrams
(contd)
Binary inputs Binary outputs
Transformer Transformer
Variant 1 Variant 1
Start BFP phase L1L2L3 1
from prot. group 2 TRIP OC01 A C 1
2 CR01 2
External start BFP OC02
3 In service
from mechanic prot. TRIP
3
4
4
Start BFP phase L1L2L3 5
OC03
from back-up prot. TRIP CR02 5 Block close command
6 breaker Q0 A-side
Spare OC04
7 6
8 7
9 CR03 8
Mechanic protection TRIP 1 OC05
Transf. prot. trip L1L2L3 group 1
10 9
OC06 Tripping relay (94-1)
Mechanic protection alarm 1
11 10 trip CB A/B/Cside *)
12 CR04
11 Transf. prot. trip start BFP
13 CR05 on C-side *)
Mechanic protection TRIP 2 OC07 12
14
OC08 13
Mechanic protection alarm 2 15 CR06
14 Remote trip 2 to B-side
16
CR07
15 Transf. prot. trip L1L2L3 group 2
A-side breaker Q0 17 Tripping relay (94-2)
manual close command OC09 trip CB A/B/Cside *)
18
Block transformer 1 1
OC10 B D
diff. protection 2
2
Transformer diff. inrush input OC11
CR08 3 Remote trip 1 to B-side
3
Transformer diff. high-set OC12 CR09
4 4 Remote Trip 1 to C-side *)
5 CR10
5 Transf. prot. trip start BFP
6 on B-side
A-side bus 1 isolator Q1 open OC13 6
7
A-side bus 1 isolator Q1 closed OC14 7
8 CR11
A-side bus 2 isolator Q2 open OC15 8 Trip phase L1
9 Trip breaker
CR12 Q0 coil 1 A-side
9 Trip phase L2
10
CR13 10 Trip phase L3
11
A-side bus 2 isolator Q2 closed OC16
11
12
A-side breaker Q0 open OC17
12
13
A-side breaker Q0 closed OC18
14 CR14 13 Trip phase L1
Trip breaker
15 CR15 14 Trip phase L2 Q0 coil 3 A-side
16
Spare OC19 CR16 15 Trip phase L3
17
Spare OC20
18
Legend:
*) C-side, if existing
Fig. 21 REB500sys: Typical assignment of the in-/outputs of transformer variant T-V1 for 500BU03
(See [2] application description)
Page 46
Substation Automation Products
Achtung
Caution
Attention
Atencion
Fig. 22 Bay unit casing for flush mounting, enclosure protection class IP 40 (without local HMI)
2
Cross section: max. 2.5 mm
Fig. 23 Centralized version based on a 19'' mounting plate with up to three bay units.
Optionally with local HMI.
Page 47
Substation Automation Products
6U=265.8
276
approx. 100
2040.5
Space for wiring
267+0.1
2000.5
189
25
210
Panel cutout
Fig. 24 Dimensional drawing of the bay unit with local HMI, classical mounting
protection type IP40
Central unit
482.6
57.1
6U=265.8
76.2
57.1
465.6
approx. 70
Rear view
approx. 235
212
443
30
Page 48
Substation Automation Products
Cubicle mounting
Fig. 26 Front view of REB500 (example only) Fig. 27 Hinged frame and rear wall
The cubicles are equipped with gratings for the fixation of incoming cables. For space reasons
there are no cable ducts.
Page 49
Substation Automation Products
Sample Combined numerical bay and station protec- Busbar protection scheme based on low-
specification tion with extensive self-monitoring and ana- impedance principle and at least two inde-
log/digital conversion of all input quantities. pendent tripping criteria
End fault protection
The architecture shall be decentralized, with
bay units and a central unit. Breaker failure protection
Breaker pole discrepancy
It shall be suitable for the protection of single
and double busbar as well as for the protec- Additional criteria for the busbar protection
tion (Main 2 or back-up) of incoming and out- as overcurrent or voltage release
going bays, lines, cables or transformer bays. Over-/undercurrent and over-/undervolt-
age back-up bay function (overcurrent
The hardware shall allow functions to be acti- directional or non-directional)
vated from a software library:
Page 50
Substation Automation Products
Distance protection function with all rele- No auxiliary CTs are necessary and the sys-
vant additional features, such as switch-on- tem contains internal check of the voltage and
to-fault, teleprotection schemes, voltage current circuits. The adaptation of the CT-
supervision, power swing blocking ratio is done by software.
Earth fault directional function based on
A modern human machine interface shall
zero components with separate communi-
allow the allocation of input and output sig-
cation scheme or using the same channel
nals.
as the distance protection
Directional sensitive earth fault protection Communication via computer or via interface
for ungrounded or compensated systems to monitoring or control systems allows the
actual configuration of the whole busbar to be
Autoreclosure function, single/three pole
displayed.
and multi-shot
Synchrocheck function with the different Event and disturbance recording shall be
operation modes (dead line and /or dead included, collection of data in the bay units,
bus check) comprehensive recording available for the
Thermal overload protection whole station in the central unit.
Peak value over-/undervoltage function The proposed system shall be easily extensi-
Transformer differential protection for the ble, in case of extensions in the substation.
protection of two or three-winding trans-
formers and autotransformers
Ordering Ordering
When sending your enquiry please provide diagram of the station. This will enable us to
the short version of the questionnaire on page submit a tender that corresponds more accu-
55 in this data sheet together with a single-line rately to your needs.
Page 51
Substation Automation Products
Equipped for
10 bay units 10
20 bay units 20
30 bay units 30
40 bay units, incl. 2nd rack 40
50 bay units, incl. 2nd rack 50
60 bay units, incl. 2nd rack 60
Communication Interface A
No 0
LON 1
IEC 103 2
IEC 61850-8-1 3
Communication Interface B
No 0
LON 1
IEC 103 2
IEC 61850-8-1 3
Page 52
Substation Automation Products
Short questionnaire
Accessories
HMI software
HMI500 Ver. 7.50/7.60 Operator Quantity 1MRB260027R0076
HMI500 Ver. 7.50/7.60 Configurator * Quantity 1MRB260027R0176
* HMI500 Configurator is including software license for 4 users
(authorization by serial number).
Please note license is only provided for trained customers!
Manuals
Operating instructions REB500/REB500sys in English Quantity 1MRB520292-Uen
Page 53
Substation Automation Products
Ordering (contd)
LHMI
500HMI03 * 0.5REB500-BU03-V7-C -A
m, local HMI with 0.5 m cable -P -F -BB Quantity
-IO -R -OC -BFP -EFP
1MRB150073R0052 -PD -DR -L -T
500HMI03 * 3 m, local HMI with 3 m cable Quantity 1MRB150073R0302
Line protection
No 0
Line variant 1 (L-V1)
Miscellaneous 1
Line variant 2 (L-V2) 2
500OCC02 Converter cable (serial) HMI-PC Quantity 1MRB380084R0001
Line variant 3 (L-V3) 3
500OCC03 Converter cable (USB) HMI-PC Quantity 1MRB380084R0003
Line variant 4 (L-V4) 4
Line variant 5 (L-V5) 5
Line variant 6 (L-V6) 6
Mounting parts
Line variant 7 (L-V7) 7
Cover plate 4R 4R (4 divisions) Quantity 1MRB400164 R0004
HMI Cover plate HMI Cover plate for mounting on unused dis- Quantity 1MRB400304 R0101
play cut-outs
Mounting plate 19" Quantity 1MRB400130 P0101
Page 54
Substation Automation Products
Short questionnaire
1. Client Client Station Client's reference Client's representive, date
2. ABB (filled in by ABB) Tender No.: Order No.: Sales Engineer Project Manager
3. Binding Single line diagram Diagram No. Date Rev. Index Rev. Date Remark :
(must show location and configuration This attachment is
of spare bays) absolutely essential !
4. HV System System Voltage [kV] Neutral Grounding Busbar configuration
Solidly grounded Single 1-1/2 Breaker
Isolated Double Ring bus
Frequency [Hz] Compensated Triple Transfer bus
Low resistance gr. Quadruple
Accessories
HMI software
HMI500 Ver. 7.60 Operator Quantity 1MRB260027R0076
HMI500 Ver. 7.60 Configurator * Quantity 1MRB260027R0176
* HMI500 Configurator is including software license for 4 users
(authorization by serial number).
Please note license is only provided for trained customers!
Manuals
Operating instructions REB500/REB500sys in English Quantity 1MRB520292-Uen
Page 55
Substation Automation Products
Ordering (contd)
LHMI
500HMI03 * 0.5 m, local HMI with 0.5 m cable Quantity 1MRB150073R0052
500HMI03 * 3 m, local HMI with 3 m cable Quantity 1MRB150073R0302
Miscellaneous
500OCC02 Converter cable (serial) HMI-PC Quantity 1MRB380084R0001
500OCC03 Converter cable (USB) HMI-PC Quantity 1MRB380084R0003
Mounting parts
Cover plate 4R 4R (4 divisions) Quantity 1MRB400164 R0004
Cover plate 8R 8R (8 divisions) Quantity 1MRB400164 R0008
Mounting plate 19" Quantity 1MRB400299 P0101
Page 56
Substation Automation Products
Mounting parts
Mounting plate 19" Quantity 1MRB400130 P0102
Page 57
Contact us
www.abb.com/substationautomation