Rotate JOG Rotate JOG Rotate JOG Current

Press Enter Press Enter Press Enter


Wheel Wheel Wheel Value

ACC (Acceleration Time) 3 sec

dEC (Deacceleration Time) 3 sec

LSP (Low Speed/ Low Freq.) 25Hz

SEt HSP (Max Speed/ High Freq.) 48Hz

ItH (Overload Setting) 19A

tLS (Low Speed Timeout) 30 sec

rSL (Wakeup Threshold) 20%

UnS (Motor Voltage) 400V

nCr(Motor Current) 19A

nSP (Motor rpm) 2900rpm


drC
Frequency Display COS(Motor PF) 0.9

Uft(Application Mode) P (Variable Torque)

tFr(Maximum Freq.) 60Hz

PIF AI3
FUn PI (Parameter regulator) (Feedback Signal (Input Sensor
Port) Connect Port)

29.9
CtL Fr1 (Reference channel) AIU1 (Internal Pressure
Set Point in meters)

2C
I_O tCC(Type of Sensor) (Two Wire Sensor
control)

FrH(Frequency reference)

SUP rFr (output freq)

LCr(Current)

Note: 1. Two Wire 0-10bar 4-20mA pressure sensor is connected to AI13 pin
2. Internal 24V DC power supply is used as the power input for sensoor
3. A jumper is used between +24VDC and LI1 (Can use it as a selector switch for Pump ON/Off)
4. You can set/change the Values By rotating the Jog

VSD Settings Flow Chart

Project Title:- Remarks:-

Drawn:- Nayantha
Supply and Installation of 1 Number of
11kW VSD to Alankulam Pump House
Date :- 02.02.2017

Rev:- Scale :- NTS