INDEX
1.General Survey
2.Working Principle
10
11
1 General Survey
1. The type of temperature controller is defined in accordance with the standard named
"Transformer Pressure-type Thermometer" formulated by the Transformer Research
Institute in ShenYang.
2
B W Y 80 3 A (TH) / 288 F C
square type
linear graduation
liquid pressure-type
temperature gauge
transformer
2. The type of temperature controller is defined in accordance with the standard named
"The Principle of Type Organization of Industrial Automatic Instrument"
2
W T Y K 80 3 A (TH) / 288 F C
square type
linear graduation
controller
liquid pressure-type
elastic component
temperature gauge
1
No TYPE & NAME MAIN USEAGE SUITABLE SITE REEE
BWY(WTYK)-
For transformer
802803(TH)Transfor Same as No1
2 capacity more
mer Temperature And is available in damp and hot site
than 1000kVA
Controller
Same as No2
BWY(WTYK)-
Adopting the technical in transducer of For transformer
802803A(TH)Transf
3 complex temperature and can simultaneously capacity more
ormer Temperature
send out the signal of Pt100 platinum than 800kVA
Controller
thermal resistor
Same as No3,4
BWYWTYK-
can simuataneously replace For transformer
802,803A(TH)/288F
6 1)WTZK-02 temperature controller capacity more
transformer temperature
2)Resistance thermometer than 8000kVA
control instrument set
3)Change-over switch
Same as No3,5
can simultaneously replace For transformer
BWY(WTYK)-
1)WTZK-02 temperature control-ler capacity more
802,803A(TH)/288FC
7 2)Resistance thermometer than 8000kVA of
transformer temperature
3)Change-over switch selr-service
control instrument set
4)XCTmovable coil thermometer power station
5)The transformer of signal
2
40 60
C
20 80
M
01 49
0 100
0 100
K 1 K3
100 0
K 2 Installation
0 100
Hole
3
The Maximun Insert Depth
3 TECHNICAL SPECIFICATION
3.1 BWYWTYK-802, 803
0~+100
0~+120
4 Controlling capability
Setting accuracy: 3
Switch difference: 62
6
40 60
C
BWY(WTYK)- 3 ATH
20 80
0 100
A1
R1
A2 0
B1 K 1 K 3
R2
100 0
B2 K2
R3
0 100
C1 setting pointer(red)
C2
2 WIRING
Open the cover of guage, reeve the wire through the cable guiding holes and connect according to
Figure 5.
Figure 5 BWYWTYK-802803
7
4.2 BWYWTYK-802803A/288F
BWY WTYK -802 803A TH temperature controller is constituented on base of
BWY WTYK -802,803 TH and get a additional case of remoting temperature measuring
instrument wnich is consist of XMT digital displat thermometer and Pt100 platinum resistor. The signal
of Pt100 platinum resistor is transmitted to the far control room of the substation by the KVV4*1.5
control cable which connected with terminal wiring board as figure 5. So that to realize the remote
measuring of the transformer oin.All connection refer as figure 6
8
4.3 BWYWTYK-802803A/288FC
The installing & operation of BWY WTYK -802, 803/288FC are just same as
BWYWTYK-802, 803A/288F. In addition, XMT-288FC digital display thermometer can translate
the signal of Pt100 platinum resistor to typical signal of 0~5V or 4~20mA which can be inputted into
the computer of selfservice power station.All connection refer as figure 7
9
5 POINTS FOR ATTENTION
1 The examination of temperature should be according to the checghing up regulation of JJG310-2002
of liquid spontaneously measurement thermometer. The temperature bulb should be inserted entirely
into the constant temperature oil box, and the temperature controller should be installed
perpendicularly, It can not get the precision of 1.5 degree in normal temperature air.
2 In the course of installing, connection of temperature controller, handle with care and operate it
strictly as technical requirements.
3 Pick out a box wrench to open the gauge cover. When closing cover, four locator should be screwed
up symmetrically, so as not to affect the airtightness of gauge.
4 In the first mounting instance, the superfluous capillary tube should be twined in a circle of diameter
more than 150mm. At each 300mm interval, the guard of capillary tube should be properly fixed for
example bind round with soft fine line of copper
5 When testing the digital display thermometer, according to the Pt100 scale value, can use standard
measuring resistor as the inlet signal to measure temperature or connect with R1, R2, R3 of 802A,
803A in a constant temperature trough to test its resistance.
6 It should be attention that the temperature bulb must be inserted into the tube fill with oil when
spot installing. The depth should be more than 150mm.
7 Water is forbidden to let in the transformers sleeve with oil inside. When the ambient
temperature drops below 0 and the transformer happens not to work. The water in the
sleeve probably freezes in an expansion to squeeze the bulb, which results in wrong
indication of the thermoregulator. So The attention must be paid to seal the bulb when
mounting it to prevent rainwater in
10
Appendix
Pt100 Industrial platinum temperature resistance scale value
As to international temperature scale IPS-90
-10 96.09 31 112.06 72 127.84 113 113.42
-9 96.48 32 112.45 73 128.22 114 143.80
-8 96.87 33 112.83 74 128.60 115 144.17
-7 97.26 34 113.22 75 128.98 116 144.55
-6 97.65 35 113.61 76 129.237 117 144.93
-5 98.04 36 113.99 77 129.75 118 145.31
-4 98.44 37 114.38 78 130.13 119 145.68
-3 98.83 38 114.77 79 130.51 120 146.06
-2 99.22 39 115.15 80 130.89 121 146.44
-1 99.61 40 115.54 81 131.27 122 146.81
0 100.00 41 115.93 82 131.66 123 147.19
1 100.39 42 116.31 83 132.04 124 147.57
2 100.78 43 116.70 84 132.42 125 147.94
3 101.17 44 117.08 85 132.80 126 148.32
4 101.56 45 117.47 86 133.18 127 148.70
5 101.95 46 117.85 87 133.56 128 149.07
6 102.34 47 118.24 88 133.94 129 149.45
7 102.73 48 118.62 89 134.32 130 149.82
8 103.12 49 119.01 90 134.70 131 150.20
9 103.51 50 119.40 91 135.08 132 150.57
10 103.90 51 119.78 92 135.46 133 150.95
11 103.29 52 120.16 93 135.84 134 151.33
12 104.68 53 120.55 94 136.22 135 151.70
13 105.07 54 120.93 95 136.60 136 152.08
14 105.46 55 121.32 96 136.98 137 152.45
15 105.85 56 121.70 97 137.36 138 152.83
16 106.24 57 122.09 98 137.74 139 153.20
17 106.63 58 122.47 99 138.12 140 153.58
18 107.20 59 122.86 100 138.50 141 153.95
19 107.40 60 123.24 101 138.88 142 154.32
20 107.79 61 123.62 102 139.26 143 154.70
21 108.18 62 124.01 103 139.64 144 155.07
22 108.57 63 124.39 104 140.02 145 155.45
23 108.96 64 124.77 105 140.39 146 155.82
24 109.35 65 125.16 106 140.77 147 156.19
25 109.73 66 125.54 107 141.15 148 156.57
26 110.12 67 125.92 108 141.53 149 156.94
27 110.51 68 126.31 109 141.91 150 157.31
28 110.90 69 126.69 110 142.29
29 111.28 70 127.07 111 142.66
30 111.67 71 127.45 112 143.04
11