Escolar Documentos
Profissional Documentos
Cultura Documentos
MANUAL
2. CONSTRUCTION STANDARDS
Version 1.44 May 2011
Housing Standards Policy Manual
Published by the Office of Housing, Victorian Government Department of Human Services, Melbourne, Victoria,
Australia.
This publication is copyright. You may make limited copies of this document in accordance with the Copyright
Act 1968 (Cth), including copies for research, study, criticism, review or news reporting. Apart from this, you
may not publish, reproduce, adapt, modify, communicate or otherwise use any part of this document (in
particular for commercial purposes).
Table of Contents
Table of Contents................................................................................................................i
Revision History...............................................................................................................viii
Foreword..........................................................................................................................ix
Introduction...........................................................................................................x
Standards..............................................................................................................xi
Purpose.................................................................................................................1
Scope....................................................................................................................1
Objectives..............................................................................................................1
2.2 Definitions..................................................................................................................2
2.4 References..................................................................................................................5
2.5 Policy.........................................................................................................................6
General..................................................................................................................6
Location.................................................................................................................6
AS4299 1995..............................................................................................................6
Energy Efficiency....................................................................................................7
Property Titles........................................................................................................8
Termite Protection..................................................................................................8
Security.................................................................................................................8
Locks.....................................................................................................................8
Fences...................................................................................................................9
Building Services....................................................................................................9
Landscaping...........................................................................................................9
2.6 Standards.................................................................................................................11
Site Selection........................................................................................................11
Ground Works......................................................................................................11
External Areas......................................................................................................11
Internal Areas......................................................................................................16
Utility Areas..........................................................................................................18
Windows..............................................................................................................21
Doors...................................................................................................................22
Locks...................................................................................................................24
Floor Finishes.......................................................................................................24
AS2055.1 1985..........................................................................................................25
Paintwork.............................................................................................................25
Insulation insulation..............................................................................................26
Building Services..................................................................................................26
BCA 1996................................................................................................................26
Electrical Services.................................................................................................27
Lighting................................................................................................................28
Appliances............................................................................................................28
Ventilation............................................................................................................30
Plumbing..............................................................................................................31
Television.............................................................................................................31
Fencing................................................................................................................33
Landscaping.........................................................................................................33
MDH Guide..............................................................................................................34
General................................................................................................................35
External Areas......................................................................................................35
AS1428.1 1998..........................................................................................................35
Internal Areas......................................................................................................37
Utility Areas..........................................................................................................38
AS4299 1995............................................................................................................39
AS4299 1995............................................................................................................41
Windows..............................................................................................................41
AS4299 1995............................................................................................................41
Doors...................................................................................................................41
Floor Finishes.......................................................................................................42
AS2055.1 1985..........................................................................................................42
Building Services..................................................................................................42
Electrical Services.................................................................................................42
AS4299 1995............................................................................................................42
AG 601 1995............................................................................................................42
Plumbing..............................................................................................................43
Fencing................................................................................................................43
BR 1994..................................................................................................................43
Landscaping.........................................................................................................44
General................................................................................................................45
External Areas......................................................................................................45
Internal Areas......................................................................................................46
Utility Areas..........................................................................................................47
Windows..............................................................................................................49
Doors...................................................................................................................50
Locks...................................................................................................................51
Floor Finishings....................................................................................................51
Paintwork.............................................................................................................51
Insulation.............................................................................................................51
Building Services..................................................................................................51
BCA 1996................................................................................................................52
AS3500 1998............................................................................................................52
Electrical Services.................................................................................................52
Lighting................................................................................................................53
Appliances............................................................................................................53
Ventilation .................................................................................................54
AS2681 1984............................................................................................................54
BCA 1996................................................................................................................54
Plumbing..............................................................................................................54
2.9 Sleepouts..................................................................................................................56
General................................................................................................................56
External Areas......................................................................................................57
Windows..............................................................................................................57
Doors...................................................................................................................57
Locks...................................................................................................................58
Floor Finishings....................................................................................................58
Paintwork.............................................................................................................58
Insulation.............................................................................................................59
Building Services..................................................................................................59
Electrical Services.................................................................................................59
..................................................................................................................59
AS3000 2000............................................................................................................59
Lighting................................................................................................................59
Appliances............................................................................................................59
Ventilation............................................................................................................59
...................................................................................................................59
The Director of Housing or its approved delegate authorises amendments to the Housing Standards Policy
Manual.
The first issue and subsequent complete re-issues of the manual are shown as version 1.0, 2.0, 3.0 etc.
Subsequent amendments for example, amendments 1, 2 and 3 are shown as version 1.1, 1.2 and 1.3; or
2.1, 2.2 and 2.3.
Amendments are summarised in the Revision History . The List of Effective Pages shows which pages have
changed.
Revision History
Foreword
The Office of Housing constructs a significant number of properties each year for the use of public and
community housing. The Construction Standards outline the level of amenity required for new Office of
Housing properties and provides the policy framework for Office of Housing construction, redevelopment, and
design and construct activities.
The standards provide, where topography and location allow, a level of adaptability to enable access and
provide amenity for clients with a disability, including those in a wheelchair, and to facilitate modification if
required in the future.
The Construction Standards have been developed in order to meet legal and Office of Housing and reflect best
practice in the low cost housing construction industry in recognition of the need to achieve maximum benefit
from available funds.
Director of Housing
1. Purchase Standards
2. Construction Standards
3. Reletting Standards
4. Maintenance Standards
5. Improvement Standards
7. Leasing Standards
8. Disposal Standards
9. Product Standards
Symbols and The Construction Standards have been developed using the following
series of symbols for reference and explanatory notes designed to help
Legend clarify the contents.
References
Explanatory notes
The explanatory notes symbol describes the decision making rationale
behind particular policy positions.
The Health and Safety symbol refers to items regarded by the OoH
as necessary to satisfy health and safety requirements.
The Supplied Item symbol refers to items that are subject to an OoH
SI forward purchase agreement with suppliers and which are available for
purchase by the OoH or the contractor, as applicable.
Purpose The purpose of this policy is to set out the Office of Housing (OoH)
requirements for the construction of public housing dwellings.
The Construction Standards are not retrospective and do not apply to the
existing OoH stock portfolio constructed or acquired prior to the approval
of these Standards.
Term Definition
Accessible Means able to be safely entered and exited without obstruction by people
with a disability including those who use a wheelchair.
Community Housing Means those properties which are the responsibility of the Community
Housing Group (not rental general stock) and are typically refuges,
transitional housing, rooming house accommodation and longer term
accommodation including supported accommodation.
Community Residential Units Means those domestic scale properties housing not more than six
residents where 24-hour on site support or care staff are employed to
assist residents in their daily activities.
Dividing fence Means a fence separating the lands of the OoH and other occupiers
(including OoH/OoH properties).
Dwelling Means a place of residence used for domestic activities, but does not
include any land associated with the dwelling.
Habitable room Means a room used for normal domestic activities, and
includes a bedroom, living room, kitchen, dining room, sewing room
BCA 1996 and family room, but
excludes a bathroom, laundry, water closet, pantry, walk in wardrobe,
corridor, hallway, lobby or other specialised spaces occupied neither
frequently nor for extended periods.
House and land packages Means dwellings offered to the OoH as part of a house and land package.
VPP 1996
Legal requirements Means all applicable statutory, regulatory and code requirements.
Modified housing Means housing purpose-built or upgraded to cater for people with specific
housing needs to enable them to participate to the degree that they are
able in normal domestic activities.
Multi-storey housing Means a building of more than two storeys containing two or more sole
occupancy units, including flats and apartments, each being a separate
dwelling.
Office of Housing requirements Means those particular policy provisions or standards requirements of the
OoH as described in this manual.
Public open space Means public thoroughfares, parks, roads, lanes and walkways or
corridors on housing developments, but does not include the private
front, rear and side yards belonging to the same dwelling or block.
Reputable manufacture Means the product or item has been manufactured and established in the
industry for at least three years and known to be free from defects.
Residential zone Means Residential zoned land use such as Residential 1, 2, Low Density
Residential, Mixed Use and Township Zones as determined by the Minister
for Planning and Local Government.
Responsible officer (RO) Means the officer (Housing Services Officer or others) responsible or
delegated for the task being described.
Rooming house Means a Boarding House as classified in the Building Code of Australia
which is a residential building that is a common place of residence for a
number of unrelated persons.
BCA 1996
Single dwelling Means a detached house or one or more attached dwellings, each being a
building separated by a fire-resisting wall.
Special needs Means the particular amenity provisions required by a client with a
disability as determined by an appropriate health professional, in addition
to, or in lieu of, those general amenity standards provided by the OoH.
Spot purchase Means the purchase of property on the open real estate market.
Water efficient appliances Means an acceptable level of water efficiency as defined by Standards
Australia.
SAA MP64 1995
Role/Title Responsibility
Director, Policy, Strategy & Approves minor amendments to Standards Policy required for the
Communications maintenance, clarification and/or editing of Housing Standards;
Manager Asset Policy Updates the Housing Standards Policy Manual; and
L
Additionally, the design of dwellings should allow for future
modifications, including full wheelchair accessibility, without
the need for extensive structural work except where the
AS4299 1995
topography of the land or the type of housing, for example,
some multi-level or medium density developments, precludes
this.
Energy Efficiency All new dwellings should be designed to achieve a six star
rating as determined using the FirstRate House Energy Rating
software or Sustainable Energy Authority of Victoria approved
equivalent, with a solar water heater installed. E
When designing dwellings a number of elements to consider to
achieve energy efficiency objectives include:
Design and All new dwellings shall be of cavity construction, solid brick or
brick veneer, with concrete slab on ground and truss roof
Construction construction wherever practicable.
Community Housing
Lighting
Locks The OoH provides locks to secure all external doors and
other devices to secure all windows.
Fire Risk All OoH fire risk management activities shall comply with
the Department of Human Services Capital Development
Management Guidelines for Fire Risk Management and the guidelines
for specific occupancy types such as single dwellings,
multi-storey housing and boarding houses, plus any
FRMG additional provisions required by regulation, code, statute
and these standards.
Termite protection
Ground Works
Termite protection of either stone chip barrier or a stainless
steel mesh is to be provided to properties considered at risk
from subterranean termites.
AS3660.1 1995
Note: Due to environmental and re-application
considerations, chemical treatments such as organo-
phosphates shall not be used for termite protection.
A durable notice shall be permanently affixed in the meter box
detailing the method of termite protection provided to the
property, date of installation and the manufacturer's
BCA 1996 recommendations for the scope and frequency of inspections.
Property numbering
External Areas
Property numbering that is clearly visible from the street is
required for all properties and is to be affixed to the mailbox,
the front security door, or (where doors are set back from
view) the front of the dwelling.
Multi-unit dwellings
Within a housing development, street names with dwelling
numbers are required at each intersection. Signage should
AS4299 1995
comply with the requirements of AS4299, Australian Standard,
Adaptable Housing. L
Mailboxes
AS4299 1995
adjacent to the junction of the footpath and the driveway).
The mailbox shall be front-opening, mounted at an accessible L
height between 800 and 1100 mm above ground level and in
accordance with the requirements of the local post office.
Car parking
Multi-unit dwellings
A car parking space to cater for residents with a wheelchair
shall be provided for each potentially accessible unit in
accordance with AS2890.1, Australian Standard, Parking
facilities.
AS2890.1 1993
Car parking shall be designed to ensure a continuous path of
travel from the vehicle parking area to the front entry of each
L
unit in accordance with AS1428.1, Australian Standard, Design
AS1428.1 1998 for access and mobility.
Where practicable, a clear line of sight from a well-lit vehicle
drop-off point to a safe pedestrian entry point should be
provided.
Car washing facilities
Balustrades
Main entries
AS4299 1995
A level, slip-resistant, hard-surfaced landing area, a minimum
of 1550 x 1550 mm, shall be provided at each entrance of the
L
dwelling.
The main front entry and, where practicable, rear entry of all
potentially accessible dwellings shall be wheelchair accessible.
Where a rear or side entry requires steps, the entry shall be
designed to have the capability to incorporate a ramp as
detailed above, if required in the future.
Ramps, where required, shall have an unobstructed minimum
AS1428.1 1998
width of 1000 mm and a maximum gradient of 1:14
constructed in accordance with AS1428.1, Australian Standard,
Design for access and mobility.
Garden lockers
Rear Yard
Each dwelling with private open space shall be provided with
Amenities storage for commonly used garden utensils.
Note: The OoH does not provide padlocks or other locks for
garden lockers of cupboards.
Clotheslines
Multi-level dwellings
Rubbish disposal
Where the front and rear yards of a property are not externally
accessible to each other (without passing through the dwelling) a
rubbish bin enclosure shall be provided adjacent to the street.
Garden taps
Living area
Living room sizes shall approximate, but be no less than:
for a one bedroom dwelling 13m2
for a two bedroom dwelling 15m2
for a three bedroom dwelling 17m2
AS4299 1995
for a four bedroom dwelling 19m2
AS1428.1 1998 for a five or more bedroom dwelling 21m2
Bedrooms
Bedrooms shall not be accessed directly from another bedroom,
kitchen or utility area.
As the bedrooms in family dwellings are required to be able to
accommodate two residents, all bedrooms shall approximate but be
no less than 11m2.
Note: Each bedroom shall be able to be furnished with two single
beds (2000 mm long x 900 mm wide), two bedside tables
and one chair plus either one dressing table or one writing
desk.
In all potentially accessible dwellings one bedroom shall be no less
than 13m2 with a minimum width of 3200 mm in order to provide
sufficient circulation space for a resident in a wheelchair.
The bedroom may not comply with AS4299 or AS1428.1 but, within
the limits of an area of 13m2 to 14m2, be designed to optimise
wheelchair access and provide space for either two single beds or
one standard double bed.
This bedroom shall be located on the ground floor to facilitate
access to the bathroom and living areas.
Note: Lockable doors to bedrooms are not preferred as they limit
use of doors as a means of egress in the case of fire or
other emergency.
A full height built-in wardrobe (minimum 1800 mm wide x 600 mm
deep) with hanging rod, shelves, four-drawer insert and
doors shall be provided in each bedroom.
Note: Built-in wardrobes are to be included in the calculation of
the minimum bedroom sizes.
Storage
Separate cupboards for the storage of linen and cleaning utensils
(linen cupboard and broom cupboard) shall be provided to all
dwellings. The minimum dimensions for each cupboard shall be
650 mm wide x 450 mm deep x 2000 mm high.
Skylights
Skylights are not to be used to provide the only source of natural
light to habitable rooms, except kitchens where unavoidable.
Where provided, skylights shall be installed with a translucent E
diffuser panel at ceiling level unless the skylight itself is double
glazed.
Skylights are not preferred in bedrooms or living areas.
AS4299 1995
household) shall be provided, the surface of which shall be suitable
for the preparation of food. At a minimum, a work bench of 800
L
mm in length shall be located adjacent to the oven, or cooktop,
and to the refrigerator space.
Refrigerator space
All sinks, cooktops and work benches shall have a 300 mm high
AG 601 1995
impervious splash back (preferably ceramic tiling).
Sinks
Bathroom
date.
L
The total area of the accessible bathroom and toilet, when
combined, shall be a minimum of 6.5m 2 with a configuration to
allow sufficient circulation space for a resident in a wheelchair in
accordance with AS4299, Australian Standard, Adaptable housing.
The bathroom in family dwellings shall have a walk-in shower recess
(i.e. with shower base with lip installed at floor level) and shower
Grabrails
In potentially accessible dwellings with framed walls, reinforced
areas for the subsequent installation of grabrails shall be provided
AS4299 1995 in the bathroom, shower recess and toilet in accordance with
AS4299, Australian Standard, Adaptable Housing.
Laundry
A room with laundry facilities shall be provided to every dwelling.
A laundry cupboard is sufficient for one bedroom units.
Multi-unit dwellings
Each unit shall be provided with individual laundry facilities located
within the dwelling.
Aluminium windows are required to be used wherever practicable.
Windows Consideration shall be given to window frame design to minimise
heat loss and gain.
BCA 1996
Fixed vents shall be provided to windows in toilets and bathrooms.
Note: Louvre windows shall not be used.
E
AS4299 1995
located at an accessible height for ease of use by the resident. L
Whilst meeting the BCA requirements for the provision of light
and ventilation and allowing for a resident to clean windows
BCA 1996 from the inside, window openings in dwellings greater than
two storeys in height shall be permanently restricted to a
maximum of 125 mm.
Window furnishings
Internal Holland blinds shall be provided to the windows of all
habitable rooms and bathrooms that do not have obscure
glazing.
E
Boxed pelmets extending beyond the window frame to allow
for curtains to be drawn completely away from the glazed area
together with curtain rod brackets shall be provided to the
window surrounds in all habitable rooms.
Flywire screens
Metal flywire screens are required to one openable window per
room and to all fixed vents.
Multi-storey dwellings
All doors (other than the doors of a dwelling) on an exit or
escape path shall be readily openable without a key (at all
times) by a single handed single action from the side that
FRMG
faces a person exiting the building.
Weather seals
All external entry doors shall be draught free and include
weather seal protection to the bottom of the door.
Note: Weather seal protection means a draught excluding
device fitted to the bottom of the door. E
Security and flywire doors
AS2804.1 1995 Security doors are provided to the main front entry only of all
dwellings. Ps
Note: A security door may be provided to the rear entry when
the rear yard is not fenced and enclosed from public SI
open space.
Security doors are not provided to sleepouts that are in an
enclosed yard. However, peepholes may be provided.
Half panel steel flywire doors
A steel half panel flywire door shall be provided to the rear
entry of all dwellings.
Ps
Note: The half panel steel flywire door is a derivative of the
security door. The lower half of the door is sheet metal and SI
the door has no locks but a snib on the inside.
Internal doors
Internal doors shall be flush panel doors with a honeycomb
Ps
AS2688 1984
core and hardboard facings. Hinged doors are preferred
except in potentially accessible dwellings where, to provide
adequate access or circulation space, a cavity or surface-
mounted sliding door is required. All doors shall be fitted with
door stops.
All internal doors shall be a minimum of 920 mm wide.
Note: An 920 mm wide door should give a clear door
opening of 820 mm. L
AS4299 1995
AS4145.2 1993
Entry doors (front and rear) are required to be fitted with good
quality dead locks that are key operated externally and Ps
openable without a key from the inside.
Window latches
Carpets
Floor Finishes
Provide hard-wearing domestic polypropylene carpet and
underlay to the main living room, bedrooms and corridors of all Ps
dwellings.
High Rise buildings with:
FRMG Solution Dyed Nylon (SDN) carpet shall be provided with
either Bridgestone Airstep Black Comfort rubber
underlay.
SI
Vinyl
General
Water
All dwellings shall have hot and cold water to sinks, basins,
BCA 1996 baths, showers, troughs and washing machine taps.
A garden tap shall be provided to the rear and, where
appropriate, to the front of all dwellings with private open space
or as required by town planning requirements.
Where mains water is not available, water tanks are to be
provided.
Shared water outlets shall be avoided and installed only to
communal areas.
Communal areas
Water for communal areas shall be provided via a separate
meter.
A garden tap (located in a public area) is required to the front
and rear of multi-unit blocks in order to service communal
landscaped areas and to provide car washing facilities to
common car parking areas.
Water pipes
Copper or polymer water pipes specified in AS3500, Australian
Standard, National plumbing and drainage may be used for
Gas
Natural gas shall be the prime source of energy for heating, hot
water and cooking for all dwellings where reticulated natural gas
is available.
E
AG 601 1995
In those areas where reticulated natural gas is not available, the
following sources of energy will be provided:
heating - off peak electricity;
domestic hot water - off peak electricity; and
cooking - day tariff electricity.
Telephone
All dwellings are required to have one telephone point located
either in the kitchen or living area, adjacent to a GPO.
AS4299 1995
Note: The OoH does not pay connection fees or provide
telephones.
Electrical Residual current devices (RCDs)
AS4299 1995
either 600 mm or, where appropriate, 900 to 1100 mm above
finished floor level (in line with the light switches) and not less
L
than 500 mm horizontally from internal corners.
AS4299 1995
bench tops with at least one GPO located within 300 mm of the
front of the bench.
L
In the bathroom the GPO shall be located adjacent to the
mirror.
As a minimum, all dwellings shall have the following electric
Lighting incandescent light outlets (light bulb type) and associated
switches mounted between 900 and 1100 mm above finished
floor level in line with and, where practical, adjacent to the door L
handles:
BCA 1996 AS4299 1995
Bedrooms 1
Living room 2
Dining room (meals area) 1
Corridor/passageway as required
Kitchen 2
Bathroom 1
Laundry 1
Toilet 1
Note: In two or more storey dwellings a two-way light switch
shall be fitted to stair lights.
All dwellings shall have the following electric incandescent light
outlets and fittings:
Front entrance, external 1
Rear entrance, external 1
AS4299 1995
Each dwelling shall have the potential to increase the
illumination level to a minimum of 300 lux if required at a later
L
date.
Multi unit dwellings
In multi-unit developments vandal proof security lighting shall
be provided to those communal areas that are used by different
households and the public such as car parks, pathways, foyers,
stairwells and communal facilities.
Where practicable, energy efficient light fittings, for example
compact fluorescent globes, shall be used.
E
Pathway lighting should be positioned at a low height to reduce
AS4299 1995 glare and provide a minimum illumination level of 50 lux at
ground level.
AS4299
located in a safe and accessible position for ease of use. L
1995
Stoves
Family dwellings (i.e. with two or more bedrooms) shall be
BCA 1996
provided with an upright 4-burner stove complete with a griller
and oven.
Ps
The stove shall be located at least 450 mm from any corner of a
room or doorway, with sufficient clearance provided to facilitate
cleaning and shall be securely attached to the floor at the rear to
SI
AS4299 1995
at the side or front of the cooktop and shall have raised cross
bars for ease of grip.
L
Where gas ovens are provided in buildings more than 3 storeys,
i.e. where sprinklers are to be installed, cook tops will be
provided with gas cut-off devices in case of fire.
Heating
Ps
All dwellings shall be provided with an efficient space heater of
sufficient size to heat the main living area. A rear register to an SI
adjacent living area may be installed where practicable.
FRMG A minimum standard of 4 stars for all gas space heaters is
required with preference being given to heaters with a higher
E
rating.
Note: Ducted central heating is not a preferred option due to
BCA 1996 fire spread and operating cost issues.
PSR 1998
not be used, however, continuous flow gas systems with
a minimum rating of 4 stars may be used where the
E
installation of storage units is not practical.
Hot water supply systems shall comply with the requirements of
the Plumbing Standards Regulations 1998, Part 4 - Hot water
PSR 1998 supply systems.
Performance Requirement
Hot water reticulation shall be capable of delivering hot water to
the bathroom(s) at less than 50oC and simultaneously to the
other wet areas at the temperature recommended by the
Fixed ventilation
Fixed ventilation in walls is not required.
Rangehoods
A rangehood, ducted and vented externally wherever
AS2682 1984
practicable, shall be provided to the kitchen over the cooktop. Ps
Note: Recirculating rangehoods should not be used, except
where the installation of a flued rangehood is
impractical.
Taps
AS4299 1995
Kitchen, laundry and bathroom taps shall have lever type or
capstan style handles with a single outlet for ease of use.
L
Singles and family dwellings
Television
One TV aerial point complete with a cable to the roof shall be
provided in the living area of each dwelling.
Smoke alarms
Ionisation type
Photo-electric type
Multi-storey dwellings
Multi-storey dwellings
Fencing The OoH contributes to the erection and repair of dividing fences in
accordance with the Fences Act 1968.
FA 1968
Note: Owners of adjoining land are required to contribute 50% of
the cost of standard fencing where fencing work is carried
out in accordance with the Fences Act 1968.
Front fencing
Boundary fencing
Family dwellings
Private enclosed space, with boundary fencing to the rear and sides
of the property, shall be provided in accordance with municipal
BR 1994
planning requirements and the Building Regulations 1994.
General
Landscaping
Low maintenance landscape works shall be provided to protect any
existing plants and incorporate appropriate tree planting.
Consideration shall be given to:
The following additional standards shall apply to the construction of dwellings for singles and
older persons.
Accommodation Type
General
One bedroom units are preferred by the OoH for the
accommodation of singles and older persons; the construction of
bedsitters is not a preferred option.
Car parking
External Areas
Off-street car parking for older persons units shall be provided as
follows:
Country regions - one car space per 2.5 dwellings.
Metropolitan regions - one car space per 3 dwellings.
For singles units, off-street car parking for one car per dwelling
shall be provided.
Car park layout and design should comply with applicable Rescode
Practice Notes for Car Parking.
Rescode
Sufficient space shall be allowed to provide, if required, hard-
surfaced, level (i.e. a maximum gradient of 1:40) car parking
spaces to cater for residents with a wheelchair in accordance with
AS2890.1 1993 AS2890.1, Australian Standard, Parking facilities.
Provide either a suitably located and drained car washing area with
AS1428.1 1998 water tap or, where appropriate, water taps located adjacent to the
common car parking areas.
Wheelchair access
roadways.
All paving and finishes on ramps, pathways and landings shall have
a slip-resistant surface with a texture easily traversable by a
AS1428.1 1998 wheelchair and gradients in accordance with AS1428.1, Australian
Standard, Design for access and mobility.
Main entries
The main front entrance and rear entrances shall be ramped where
required with a level, slip-resistant, hard-surfaced landing area, a
L
minimum of 1550 x 1550 mm, at both entrances. Ramps shall
AS1428.1 1998 have an unobstructed minimum width of 1000 mm, a maximum
gradient of 1:14 and a handrail(s) in accordance with AS1428.1,
Australian Standard, Design for access and mobility.
Where an entry requires steps, the entry shall be designed to have
the capability to incorporate a ramp, as detailed above, if required
in the future.
External landings shall be level (maximum gradient of 1:40) with a
low threshold to exclude water and allow for the smooth transition
AS4299 1995 of a wheelchair in compliance with AS4299, Australian Standard,
Adaptable housing.
Note: The OoH does not provide padlocks or other locks for garden
lockers of cupboards.
Clotheslines
Living areas
Internal Areas
The living room of singles and older persons dwellings shall
approximate, but be no less than, 13m2.
AS4299 1995
Corridors shall be a minimum of 1000 mm wide. Door approaches
AS1428.1 1998 shall comply with AS1428.1, Australian Standard, Design for access
and mobility.
To facilitate access and to provide sufficient circulation space to
manoeuvre a wheelchair, an open plan design and minimum use of
corridors may be adopted without substantially increasing the overall
size of the dwelling.
Meals area
The meals area in singles and older persons dwellings shall
approximate, but be no less than, 7m2.
Bedrooms
Bedrooms shall not be accessed directly from another bedroom,
kitchen or utility area.
A full height built-in wardrobe (minimum 1800 mm wide x 600 mm
deep) with hanging rod, shelves and four-drawer insert shall be
provided in each bedroom.
Note: Built-in wardrobes are to be included in the calculation of the
minimum bedroom sizes.
Bi-fold or sliding doors may be fitted to the built-in wardrobe where
circulation space is limited.
2nd bedroom
The second bedroom, where provided, shall approximate, but be
no less than, 9m2 with a minimum width of 2700 mm.
Storage
Shelving in storage units such as wardrobes, cupboards and open
shelving throughout the dwelling shall be at an accessible height
and depth in accordance with AS1428.2, Australian Standard,
L
AS1428.2 1992
Design for access and mobility.
AS1428.2 1992
Rods and hooks in wardrobes shall be a maximum of 1350 mm
from finished floor level in accordance with AS1428.2, Australian L
Standard, Design for access and mobility.
Ensure the floors of wardrobes and other cupboards are continuous
with the adjoining floor and have a clear accessible width of 760
mm to provide ease of use by a resident in a wheelchair.
Sliding cupboard doors are preferred where practicable.
Kitchen
Utility Areas
The kitchen area shall have a minimum width of 2700 mm to allow
sufficient circulation space for a client in a wheelchair to approach
AS4299 1995 all appliances and cupboards in accordance with AS4299, Australian
Standard, Adaptable housing.
Note: A 2700 mm width will provide 1550 mm clearance between
cupboards to both walls.
AS4299 1995
household) shall be provided, the surface of which shall be suitable
for the preparation of food. A work bench a minimum of 800 mm
L
in length, where space permits, shall be located adjacent to the
refrigerator space and the cooktop.
Work benches in singles and older persons dwellings shall be post-
formed to minimise accidents.
Refrigerator space
A minimum 1800 mm high x 900 mm wide x 650 mm deep space is
required for a refrigerator.
Sinks
A single bowl stainless steel sink with single drainer or, where space
permits, a 1 centre bowl stainless steel sink with single drainer, shall
be provided to all singles and older persons dwellings. The depth of
AS4299 1995 the single or main sink bowl shall be a maximum of 150 mm.
Bathroom
Singles and older persons dwellings shall be provided with a combined
bathroom, laundry and toilet. In addition to the common
requirements for bathrooms outlined in section 2.6, each combined
L
bathroom, laundry and toilet shall contain a stepless shower.
The combined bathroom, laundry and toilet shall be a minimum of
7.4m2 in size with a configuration to allow sufficient circulation space
for a resident in a wheelchair.
AS4299 1995
Wherever practicable, sanitary plumbing shall be concealed.
Stepless shower
AS4299 1995
Provide a shower area of 1100 mm x 1160 mm without steps or kerbs,
its base graded into a waste with a slope of not less than 1:60 and not
greater than 1:40. The remainder of the bathroom area shall be
SAA MP64 1995 graded with a fall to the shower waste (or an alternate floor waste) at
AS1428.1 1998 a minimum gradient of 1:100.
Provide, as a minimum, an A rated water saving shower handset for all
mains pressure hot water systems, with a AAA to be preferred should E
water pressure allow, with flexible heavy duty hose and bracket
AS3740 1994 together with a shower seat and grabrail located within the shower
area, installed in accordance with AS1428.1, Australian Standard,
L
Design for access and mobility.
The shower taps and controls shall be accessible from outside the
shower area with the water stream directed away from the shower
entrance.
The shower area (and surrounding area where required) shall be
waterproofed in accordance with AS3740 , Australian Standard,
Waterproofing of wet areas within residential buildings . Where
provided, ceramic tiling shall extend to a height of 1800 mm above
finished floor level.
Provide an aluminium shower rail to enable a curtain to fully enclose
the shower compartment.
Note: The OoH does not provide shower curtains.
The soap holder for the shower shall be fully recessed and located
between 900 and 1100 mm above finished floor level.
Toilet facilities
BCA 1996
action or enlarged push button flushing control located between 800
and 1100 mm above finished floor level. The WC pan shall be
E
connected to a public sewerage system or a septic tank system
approved by the relevant authority.
SAA MP64 1995
A grabrail fixed to the building structure and located adjacent to the
WC pan.
A toilet paper dispenser located adjacent to the WC pan.
Laundry facilities
Laundry facilities located within the combined bathroom, laundry and
toilet shall include the following:
a stainless steel laundry trough with a 200 mm high impervious
splash back (preferably ceramic tiling), hot and cold water taps, an
overflow suds bypass and washing machine waste outlet;
space for a washing machine (900 wide mm x 600 mm deep)
adjacent to the trough with hot and cold washing machine taps
located so that either a front or top loading washing machine may
be installed;
a visible horizontal timber batten mounted 1800 mm above finished
floor level and located above the washing machine to provide a
secure support for a clothes dryer; and
a cupboard with minimum dimensions of 450 mm wide x 450 mm
deep x 2000 mm high.
Note: The OoH does not provide washing machines or clothes dryers
to individual dwellings.
Safety and
Support Features
Grabrails L
Stainless steel grabrails fixed to the building structure (reinforced
areas as outlined below) shall be provided in the combined bathroom,
laundry and toilet adjacent to the WC pan and in the shower recess in
AS1428.1 1998
accordance with AS1428.1, Australian Standard, Design for access and
mobility.
Note: A grabrail is a rail used to provide a steadying or stabilising
assistance to a person engaged in a particular function.
Towel rails shall be of a similar strength to grabrails unless their
appearance is quite distinct to that of the grabrail(s).
In dwellings with framed walls reinforced areas for the subsequent
installation of additional grabrails shall be provided in the bathroom
AS4299 1995
in accordance with AS4299, Australian Standard, Adaptable Housing.
External awnings
Locks
All entry doors are required to be keyed alike.
Ceramic tiles
Provide slip-resistant ceramic tiles to the combined bathroom,
AS2055.1 1985 laundry and toilet floor, including the shower recess, extending to
a height of 150 mm above finished floor level.
Fencing Private enclosed space to single storey singles and older persons
dwellings is required to the rear area only and shall be provided
in accordance with municipal planning requirements and the
Building Regulations 1994 . The preference for rear area fencing
BR 1994 is timber paling, 1650 mm nominal height from the ground.
Private open spaces are for the use of individual tenants and
are to be maintained by the tenants.
Construction
Movable units are self-contained, approximately 40m 2 in size
and comprise a bedroom, living area, kitchenette and an
ensuite bathroom. Movable units are temporary buildings, of
demountable construction and externally clad with fibre
cement sheeting. The roofing is metal sheeting and the
internal walls are lined with plasterboard, cement sheeting or
plywood panelling.
Disability modifications
Access and minor modifications, such as ramps, handrails and
additional grabrails may be readily made to movable units for
clients who have a disability. However, due to the nature of
construction of the movable units, only non-structural
modifications can be made.
Other modifications of a minor nature which may be made to
movable units include those for clients with a hearing
impairment and any other modifications outlined in Chapter 10
HSPM Ch. 10
of this manual which do not necessitate structural work to the
unit.
Note: Timber ramps are preferred due to the temporary nature
of moveable units.
External Areas Moveable units shall be located as close as practicable to the
main dwelling and existing services.
Paving
Where the main dwelling is privately owned, provide a
600x600mm concrete paver pathway from the rear door of the
main dwelling to the moveable unit.
Where the main dwelling is an OoH property, provide a
continuous, accessible, hard-surfaced pathway with an
AS4299 1995 unobstructed width of 1000 mm and a maximum gradient of
1:14 from the main dwelling to the movable unit.
All paving and finishes on ramps, pathways and landings
shall have a slip-resistant surface with a texture easily
AS1428.1 1998 traversable by a wheelchair and gradients in accordance
with AS1428.1, Australian Standard, Design for access and
mobility.
Steps and stairs
The configuration of steps to movable units shall comply
with AS1428.2, Australian Standard, Design for access and
L
AS1428.2 1992 mobility .
Note: Steps and stairs may be preferred to ramps by
some clients with a mobility disability such as
some who use a walking frame.
All paving and finishes on steps and stairs shall have a slip-
resistant surface.
Balustrades
A balustrade shall be provided to any stairway, ramp,
balcony, verandah or similar situation which is more than
600 mm above the adjacent floor or ground level in
BCA 1996 accordance with the requirements of the Building Code of
Australia.
Note: Any horizontal elements of the balustrade between
150 and 760 mm above the floor must not facilitate
climbing.
Entry
A roofed sheltered area immediately outside the front
entrance is required to all movable units.
The front entrance may be ramped where required with a
level, slip-resistant, hard-surfaced landing area with a
L
minimum area of 1550 x 1550 mm. Ramps shall have an
AS1428.1 1998 unobstructed minimum width of 1000 mm, a maximum
gradient of 1:14 and a handrail(s) in accordance with
AS1428.1, Australian Standard, Design for access and
mobility .
As movable units are temporary dwellings designed to be
demounted and relocated, consideration should be given
when constructing a ramp to its eventual removal. It is
preferred therefore that substantial concrete ramps are not
constructed.
External landings shall be level (maximum gradient of 1:40)
with a low threshold to exclude water and allow for the
AS4299 1995 smooth transition of a wheelchair in compliance with
AS4299, Australian Standard, Adaptable housing.
Internal Areas Bedroom
A full height built-in wardrobe (minimum 600 mm wide x
570 mm deep) with a hanging rod and shelves shall be
provided in each bedroom.
Bi-fold or sliding doors may be fitted to the built-in
wardrobe where circulation space is limited.
Storage
A cupboard for the storage of linen and cleaning utensils
(linen and broom cupboard) shall be provided to all units.
The minimum dimensions for each cupboard shall be 450
mm wide x 450 mm deep x 2000 mm high.
AS1428.2 1992
Shelving in storage units such as wardrobes, cupboards
and open shelving throughout the unit shall be at an L
accessible height and depth in accordance with AS1428.2,
Australian Standard, Design for access and mobility.
Rods and hooks in the wardrobe shall be a maximum of
1350 mm from finished floor level in accordance with
AS1428.2, Australian Standard, Design for access and
L
AS1428.2 1992 mobility.
Sliding cupboard doors may be provided where practicable.
AS4299 1995
The cooktop and, where practicable, the refrigerator shall
be located adjacent to a work bench which, where space
L
permits, shall be a minimum of 800 mm in length.
Refrigerator space
Splash backs
Sinks
AS4299 1995
where space permits, a 1 centre bowl stainless steel sink
with single drainer, shall be provided. The depth of the
L
single or main sink bowl shall be a maximum of 150 mm.
Ensuite bathroom
Toilet facilities
Laundry facilities
AS4299 1995
Window fittings that are easily gripped by the hand should
be located at an accessible height for ease of use by the
L
resident.
Window furnishings
Boxed pelmets extending beyond the window frame to
allow for curtains to be drawn completely away from the
glazed area together with curtain rod brackets shall be
provided to the window surrounds in all habitable rooms.
Flywire screens
External door
The external (entry) door shall be a flush panel solid door
AS2688 1984
with blockboard or particleboard core preferably without
glazed panels or sidelights. All external doors shall have Ps
three hinges and paint grade veneer door facings and shall
be fitted with door stops.
Weather seals
The external entry door shall be draught free and include
weather seal protection to the bottom of the door.
Internal doors
Internal doors shall be flush panel doors with a honeycomb
core and hardboard facings. Hinged doors are preferred
except where, to provide adequate access or circulation Ps
AS2688 1984 space, a cavity or surface-mounted sliding door is required.
All doors shall be fitted with door stops.
Door furniture
Fit lever type door handles operable with one hand that
L
AS1428.1 1998
comply with the requirements of AS1428.1, Australian
Standard, Design for access and mobility at a height of
between 900 and 1100 mm from finished floor level.
Window latches
Windows are to be secured by appropriate catches.
Floor Finishings Provide a continuous floor level throughout the unit with
special attention to areas where there is a change in floor
L
finish.
FRMG Carpets
Ps
Single, low level dwellings with polypropylene carpet shall
be provided with either Bridgestone rubber or Dunlop
SI
polyurethane underlay.
Note: The current supplied item carpet and underlay
comply with AS/NZS 2455 and AS 4288.
Vinyl
Slip-resistant sheet vinyl flooring with a 2 mm wear layer
AS2055.1 1985 (not including laminations, plastics and fibrous materials)
shall be provided to the kitchenette and the ensuite
bathroom.
Paintwork All paints used for the painting of movable units are
required to be Australian Paint Approval Scheme approved
materials.
For details of the latex (acrylic) systems and preparation
work required for internal and external paintwork, refer to
the relevant paragraphs in section 2.6 of this chapter.
E
and R1.5 batts to all other external walls.
R2.5 batts and reflective foil sarking under the roofing
material.
Note: Loose insulation material is not permitted.
Service connections are paid by the OoH up to an amount
Building Services set from time to time by the Director, Property Services &
Asset Management. The applicant is responsible for those R
service connection costs that exceed the limit.
Services separately metered
Where the main dwelling is an OoH property, electricity and
gas services to the movable unit shall be metered
AG 601 1995 separately to the main dwelling. A check meter shall be
installed for the water supply to the unit.
All meters are to be located so as not to impede pathways
and shall be accessible to meter readers.
Where the main dwelling is privately owned, the electricity
and gas services to the movable unit may be metered
separately or connected to the main dwelling supply, as
negotiated with the dwelling owner.
Water
All units shall have hot and cold water to sinks, basins,
showers, troughs and washing machine taps.
BCA 1996 Where the main dwelling is an OoH property and mains
water is not available, a water tank may be provided to the
movable unit.
Water pipes
AS3500 1998
in external exposed applications. Dead legs on hot water
pipes shall not exceed 2000 mm.
E
Gas
AG 601 1995
Unless the tenant requests otherwise, natural gas shall be
the prime source of energy for heating, hot water and E
cooking for all units where reticulated natural gas is
available.
In those areas where reticulated natural gas is not
available, either LPG gas shall be used for heating, hot
water and cooking or off peak electricity for domestic hot
water and day tariff electricity for heating and cooking.
Telephone
The tenant is responsible for the connection a telephone
service if required. However, conduit to facilitate its
connection is laid by the OoH.
Note: The OoH does not pay connection fees or provide
AS4299 1995
telephones.
Electrical Services Residual current devices
Switchboard type RCDs shall be provided to all general
power outlet and lighting circuits.
RCDs are not required to circuits for fixed electric cooking
appliances such as ranges, ovens or hotplates.
FRMG AS3000 2000
Power outlets
The following double general purpose outlets (GPOs) are
required:
Bedroom 2
Living area 3
Kitchenette 2
GPO for refrigerator 1
Ensuite bathroom 2
Note: The refrigerator GPO is to be easily reachable when
AS4299 1995 the refrigerator is in its operating position.
Each GPO shall be supplied with neon indicators and
mounted either 600 mm or, where appropriate, 900 to
1100 mm above finished floor level (in line with the light
AS4299 1995 switches) and not less than 500 mm horizontally from
internal corners.
Locate GPOs in the kitchen (for appliances) 300 mm above
bench tops with a least one GPO located within 300 mm of L
the front of the work bench.
AS4299 1995
One GPO in the bathroom shall be located adjacent to the L
mirror.
As a minimum, movable units are required to have the
Lighting following electric incandescent light outlets (light bulb type)
and associated switches mounted between 900 and 1100 mm
above finished floor level in line with and, where practical,
BCA 1996
adjacent to the door handles:
L
Bedroom 1
Living room 2
AS4299 1995
Kitchenette 1
Ensuite Bathroom 1
AS4299 1995
Front entrance, external 1
Each dwelling shall have the potential to increase the L
illumination level to a minimum of 300 lux if required at a
later date.
Appliances Controls on appliances should be easily gripped by the
hand and located in a safe and accessible position for ease L
of use.
AS4299 1995 Stoves
Provide an elevated stove, preferably gas where reticulated
natural gas is available, located at least 450 mm from any
corner of a room, cupboard or doorway with sufficient
SI
BCA 1996
clearance provided to facilitate cleaning and securely
attached at the rear to prevent tilting. A work bench shall
be adjacent to the cooktop and refrigerator.
The controls shall be located at the front of the stove and
either at the side or front of the cooktop and shall have
AS4299 1995 raised cross bars for ease of grip. Ps
Where gas ovens are provided in buildings more than 3
L
storeys, i.e. where sprinklers are to be installed, cook tops
will be provided with gas cut-off devices in case of fire.
Heating
All units shall be provided with an efficient space heater of
sufficient size to heat the living area. A minimum standard
of 4 stars for all gas space heaters is required with
SI
preference being given to heaters with a higher rating.
Individual heaters shall be fixed in position and be
Ps
BCA 1996
constructed, installed and guarded in accordance with
appropriate Australian Standards and the Building Code of
Australia.
E
Note: Due to relocation difficulties, electric night storage
heaters (heat banks) shall not be provided to
movable units.
Hot water units
Movable units shall have, as a minimum, a 90 litre gas or
160 litre off-peak electric hot water service. Ps
Hot water units shall be located as close as practicable to
the hot water outlets.
SI
Note: Instantaneous day rate electric hot water systems
shall not be used, however, continuous flow gas
systems with a minimum rating of 4 stars may be
used where the installation of storage units is not
practical.
Hot water supply systems shall comply with the
PSR 1998
requirements of the Plumbing Standards Regulations
1998, Part 4 - Hot Water Supply systems.
E
Performance Requirement
In constructing new movable units, or where major
PSR 1998
alterations are to be made to the bathroom, the hot water
reticulation shall deliver hot water to the bathroom and
kitchenette at less than 50o
Exhaust fans
Ventilation An exhaust fan shall be provided to the ensuite bathroom
BCA 1996 and in the kitchenette above the cooktop.
The fans shall be ducted, flued and discharged externally.
AS2681 1984 Fixed ventilation
Fixed ventilation in walls is not required.
Plumbing Taps
The kitchenette and ensuite bathroom taps shall have
AS4299 1995
lever type or capstan style handles with a single outlet for
ease of use.
L
Wherever practicable, sanitary plumbing shall be
concealed.
Fire Risk Management Fire risk management compliance shall be in accordance
with the requirements of the current edition of the
Department of Human Services Capital Development
FRMG Guidelines - Fire Risk Management Policy and Procedures,
Fire Risk Management Engineering Guidelines and the
guidelines for specific occupancy types, plus any
additional provisions required by regulation, code, statute
and these Standards.
Smoke alarms
Photoelectric type smoke alarms are required to all
movable units. All smoke alarms shall be connected to a
BCA 1996 mains powered lighting circuit and, where more than one
BCC, Practice Note 27, 1996
smoke alarm is provided, the smoke alarms shall be inter-
connected including, if required, to the main dwelling
Ps
AS3786 1993Smoke alarms shall be of
the sealed type, mains powered with a
rechargeable battery, test button and
with a minimum 5-year guarantee.
2.9 Sleepouts
The following standards shall apply to the construction of all new and, where practicable,
relocated sleepouts.
Sleepouts are provided to those public housing households
General who are eligible and who require additional, generally short
term, accommodation. Sleepouts are provided in lieu of
extending the existing house or relocating the household to
larger premises.
Construction
Disability modifications
Location
Sleepouts are required to be located as close as practicable to
the main dwelling and existing electrical services.
Consideration should be given to the orientation of a sleepout
in order to gain maximum protection of the entry from
prevailing weather.
E
Paving
External Areas
Where a pathway is required between the main dwelling and
the sleepout, provide pre-cast concrete paving blocks 600 mm
x 600 mm.
AS4299 1995
Window fittings that are easily gripped by the hand should be
located at an accessible height for ease of use by the resident. L
Note: Security screens such as roller shutter screens or bars
shall not be fitted to windows.
All glazing shall be in accordance with AS1288, Australian
AS1288 1994 Standard, Glass in buildings - Selection and installation.
Window furnishings
Boxed pelmets extending beyond the window frame to allow
for curtains to be drawn completely away from the glazed area
together with curtain rod brackets shall be provided to the
window surrounds in all habitable rooms.
E
Internal Holland blinds shall be provided to all windows of
sleepouts.
Flywire screens
Metal flywire screens are required to all fixed vents and to two
openable windows per sleepout for the purposes of cross-
ventilation.
External door
Doors
The external (entry) door shall be a flush panel solid door with
blockboard or particleboard core preferably without glazed
AS2688 1984 panels or sidelights. All external doors shall have three hinges Ps
and paint grade veneer door facings and shall be fitted with
door stops.
Door furniture
Window latches
Windows are to be secured by appropriate catches.
Note: The OoH does not provide keyed window locks as they
RTA 1997, s.70
limit use of the windows as a secondary means of
egress in the case of fire or other emergency.
Carpet
Floor Finishings
Single, low level dwellings with polypropylene carpet shall be Ps
provided with either Bridgestone rubber or Dunlop
FRMG
polyurethane underlay. SI
Note: The current supplied item carpet and underlay comply
with AS/NZS 2455 and AS 4288.
All paints used for the painting of sleepouts are required to be
Paintwork Australian Paint Approval Scheme approved materials.
Ps
For details of the latex (acrylic) systems and preparation work
HPSM Ch. 2 required for internal and external paintwork, refer to the
relevant paragraphs in section 2.6 of this chapter.
Insulation Ceiling, wall and roof insulation
SUBJECT:
Signed:
Requesting Officer
/ /
A Ceramic tiles, 25
Singles and OP dwellings, 43
Accessible Clothes dryers, 21
Definition, 2 Clotheslines, 15
Accessible dwellings Singles and OP dwellings, 37
Bathroom, 20 Communal open spaces, 33, 34
Bedroom, 17 Policy, 10
Car parking, 12 Community Housing
External doors, 22 Definition, 2
Internal doors, 24 Community residential unit
Kitchen, 18 Definition, 2
Laundry, 21 Construction
Living areas, 17 Definition, 2
Paving and pathways, 13 Corridors, 17
Policy, 6 Multi unit dwellings, 16
Stepless shower, 20 Singles and OP dwellings, 37
Visitable toilet, 19 Cupboards, 18
Amenity and Accessibility Movable units, 48
Policy, 6 Singles and OP dwellings, 39
Appliances
Heating, 29
Hot water units, 30
D
Movable units, 55 Definitions, 2
Singles and OP dwellings, 43 Design and construction
Sleepouts, 60 Policy, 7
Stoves, 29 Disability modifications
Awnings Movable units, 46
Movable units, 51 Sleepouts, 57
Singles and OP dwellings, 42 Dividing fence
Definition, 2
B Door furniture, 24
Movable units, 52
Balustrades, 14 Singles and OP dwellings, 42
Movable units, 47 Sleepouts, 59
Bathroom, 19 Door locks, 24
Fittings, 20 Movable units, 52
Movable units, 48 Singles and OP dwellings, 42
Singles and OP dwellings, 40 Sleepouts, 59
Bedrooms, 17 Doors, 22
Movable units, 47 Entry, 22
Singles and OP dwellings, 37 Entry, Movable units, 51
Bedsitters, 35 Entry, Singles and OP dwellings, 42
Building services, 26 Entry, Sleepouts, 58
Movable units, 53 Flywire, 23
Policy, 9 Flywire, Movable units, 51
Sleepouts, 60 Flywire, Sleepouts, 59
Internal, 23
C Internal, Movable units, 52
Internal, Singles and OP dwellings,
Car parking, 12 42
Singles and OP dwellings, 35 Locks, 24
Car washing facilities, 12 Movable units, 51
Singles and OP dwellings, 35 Security, 23
Carpets, 25 Security, Movable units, 51
Movable units, 52 Security, Sleepouts, 59
Sleepouts, 59 Singles and OP dwellings, 42
Carports and garages, 12 Sleepouts, 58