Você está na página 1de 39

RC Detailing to Eurocode 2

Jenny Burridge
MA CEng MICE MIStructE
Head of Structural Engineering

Structural Eurocodes

BS EN 1990 (EC0): Basis of structural design

BS EN 1991 (EC1): Actions on Structures

BS EN 1992 (EC2): Design of concrete structures

BS EN 1993 (EC3): Design of steel structures

BS EN 1994 (EC4): Design of composite steel and concrete structures

BS EN 1995 (EC5): Design of timber structures

BS EN 1996 (EC6): Design of masonry structures

BS EN 1999 (EC9): Design of aluminium structures

BS EN 1997 (EC7): Geotechnical design

BS EN 1998 (EC8): Design of structures for earthquake resistance


Eurocode 2 - contents

General
Basis of design
Materials
Durability and cover to reinforcement
Structural analysis
Ultimate limit state
Serviceability limit state
Detailing of reinforcement and prestressing tendons General
Detailing of member and particular rules
Additional rules for precast concrete elements and structures
Lightweight aggregated concrete structures
Plain and lightly reinforced concrete structures

Eurocode 2 - Annexes

A. (Informative) Modification of partial factors for materials


B. (Informative) Creep and shrinkage strain
C. (Normative) Reinforcement properties
D. (Informative) Detailed calculation method for prestressing steel
relaxation losses
E. (Informative) Indicative Strength Classes for durability
F. (Informative) Reinforcement expressions for in-plane stress
conditions
G. (Informative) Soil structure interaction
H. (Informative) Global second order effects in structures
I. (Informative) Analysis of flat slabs and shear walls
J. (Informative) Examples of regions with discontinuity in geometry or
action (Detailing rules for particular situations)

EC2 Annex J - replaced by Annex B in PD 6687


Standards
BS EN 13670
Execution of
Structures

N.A.
BS EN 206-1 NSCS
Specifying BS EN 1992
Concrete Design of concrete structures
BS EN 10080
Part 1-1: General & buildings Reinforcing
BS 8500 Part 1-2: Fire design Steels
Specifying
Part 2: Bridges
Concrete
Part 3: Liquid retaining BS 4449
Reinforcing
Steels

PD 6687-1 (Parts 1 & 3)


National Annex
PD 6687-2 ( Part 2) BS 8666
Reinforcement
Scheduling

Specification NSCS, Finishes

NSCS Guidance:
1 Basic
2 Ordinary
3 Plain
4 Special Visual Concrete
Labour and Material (Peri)

24%
58%

18%

Rationalisation of Reinforcement

Optimum cost depends


on:
Material cost
Labour
Plant
Preliminaries
Finance
Team decision required
Detailing

Reinforcement
Reinforcement

EC2 does not cover the use of plain or mild steel reinforcement

Principles and Rules are given for deformed bars, decoiled rods,
welded fabric and lattice girders.

EN 10080 provides the performance characteristics and testing methods


but does not specify the material properties. These are given in Annex
C of EC2

Properties of reinforcement
(Annex C)
Product form Bars and de-coiled rods Wire Fabrics

Class A B C A B C

Characteristic yield 400 to 600


strength fyk or f0,2k (MPa) cold worked hot rolled seismic

k = (ft/fy)k 1,05 1,08 1,15 1,05 1,08 1,15


<1,35 <1,35

Characteristic strain at 2,5 5,0 7,5 2,5 5,0 7,5


maximum force, uk (%)

Fatigue stress range


(N = 2 x 106) (MPa) with 150 100
an upper limit of 0.6fyk

The UK has chosen a maximum value of characteristic yield strength, fyk, = 600 MPa,
but 500 MPa is the value assumed in BS 4449 and 4483 for normal supply.
Extract BS 8666

www.ukcares.co.uk
www.uk-bar.org

UK CARES (Certification - Product & Companies)

1. Reinforcing bar and coil


2. Reinforcing fabric
3. Steel wire for direct use of for further
processing
4. Cut and bent reinforcement
5. Welding and prefabrication of reinforcing
steel
www.ukcares.co.uk
www.uk-bar.org

Reinforcement supply

Coil up to 16mm (2.5T)

Bar 12,14,15 and 18m

Cut and bent approx 550 to 650/T


Table power bender
Health & Safety

Potential Risk factor


High Risk
Low

Medium
33,51,56,63,64 & 99?
High

SC Detail Comment Designer Fabricator

33 Sausage Link. This shape is designed for See Note SN2.


Health and safety risk is high with producing small to medium Great care should be taken
larger diameter bar. sized links in small diameter when bending this shape. If
Also the risk increases with small bar. the operator has concerns
dimensions. Do not detail this shape in when producing this shape
When bent on an automatic link bender large diameter bar, try to he should consult his
with small diameter bars the risk is use an alternative (eg. 2 no. supervisor.
relatively low. When bending on a shape code 13s facing each
manual bender the risk is high, other to create a shape
especially with larger diameters and code 33).
non standard formers. See Note SN2.
64 Boot Link. Smaller diameter bars cause
Greater risk than shape code 51 as the less of a problem as they
bars have to cross over twice to can often be produced on
achieve the shape. an automatic link bending
Health and safety risk becomes higher machine. Larger diameter
with larger diameter bar. bars have to be produced on
Also the risk increases with small a manual power bender with
dimensions. the potential to trap the
See Note SN2. operators fingers. Try to
When bent on an automatic link bender avoid/minimise the use of
with small diameter bars the risk is shapes which cause a scissor
relatively low. When bending on a action, especially with
manual bender the risk is higher, larger diameter bars.
especially with larger diameters.

Bending

Minimum Bending & projections

Minimum Bends

6mm - 16mm = 2x Dia Internal

20mm - 50mm = 3.5x Dia Internal

Minimum of 4 x dia between bends

End Projection = 5 x Dia from end of bend


BS8666, Table 2
Tolerances (not in EC2BS8666)

Minimum Cover for Bond

For bars: Bar diameter

For post-tensioned tendons:

Circular ducts: Duct diameter

Rectangular ducts: The greater of:


the smaller dimension or
half the greater dimension

For pre-tensioned tendons:

1.5 x diameter of strand or wire


2.5 x diameter of indented wire
Structural Fire Design
BS EN 1992-1-2

Scope:
Part 1-2 Structural fire design gives several methods for fire engineering
Tabulated data for various elements is given in section 5

Reinforcement cover
Axis distance, a, to centre of bar
a = c + m/2 + l

Axis
a Distance

Allowance in Design for


Deviation

cdev: Allowance for deviation = 10mm

A reduction in cdev may be permitted:

for a quality assurance system, which includes measuring concrete


cover,
10 mm cdev 5 mm

where very accurate measurements are taken and non conforming


members are rejected (eg precast elements)
10 mm cdev 0 mm
Nominal Cover

Nominal cover, cnom

Minimum cover, cmin


cmin = max {cmin,b; cmin,dur ; 10 mm}

Allowance for deviation, cdev

Axis distance, a
Fire protection

Procurement

Lead-in times should be 4 weeks for rebar

Express reinforcement (and therefore expensive) 1 7 days

The more complicated the scheduling the longer for bending


Standard Detailing

Practicalities
12m maximum length H20 to H40
(12m H40 = 18 stone/ 118Kg)
Health & safety
9m maximum length H16 & H12
6m maximum length H10 & H8
Transport
Fixing

Control of Cracking
EC2: Cl. 7.3

In Eurocode 2 cracking is controlled in the following ways:

Minimum areas of reinforcement cl 7.3.2 & Equ 7.1

As,mins = kckfct,effAct this is the same as

Crack width limits (Cl. 7.3.1 and National Annex). These


limits can be met by either:

direct calculation (Cl. 7.3.4) crack width is Wk Used


for liquid retaining structures

deemed to satisfy rules (Cl. 7.3.3)


Note: slabs 200mm depth are OK if As,min is provided.
Minimum Reinforcement Area
EC2: Cl. 9.2.1.1, Eq 9.1N

The minimum area of reinforcement for slabs (and beams) is given by:

0.26 fctm bt d
A s,min 0.0013 b t d
fyk

Crack Control Without Direct


Calculation EC2: Cl. 7.3.3

Provide minimum reinforcement.


Crack control may be achieved in two ways:
limiting the maximum bar diameter using Table 7.2N
limiting the maximum bar spacing using Table 7.3N

Note: For cracking due to restraint use only max bar size
Spacing of bars
EC2: Cl. 8.2

Clear horizontal and vertical distance , (dg +5mm) or 20mm

For separate horizontal layers the bars in each layer should be


located vertically above each other. There should be room to allow
access for vibrators and good compaction of concrete.

Ultimate bond stress


EC2: Cl. 8.4.2
The design value of the ultimate bond stress, fbd = 2.25 12fctd
where fctd should be limited to C60/75
1 =1 for good and 0.7 for poor bond conditions
2 = 1 for 32, otherwise (132- )/100
Direction of concreting Direction of concreting

250

a) 45 90 c) h > 250 mm
Direction of concreting
Direction of concreting

300
h h

b) h 250 mm d) h > 600 mm


unhatched zone good bond conditions
hatched zone - poor bond conditions
Basic required anchorage length
EC2: Cl. 8.4.3

lb,rqd = ( / 4) (sd / fbd)

where sd is the design stress of the bar at the position


from where the anchorage is measured.

For bent bars lb,rqd should be measured along the


centreline of the bar

Design Anchorage Length, lbd


EC2: Cl. 8.4.4

lbd = 1 2 3 4 5 lb,rqd lb,min

However:
(2 3 5) 0.7
lb,min > max(0.3lb,rqd ; 10, 100mm)
Alpha values
EC2: Table 8.2

Table 8.2 - Cd & K factors


EC2: Figure 8.3

EC2: Figure 8.4


Anchorage of links
EC2: Cl. 8.5

Design Lap Length, l0 (8.7.3)


EC2: Cl. 8.7.3

l0 = 1 2 3 5 6 lb,rqd l0,min

1 2 3 5 are as defined for anchorage length

6 = (1/25)0,5 but between 1.0 and 1.5


where 1 is the % of reinforcement lapped within 0.65l0 from the
centre of the lap

Percentage of lapped bars < 25% 33% 50% >50%


relative to the total cross-
section area
6 1 1.15 1.4 1.5
Note: Intermediate values may be determined by interpolation.

l0,min max{0.3 6 lb,rqd; 15; 200}


Worked example

Anchorage and lap lengths

Anchorage Worked Example

Calculate the tension anchorage for an H16 bar in the


bottom of a slab:
a) Straight bars
b) Other shape bars (Fig 8.1 b, c and d)

Concrete strength class is C25/30


Nominal cover is 25mm
Bond stress, fbd
fbd = 2.25 1 2 fctd EC2 Equ. 8.2
1 = 1.0 Good bond conditions
2 = 1.0 bar size 32
fctd = ct fctk,0,05/c EC2 cl 3.1.6(2), Equ 3.16
ct = 1.0 c = 1.5
fctk,0,05 = 0.7 x 0.3 fck2/3 EC2 Table 3.1
= 0.21 x 252/3
= 1.8 MPa
fctd = ct fctk,0,05/c = 1.8/1.5 = 1.2

 fbd = 2.25 x 1.2 = 2.7 MPa

Basic anchorage length, lb,req

lb.req = (/4) ( sd/fbd) EC2 Equ 8.3


Max stress in the bar, sd = fyk/s = 500/1.15
= 435MPa.
lb.req = (/4) ( 435/2.7)
= 40.3
For concrete class C25/30
Design anchorage length, lbd

lbd = 1 2 3 4 5 lb.req lb,min


lbd = 1 2 3 4 5 (40.3) For concrete class C25/30

Alpha values
EC2: Table 8.2 Concise: 11.4.2
Table 8.2 - Cd & K factors
EC2: Figure 8.3 Concise: Figure 11.3

EC2: Figure 8.4

Design anchorage length, lbd


lbd = 1 2 3 4 5 lb.req lb,min
lbd = 1 2 3 4 5 (40.3) For concrete class C25/30
a) Tension anchorage straight bar
1 = 1.0
3 = 1.0 conservative value with K= 0
4 = 1.0 N/A
5 = 1.0 conservative value
2 = 1.0 0.15 (cd )/
2 = 1.0 0.15 (25 16)/16 = 0.916
lbd = 0.916 x 40.3 = 36.9 = 590mm
Design anchorage length, lbd
lbd = 1 2 3 4 5 lb.req lb,min
lbd = 1 2 3 4 5 (40.3) For concrete class C25/30
b) Tension anchorage Other shape bars
1 = 1.0 cd = 25 is 3 = 3 x 16 = 48
3 = 1.0 conservative value with K= 0
4 = 1.0 N/A
5 = 1.0 conservative value
2 = 1.0 0.15 (cd 3)/ 1.0
2 = 1.0 0.15 (25 48)/16 = 1.25 1.0
lbd = 1.0 x 40.3 = 40.3 = 645mm

Worked example - summary

H16 Bars Concrete class C25/30 25 Nominal cover


Tension anchorage straight bar lbd = 36.9 = 590mm
Tension anchorage Other shape bars lbd = 40.3 = 645mm
lbd is measured along the centreline of the bar
Compression anchorage (1 = 2 = 3 = 4 = 5 = 1.0)
lbd = 40.3 = 645mm
Anchorage for Poor bond conditions = Good/0.7
Lap length = anchorage length x 6
Anchorage & lap lengths
How to design concrete structures using Eurocode 2

Arrangement of Laps
EC2: Cl. 8.7.2, Fig 8.7

If more than one layer a maximum


of 50% can be lapped
Arrangement of Laps
EC2: Cl. 8.7.3, Fig 8.8

Transverse Reinforcement

Anchorage of bars

There is transverse tension reinforcement required


Transverse Reinforcement

Lapping of bars

F tan

F F
F tan

F/2 F/2

There is transverse tension reinforcement required

Transverse Reinforcement at Laps


Bars in tension
EC2: Cl. 8.7.4, Fig 8.9 only if bar 20mm or laps > 25%
Where the diameter, , of the lapped bars 20 mm, the transverse
reinforcement should have a total area, Ast 1,0As of one spliced bar. It
should be placed perpendicular to the direction of the lapped
reinforcement and between that and the surface of the concrete.

If more than 50% of the reinforcement is lapped at one point and the
distance between adjacent laps at a section is 10 transverse bars should
be formed by links or U bars anchored into the body of the section.
The transverse reinforcement provided as above should be positioned at
the outer sections of the lap as shown below.

Ast /2
Ast /2
l 0 /3
l 0 /3
150 mm F
Fs s

l0
Beams
EC2: Cl. 9.2
As,min = 0,26 (fctm/fyk)btd but 0,0013btd

As,max = 0,04 Ac
Section at supports should be designed for a
hogging moment 0,25 max. span moment
Any design compression reinforcement () should be
held by transverse reinforcement with spacing 15

Beams
EC2: Cl. 9.2

Tension reinforcement in a flanged beam at


supports should be spread over the effective width
(see 5.3.2.1)
Shear Design: Links
EC2: Cl. 6.2.3

Variable strut method allows a shallower strut angle


hence activating more links.
As strut angle reduces concrete stress increases

V s V

z d z d

x x

Angle = 45 V carried on 3 links Angle = 21.8 V carried on 6 links

Short Shear Spans with Direct


Strut Action
EC2: Cl. 6.2.3 (8)

d d

av av

Where av 2d the applied shear force, VEd, for a point load


(eg, corbel, pile cap etc) may be reduced by a factor av/2d
where 0.5 av 2d provided:
The longitudinal reinforcement is fully anchored at the support.
Only that shear reinforcement provided within the central 0.75av is
included in the resistance.

Note: see PD6687-1:2010 Cl 2.14 for more information.


Shear reinforcement
EC2: Cl. 9.2.2

Minimum shear reinforcement, w,min = (0,08fck)/fyk

Maximum longitudinal spacing, sl,max = 0,75d (1 + cot)

For vertical links sl,max = 0,75d

Maximum transverse spacing, st,max = 0,75d 600 mm

Shear Design
EC2: Cl. 6.2.3

z d

x
s V

z d

x
Curtailment of reinforcement
EC2: Cl. 9.2.1.3, Fig 9.2

Envelope of (M Ed /z +N Ed )
lbd
Acting tensile force lbd

Resisting tensile force lbd

Ftd
al

al
lbd
Ftd
lbd lbd
Shift rule
lbd lbd

For members without shear reinforcement this is satisfied with al = d

For members with shear reinforcement: al = 0.5 z Cot


But it is always conservative to use al = 1.125d

Anchorage of Bottom
Reinforcement at End Supports
EC2: Cl. 9.2.1.4
Tensile Force Envelope
al

Shear shift rule

Simple support (indirect) Simple support (direct)

As bottom steel at support 0.25 As provided in the span

lbd is required from the line of contact of the support.


Transverse pressure may only be taken into account with
a direct support.
Simplified Detailing Rules for
Beams

Supporting Reinforcement at
Indirect Supports
EC2: Cl. 9.2.5
B
A supporting beam with height h1
B supported beam with height h2 (h1 h2)
h 2 /3
h 2 /2

Plan view

The supporting reinforcement is in


h 1 /3
addition to that required for other A
reasons h 1 /2

The supporting links may be placed in a zone beyond


the intersection of beams
Solid slabs
EC2: Cl. 9.3
Curtailment as beams except for the Shift rule al = d
may be used
Flexural Reinforcement min and max areas as beam
Secondary transverse steel not less than 20% main
reinforcement

Reinforcement at Free Edges

Solid slabs
EC2: Cl. 9.3

Where partial fixity exists, not taken into account in design: Internal
supports: As,top 0,25As for Mmax in adjacent span
End supports: As,top 0,15As for Mmax in adjacent span

This top reinforcement should extend 0,2 adjacent span


Particular rules for flat slabs
Distribution of moments
EC2: Table I.1

Particular rules for flat slabs

EC2: Cl. 9.4

Arrangement of reinforcement should reflect behaviour


under working conditions.

At internal columns 0.5At should be placed in a width =


0.25 panel width.

At least two bottom bars should pass through internal


columns in each orthogonal directions.
Columns
EC2: Cl. 9.5.2

h 4b
min 12
As,min = 0,10NEd/fyd but 0,002 Ac

As,max = 0.04 Ac (0,08Ac at laps)

Minimum number of bars in a circular column is 4.

Where direction of longitudinal bars changes more than


1:12 the spacing of transverse reinforcement should be
calculated.

Columns
150mm
EC2: Cl. 9.5.3

scl,tmax

150mm

scl,tmax = min {20 min; b ; 400mm}

scl,tmax should be reduced by a factor 0,6:


in sections within h above or below a beam
or slab
near lapped joints where > 14.
A min of 3 bars is required in lap length
scl,tmax = min {12 min; 0.6b ; 240mm}
Walls
Vertical Reinforcement
As,vmin = 0,002 Ac (half located at each face)
As,vmax = 0.04 Ac (0,08Ac at laps)
svmax = 3 wall thickness or 400mm
Horizontal Reinforcement
As,hmin = 0,25 Vert. Rein. or 0,001Ac
shmax = 400mm
Transverse Reinforcement
Where total vert. rein. exceeds 0,02 Ac links required as
for columns
Where main rein. placed closest to face of wall links are
required (at least 4No. m2). [Not required for welded mesh or bars
16mm with cover at least 2.]

Detailing Comparisons

Beams EC2 BS 8110


Main Bars in Tension Clause / Values Values
As,min 9.2.1.1 (1): 0.26 fctm/fykbd 0.0013 bh
0.0013 bd
As,max 9.2.1.1 (3): 0.04 bd 0.04 bh
Main Bars in Compression
As,min -- 0.002 bh
As,max 9.2.1.1 (3): 0.04 bd 0.04 bh

Spacing of Main Bars


smin 8.2 (2): dg + 5 mm or or 20mm dg + 5 mm or
Smax Table 7.3N Table 3.28
Links
Asw,min 9.2.2 (5): (0.08 b s fck)/fyk 0.4 b s/0.87 fyv
sl,max 9.2.2 (6): 0.75 d 0.75d
st,max 9.2.2 (8): 0.75 d 600 mm d or 150 mm from main bar
9.2.1.2 (3) or 15 from main bar
Detailing Comparisons

Slabs EC2 BS 8110


Main Bars in Tension Clause / Values Values
As,min 9.2.1.1 (1): 0.26 fctm/fykbd 0.0013 bh
0.0013 bd
As,max 0.04 bd 0.04 bh
Secondary Transverse Bars
As,min 9.3.1.1 (2): 0.2As for single way 0.002 bh
slabs
As,max 9.2.1.1 (3): 0.04 bd 0.04 bh
Spacing of Bars
smin 8.2 (2): dg + 5 mm or or 20mm dg + 5 mm or
9.3.1.1 (3): main 3h 400 mm
Smax secondary: 3.5h 450 mm 3d or 750 mm
places of maximum moment:
main: 2h 250 mm
secondary: 3h 400 mm

Detailing Comparisons
Punching Shear EC2 BS 8110
Links Clause / Values Values
Asw,min 9.4.3 (2): Link leg = 0.053 sr st Total = 0.4ud/0.87fyv
(fck)/fyk
Spacing of Links
Sr 9.4.3 (1): 0.75d 0.75d
St 9.4.3 (1): 1.5d
within 1st control perim.: 1.5d
outside 1st control perim.: 2d
Columns
Main Bars in Compression
As,min 9.5.2 (2): 0.10NEd/fyk 0.002bh 0.004 bh
As,max 9.5.2 (3): 0.04 bh 0.06 bh
Links
Min size 9.5.3 (1) 0.25 or 6 mm 0.25 or 6 mm
Scl,tmax 9.5.3 (3): min (12min; 0.6 b;240 mm) 12
9.5.3 (6): 150 mm from main bar 150 mm from main bar
How toCompendium

Detailing
www.eurocode2.info

Keep up to date
Download:
Column charts
Derivations
Worked examples
How to guides
& more

Você também pode gostar