Você está na página 1de 18

ZN551 Control Module

Technical Instructions

What is the ZN551 control module? ........................................................................... 2


Module driver and control program ................................................................ 2
Specifications ............................................................................................... 2
Inputs ........................................................................................................... 3
Room sensors................................................................................................ 3
Digital outputs............................................................................................... 3
Analog outputs.............................................................................................. 3
To mount the ZN551.................................................................................................. 4
Wiring for power ........................................................................................................ 4
To wire for power............................................................................................ 4
To address the ZN551................................................................................................ 5
Wiring for communications ........................................................................................ 5
Wiring specifications ..................................................................................... 5
To wire the ZN551 for communications .......................................................... 5
Wiring inputs and outputs .......................................................................................... 6
Wiring specifications ..................................................................................... 6
To wire inputs and outputs ............................................................................. 7
Downloading memory ................................................................................................ 9
To download memory in WebCTRL .................................................................. 9
To assign inputs or outputs to points........................................................................... 9
Input values.................................................................................................10
Output values ..............................................................................................10
Resolution values ........................................................................................11
Offset/Polarity values..................................................................................11
Using flow sensors................................................................................................... 12
To connect the duct tubes to the flow sensors ...............................................12
To wire the flow sensor to the control module................................................12
To set up the Airflow Control microblock .......................................................12
To set up the module driver ...................................................................................... 13
Driver ..........................................................................................................13
Device.........................................................................................................14
Notification Class #1 ...................................................................................14
Common Alarms..........................................................................................15
Custom Translation Tables...........................................................................15
To communicate through the local access port .......................................................... 16
To set up a Local Access connection in WebCTRL ..........................................16
Troubleshooting ...................................................................................................... 16
Formatting the control module .....................................................................17
LED's..........................................................................................................17
Manufacture date........................................................................................18
Compliance ............................................................................................................ 18

Automated Logic Corporation 1150 Roberts Blvd. Kennesaw, GA 30144 770/429-3000 Fax 770/429-3001
www.automatedlogic.com 2005 Automated Logic Corporation. All rights reserved throughout the world. Automated
Logic Corporation, the Automated Logic logo, WebCTRL, EIKON, BACview, SuperVision, and InterOp are registered
trademarks, and Alert is a trademark of Automated Logic Corporation. BACnet is a registered trademark of ASHRAE.
All other brand and product names are trademarked by their respective companies.
What is the ZN551 control module?
The ZN551 control module is used for zone control.

Module driver and Module driver DRV_ZN


control program
Maximum number of control 1
programs
Maximum number of 200
BACnet objects*
* Depends on available memory

Specifications Power 24 Vac 10%, 5060 Hz, 15 VA


26 Vdc (25 V min, 30 V max)
CMnet port For communication with the control module network using
ARC156 or MS/TP (9600 bps76.8 kbps)
Rnet port For RS room sensors. The Rnet port supports up to four
RS sensors and one RS Pro or RS Plus sensor for
averaging or high/low select control.
NOTE The ZN551 does not support BACview.
LStat port For LogiStat and LogiStat Plus room sensors. The LogiStat
port uses two universal inputs.
NOTE The ZN551 does not support the LogiStat Pro. Use
an RS Pro on the Rnet port instead.
Local access port For system start-up and troubleshooting

Inputs 5 inputs configurable for thermistor or dry contact. Inputs


1 and 2 are also configurable for 05 Vdc. Inputs 4 and 5
are used when a LogiStat sensor is connected, but are
available if an RS room sensor is connected.
Input resolution 10 bit A/D

Digital outputs 5 digital outputs, relay contacts rated at 1 A max. @ 24


Vac/Vdc. Configured normally open.
Analog output 1 analog output, 010 Vdc (5 mA max)

Output resolution 8 bit D/A

Memory 512 kB non-volatile battery-backed RAM, 1 MB Flash


memory, 16-bit memory bus
Battery 10-year Lithium CR2032 battery provides a minimum of
10,000 hours of data retention during power outages
Protection Incoming power and network connections are protected
by non-replaceable internal solid-state polyswitches that
reset themselves when the condition that causes a fault
returns to normal. The power, network, analog inputs,
analog outputs, and relay output connections are also
protected against voltage transient and surge events.

ZN551 Control Module Rev. 3/17/2005 2 2005 Automated Logic Corporation


Status indicators LED's indicate status of communications, running, errors,
power, and digital outputs
Environmental operating 0 to 130F (-17.8 to 54.4C), 1090% relative humidity,
range non-condensing
Physical Rugged GE C2950 Cycoloy plastic

Overall dimensions Width: 5 1/16 in. (12.9 cm)


Height: 5 11/16 in. (14.4 cm)
Mounting dimensions 5 9/16" (14.1 cm) between mounting slot centerlines
Weight 0.6 lbs (0.27 kg)
BACnet support Conforms to the Advanced Application Controller (B-AAC)
Standard Device Profile as defined in ANSI/ASHRAE
Standard 135-2004 (BACnet) Annex L
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-
Class A, CE EN50082-1997

Inputs The ZN551 has 5 inputs that accept the following signal types:

These Support this


inputs... signal type... Description
All Thermistor Precon type 2 (10 kOhm at 77F). Input voltages will be
from 0.33 Vdc to 2.52 Vdc for thermistors.
All Dry contact A 3.3 Vdc wetting voltage detects contact position,
resulting in a 0.3 mA maximum sense current when the
contacts are closed.
IN-1, IN-2 05 Vdc The output impedance of a 05 Vdc source must not
exceed 100 Ohms. The input impedance of the ZN551
is approximately 30 kOhm.
IN-4, IN-5 LogiStat IN-4See Thermistor.
IN-5Setpoint adjust. Input voltages should be from
1.43.4 Vdc.

NOTE A LogiStat sensor connected to the ZN551 uses IN-4 and IN-5. An RS
room sensor connected to the Rnet port does not use these inputs.

Room sensors You can wire an RS Standard, RS Plus or RS Pro to the ZN551's Rnet port.
Or you can wire a LogiStat or LogiStat Plus to the ZN551's LStat port. See the
RS Room Sensors Technical Instructions (http://info.automatedlogic.com) or
the LogiStat Sensors Technical Instructions (http://info.automatedlogic.com).

NOTE The ZN551 does not support the LogiStat Pro.

Digital outputs The ZN551 has 5 digital outputs. You can connect each output to a
maximum of 24 Vac/Vdc. Each output is a dry contact rated at 1 A, 24 V
maximum and is normally open.

Analog outputs The ZN551 has 1 analog output that supports voltage devices from 0-10 Vdc.
The controlled device must have a minimum of 2000 Ohms resistance

ZN551 Control Module Rev. 3/17/2005 3 2005 Automated Logic Corporation


measured from its input to ground and must share the same ground as the
control module.

To mount the ZN551


Screw the ZN551 into an enclosed panel using the mounting slots provided
on the cover plate. Leave about 2 in. (5 cm) on each side of the control
module for wiring.

Mounting slot

Mounting slot

Wiring for power


CAUTIONS

The ZN551 is a Class 2 device (less than 30 Vac, 100 VA). Take
appropriate isolation measures when mounting it in a control panel
where non-Class 2 devices (120 Vac or greater) are present.
Do not power pilot relays from the same transformer that powers the
ZN551.

NOTE You can power several control modules from the same transformer if
you maintain the same polarity.

To wire for power 1 Remove power from the 24 Vac transformer.


2 Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac.
3 Connect the transformer wires to the screw terminal connector.
4 Apply power to the transformer.
5 Measure the voltage at the ZN551s power input terminals to verify that
the voltage is within the operating range of 21.626.4 Vac.
6 Insert the screw terminal connector into the ZN551's power terminals.
7 Verify that the Power LED is on and the Run LED is blinking.

ZN551 Control Module Rev. 3/17/2005 4 2005 Automated Logic Corporation


To address the ZN551
You can address the ZN551 before or after you wire the control module for
power.

1 If the ZN551 has been wired for power, pull the screw terminal connector
from the control module's power terminals labeled Gnd and 24 Vac. The
control module reads the address each time you apply power to it.
2 Using the rotary switches, set the control module's address to match the
Address in the control module's Device Properties dialog box in
SiteBuilder. Set the Tens (10's) switch to the tens digit of the address,
and set the Ones (1's) switch to the ones digit.
EXAMPLE If the control modules address is 35, point the arrow on the
Tens (10's) switch to 3 and the arrow on the Ones (1's) switch to 5.
10's 1's

Wiring for communications


The ZN551 communicates using BACnet on the following types of network
segments:

ARC156 communicating at 156 kbps


MS/TP communicating at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps

NOTE ARC156 is a unique implementation of the industry standard


ARCNET. For a summary of differences between ARCNET and ARC156, see
the ARC156 Wiring Technical Instructions (http://info.automatedlogic.com).

Wiring specifications For... Use... Maximum Length

ARC156 22 AWG, low-capacitance, twisted, 2000 feet (610 meters)


stranded, shielded copper wire*
MS/TP A dedicated 22 AWG to 18 AWG 3000 feet (914.4 meters) for 9600
twisted pair wire (EIA-485) bps, 19.2 kbps, or 38.4 kbps
2000 feet (610 meters) for 76.8 kbps
* See the ARC156 Wiring Technical Instructions (http://info.automatedlogic.com).

To wire the ZN551 for 1 Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac.
communications
2 Check the communications wiring for shorts and grounds.
3 Connect the communications wiring to the control modules screw
terminals labeled Net +, Net -, and Shield.
NOTE Use the same polarity throughout the network segment.

ZN551 Control Module Rev. 3/17/2005 5 2005 Automated Logic Corporation


4 Set the communication type and baud rate.

Set Communications
For... Selection jumper to... Set DIP switches 1 and 2 to...
ARC156 ARC156 N/A. Baud rate will be 156 kbps
regardless of the DIP switch settings.
MS/TP MSTP The appropriate baud rate. See the MSTP
Baud diagram on the control module.

NOTE Use the same baud rate for all control modules on the network
segment.
5 Insert the power screw terminal connector into the ZN551's power
terminals.
6 Verify communication with the network by viewing a module status
report in WebCTRL.

Wiring inputs and outputs


Wire the ZN551's inputs and outputs as follows.

Wiring specifications Input wiring


Input Maximum length Minimum gauge Shielding

05 Vdc 1000 feet 26 AWG Shielded


(305 meters)
Thermistor 1000 feet 22 AWG Shielded
Dry contact (305 meters)
RS room sensors 500 feet 22 AWG, Shielded or
(152 meters) 4 conductor1 unshielded

LogiStat 100 feet 22 AWG2 Unshielded


(30 meters)
1 See the RS Room Sensors Technical Instructions (http://info.automatedlogic.com).
2 See the LogiStat Sensors Technical Instructions (http://info.automatedlogic.com).

Output wiring
To size output wiring, consider the following:

Total loop distance from the power supply to the control module, and
then to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires,
this is twice the cable length.
Acceptable voltage drop in the wire from the control module to the
controlled device
Resistance (Ohms) of the chosen wire gauge
Maximum current (Amps) the controlled device requires to operate

ZN551 Control Module Rev. 3/17/2005 6 2005 Automated Logic Corporation


To wire inputs and 1 Verify that the ZN551's power and communications connections work
outputs properly.
2 Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac.
3 Connect the input wiring to the screw terminals on the ZN551.
NOTE Connect the shield wire to the GND terminal with the ground
wire.

Any input

thermistor Gnd

Relay, Any input


dry contact
Gnd
+V

DC +V
power Out 0-5Vdc
supply Gnd
Gnd
Gnd

4 To wire a room sensor to the ZN551, wire the ZN551's terminals to the
room sensor's terminals.
For an RS room sensor, wire each terminal on the ZN551's Rnet port
to the terminal of the same name on the RS room sensor.
NOTE If wiring an RS room sensor with shielded wire, connect the
shield wire to the GND terminal with the ground wire.
For a LogiStat room sensor, use the following table.

Wire this terminal To this terminal on


on the LStat port... the LogiStat sensor
Gnd Gnd
IN-4 Temp
IN-5 SW
LED LS5v

5 Set the appropriate jumpers on the ZN551.

To use... For...

IN-1 or IN-2 Thermistor Set jumpers IN-1 or IN-2 to the type of signal the
Dry contact input will receive.
05 Vdc
IN-4 or IN-5 Thermistor Verify the LStat/IN-4 jumper is on.
Dry contact
IN-4 and IN-5 LogiStat 1. Remove the jumper from LStat/IN-4.
2. Set the LStat/Rnet jumper to LStat.
Rnet Port RS sensor Set the LStat/Rnet jumper to Rnet.

ZN551 Control Module Rev. 3/17/2005 7 2005 Automated Logic Corporation


LStat
Rnet

LStat
IN-4

IN-1
Thermistor/dry contact
0-5Vdc
IN-2
Thermistor/dry contact
0-5Vdc

6 Connect the digital output wiring to the screw terminals on the ZN551
and to the controlled device.

Any DO Motor

Any DO

Bus 24 Vac or
24 Vdc

7 Connect the analog output wiring to the screw terminals on the ZN551
and to the controlled device.

Gnd
Motor 0-10 V
Any AO +

Gnd
Valve 0-10 V
Any AO +

NOTE Current from the analog outputs can drive a 20 mA device. To use
an analog output for this purpose, you may need to add a 1/2 watt
resistor in series with the device to achieve the required total resistance
of 500 Ohms. For example, to drive a device that has 100 Ohms of
resistance, wire a 400 Ohm resistor in series with the 20 mA device to
achieve 500 Ohms resistance.
8 Insert the power screw terminal connector into the ZN551's power
terminals.

ZN551 Control Module Rev. 3/17/2005 8 2005 Automated Logic Corporation


Downloading memory
Download memory to a control module to do either of the following:

Send control programs, the module driver, editable properties, and


schedules to a control module for the first time. The first download takes
longer than subsequent downloads.
Send changes such as a change to a control program, an upgrade to the
module driver, or a change to the control module's address.

The ZN551 can store one DRV_ZN module driver and one control program.

CAUTIONS

The control module automatically halts before and restarts after a


memory download, causing the shutdown and restart of any equipment
controlled by the module.
Downloading memory overwrites all control programs in the control
module causing it to lose stored data.

You download memory from WebCTRL. If your network is complete, you can
download from any network browser. If not complete, connect a laptop with a
local copy of the system database to the ZN551's local access port. See steps
13 of To communicate through the local access port (page 16).

To download memory 1 On WebCTRL's CFG tree, click Download.


in WebCTRL 2 Select the Memory checkbox.
NOTE A memory download includes a Parameters and Schedules
download.
3 On the Network tree on the right, select the control module you want to
download to.
4 Click Add to add the control module to the Download Items list.
5 Click Download Selected Items.

If the download fails, the control module appears in the Failures box. Since
this indicates a system problem, do not clear the failure. Locate and resolve
the problem, then retry the download. To retry, select the control module in
the Failures box, then repeat steps 4 and 5 above.

To assign inputs or outputs to points


To use an input or output, you must assign it to its corresponding point in
the control program.

1 In WebCTRL's GEO tree, select the equipment controlled by the ZN551.

2 From the menu , select Point Checkout.

ZN551 Control Module Rev. 3/17/2005 9 2005 Automated Logic Corporation


3 In the Num field for each point, type the number of the control module's
corresponding input or output. For example, if you use DO1 on the
ZN551 for the point Fan S/S, type 1 in the Num field for Fan S/S.
NOTE Exp (expander number) is 0 for the ZN551.
4 Enter the appropriate values for each input and output in the remaining
columns. See Input values, Output values, Resolution values and
Offset/Polarity values below.
NOTE You can also enter these values in EIKON for WebCTRL.
5 If you have not performed the initial memory download to the ZN551, you
must download now so you can verify inputs and outputs.
6 To verify each input's operation, force each sensor to a known value, then
compare it to the Value shown on the control program's Point Checkout
tool in WebCTRL.
7 To verify each output's operation, lock each output to a known condition
on the control program's Point Checkout tool in WebCTRL, then verify
that the equipment operates correctly.

Input values Input I/O Type Sensor/Actuator Type Min/Max

Analog (BAI)

05 Vdc 05 Volt Linear Full Range Engineering values


associated with 0 Vdc (Min)
and 5 Vdc (Max)1
Thermistor Thermistor Select your Thermistor N/A
type or set up and select
a Non-Linear, Custom
Table2
Digital (Binary) (BBI)

Dry Contact Dry Contact N/A N/A

1 The sensor reads a value and sends a corresponding signal (Volt, mA, or psi) to the
ZN551's physical input. The Analog Input microblock uses the Min and Max values to
linearly translate the signal into the engineering value used in subsequent control logic.
For example, set Min to 0 and Max to 10 for a 420 mA sensor that measures velocity
from 0.0 to 10.0 inches/second so that when the input reads 4 mA, the microblock
outputs a value of 0. Similarly, when the input reads 8 mA, the microblock outputs a
value of 2.5.
2 To set up a custom translation table, see the module driver's Custom Translation Tables
properties page in WebCTRL.

Output values Output I/O Type Sensor/Actuator Type Min/Max

Analog (BAO)

010 Vdc Electrical Linear Full Range Engineering values


010 Volt associated with 0 Vdc (Min)
and 10 Vdc (Max)1
210 Vdc Electrical Linear w/Offset, Engineering values
010 Volt 210 Volts associated with 2 Vdc (Min)
and 10 Vdc (Max)1

ZN551 Control Module Rev. 3/17/2005 10 2005 Automated Logic Corporation


Output I/O Type Sensor/Actuator Type Min/Max

Digital (Binary) (BBO)

Relay Relay/Triac N/A N/A


Output
1 The Analog Output microblock uses the Min and Max values to linearly translate its
EIKON for WebCTRL wire value into a physical output signal (Volt, mA, or psi) sent from
the ZN551 to an actuator. For example, set Min to 0 and Max to 100 for an Analog
Output microblock that receives a 0 to 100% open signal from a PID microblock and
that controls a 010 Vdc actuator so that when the PID signal is 100%, the ZN551
output is 10 Vdc. Similarly, when the PID signal is 50%, the ZN551 output is 5 Vdc.

Resolution values Resolution is not particular to a type of input or output, but the module
driver handles analog and digital (binary) inputs and outputs differently. To
set these values appropriately, you should understand how the module driver
uses them.

Resolution Notes

Analog Input (BAI) The driver truncates the microblock's present value according
to the resolution.
EXAMPLE If the calculated present value is 13.789 and you
set the Resolution to 0.1, the control program uses 13.7 for
any calculations downstream from the microblock.
Analog Output (BAO) The driver truncates the wire input value to the microblock
before performing any scaling calculations.
EXAMPLE If the wire input value is 13.789 and you set the
Resolution to 0.1, the microblock uses 13.7 for any scaling
calculations.
Digital Inputs and N/A
Outputs

Offset/Polarity values Offset/Polarity is not particular to a type of input or output, but the module
driver handles analog and digital (binary) inputs and outputs differently. To
set these values appropriately, you should understand how the module driver
uses them.

Offset/Polarity Notes

Analog Input (BAI) Offset value (positive or negative) adds a fine adjustment to a
sensor reading after all scaling for calibration.
EXAMPLE If a sensor reads 74.9F when the actual
measured value is 73.6F, enter an Offset of 1.3 to
calibrate the sensor to the measured value.
Analog Output (BAO) You can use the Offset value (positive or negative) to
calibrate an output, but you generally do not need to. If used,
the driver adds the offset value to the wire input value before
performing any scaling calculations to determine the ZN551's
output.

ZN551 Control Module Rev. 3/17/2005 11 2005 Automated Logic Corporation


Offset/Polarity Notes

Digital (Binary) Input Polarity determines the microblock's present value when no
(BBI) signal is received from the equipment.
When no signal is received from the equipment, if Polarity is
set to:
normalpresent value is off
reversedpresent value is on
Digital (Binary) Output Polarity determines the ZN551's output based on the control
(BBO) program's signal to the microblock.
When the control program's signal to the microblock is on, if
Polarity is set to:
normaloutput is on
reversedoutput is off
NOTE Regardless of Polarity, the output will be off if the
ZN551 loses power.

Using flow sensors


In a single duct system, the ZN551 controls airflow in the zone using a USF
flow sensor and an actuator connected to two digital outputs.

In a dual duct system, the ZN551 controls airflow in the zone using a UDF
flow sensor and two actuators, with each actuator connected to two digital
outputs.

To connect the duct USF


tubes to the flow sensors 1 Connect the ducts total pressure tube to the USF's High connector.
2 Connect the ducts static pressure tube to the USF's Low connector.

UDF
Follow the procedure for a USF, but connect one duct's tubes to the UDF's
Flow #1 connectors and the other duct's tubes to the UDF's Flow #2
connectors.

To wire the flow sensor Use the cable included with the flow sensor (ALC part #235012) or a 20 AWG,
to the control module 4-conductor cable, maximum length 4 feet (1.22 meters).

1 Turn off the control module's power.


2 Connect the ends of the cable to the 4-pin connector on the flow sensor
and to the 4-pin connector on the control module.

To set up the Airflow The ZN551's control program must include one Airflow Control microblock
Control microblock for a single duct system or two of the microblocks for a dual duct system.
You must set up the Airflow Control microblock for each flow sensor.

ZN551 Control Module Rev. 3/17/2005 12 2005 Automated Logic Corporation


For a single duct system
1 In WebCTRL, on the control program's Logic page, select the U-Line
Airflow Control microblock.
2 On the Details tab in the Flow Sensor field under Hardware
Configuration, select External flow sensor.
3 In the Input Number field, type 1.
4 In the I/O Type field, select Flow Input.
5 At the bottom of the Details tab, click the plus sign (+) to the left of Flow
Input (AI) Configuration.
6 In the Sensor Type field under Calibration, select No Translation.

For a dual duct system


1 In WebCTRL, on the control program's Logic page, select the Airflow
Control microblock for Flow #1.
2 On the Details tab in the Flow Sensor field under Hardware
Configuration, select External flow sensor.
3 In the Input Number field, type 1.
4 In the I/O Type field, select Flow Input.
5 At the bottom of the Details tab, click the plus sign (+) to the left of Flow
Input (AI) Configuration.
6 In the Sensor Type field under Calibration, select No Translation.
7 On the Logic page, select the airflow control microblock for Flow #2.
8 Repeat steps 2 through 6 for Flow #2, typing 2 in step 3.

NOTE When performing test and balance, follow the steps under Test and
Balance on the Airflow Control microblock's Properties page Details tab in
WebCTRL.

To set up the module driver


After you download the module driver and control program to the ZN551, you
may want to change the module driver's properties to suit your application.

1 On WebCTRL's NET tree, click the plus sign (+) to the left of your ZN551.
NOTE Driver properties are on the Driver Properties page and on its
children in the tree.
2 Click the page you want to view, then change properties as needed.

Driver On this page, you can change the following properties:


Module clock synchronization and failure. See table below.
Network Input microblock communication properties.

ZN551 Control Module Rev. 3/17/2005 13 2005 Automated Logic Corporation


Module Clock

Clock Fail Date and Time Date and time control program uses when module's real-
time clock is invalid.
TIP Use an occupied date and time (such as a Tuesday
at 10 a.m.) so the equipment does not operate in
unoccupied mode if the module loses power during
occupancy.
Time Synch Sensitivity On a Time Synch signal, update the module clock only if
(seconds) the module time differs from the signal time by more
than this value.

Device On this page, you can change the following properties:


BACnet device object properties for the ZN551
ZN551 network communication

Configuration NOTE The three APDU fields refer to all networks over
which the ZN551 communicates.
Max Masters and Max Info Apply only if the ZN551's parent network is an MS/TP
Frames network.

Notification Class #1 WebCTRL alarms use Notification Class #1. A BACnet alarm's Notification
Class defines:
Alarm priority for Alarm, Fault, and Return to Normal states
Options for BACnet alarm acknowledgement
Where alarms should be sent (recipients)
NOTE You may need to set up additional Notification Classes if your system
will handle Life Safety alarms or if you need to send certain types of alarms
only to an alarm manager other than WebCTRL.

Priorities NOTE BACnet defines the following Network message


priorities for Alarms and Events.
Priority range Network message priority

0063 Life Safety

64127 Critical Equipment

128191 Urgent

192255 Normal

Priority of Off-Normal BACnet priority for Alarms.

Priority of Fault BACnet priority for Fault messages.

Priority of Normal BACnet priority for Return-to-normal messages.

ZN551 Control Module Rev. 3/17/2005 14 2005 Automated Logic Corporation


Ack Required for Off-Normal, Requires a control module acknowledgement for each
Fault, and Normal message type. Normally not required.
TIP To require operator acknowledgement for an Alarm
or Return-to-normal message (stored in the WebCTRL
database) change the acknowledgement settings on
WebCTRL's Alarm > Enable/Disable tab for an alarm
source or an alarm category.
Recipient List

Recipients The first row in this list is the WebCTRL Server. Do not
delete this row. Click Add if you want other BACnet
devices to receive alarms.
Recipient Description Name that appears in the Recipients table.

Recipient Type Use Address (static binding) only for third-party BACnet
device recipients that do not support dynamic binding.
Recipient Device Object Type the Device Instance from SiteBuilder (or from the
Identifier network administrator for third-party devices) in the #
field.
Process Identifier Change for third-party devices that use a BACnet Process
Identifier other than 1. WebCTRL processes alarms for
any 32-bit Process Identifier.
Issue Confirmed Select to have a device continue sending an alarm
Notifications message until it receives delivery confirmation from the
recipient.

Common Alarms On these pages, you can change the following control module alarm
properties:
BACnet alarm object properties
Enable/disable
Delays
NOTE To set up alarm actions for control module generated alarms, see
Setting up alarm actions in WebCTRL Help.

Module Generated Alarm

Description Short message shown on WebCTRL's Alarm page or in an


alarm action when this type of alarm is generated.
Events

Alarm Category and Alarm See Customizing alarms in WebCTRL Help.


Template
Enable Clear these checkboxes to disable Alarm or Return to
normal messages of this type from this control module.
Notification Class Do not change this field.

Custom Translation On the Custom Translation Table pages, you can edit the tables used to
Tables translate raw sensor data to engineering units for inputs associated with
Non-Linear, Custom Table sensor/actuator types.

ZN551 Control Module Rev. 3/17/2005 15 2005 Automated Logic Corporation


To communicate through the local access port
Using a computer and an APT, you can communicate locally with the ZN551
to download memory or to troubleshoot.

PREREQUISITES

A computer with an RS232 port


An APT with cables. See the APT Technical Instructions
(http://info.automatedlogic.com).

1 Connect the computer to the APT, and then the APT to the control
module.

Connect to the
control modules
Local Access port

Rnet
adapter
9-pin
cable
APT cable

8-pin
APT cable

2 Set the APT's Mode Select switch to 485.


3 Set the APT's Exec. 4 Relay switch to Network.

To set up a Local 1 On the CFG tree, select Connections.


Access connection in 2 On the Configure tab, click Add.
WebCTRL 3 From the Type drop-down list, select BACnet Local Access.
4 Optional: Edit the Description.
5 Type the computer's Port number where your APT is connected.
6 Set the Baud rate to 115200.
7 Click Accept.
8 On the View tab, click the drop-down arrow next to your device's
network Connection, then select BACnet Local Access.
9 Click Accept.
10 On the Configure tab, select BACnet Local Access, then click Start.

Troubleshooting
If you have problems mounting, wiring, or addressing the ZN551, contact
ALC Technical Support.

ZN551 Control Module Rev. 3/17/2005 16 2005 Automated Logic Corporation


Formatting the control If you cannot communicate with a control module after downloading memory
module to it, as a last resort, you can manually format the control module to erase its
memory.

1 Pull the screw terminal connector from the control module's power
terminals labeled Gnd and 24 Vac. Make sure the address switches are
not set to 0, 0.
2 Short the Format jumpers pins.
3 Insert the power screw terminal connector into the ZN551's power
terminals.
4 Continue to short the jumper until the Error LED flashes three times in
sync with the Run LED.
5 Remove the short.
6 Download memory to the ZN551.

LED's The LED's on the ZN551 show the status of certain functions.

If this LED is on... Status is...

Power The ZN551 has power

Rx The ZN551 is receiving data from the network segment

Tx The ZN551 is transmitting data over the network segment

DO# The digital output is active

The Run and Error LED's indicate control module and network status.

If Run LED shows... And Error LED shows... Status is..

2 flashes per second Off Normal

2 flashes per second 2 flashes, Five minute auto-restart delay


alternating with Run LED after system error
2 flashes per second 3 flashes, Control module has just been
then off formatted
2 flashes per second 4 flashes, Two or more devices on this
then pause network have the same
ARC156 network address
2 flashes per second On Exec halted after frequent
system errors or control
programs halted
5 flashes per second On Exec start-up aborted, Boot is
running
5 flashes per second Off Firmware transfer in
progress, Boot is running
7 flashes per second 7 flashes per second, Ten second recovery period
alternating with Run LED after brownout

ZN551 Control Module Rev. 3/17/2005 17 2005 Automated Logic Corporation


If Run LED shows... And Error LED shows... Status is..

14 flashes per second 14 flashes per second, Brownout


alternating with Run LED

Manufacture date When troubleshooting, you may need to know a control module's
manufacture date.

Obtain the manufacture


date from a... Notes
Module status report (modstat) To obtain a modstat in WebCTRL:
1. Select the control module in the NET tree.
2. Press Ctrl+M.
3. Type modstat.
4. Click OK.
The report shows the date under Main board
hardware.
Sticker on the back of the The first three characters on the sticker show the
main control module board control module type. The next three characters
show the year, month, and day of manufacture.
(The month digit is in hexadecimal format.)

Compliance
This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.

CAUTION Changes or modifications not expressly approved by the


responsible party for compliance could void the users authority to operate
the equipment.

ZN551 Control Module Rev. 3/17/2005 18 2005 Automated Logic Corporation

Você também pode gostar