Você está na página 1de 26

NDICE

1.0 ANTECEDENTES ____________________________________________________________ 3


2.0 PLANOS:____________________________________________________________________ 3
3.0 CONSIDERACIONES DE DISEO ______________________________________________ 5
Normas de diseo y consideraciones adoptadas: _________________________________________ 5
Parmetros de Diseo Sismo-resistente: ________________________________________________ 5
Anlisis _________________________________________________________________________ 6
Metrados de Carga _________________________________________________________________ 6
Especificaciones tcnicas ___________________________________________________________ 6
4.0 ESTRUCTURACIN __________________________________________________________ 7
CARGA DE VIENTO ______________________________________________________________ 7
CARGA SSMICA ________________________________________________________________ 8
COMBINACIONES DE CARGA ____________________________________________________ 9
RESULTADOS ___________________________________________________________________ 9
5.0 CONCLUSIONES Y RECOMENDACIONES _____________________________________ 14
MEMORIA DE CLCULO ESTRUCTURAL

OBRA : CERCO DE ACERO EMPERNADO CON MALLA.


PROPIETARIO : CONTILATIN DEL PER S.A.
UBICACIN : Lurn, Lima
FECHA : Lima, Julio del 2017

1.0 ANTECEDENTES

La presente memoria de clculo desarrolla el diseo estructural de un cerco


perimtrico de perfiles de acero con una cubierta de malla anti polvo para
salvaguardar el bienestar de los propietarios aledaos a la empresa.

El proyecto a construirse, se compone por perfiles tubulares reticulados


verticales espaciados a 4.00 metros reforzados de acuerdo a una configuracin
de diferentes alturas segn su desarrollo, as mismo, se tiene correas
horizontales para unin de los reticulados y la fijacin de la malla tensado a lo
largo de los 80 metros y 48 metros del cerco. La altura del cerco de acero es de
11 metros a partir de la base rgida proyectada (Zapatas conectadas con vigas
de cimentacin), el anclado de la estructura reticulada ser con planchas de
acero soldadas con cartelas para el reticulado de acero y plancha adosada al
concreto de la zapata.

El proyecto, materia de construccin, ha sido proyectado por un ingeniero civil,


de acuerdo a los lineamientos de distribucin, espacio, dimensionamiento y
consideraciones necesarias para el diseo de los elementos de concreto
conforme lo estipula el Reglamento Nacional de Construcciones (RNE).

2.0 PLANOS:

3
PLANTA:
PRIMER TRAMO

SEGUNDO TRAMO

ELEVACIN:

PRIMER TRAMO

SEGUNDO TRAMO

4
MODELO TRIDIMENSIONAL PARA EL ANLISIS (tramo 40 metros)

3.0 CONSIDERACIONES DE DISEO

Normas de diseo y consideraciones adoptadas:


Norma E-020, Cargas.
Norma E-030, Diseo Sismo-resistente (RNE).
Norma E-060, Concreto Armado (RNE).
Norma E-090, Estructuras Metlicas (RNE).
Manual of Steel Construction, AISC-LRFP
Libro Concreto Armado II UNI Facultad de Ingeniera Civil.

Parmetros de Diseo Sismo-resistente:


Ubicacin: Lurn, Lima.
Uso: Edificacin Comn, U=1.0 ; Categora C
Suelo: Suelos Blandos (S3) (Segn indica el Estudio Geotcnico para
la Cimentacin).
Factor de zona: Zona 4, Z=0.45.
Factor de Suelo: S=1.10
Periodo TP (seg) = 1.0
Periodo TL (seg) = 1.6

5
Factor de amplificacin Ssmica:
T = hn / CT = 11/45 = 0.24
T < TP => C = 2.50

Coeficiente Bsico de Reduccin: R0 = 8 (Prticos dctiles con uniones


resistentes a momentos).

Anlisis
Los elementos estructurales se han diseado para obtener en todas sus
secciones, resistencias de diseo por lo menos iguales a las resistencias
requeridas, calculadas para las cargas de diseo en el estado de servicio.

Metrados de Carga
El metrado se ha realizado individualmente en cada elemento estructural,
asumiendo las reas tributarias correspondientes.

Especificaciones tcnicas
Materiales:
Perfiles, planchas, redondos y angulares lisos de calidad de acero
estructural conforme a la Norma ASTM A36 (fy=2530 Kg/cm2).
Los electrodos a usarse sern clase AWS E070xx, salvo indicacin
contraria (electrodo supercito).
Pernos de anclaje: ASTM-A-325.
Proteccin con pintura:
El acondicionamiento del metal ser segn las especificaciones
SSPC-SP-10 (o granallado metal blanco).
Primera capa anticorrosivo epoxico poliamida a un espesor seco de
2mils, similar a amercoat 71, Ameron.
Fabricacin:
Todos los materiales antes de ser usados debern estar derechos, los
alineamientos debern cumplir con las tolerancias permitidas.
Todas las medidas indicadas debern verificarse en obra antes del
armado de los distintos elementos, con el fin de adecuar las
longitudes de los articulados y viguetas a las longitudes reales en
obra.

6
Soldadura:
Todas las uniones soldadas se realizarn por el proceso de arco
elctrico conforme a lo especificado en el cdigo de soldadura del
American Welding Society.
Todo el equipo de soldadura debern ser calificados con experiencia
demostrada en el trabajo de estructuras.

4.0 ESTRUCTURACIN

CARGA DE VIENTO

La estructura perimetral est expuesta a la accin del viento y ser diseado


para resistir cargas (presiones y succiones) exteriores e interiores debidas al
viento, suponiendo que esta acta perpendicular al cerco en toda su rea.
Velocidad de diseo: Vh = V*(h/10)0.22 (E020, 12.3)
Velocidad de diseo para la zona de anlisis: V = 75 Km/h (debido a que
supera los 10 metros de altura se tomar la velocidad mxima segn el
mapa elico del Per).
Velocidad aplicada a la estructura para una altura de 11 metros:
V11 = 75 km (la altura es mayor a 10 metros asi que se asume la
mxima velocidad de diseo para la zona).
Carga exterior de viento: Ph = 0.005*C*(VH)2 (E020, 12.4)
Factor de forma C
Ce = 1.5 (Anuncios muros aislados, elementos con una
dimensin corta en la direccin del viento). (E020, Tabla 4)
Carga interna de Viento: Ci = 0.3 (panel con abertura, aplicado por
tratarse de malla)
C = Ce Ci C = 1.5 0.3 = 1.2
P11 = 0.005*1.2*(75)2*1.2 = 40.50 Kg/m2 (Se multiplica
adicionalmente por 1.2 segn nos indica E020, 12.2, Tipo 2 donde
indica que las edificaciones cuya esbeltez las hace sensibles a las
rfagas en general estructuras con una dimensin corta en una
direccin del viento).
Para el ancho tributario tpico de columna: a = 4.00 m
Se aplica la carga repartida:

7
W = (40.50 Kg/m2)*(4.00m) = 162 Kg/m

Carga horizontal aplicada por efecto del viento repartido para el anlisis.

CARGA SSMICA

Se considera a la malla como elemento no estructural porque no aporta masa


al sistema, por eso su aporte a la rigidez no es significativo.
La estructura se disear para alcanzar adecuada resistencia y rigidez ante
acciones ssmicas.

Se tiene los siguientes parmetros Sismo-resistentes:

Ubicacin: Lurn, Lima.

Factor de zona: Zona 4, Z=0.45 (E030, Tabla 1).

8
Uso: edificacin comn.

Factor de uso U=1.0; Categora C (E030, Tabla 5).

Tipo de Suelo: Suelos Blandos (S3) (Segn indica el Estudio

Geotcnico para la Cimentacin).

Factor de suelo: S=1.10 (E030, Tabla 3).

Fuerza horizontal mnima:

Fh = 0.5*Z*U*S*(Peso) (E030, 6.3).

Fh = 0.5*0.45*1*1.10*P = 0.2475*P = 0.25*P

Por lo tanto, la fuerza ssmica horizontal es de 0.25 veces su peso

aplicada a ambas direcciones.

Peso estructura para 40m: 2,684.97 kg

Table 28: Material List 2 - By Section Property


Section Object Type Num Pieces Total Length TotalWeight
m Kgf
TUBO 4"x4"x2.5mm Frame 11 121. 955.86
TUBO 3"x3mm Frame 11 93. 503.6
TUBO 4"x2"x2mm Frame 40 160. 745.47
3/4" Frame 383 213.45432 480.04
-------------
2,684.97 Kg

COMBINACIONES DE CARGA

A continuacin se presenta las siguientes combinaciones de cargas sobre la


estructura como requisito general que exige el RNE.

Comb1 = 1.4D +1.7L Comb2 = 1.25*(D+L+W) Comb3 = 1.25*(D+L-

W) Comb4 = 0.9*D+SX Comb5 = 0.9*D-SX Comb6 = 0.9*D+SY

Comb7 = 0.9*D-SY Comb8 = Envolvente = Comb

RESULTADOS
DESPLAZAMIENTOS
El mayor efecto de desplazamiento lateral se obtiene por la combinacin de
cargas (Comb2), el cual combina un incremento del 25% a la carga muerta,
carga viva y carga de viento a la estructura.

9
Para el pilar reticulado (central y de extremos)
Desplazamiento mximo: 1 = 8.10 mm
Segn la Norma Tcnica E.030 Diseo Sismo - resistente del Reglamento
Nacional de Edificaciones, se tiene que el lmite de distorsin del acero:

/H 0.010 (E030, Tabla 11)

Y para este pilar se tiene: /H = 8.10 / 11000 = 0.001 0.010 (OK)

Para uno de los pilares reticulado (intermedio)


Desplazamiento mximo: 1 = 22.90 mm
Y para este pilar se tiene:

/H = 22.90 / 11000 = 0.002 0.010 (OK)

10
Para uno de los pilares reticulado (intermedio)
Desplazamiento mximo: 1 = 88.24 mm
Y para este pilar se tiene: /H = 88.24 / 11000 = 0.008 0.010 (OK)

DISEO PARA UN MIEMBRO SOMETIDO A FLEXIN

Momento mximo: Mu = 968.2 kgf-m = bMn

Zx Mu / bFy = 96820 / 0.9x2531 = 42.50 cm3 = 2.59 pulg3

11
Ensayando perfil tubo 100x100x2.5, se tiene Zx = 43.70 cm3 > 42.50 cm3 (OK)

DISEO DE CIMENTACIN
Para el diseo de cimentaciones se considerara zapatas conectadas con
vigas de cimentacin debido a las condiciones del suelo.
Datos para el diseo de zapatas y vigas de cimentacin recopilados del
Informe Tcnico Estudio Geotcnico para la Cimentacin (AC
Consultores).

Presin admisible del suelo mxima (capacidad admisible):


- rea ocupados por silos 1.50 Kg/cm2.
- Instalaciones industriales de la planta 1.00 Kg/cm2.
Profundidad de la cimentacin: 1.00 metro.
Peso unitario promedio del suelo: = 1.63 Tn/m3
Angulo de friccin interna: =25
Nivel fretico promedio: 1.50 metros.
Nivel fretico zona cerco: Ps03 = 1.20 m; Ps11 = 1.20 m y Ps09 = 1.60 m.
Profundidad de cimentacin: -1.00 respecto al NTN.

TABLA DE REACCIONES EN EL CIMIENTO


TABLE: Joint Reactions
Joint OutputCase StepType F1 F2 F3 M1 M2 M3
Text Text Text Kgf Kgf Kgf Kgf-m Kgf-m Kgf-m
12 Envolvente Max 3.856E-10 1255.94 3281.34 153.33 0 0
13 Envolvente Max 1.704E-09 971.56 3219.87 58.07 9.002E-14 1.8E-13
58 Envolvente Max 9.417E-10 1255.08 3253.15 153.43 0 0
59 Envolvente Max 2.514E-09 972.42 3201.47 58.06 2.198E-13 4.396E-13
104 Envolvente Max 4.02E-09 1255.08 3253.15 153.43 0 0
105 Envolvente Max 6.234E-10 972.42 3201.47 58.06 9.383E-13 1.877E-12
150 Envolvente Max 2.4E-09 1255.5 3267.66 153.39 0 0

12
151 Envolvente Max 1.685E-09 972 3210.49 58.07 5.601E-13 1.12E-12
189 Envolvente Max 9.255E-10 1255.5 3267.66 153.39 0 0
190 Envolvente Max 8.834E-10 972 3210.49 58.07 2.16E-13 4.321E-13
228 Envolvente Max 3.438E-09 1255.02 3254.34 153.5 0 0
229 Envolvente Max 3.013E-09 972.48 3200.93 58.07 8.025E-13 1.605E-12
254 Envolvente Max 1.456E-09 1255.02 3254.34 153.5 0 0
255 Envolvente Max 3.907E-09 972.48 3200.93 58.07 3.4E-13 6.799E-13
280 Envolvente Max 1.573E-09 1255.5 3267.66 153.39 0 0
281 Envolvente Max 7.124E-10 972 3210.49 58.07 3.671E-13 7.343E-13
319 Envolvente Max 3.223E-09 1255.5 3267.66 153.39 0 0
320 Envolvente Max 1.377E-09 972 3210.49 58.07 7.522E-13 1.504E-12
358 Envolvente Max 2.722E-09 1255.02 3254.34 153.5 0 0
359 Envolvente Max 4.563E-09 972.48 3200.93 58.07 6.354E-13 1.271E-12
384 Envolvente Max 7.342E-09 1255.02 3254.34 153.5 0 0
385 Envolvente Max 8.641E-09 972.48 3200.93 58.07 1.714E-12 3.427E-12

ZAPATA 01 (TPICA)

Fv = Fv nudo 12 + Fv nudo 13
Fv = 3281.34 Kgf + 3219.87 Kgf
Fv = 6501.21 Kgf

Fh = Fh nudo 12 + Fh nudo 13
Fh = 1255.94 984.02
Fh = 271.92 Kgf

Mx = Mx nudo 12 + Mx nudo 13
Mx = -154.88 + 58.07
Mx = -96.81 Kgf-m

13
DISEO DE ZAPATA Z1

Y
P
1 c 2 h'
b1

x
b

Df
a1 a b2 X
y B h
a b
b2

3 d 4

A
D A T O S
GEOMETRIA CARGA

A= 1.00 m a1 = 0.28 m P= 6.50 ton.


B= 1.50 m a2 = 0.27 m Vx = 0.00 ton.
a (C1)= 0.45 m b1 = 0.30 m Mx = 0.10 ton-m
b (C2)= 0.90 m b2 = 0.30 m Vy = 0.27 ton.
h= 0.50 m a3 = 0.01 m My = 0.00 ton-m
Df = 0.70 m b3 = 0.00 m
h= 0.10 m
recubrimiento r = 10.0 cm. fac. de carga Fc = 1.4
cap.de carga qa = 10.0 ton/m2 acero de ref. fy = 4200 kg/cm2
Relleno gs = 1.63 ton/m3 concreto f'c = 210 kg/cm2
zona sismica = si
Constantes

f*c = 0.8 f'c f*c = 168 kg/cm2

f''c = 0.85 f*c f''c = 142.8 kg/cm2


*
fc
1 0.851.05 b1 = 0.85
1400
0 .7 f ' c rmin = 0.002415
min
fy
f ' ' c 6000 1
b x rb = 0.01700
fy 6000 fy
rmax = 0.01275
DISEO DE ZAPATA Z1

Peso de la estructura

zapata = A x B x h x 2.40 = = 1.8000 ton.


dado = a x b x ( Df - h + h) x 2.40 = = 0.292 ton.
relleno = [( A x B ) - ( a x b ) ] x ( Df - h ) x gs = 0.36 ton. Peso cim.= 2.45 ton.
P= = 6.50 ton.
PT = 8.94857 ton.
Momentos en direccin X

zapata = 1.80 x 0.50 = 0.90 ton-m


dado = 0.29 x 0.50 = 0.14 ton-m
relleno = 0.36 x 0.50 = 0.18 ton-m
P= 6.50 x 0.50 = 3.22 ton-m
MRY = 4.44 ton-m
Momentos en direccin Y

zapata = 1.80 x 0.75 = 1.35000 ton-m


dado = 0.29 x 0.75 = 0.218700 ton-m
relleno = 0.36 x 0.75 = 0.267728 ton-m
P= 6.50 x 0.75 = 4.875000 ton-m
MRX = 6.71143 ton-m
Revisin de la estabilidad

MVX = MY+ VX(Df+h) MVX = 0.00 ton-m


Momentos de volteo
MVY = MX+ VY(Df+h) MVY = 0.31 ton-m

Mex = MRY Mex = 4.44 ton-m


Momentos de equilibrio
Mey = MRX Mey = 6.71 ton-m

Factor de seguridad al volteo

FSvx = Mex / Mvx FSvx = #DIV/0! > 1.5 #DIV/0!

FSvy = Mey / Mvy FSvy = 21.51 > 1.5 OK

Esfuerzos de contacto sobre el suelo.

Propiedades de la zapata
AR = A x B AR = 1.500 m2

AB 3 AB 2
IX = 0.281 m4 SX = 0.375 m3
12 6
BA 3 m4 BA 2 m3
IY = 0.125 SY = 0.250
12 6
DISEO DE ZAPATA Z1

Esfuerzo Maximo

Momento total alrededor de X

M ' x M vy P b3 0.312 ton-m

Momento total alrededor de Y

M ' y M vx Pa3 0.033


ton-m

PT M' y M' x
q1 (A/ 2) (B / 2) 6.668 ton/m2
AR Iy Ix
PT M ' y M' x
q2 ( A/ 2) (B / 2) 6.928 ton/m2
AR Iy Ix
PT M' y M' x
q3 (A/ 2) (B/ 2) 5.004 ton/m2
AR Iy Ix
PT M' y M' x
qc (A/ 2) (B/ 2) 5.264 ton/m2
AR Iy Ix

q mx.= 6.93 ton/m2 < qadm = 10.00 ton/m2

q min.= 5.004 ton/m2 No hay tensiones

Los esfuerzos sern los siguientes:

PT M ' x M' y
qa ( y) ( A / 2) q a= 6.25 ton/m2
AR 7 Ix Iy
PT M ' x M' y
qb ( y) ( A / 2) q b= 6.51 ton/m2
AR Ix Iy
PT M ' x M' y
qc ( B / 2) ( x) q c= 6.86 ton/m2
AR Ix Iy

PT M ' x M' y q d= 5.20 ton/m2


qd (B / 2) ( x)
AR Ix Iy
Si consideramos para diseo un ancho unitario de 1.0 mts.

Peso de relleno w = ( Df - h ) x gs x 1.0 = 0.326 ton/m


Peso de zapata w = h x 2.40 x 1.0 = 1.2 ton/m
=========
peso total wt = 1.526 ton/m
DISEO DE ZAPATA Z1

Diseo a lo largo del eje X


Interpolando el esfuerzo al pao de la columna en el plano a-b
A
q1(a-b) = 6.252 ton/m2 a1 a a2 h'
q2 (a-b) = 6.325 ton/m2
q3 (a-b) = 6.442 ton/m2
q4 (a-b) = 6.512 ton/m2 wt

Momentos en los paos (puntos 2 y 3) Df d d


Mp2 = 0.1862 ton-m
Mp3 = 0.181 ton-m h

Cortantes a un peralte del paos (puntos 1 y 4)


qb
Vp1 = 1.323 t
Vp4 = 1.346 t
q3 q4
qa q2
Se tomaran los elementos mcanicos mayores q1

Mp = 0.186 ton-m Mpu = Mp x Fc Mpu = 0.261 ton-m


Vp = 1.323 ton
Vpu = Vp x Fc Vpu = 1.852 ton

Flexin
si tenemos que: b= 100 cm FR = 0.9 para flexin
d= 40 cm
h= 50 cm
f ''c 2Mpu
1 1 r= 0.00004
fy FRbd 2 f ' ' c
rmax > r rmin entonces r = 0.002415 0.00004

As = rbd As = 9.66 cm2/m

se propone usar varillas # 1/2 pulg Av = 1.27 cm2

100 Av
S S= 13.1 cm
As

usar varillas del # 1/2 @ 12.5 cm


DISEO DE ZAPATA Z1

Cortante por tensin diagonal


Vcr FRbd.(0.2 20). f *C Vcr 0 . 5 F R bd . f *C
100 Av
As As = 10.1 cm2/m
S
As r= 0.0025335

bd
Vcr = 10397 kg
Vcr = 10.397 ton > Vpu = 1.852 Ok

Diseo a lo largo del eje Y


Interpolando el esfuerzo al pao de la columna en el plano c-d
B
q1(c-d) = 6.863 ton/m2 b1 b b2 h'
q2 (c-d) = 6.531 ton/m2
q3 (c-d) = 5.532 ton/m2
q4 (c-d) = 5.199 ton/m2 wt

Momentos en los paos (puntos 2 y 3) Df d d

Mp2 = 0.24 ton-m


Mp3 = 0.17 ton-m h

Cortantes a un peralte del pao (puntos 1 y 4) qd


Vp1 = 1.601 t
Vp4 = 1.102 t q4
qc q3
q2
q1
Se tomaran los elementos mcanicos mayores

Mp = 0.235 ton-m Mpu = Mp x Fc Mpu = 0.329 ton-m


Vp = 1.601 ton
Vpu = Vp x Fc Vpu = 2.242 ton

Flexin
si tenemos que: b= 100 cm FR = 0.9 para flexin
d= 40 cm
h= 50 cm

f ''c 2Mpu
1 1 r= 0.00005
fy FRbd 2 f ' ' c
rmax > r rmin entonces r = 0.002415 0.00005

As = rbd As = 9.66 cm2/m


se propone usar varillas # 1/2 Av = 1.27 cm2

100 Av
S S= 13.1 cm
As

usar varillas del # 1/2 @ 12.5 cm


DISEO DE ZAPATA Z1

Cortante por tensin diagonal

Vcr FRbd.(0.2 20). f *C Vcr 0 . 5 F R bd . f *C

100 Av
As As = 10.1 cm2/m
S
As r= 0.0025335

bd
Vcr = 10397 kg
Vcr = 10.397 ton > Vpu = 2.242 Ok

Acero por cambios volumtricos


Este acero se coloca en el lecho opuesto al acero por flexin en ambos sentidos y solo si h es mayor o igual a15 cm

As = 0.003bd As = 12.00 cm2/m

se propone usar varillas # 1/2 Av = 1.27 cm2

100 Av
S S= 10.6 cm
As
usar varillas del # 1/2 @ 10 cm
Cortante por penetracin
Y
columna
o dado

d/2 C1 = 45 cm
C2 = 90 cm

c2+d C2 X C1 + d = 85 cm
C2 + d = 130 cm

d/2 proyeccin de la superficie


que resiste la penetracin

d/2 C1 d/2

C1+ d

Elementos mecanicos en el espesor medio de la zapata.

Superestructura = .................................................................... = 6.500 ton.


Relleno ----------- = [ ( C1+ d ) ( C2+d ) - (C1 x C2 ) ] x (Df - h) x gs = 0.228 ton.
zapata ------------ = ( C1 + d ) (C2 + d ) x h x 2.40 .......................... = 1.326 ton.
=======
P= 8.054 ton.
DISEO DE ZAPATA Z1

En direccin X y Y

Mx = Mx + Vy ( Df - 0.5h ) Mx = 0.218 ton-m

My = My + Vx ( Df - 0.5h ) My = 0.000 ton-m

Esfuerzo por penetracin


P x My(C1 d ) y Mx(C 2 d )
v
Ac 2 Jcy 2 Jcx
1
x 1 ax = 0.35
C1 d
1 0.67
C2 d
1
y 1 ay = 0.45
C2 d
1 0.67
C1 d

Ac 2d(C1C22d) Ac = 17200 cm
2

d(C2 d)3 (C2 d)d3 d(C1 d)(C2 d)2


Jcx Jcx = 4.5E+07 cm
4

6 6 2
d(C1 d)3 (C1 d)d3 d(C2 d)(C1 d)2
Jcy Jcy = 2.4E+07 cm
4

6 6 2
Sustituyendo valores:
v= 0.5 kg/cm2

El esfuerzo ltimo por penetracin sera: vu = v x FC vu = 0.68 kg/cm2

Esfuerzo resistente del concreto

vCR FR f c * vCR = 9.07 kg/cm2

vCR = 9.07 kg/cm2 > vu = 0.68 kg/cm2 Ok

Por lo tanto, el espesor de la zapata propuesto es correcto.


Planta B' DISEO DE ZAPATA Z1

100
El armado esquematicamente queda de la siguiente manera vars 12"@.125
Dado
30
vars 12"@.125
70
50

100
vars 12"@.125
Plantilla f'c=100kg/cm2
90
Corte A-A' e=15cm
150

vars 12"@.125

vars 12"@.125
A A' 70
30 50

150
28 45 28 Plantilla f'c=100kg/cm2
vars 12"@.125 e=15cm
B Corte B-B'
DISEO DE VIGA DE CONEXIN
A= 1
B= 1.5
a= 0.45 origen= 0.50
b= 0.90
L= 4m
P= 6.50 Ton
h = L = 0.571 m
7 h/2= 0.2857
b = P1 = 0.052 m
31*L

Usar: b x h = 0.25 x 0.60 m

PESO PROPIO DE LA VIGA DE CONEXIN


Wv= 0.25 * 0.6 * 2.4 = 0.36 Tn/m

DISEO DE LA VIGA DE CONEXIN

P1U = 9.10 Tn
wv = 0.50 Tn/m
2

wnu
1.00 RN = reaccion neta de la zapata exterior

Rnu
0.500
3.725
0.5 4.00

P1U = 9.10 Tn
Wvu = 0.504 Tn/m

M2= 0
RNU *3.725=P1U * 4+0.504*4.5/2
RNU = 11.1417 Tn

WNU = RNU = 11.142 Tn/m


S1
SECCION DE MOMENTO MAXIMO, Xo S

Vx=(Wnu-Wvu)Xo-P1U=0

Xo = 0.855 m < S = 1.00 m CONFORME

=
2 2

Mumax = -1.8448 Tn-m

As = 1.0274 cm
=
2

a = 0.97 cm
=
0.85

As = 0.82 cm a = 0.772 cm
As = 0.819 cm a = 0.771 cm
As = 0.819 cm a = 0.771 cm
As = 0.819 cm a = 0.771 cm CONFORME

USAR: 0.41 3 5/8 "

r = 0.004
=

14 rmin = 0.0033
=

r > rmin CONFORME


REFUERZO EN LA CARGA INFERIOR

= ,
3 2

As = 2.969 cm
Asmin = 4.375 cm

COMO As < Asmin USAR: 2.2103 3 5/8 "

ESQUEMA DE DISTRIBUCION DE ACERO

3 5/8 "

3 5/8 "

DISEO POR CORTE

P
d V2U
W VU

W NU

= +

V1U = 6.08857226 Tn

V2U = 1.53774497 Tn

Vu = 1.54 = 1.8091 Tn
0.85
= 0.53

Vc = 10.1343 Tn Vn < Vc
CONFORME

USAR :Estribo de montaje S 36*f S 68.76 cm


Estribo: f 3/8" @ 0.65 m
5.0 CONCLUSIONES Y RECOMENDACIONES

La columna reticulada compuesta por:


Brida superior : Tubo cuadrado 4"x4"x2.5mm
Brida inferior : Tubo circular 3"x3mm
Diagonales : Barra lisa 3/4"
Vigas : Tubo rectangular 4"x2"x2mm

Cumplen con los requisitos resistentes frente a cargas de viento y sismo


exigidos.

El diseo de Zapatas 1.00x1.50x0.50 m y vigas de cimentacin 0.25x0.60


cumplen con los requisitos de diseo de cimentaciones segn el RNE-
E060.
Se recomienda agregar arriostres tipo aspa entre parantes para
contener posibles efectos de carga lateral.
Se recomienda reforzar el Tubo 100x100x2.5 aumentando su espesor
para el segundo tramo de altura (a partir de los 6 metros en los pilares
intermedios).
Se recomienda usar malla geo sinttica para evitar filtraciones de sales
o sulfatos que afecten al cimiento
Se recomienda usar para las zapatas, vigas de cimentacin y pedestal
conccreto de resistencia a la compresin de 210 Kg/cm2 de cemento
Portland tipo V Tipo IP (uso para zonas con presencia de sales y
sulfatos agresivos).
Con esto, la estructura cumple con la filosofa y principio de diseo
segn el RNE vigente.

14