Escolar Documentos
Profissional Documentos
Cultura Documentos
KTS valve is a supply air valve for ceiling mounting in offices, houses etc.
ceiling or free space mounting
directional air pattern
good adjusting features
easy measurement of the air flow
ABB Flkt Oy
Division Lapinleimu ABB
ABB KTS Supply air valve
CONSTRUCTION INSTALLATION
The KTS is manufactured from sheet steel and stove Mounting ring KKK, KKL or KKT is fitted into the
enamelled in white. Other colours are available to special duct with screws or rivets. The valve is fitted into the
order. valve by a screwing action to locate lugs into indents
The body is equipped with cellular plastic gasket to in the mounting ring. The valve can also be fitted with
form an airtight seal with the mounting ring. The valve springs (model KTS-J) and the mounting ring is not
is equipped with a sector plate for direction of the air needed.
flow.
Adjustment of the valve or sector plate is achieved by ACCESSORIES
simply rotating the disc and/or sector plate to the desired
setting and secured by means of a single lock nut. In order to protect the ceiling an extra protection plate
SL and extension collar KR are available, both made of
DIMENSIONS sheet steel and stove enamelled white. The protection
plate is fitted between the air valve and the ceiling, outer
diameter 315 mm.
The depth of the extension collar is 50mm.
s (mm)
B
OF AIR FLOW
Product
Size
Protection plate
D2
D2
Mounting ring
d
DIFFUSION PATTERN
2 KTS.2
KTS Supply air valve ABB
SELECTION DIAGRAM
pt (Pa)
qv(l/s) qv(l/s)
3
qv(m /h) qv(m3/h)
pt (Pa)
qv(l/s) qv(l/s)
qv(m3/h) qv(m3/h)
pt (Pa)
qv(l/s) qv(l/s)
qv(m3/h) qv(m3/h)
KTS without sector plate The average sound attenuation L from duct to room
including the orifice attenuation of the connecting duct
CORRECTION Koct (dB) in ceiling installation, is obtained in the table above.
KTS Middle frequency by octave band (Hz)
DESCRIPTIONS
125 250 500 1000 2000 4000 8000
100 -2 2 1 -1 -4 -5 -11 qv air volume (l/s),(m 3/h)
125 4 5 3 -1 -11 -17 -29 p t total pressure drop (Pa)
160 7 6 3 -2 -11 -19 -32 L p10A sound pressure level with 4 dB
Toler. 3 2 2 2 2 2 3 room attenuation (10 m2sab) [dB(A)]
L 0,2 throw corresponding 0,2 m/s
final velosity (m)
Sound power levels by octave bands are obtained by
Lw oct sound pressure level (dB)
adding to total sound pressure level Lp10A, dB(A) the
L sound attenuation (dB)
corrections Koct presented in the table according to the
Koct correction (dB)
following formula:
t temperature difference between
the supply air and the room air (C)
L w oct = Lp 10A + Koct
ABB
ABB Flkt Oy
Division Lapinleimu
P.O.Box 6
FIN-37801 TOIJALA, FINLAND
tel.int. +358 10 22 3001
telefax int. +358 10 22 37217 KTS/ENG/FIFLO 07.98/2500/Tekstitaso Oy & Offset/All rights reserved.