Você está na página 1de 6

engineers newsletter providing insights for todays

hvac system designer

ASHRAE/IESNA 90.11999 update


90.1 Ways to Save Energy
from the editor
Five years have elapsed since we last
devoted an Engineers Newsletter to
A ctually, ASHRAE/IESNA Standard
90.11999 offers many more than
90 ways to save energy. This article
Whats new in Standard 90.1
1999? Reorganized for ease of use, the
new standard clarifies requirements
one of the most far-reaching standards shares some of them, with particular and provides a simplified compliance
in the building industry: Standard 90.1, attention to the standards effect on the path for small commercial buildings.
Energy Standard for Buildings Except design of HVAC systems. First, More importantly, the 1999 edition
Low-Rise Residential Buildings. The however, lets briefly review the expands the standards scope to
then-proposed revision was approved in purpose and scope of the standard, include new and existing buildings and
1999, and the first printed copies were how the 1999 edition differs from its building systems. For alterations and
made available at ASHRAEs winter predecessor, and what compliance additions, the 90.1 Users Manual notes
2000 meeting in Dallas. It was an entails. that, In general, the Standard only
immediate selloutand with good applies to building systems and
reason. Each day brings new concerns equipmentthat are being replaced.
about finite natural resources, waste,
soaring energy costs, and global Energy-Efficient Buildings Other improvements to the standard
warming. As its title and purpose suggest, the include information for a broader range
objective of Standard 90.1 is to of climate locations and separate
Standard 90.1 is a national consensus provide minimum requirements for editions for inchpound (IP) units and
standard that was developed jointly by the energy-efficient design of the International System of Units (SI).
the American Society of Heating, commercial buildings. It does not apply Also, a life-cycle-cost analysis was used
Refrigerating and Air-Conditioning to low-rise residential buildings, which to define the criteria in the 1999 edition
Engineers, Inc. (ASHRAE) and the are covered under Standard 90.2. and thereby balance energy efficiency
Illuminating Engineering Society of with economic reality.
North America (IESNA). It sets
minimum requirements to promote the Standard 90.11999 What does compliance entail?
principles of effective, energy- includes alterations Standard 90.11999 addresses building
conserving design for buildings and components and systems that affect
building systems. of, and additions to, energy usage. The technical sections of
buildings and the the standard, Sections 5 through 10,
Why revisit this topic now? For two specifically address components of the
reasons. The minimum equipment
systems they entail. building envelope, HVAC systems and
efficiencies required under ASHRAE/ equipment, service water heating,
IESNA 90.11999 become effective power, lighting, and motors. Each
after October 29, 2001. Also, after a Moreover, Standard 90.1 focuses technical section contains general
year of comparative analyses with the on comfort conditioning rather than requirements and mandatory
1989 edition, the U.S. Department of industrial, manufacturing, or provisions; some sections also include
Energy is about to release a commercial processes. Note, too, that prescriptive and performance
determination that could require states the stated purpose of the standard is to requirements.
to adopt codes at least as stringent as provide minimum requirements; a
those in the 1999 standard. designer or owner can always exceed For example, Section 5, Building
these basic conditions for compliance. Envelope, addresses walls, roofs,

2001 American Standard Inc. All rights reserved Volume 30, No. 1
floors, and fenestration. U-factors, Figure 1. Compliance Paths for ASHRAE/IESNA 90.11999
solar-heat-gain coefficients, and
allowable areas define both prescriptive prescriptive
and performance
and performance criteria based on
requirements
climate, space conditioning category
general
(residential, nonresidential, and
and mandatory
semiheated), and construction class. provisions
The 1999 standard organizes all proposed Energy Cost 90.1-compliant
prescriptive requirements in a single building design Budget (ECB) building
method
table.

In Section 9, Lighting, the 1999


standard consolidates all lighting power energy cost of a base design that fulfills Section 6 of ASHRAE/IESNA 90.11999
requirements on a single page. Design the prescriptive requirements. Using describes mandatory and prescriptive
professionals will notice lower power the ECB approach requires simulation requirements for commercial heating,
inputs for most building categories, software that can analyze energy ventilating, and air-conditioning
plus the addition of mandatory lighting consumption in buildings and model systems. It also defines three methods
controls. Fewer exempt areas are the energy features in the proposed for compliance:
permitted in and around the building, design. Standard 90.1 sets minimum
too. requirements for the simulation A Prescriptive Path, which
software; suitable programs include comprises mandatory provisions and
To comply with Standard 90.11999, BLAST, DOE-2, and TRACE. prescriptive requirements
the prospective design must first
An Energy Cost Budget Method,
satisfy the general requirements and
which combines mandatory
mandatory provisions of each technical
provisions and a computerized
section. But thats not all. The design Energy-Conscious Comfort methodology that permits tradeoffs
must either (a) fulfill the prescriptive What is now the HVAC section of between various building systems
and performance requirements Standard 90.1, Section 6, represents a and components
described in each technical section or substantial reorganization of several
(b) satisfy the energy cost budget (ECB) sections in the 1989 edition. It presents A Simplified Approach Option,
method; see Figure 1. HVAC-related requirements in order of which consists of a subset of all
complexity, beginning with the simplest mandatory provisions and
The ECB method permits tradeoffs and most common design obligations. prescriptive requirements
between building systems (lighting and Because the HVAC section is 21 pages
fenestration, for example) if the annual (and this newsletter is not), this article For small buildings, the simplified
energy cost estimated for the proposed limits itself to summarizing the key approach consolidates the provisions
design does not exceed the annual requirements. EN editor on roughly two pages so that design
professionals can quickly locate all
applicable requirements. As Figure 2
Figure 2. Compliance Paths for HVAC Design under ASHRAE/IESNA 90.11999 implies, stringency is equivalent to the
Prescriptive Path; the difference lies in
mandatory prescriptive ease of use and the degree of flexibility
provisions requirements allowed. Eligibility for this approach
requires that the building occupy less
Energy Cost
than 25,000 ft2 of gross floor area and
Budget (ECB) not more than two stories. Another
method prerequisite (there are others) is that
Simplified
each air-cooled or evaporatively cooled
Approach HVAC system serves only one zone.
(small buildings only)
Option
proposed HVAC design 90.1-compliant HVAC system

(continues inside flap)

2 Trane Engineers Newsletter Vol. 30, No. 1


Mandatory HVAC Provisions. Table 1. Comparison of Equipment Efficiencies (90.11989 versus 90.11999)
Mandatory requirements for HVAC
Minimum Efficiency a
systems include mechanical equipment
Equipment Type Per 90.11989 After 29-Oct-2001 Test Procedure
efficiencies, controls, construction,
Rooftop air conditioner, 15 tons 8.5 EER b 9.7 EER b ARI 340/360 c
insulation, and completion. These
requirements are an integral part of Water-source heat pump, 4 tons 9.3 EER 12.0 EER ARI 320 d
(cooling mode) (85F EWT) (86F EWT) (ARI/ISO-13256-1
every compliance path. after 29-Oct-2001)
Water-cooled screw chiller, 125 tons 3.80 COP 4.45 COP ARI 590 e
Mechanical equipment efficiency. 3.90 IPLV 4.50 IPLV
The 1999 standard revises the Water-cooled centrifugal chiller, 300 tons 5.20 COP 6.10 COP ARI 550 e
minimum efficiency requirements for 5.30 IPLV 6.10 IPLV e
many types of HVAC equipment and a Coefficient of performance (COP), energy efficiency ratio (EER), entering water temperature (EWT), integrated part-load
adds efficiency requirements for heat- value (IPLV)
b Deduct 0.2 from the required EER if the rooftop air conditioner includes a heating section other than electric resistance heat.
rejection equipment, ground-source
c ARI 340/360, Commercial and Industrial Unitary Air-Conditioning and Heat Pump Equipment
heat pumps, and absorption chillers.
d ARI 320, Water-Source Heat Pumps
Standard 90.11999 also provides
e Near the end of the ASHRAE/IESNA 90.11999 approval process, the Air-Conditioning and Refrigeration Institute (ARI)
tables for centrifugal chillers selected at combined and replaced ARI 5501992 and ARI 5901992 with ARI 550/5901998, Water Chilling Packages Using the Vapor
nonstandard conditions (leaving chilled Compression Cycle. As a result, the committee responsible for the continuous maintenance of Standard 90.1 released
Addendum 90.1j, which revised the efficiencies for subject chillers to reflect the new part-load rating method in ARI 550/
water temperatures, entering 5901998. Although the addendum raises the IPLV requirements for electrical chillers (from 6.10 to 6.40 for the 300-ton
condenser water temperatures, or water-cooled centrifugal chiller in this example), full-load requirements remain unchanged. Adoption of the addendum
appears imminent because the public review period held last summer (2000) did not elicit comments.
condenser water flow rates).

For equipment covered under the Shutoff damper controls that of sense. Even if an engineer designs a
previous edition, the 1999 standard automatically close when the great system, its unlikely that energy
allows the present (1989) efficiencies systems or spaces served are not in savings will accrue if the operator
until October 29, 2001. After that time, use (These dampers must also have doesnt know how the system should
new requirements take effect. Table 1 a maximum allowable leakage rate.) work.
compares before and after
Zone isolation capabilities that
minimum efficiency ratings for several The standard also addresses balancing
permit areas of the building to
types of equipment. The following for air systems larger than 1 hp and for
continue operating while others are
requirement becomes critical if two or hydronic systems larger than 10 hp. It
shut down
more rating conditions are cited: also requires control elements to be
Automatic shutdown calibrated, adjusted, and in proper
Where multiple rating conditions or working condition for buildings that
Setback controls
performance requirements are provided, exceed 50,000 ft2.
the equipment shall satisfy all stated Optimum start controls after the
requirements, unless otherwise system airflow exceeds 10,000 cfm
exempted by footnotes in the table. Prescriptive HVAC Requirements.
[Section 6.2.1] Under the Prescriptive Path, a
Construction, insulation, and prospective HVAC design must satisfy
In the case of the centrifugal chiller completion. Mandatory HVAC specific prescriptive requirements in
in Table 1, both the full-load COP and requirements also address construction addition to the mandatory provisions
IPLV must be 6.10 or better, that is, (duct sealing, leakage tests) and reviewed above.
0.576 kW/ton or less. [kW/ton = insulation of ducts and piping. Climate
3.516 /COP] and placement dictate insulation Economizers. Climate and equipment
requirements for ducts; for piping, the size dictate the prescriptive
Controls. The 1999 standard also requirements depend on pipe location requirements for airside and waterside
contains extensive HVAC control and the operating temperature range of economizers. Table 2 offers examples
requirements regarding deadbands, the fluid. of economizer requirements for several
restrictions for set-point overlap, and locations.
off-hour controls. Stipulations for off- Drawings, manuals, and a narrative of
hour controls include all of the system operation must be supplied to The economizer must also be
following the building owner which makes a lot integrated, that is, capable of operating

providing insights for todays HVAC system designer 3


trim for foldout
in conjunction with mechanical Air system design and control. pressure set point can be reduced
cooling. In addition, the pressure Fan power limitations, now dynamically, which lets energy
drop of the waterside economizer expressed in terms of nameplate savings accrue rapidly. (For more
must be less than 15 feet of water or power, must be met when the total information, see VAV System
a secondary loop must be created to fan power for the system exceeds Optimization: Critical Zone Reset,
avoid its pressure drop altogether 5 hp. The 1999 standard increases Engineers Newsletter 202, 1991.)
when the economizer is not in use. the power allowance to compensate
for pressure increases imposed by Hydronic system design and
An economizer can be omitted from specific filtration or heat-recovery control. Like the fan on the air side
unitary equipment if its performance devices and when the supply-air of the system, the 1999 standard
is efficient enough. For example, the temperature is less than 55F. requires that the pump in a variable-
requirement for a 20-ton rooftop air flow system draws substantially less
conditioner in Tucson, which has Fans of 30 hp and larger must use power at part load. Unless there are
6,921 Cooling Design Daysbase 50 less than 30 percent of design three or fewer control valves in the
(CDD50), is 9.7 EER. If the EER of power at 50 percent of design air system, each pump with a head
the selected rooftop air conditioner volume and at one-third of the total greater than 100 feet and a motor
is 11.1 or better, an economizer is design static pressure. This larger than 50 hp must include a
unnecessary. requirement will almost certainly means for reducing electrical
prompt increased use of variable- demand to 30 percent of design
Simultaneous heating and speed drives or vaneaxial fans in power at 50 percent of design water
cooling. Although the 1999 systems of this size. flow. This requirement will
standard limits this practice, it does undoubtedly prompt greater use of
not ban simultaneous heating and Another notable addition to this set variable-speed drives.
cooling. Exceptions provide of prescriptive requirements is the
sufficient flexibility to maintain either following: Supply-temperature reset is
temperature or humidity control. For required, toobut not for variable-
example, unlimited reheat is 6.3.3.2.3 Set Point Reset. For flow systems nor where it
permitted if at least 75 percent of systems with direct digital control of cannot be implemented without
the reheat energy originates from a individual zoned boxes reporting to causing improper operation of
site-recovered or on-site solar the central control panel, static heating, cooling, humidifying or
pressure set point shall be reset
energy source. Such provisions dehumidifying systems.
based on the zone requiring the most
should increase the popularity of
pressure; i.e. the set point is reset
heat-recovery designs that salvage lower until one zone damper is nearly
Heat-rejection equipment. For
heat from the condenser in an wide open. heat-rejection equipment such as
applied chilled-water system or a cooling towers, the fan must be able
desuperheater in a direct-expansion Also known as fan-pressure to reduce its speed to two-thirds or
system. optimization, the basic premise of less if its motor is 7.5 hp or larger.
set point reset is that the static- Beyond this power limit, a cooling
tower with less than two cells must
be equipped to reduce fan speed on
Table 2. Example Economizer Requirements from ASHRAE/IESNA 90.11999 a all cellsperhaps with pony motors,
1% Time at two-speed motors, or variable-speed
Cooling-Design 55F < OATdb < 69F System Size that drives. If the cooling tower has three
Locale WB from 8 a.m.4 p.m. Requires an Economizer
cells, at least two of them must be
Chicago, Ill. 73F 613 hr 135,000 Btu/h
equipped with speed control.
Denver, Colo. 59F 739 hr 65,000 Btu/h
Miami, Fla. 77F 259 hr No economizer required Energy recovery. Systems larger
Minneapolis, Minn. 71F 566 hr No economizer required than 5,000 cfm that bring in lots of
New York, N.Y. 73F 790 hr 135,000 Btu/h outdoor air (at least 70 percent of
San Francisco, Calif. 62F 1,796 hr 65,000 Btu/h
trim for foldout

Tucson, Ariz. 65F 716 hr 65,000 Btu/h


a Wet-bulb (WB) temperature, outdoor-air dry-bulb temperature (OATdb )

providing insights for todays HVAC system designer 4


trim for foldout

(continued from inside)

design airflow) must include energy 6 million Btu/h, and where the Energy Codes. The Energy Policy
recovery; the means of recovery service-water heating load exceeds Act or EPAct (P.L. 102-486) requires
must be at least 50-percent 1 million Btu/h. states to certify that their energy
effective. This proviso will probably codes meet or exceed the
lead to the increased use of energy The 1999 standard also requires requirements of ASHRAE Standard
recovery in air handlers dedicated to radiant heating for unenclosed 90.11989. EPAct also requires that
ventilation, particularly in retrofit spaces and exhaust-hood control to the U.S. Department of Energy
applications in which ventilation reduce energy consumption at part- (DOE) evaluate subsequent revisions
airflow is brought into compliance load conditions. of Standard 90.1 to determine
with ANSI/ASHRAE 62.1. whether they improve energy
efficiency in commercial buildings.
Exceptions to this airside The DOE analyzed the 1999 edition
requirement include (but are not last year and recently drafted its
limited to) series-style energy How Will 90.11999 determination; when this EN was
recovery and systems in which the Affect You? printed, the draft was undergoing an
largest exhaust air stream is less Apart from the specific influences internal review. Upon its release, the
than 75 percent of design outdoor on HVAC designs just described, DOEs determination could require
airflow. ASHRAE/IESNA 90.1 will almost states to adopt codes at least as
certainly prompt increased vigilance stringent as the 1999 standard.
Heat recovery for service water from professionals in the building
heating is required in facilities that and building systems communities. ASHRAE/IESNA 90.11999 has
operate 24 hours a day, where the The reasons are twofold: energy already been approved for inclusion
heat rejection capacity exceeds codes and continuous in the International Code Councils
maintenance of the standard. model code, which currently
references the 1989 edition. (The
ICC represents the International
Conference of Building Officials,
A Quantifiable Increase in Energy Efficiency ICBO; Building Officials and Code
The U.S. DOE posted the results of its Both the report and SSPC 90.1, the Administrators, BOCA; and the
quantitative analysis on its Web site, ASHRAE committee responsible for Southern Building Code Congress
www.eren.doe.gov. Titled Commercial maintaining the standard, acknowledge
International, SBCCI.) In a related
Buildings Determinations that increased efficiency is not
Explanation of the Analysis and necessarily true for all building types press release, ASHRAE President
Spreadsheet, the report observes that nor for all components and systems. In James E. Wolf noted that the ICCs
Overall, considering those differences some instances, the 1989 standard was adoption of the 1999 standard
that can be reasonably quantified, the either unjustifiably stringent (metal recognizes the incorporation of
1999 edition [of ASHRAE/IESNA roofs, for example) from a cost
new technologies, increased energy
Standard 90.1] will increase the energy standpoint or did not adequately reflect
efficiency of commercial buildings. real-world conditions (warehouse savings, and easier use.
lighting).
The significance of Standard 90.1
Estimated Energy Savings with ASHRAE/IESNA 90.11999 1999s inclusion in the ICC energy
Percentage Change in Whole-Building Energy Use Intensity (EUI) code is far-reachingand perhaps
Floor Area
Building Type Weighting Electricity Gas Site EUI Source EUI $UI (USD) immediate, depending on your
Assembly 0.068 9.5 5.3 4.4 7.2 7.5 location. As of January 1, 2001,
Education 0.218 11.4 6.3 5.2 8.6 9.0 Massachusetts had actually
Food 0.027 1.2 1.7 0.4 0.8 0.9 incorporated the 1999 standard (with
Lodging 0.079 0.2 6.5 1.7 0.6 0.5
minor modifications) into its state
Office 0.190 10.6 12.7 8.2 9.7 9.8
energy code. Many other states
Retail 0.246 15.7 30.7 12.7 14.7 14.9

Warehouse 0.173 71.6 11.3 45.1 58.7 59.7

National 1.000 7.3 8.6 3.9 5.9 6.2


trim for foldout

(continues on back)

5 Trane Engineers Newsletter Vol. 30, No. 1


including California, Kentucky, South contractors, and engineers to monitor
Carolina, and Wisconsinare currently the standards activity closely.
considering its implementation.

Put simply, state and local code-writing


bodies are quickly accepting ASHRAE/ Closing Thoughts By Mick Schwedler, PE, applications
IESNA 90.11999 as the standard of ASHRAE/IESNA 90.11999 sets a new engineer, and Brenda Bradley,
care in their jurisdictions. (When this standard for energy consumption in information designer, The Trane
EN went to press, the February 2001 commercial buildings. Its impact is real; Company. (Mick served more than
ASHRAE Journal announced the it is already being included in state and five years as a member of ASHRAE
standards adoption by the American model building codes. Make sure that SSPC 90.1.)
National Standards Institute, ANSIa youre aware of the standard, its
fact that should further accelerate implications, and how it affects the You can find this and other issues of
widespread acceptance.) designs you use to satisfy your clients. the Engineers Newsletter in the
Implement the standards minimum commercial section of www.trane.com.
Continuous Maintenance. As a requirements as the basis for future To comment, send a note to The Trane
continuous-maintenance standard, designsthen apply your engineering Company, Engineers Newsletter Editor,
ASHRAE/IESNA 90.1 remains a and business acumen to determine the 3600 Pammel Creek Road, La Crosse,
dynamic document. Rather than extent to which it is prudent to exceed WI 54601, or e-mail us from the Trane
periodic updates (every five years, for those minimum standards. Web site.
example), committee members can
request changes to the standard at any
time. Public proposals submitted by
February 20 are considered at the How to Learn More about ASHRAE/IESNA 90.11999
ASHRAE annual meeting (usually held
Read the new 90.1 Users Manual broadcast last September, the two-hour
in June). If the committee sees merit in (ISBN 1-883413-79-6) published by program reviews the general requirements
a proposed change, it issues an ASHRAE and cosponsored by IESNA. The of the standard and specifically addresses
addendum for public review and users manual effectively combines the envelope, HVAC, and lighting sections.
comment. When consensus is reached, explanations of requirements with
illustrations and examples of systems that To order the videotape and/or view the
the addendum is incorporated in the
demonstrate compliance and non- presentations and a transcript of the
standard. compliance with the standard. A CD-ROM ensuing question-and-answer session,
accompanies the manual. It contains visit:
Twenty-nine addenda were released for EnvStd 4.0 software to aid the calculation www.eren.doe.gov/buildings/codes_standards/
of building envelope tradeoffs, as well as a buildings/satellite_post.html
public review and comment last
complete set of electronic compliance
summer. Only 12 of these elicited
forms and worksheets. Attend training. ASHRAE hopes to
comments (to which the committee is follow up the short courses offered last
responding) and one addenda was Both the standard and the 90.1 Users year with a two-day course on all sections
withdrawn. Adoption of the other 16 Manual are available from ASHRAE at of the standard as part of its ASHRAE
addenda is likely to occur soon. From www.ashrae.org/bookstore. Member/ Professional Development Series. The
nonmember pricing is $75/$98 USD for the request for proposal issued in November
this activity, its clear that Standard 90.1
standard and $59/$75 USD for the users calls for completion in September 2001
will be revised more often. For this manual. (Be sure to check the ASHRAE and delivery during the 2002 ASHRAE
reason, we encourage building owners, Web site for errata information.) winter meeting. For more information
about the course or about Standard 90.1,
Watch a videotape of the U.S. Department contact ASHRAE at www.ashrae.org, or
call them at 800-527-4723 (U.S. and
of Energy telecast, Standard 90.11999:
The Next Generation of Commercial Canada) or 404-636-8400.
Building Energy Standards. Originally

The Trane Company


An American Standard Company
www.trane.com
Trane believes the facts and suggestions presented here to be accurate. However,
For more information, contact your
local district office or e-mail us at final design and application decisions are your responsibility. Trane disclaims
comfort@trane.com any responsibility for actions taken on the material presented.

6 ENEWS-30/1

Você também pode gostar