RELAY SETTING FORMAT

FORMAT NO MR /ENGG/07 Rev-0


Recommended settings for PRPD DEPARTMENT :
Relay type MICOM P741 & ENGINEERING
MICOM P743- 230kV CHKD REV DATE : 19.12.08
REV NIL : 0
Page 1 of 1
SUBSTATION : PUGALUR APPD

MICOM P741 :

KCZ 30%

IDCZ>2 1045A

K2 65%

ID>2 1045A

ID>1 70A

K1 0%

ID>1 Alarm Timer 5 Secs

CZ circ. flt mode Alarms latched

Zx circ. Flt mode Alarms latched

Circulatory reset 60 Secs

Circ block mode Blocking/ phase

CZ PU Error mode Alarms latched

Zx PU Error mode Alarms latched

PU Error timer 5 Secs

PU Error reset 60 Secs

MICOM P743 :

Phase CT Primary 1600A

Phase CT secondary 1A

Above Settings implemented as on date ___________

SIGNATURE (S/S INCHARGE)

Note :To return the signed copy to Engineering after implementation


RELAY SETTING FORMAT

FORMAT NO MR /ENGG/07 Rev-0


Recommended settings for PRPD DEPARTMENT :
Relay type MICOM P741 & ENGINEERING
MICOM P743- 230kV CHKD REV DATE : 19.12.08
REV NIL : 0
Page 1 of 1
SUBSTATION : PUGALUR APPD

RBph/RBN 1

Standard Input British Standard

Knee point voltage 1600V

RCT Sec 8 ohm

Effective burden of CT lead To be measured/verified at site

I> DZ Current Set 1045A

I> DZ Time Delay 50 msec

IN> DZ Current Set Disable

CB Fail :

Control by I<

I< 160A

CB Fail Timer 1 100 msec

CB Fail Timer 2 100 msec

CB Fail Timer 3 200 msec

CB Fail Timer 4 200 msec

Error Factor Kce 40%

Alarm Delay Tce 5 Sec

Above Settings implemented as on date ___________

SIGNATURE (S/S INCHARGE)

Note :To return the signed copy to Engineering after implementation