Escolar Documentos
Profissional Documentos
Cultura Documentos
k = 2/3. The thickness of the upper layer was varied and the
Where S11 is:
obtained simulated values were compared with those from
the Tagg formula [12], Table I. , , , , ,
TABLE I , ,
COMPARISON WITH TAGG FORMULA FOR UPPER LAYER ROD
Parameters/Results 1 SIM 2 SIM 3 SIM 4 SIM 2 1"
Upper layer thick, D (m) 4 6 9 11
# , ,
Resistance (Tagg),
154 160 163 164
2 "
k=-2/3 ()
Resistance Matrix Method,
with and # 1
155 159 161 162
k=-2/3 ( )
Error to Tagg (%) 0.6 0.6 1.2 1.2
Resistence (Tagg), For the grid shown in Fig. 1 the resistance was calculated
38.7 36.6 35.0 35.1
k=2/3 () considering that the resistivity of the upper layer is
Resist. Matrix Method, 3000 m, the resistivity of the lower layer is 22 m and the
37.9 36.0 35.0 34.7
k=2/3 () thickness of the upper layer is 0.2 m. The grid was buried to
Error To Tagg (%) 2.3 1.6 0.0 1.1
a depth of 0.6 m. Note that the conductors were considered
to have an area of 50 mm2 [13]. The obtained value of the
resistance using the software program developed was
The results are close to those from Tagg formula. It is 0.924 . This value has an error of 7.6% for the 1
interesting to note that when the thickness of the upper layer measured value, and a deviation of 5.4% for the 0.987
is 11 m, and considering the IEEE model [12], which is calculated value [13].
entirely in the referred layer, since the zero volt
equipotential will be at 3+7.6 m depth, so the result will be
similar to that obtained in homogeneous soil with resistivity
equal to that of the upper layer. In fact, for homogeneous
soil, in the first case k = -2/3, a rod with these characteristics 6m
has a resistance of 167 using Dwight formula [12]. For
k = 2/3 the same formula obtains a value of 33.5 .
B. Horizontal buried conductor
The analysis of horizontally buried conductors in the 12 m
upper layer was also considered. A horizontal electrode with Fig. 1. Buried Grid
10 m length and 50 mm2 area, buried to a depth of 0.5 m
was simulated. The same two soil types were considered. IV. TWO LAYER ROD
The simulated values were compared with those from Tagg
formula [12]. The different simulations are summarized in When considering a rod that crosses through the two
Table II. The differences between the values of Tagg layers, calculating the potential at a point that is in a
formula and the matrix method are very small. different layer of the point source is required. To calculate
the potential in the upper layer, due to a point source in the
TABLE II lower layer, the formula is [11]:
COMPARISON WITH TAGG FORMULA FOR UPPER LAYER HORIZONTAL
CONDUCTOR , , &
'& , , , (3)
%
1 2 3 4 5
Parameters/Results
SIM SIM SIM SIM SIM where i is the conductivity of the i layer and S21 is [11]:
Upper layer thick, D (m) 1 2 4 6 8
1 1
Resistance 0.2 m displacement, () 52.4 58.4 77.9
8
- 4+ - 4" -
Error to Tagg (%) -13 -24 -32
As can be seen in the last row of Table VII, the errors for
negative k are small. For positive values of k the results are
not conservative, although errors are not too high. In this
case the 0.2 m displacement appears to be the best option.
V. CONCLUSION
[3] Sharma, De Four, Parametric Analysis of Grounding Systems in Two-
The matrix method produces very good results (less than Laier Earth using Galerkins Moment Method, IEEE 2006.
3 % error) when the electrodes are in a single layer, in a two [4] Colominas, Gomez-Calvino, Navarrina, Casteleiro. A general
numeric model for grounding analysis in layered soils. Advances in
layer soil. With rods crossing the two layers, if the Engineering Software 33, 2002.
resistivity of the lower layer is larger, the method gives [5] Colominas, Navarrina, Casteleiro, A Numerical Formulation for
results with 20 % maximum errors. This error can be Grounding Analysis in Stratified Soils, IEEE Transactions on Power
reduced by displacing the surface points in the top layer to Delivery, VOL. 17, NO. 2, April 2002.
[6] Colominas, Aneiros, Navarrina, Casteleiro, A BEM Formulation for
0.1 or 0.2 m away from the axis rod. Computational Design of Grounding Systems in Stratified Soils,
If the upper layer is the most resistive, a more common Computational Mechanics: New Trends and Applications, Idelsohn,
case, the method obtains unacceptable results, even Onate and Dvorkin (Eds) CIMNE, Barcelona, Spain 1998.
[7] Adriano, Bottauscio, Zucca, Boundary Element Approach for the
displacing the surface points in the upper layer 0.1 or 0.2 m analysis and design of grounding systems in presence of non-
away from the rod axis. The points in the lower layer have homogeneousness, IEE Proceedings Gener. Transm. Distrb. Vol 150,
images on the upper layer that are discontinuity points of the No. 3, May 2003.
[8] Coa, Comparative Study between IEEE Std.80-2000 anf Finite
Sunde solution, not allowing for potential calculations in Elements Method application for Grounding System Analysis, 2006
these points. In the vicinity of those points, for the negative IEEE.
voltage reflexion coefficient, the calculated potential can [9] Ma, Dawalibi, Southey, On the equivalence of uniform and two-layer
soils to multilayer soils in the analysis of grounding systems, IEE
even be negative. This kind of problem has not been Proceedings Gener. Transm. Distrb. Vol 143, No. 1, January 1996.
reported in the literature. Although the matrix method is not [10] Liu, Theethayi, Thottappillil, Gonzalez, Zitnik. An improved model
commonly used, some methods are obtained by integrating for soil ionization around grounding systems and its application to
stratified soil. Journal of Electrostatics 60, 2004.
the S functions, propagating the discontinuity points. [11] Joy, Meliopoulos e Webb, Touch and Step Calculations for
The use of Kinderman formula for an apparent resistivity Substation Grounding Systems, approved by the IEEE Substation
in homogeneous soil can overcome the problems for Committe of the IEEE Power Engineering Society, 1979.
negative reflexion coefficient, exploring the knowledge we [12] Grounding of Industrial and Commercial Power Systems, IEEE Std
142-2007.
have in that soil type. [13] Alonso, Fernandez e Figueras, Modelo para el Analise de Redes de
Tierra por Elementos Finitos. Calculo de la Resistncia de Tierra. 5
REFERENCES Jornadas Hispano-Lusas de Ingenieria Elctrica, Salamanca 1997,
Actas Tomo I.
[1] Salama, Elsherbiny, Chow. Calculation and interpretation of a [14] Kindermann e Campagnolo, Aterramentos Elctricos, Editora Sagra
grounding grid in two-layer earth with the synthetic-asymptote DC, Luzzato, 3 edio, Rio Grande do Sul, 1995.
approach. Electric Power Systems Research 35, 1995.
[2] Berberovic, Haznadar, Stih. Method of moments in analysis of
grounding systems. Engineering Analysis with Boundary Elements
27, 2005.