Escolar Documentos
Profissional Documentos
Cultura Documentos
respect to one or more time intervals. There are time The black curve shows an example of the movement
intervals which must be shorter than a specific of the impedance locus. The two red lines are the
(settable) value, others must be longer. blinders for slip number counter. The red impedance
The change of the impedance values must occur circle limits the working area of the function.
quite smooth, otherwise protective function The following picture shows one application
algorithms will block. Therefore standard test tools example in the ANDRITZ Hydro HIPASE Protection
like QuickCMC are not applicable. StateSequencer System (short HIPASE). It provides the Out-of-Step
and Ramping test module are possible with one slip, function by a single block (POU) in the Function
but it becomes very difficult when testing more than Block Diagram.
one slips.
There are two ways to develop the test trajectory.
Either to make a network simulation with stability
study. The other way is direct testing of the
characteristic of the protective function. For
Figure 4: HIPASE Out-of-Step Protective Function
development the second way is more useful so that
all parameters can be tested.
The left side shows the inputs (CTs, VTs, digital
A suitable tool was found with the CMEngine blocking and forcing signals), the right side the
program library. A sequence of commands can be outputs (digital Start and Operate events,
stored in the sequence buffer in the CMC test device measurement signals) of the protective function.
for later execution. It will be shown later how this
The parameters of the protective function can be
feature will be used to test out-of-step protective
edited with the HIPASE Touchpanel.
functions.
The tool ProCmc was created for easy and quick Depending on the time length of the impedance steps
working with OMICRON CMC test systems. It runs on the application calculates impedance points with
Microsoft Excel with Visual Basic for Applications linear approximation.
(VBA). This platform was used because it is installed The example above gives the following test
on all computers in the company. It also provides an trajectory (black curve):
easy to use user interface with worksheets.
The heart of the communication to OMICRON CMC
test system is the CMEngine program library which
is installed together with OMICRON Test Universe. In
ProCmc there is a class module in VBA which
provides enumerations, properties and methods
which can be used when creating specific test
applications. This module creates a reference to the
CMEngine object.
The first worksheet on ProCmc is used to connect
and disconnect with an OMICRON CMC test system.
The Start and Operate output of the function is 5.3 ProCmc with Pole Slip Counter
connected to binary inputs at CMC test system.
During the test the impedance value at the Start and The Pole Slip Counter is triggered with the
Operate event is recorded and stored in in the result Underexcitation protective function. Therefore it is
table in the worksheet. Additional the two events are important to have a look to the characteristic of this
shown in the impedance plane with yellow (Start) function.
and red (Operate) pointers. This gives an optical The characteristic in the load plane is a curved
feedback of the test results. straight line in the leading area. In the following
picture the load diagram is displayed with the
5.2 ProCmc with Blinders reactive power on the abscissa and the active power
on the ordinate. That means positive active power is
The sequencer impedance can be used to test
in the upper area, lagging reactive power (over-
different types of Out-of-Step protective functions.
excitation) is on the right side. Leading reactive
The impedance plane not only shows the test
power (under-excitation) is on the left side.
trajectory, but also the characteristic of the
protective function. The next picture shows the two
blinders as straight line and the impedance circle
according the settings of the protective function.
locus crosses the green curve on the right side again. shown in the impedance plane. With this it can be
These pulses are counted by the Pole Slip Counter checked if the test trajectory is well prepared.
and after reaching of the desired total pole slip The binary input of the CMC test system for Start and
numbers the Operation event picks up. Operate event can be selected. Additional a binary
The pole slip counting is equipped with time output can be selected which is closed during the
supervision, after which the actual pole slip number test.
is reset to zero. There is also a maximum time delay The following picture shows the first page of the test
between two counting inputs. report.
6 Test Report
When testing protective functions test reports are
important. A lot of time is spent to prepare these
documents. Therefore it is necessary to produce
them automatically as much as possible.
The worksheet with tables, charts, input data and
test results is prepared with printing areas and can
be used for direct printing.
The first page shows the settings of the protective
function. According these values the characteristic is Figure 18: Test Report for 78G Page 2