Você está na página 1de 23

Planning Guide

Planning Guide
SIGMA constantly endeavors to improve products so that information in this catalog is subject to change without notice.
2010. 06 Printed in Korea / Revision No. 2
Your partner for Elevator

The Changwon Factory The Design Center SIGMA in the world

The Changwon Factory in Korea which is The Design Center in Korea provides SIGMA has been serving you in more
referred as the single largest elevator perfect customer satisfaction by meeting than 70 countries around the world for
plant provides one-stop manufacturing any customer needs over 35 years
of high quality

Annual production Capacity (as of 2007) Established in 1995 Accumulated Sales (as of 2007)
- Elevator : 15,000 units - over 160,000 units
Safety & Reliability
SIGMA Elevator companys number one priority is safety. Our basic spirit to ensure safety
is through control technology such as back-up solution, safety drive operation and more
than 10 other safety devices.

We execute more than 30 kinds of reliability tests. These intense quality assurance
programs make fool-proof products from design stage.

Through SIGMA Net which monitors elevator, escalator and movingwalks by internet-
based software, our elevator not only provides a comprehensive and easy-to-use interface
but also brings perfect quality to reality.

Ride Comfort SIGMA provides best-in-class ride quality on every lift we install.
High switching speed of power device in the drive(IGBT) reduces
motor noise. Moreover, door operator with VVVF control ensures
Vibration and Burst Test silent door movement. The result of modern technology allows
EMI Test ESD Test
(Electro Magnetic Interference) Dropping Test (Electro Static Discharge) SIGMA to reduce vibration and noise to a minimum level.

Customers define luxury as a swift, smooth and silent ride. Our


seamless interface between tenant requirements and elevator
performance meets the exact standards and higher expectation
of customers.

Energy & Distributed Inverter(Di) control drastically improves reliability and


performance of elevators. By adopting Di control, the control
panel size has been reduced by 46% not to mention wiring and

Space Saving installation time. The formation of high efficiency and


compactness allows the traction machine to save energy by 50%
and provide installation space.

SIGMAs sophisticated, state-of-the-art fuzzy logic reduces


waiting time and enhances performance efficiency at a particular
moment, depending on its location, direction, load and the overall
passenger calls currently on the system. SIGMAs modern
microprocessor technology can be used to optimize group
performance to satisfy high customer standards.
Elevator Equipment Plan
3 Proper Number of Passenger and Car service
Elevators have an important role as a mode of carriage as well as determining the capacity of a building.
The scale, usage and transient population of a given building should be considered when planning an elevator.
In general, the following is recommended.

Passenger(load) : 17(1150kg), 20(1360kg) & 24(1600kg)


Car opening type : Center opening, Entrance width : 900~1100mm
1 Type of Elevator Car size : less than 1700mm
Planning Guide

Planning Guide
Floors
Type of elevator Service 50F

Passenger elevator Carriage of occupants and guests

7.0
40F
Elevator for the disabled Carriage of wheelchair user

6.0
5.0
Emergency elevator For emergency situation
30F

4.0
Freight elevator Carriage of office supplies, equipment & aids

3.5
Car elevator Carriage of car for parking 20F
Economy-oriented car speed application

3.0
Escalator Carriage of occupants and guests

2.5
Typical car speed application

2.0
10F

Service-focused car speed application

Speed (m/s)

2 Required Number of Elevators

Determining the required number of elevators and their car speeds as well as serving floors are key 4 Elevator speed
factors that decide the service quality of the building. In order to make arrangements for elevators
to operate efficiently in a building, traffic analysis and simulations are often carried out in the early The recommended operating time from main floor to top floor should be less than 30 seconds
stages of building planning. Elevator speed and zoning can be calculated from the matrices below. as a rated speed for over 15 floors office building.

Floors
Building Type Required No. of Elevators Capacity per Car
45FL
40FL

Building population Rentable floor space of 35FL 20, 24 Passenger


Diversified
of 250-300 per unit 2,000-2,400 m2 per unit 30FL
Office 25FL
17/20/24 persons
Buildings 20FL
13, 15, 17, 20, 24 Passenger
Single Building population Rentable floor space of 15FL

Purpose of 150-200 per unit 1,200-1,600 m2 per unit 10FL


6, 9, 11, 13, 15
5FL Passenger

If restaurants are arranged 0.75 1.0 1.5 1.75 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0
100 guest rooms Speed (m/s)
Luxury on the top floor, extra elevator(s)
per unit
should be added.

Hotels 17/20/24 persons


No. of service elevators that should 5 Service floors
150-200 guest be planned is approximately two
Regular
rooms per unit thirds of the numbers of passenger In order to service properly, the recommended number of servicing floors is 10 to 15.
elevators to be installed. For more than 20 floors, we recommend that the elevators should be divided into more than
2 groups. Service floor of every elevator within the same group should be identical.

6 _ Planning Guide Planning Guide _ 7


Zoning Example
6 Dividing Serving Floors (Zoning)
Transfer Floor
For skyscrapers or super high rise buildings, it is necessary to divide a building into groups of
contiguous elevator serving floors, called zones, e.g. in low, middle and high zones, in order to
provide every passenger with as equal elevator service as possible. This theoretical building division
into groups of floors for elevator service is called zoning.
Transfer Floor
Planning Guide

Planning Guide
The zoning will bring about the following benefits :
Carrying passengers to their destination zone as fast as possible, express zones are provided to
run express or shuttle elevators between the lobby and each zone. This will also maximize high
speed elevator performance, reduce round trip time, increase passenger handling capacity, and
Low Zone Middle Zone High Zone
reduce the required number of elevators.
Each zone is recommended to have 7-10 service floors.
Space above the low and middle zone elevator hoistways in the building is available for use as
offices and other purposes. The elevator hall space between express elevator serving floors is also
available for use as storage. Rentable space in the building will thus be increased.

8 Handling Capacity

Handling capacity is estimated by taking into account elevator speed, passengers, units,
service floors and height of floor
7 Planning elevators in a building
5 x 60 x Total No of Passengers x Units
It is recommended that one tenant avoid occupying floors in different zones. In a single purpose Handling Capacity for 5 min = x 100
building (in which the entire space or a substantial portion of the entire space is occupied by only Average operating time x No. of Passengers
one firm), it is also recommended that the firms functions be arranged on the floors so as to
minimize traffic demand between zones and that restaurants and conference rooms be arranged on
Market Segment Handling Capacity (%)
elevator transfer floors.
Elevators should be arranged so that building occupants and visitors can go straight to public space Office Building for General Purpose 20 ~ 25
floors such as the main lobby and cafeteria/restaurant floors from all other floors. Office Building for Multiple Purpose 16 ~ 20
The top and bottom serving floors of a zone should be overlapped with the bottom and top serving Government Building 14 ~ 18
floors of its each adjoining zone respectively as elevator transfer floors.
Rental Office Building 11 ~ 15
If each elevator zone has too many serving floors, the required number of elevators will increase and
the zoning benefits will be ruined as a result. In general, the recommended number of serving floors Hotel 8 ~ 10
in a zone is 7 to 10.
The number of elevators planned in a zone can be roughly found to be appropriate or not by the
formula the number of serving floors in a zone divided by the number of elevators planned as
indicated in the table of Elevator Requirement Efficiency in a Zone below. The recommended 9 Average Departure Terms
number of elevator units in a zone is 8 at the maximum.

2-3 Good Average operating time divided by units is equal to Average departure terms.
No. of Serving Floors in a Zone These terms become the basis for measuring average waiting time. Please refer to the
Elevator Requirement Efficiency in a Zone = 3-4 Acceptable following table.
No. of Elevator Units in a Zone
4 Unacceptable
Market Segment Term of departure
For example, when there are 12 floors in a zone and the number of elevators is 6, then the elevator
Major Office Building Within 30 seconds
requirement efficiency in this zone is 126 = 2.
Small-Medium Office Building Within 40 seconds

Hotel Within 50 seconds

8 _ Planning Guide Planning Guide _ 9


10 Positioning of Grouped Elevators 11 Elevator Arrangements in a Group

Positioning of grouped elevators is as important as elevator zoning and independent elevator Two-Car Groupings
position in a building. Generally, it should be placed in a way so that a walking distance for users is
minimal. In addition to the number of elevators in a group, the following should be taken into Side-by-side arrangement
consideration.
For a two-car group, side-by-side arrangement is best. Passengers face both cars and react
immediately to a direction lantern for an arriving car, with minimum walking distance. Two cars
Planning Guide

Planning Guide
facing each other constitute an acceptable alternative as the passenger needs only turn around to
be facing an elevator.
Separation of the elevators should be avoided. When the separation is great, it is hard to see which
The car inside shall allow for the turning of a wheelchair elevator is coming and recognize them as a group.

Minimum distance from wall to elevator door shall be not less than 1.5m.

Lobby must be open at both ends

When one end of the lobby is closed (alcove arrangement), the


entrance of the lobby is often crowded and elevators near the end The lobby in front of the elevators should, at a minimum, be
are less used, reducing operating efficiency. However, ancillary as wide as the elevators are deep. (main floor is even wider)
lobbies can be closed at one end because its traffic is less and
congestion is less of an issue. When the lobby is too narrow, it takes more time for people
overflowing the lobby to ride the elevator, which slows down
elevator operation as a result.
When the cars are opposite each other, the reguired area should
be one and one-half to two times as deep.

Three-Car Groupings
Columns must not stick out into lobby
The arrangement of three cars in a row is preferable
When a column sticks out into lobby, it is hard for users to see the because passengers can react immediately to a direction
elevator beyond the column and they are likely to miss the elevator. lantern or arriving car.

Two cars opposite one arrangement makes walking distance


shorter, but there is very little difference in walking time with
either of the three-car arrangements, as the turn-around reaction
time offsets the shorter distance. Moreover, three-car
arrangements are more aesthetically pleasing.

The lobby width should be about one and one-half times or


Entrance of elevators must not be excessively drawn 1.6m minimum.
When the entrance of elevators is excessively drawn, it is hard for users Passengers should be able to stand back far enough to see the
to see and ride the elevator.
entrances of all three cars, which requires more depth than two-
car arrangements. With the one-opposite-two arrangement, lobby
width should be from one and one-half to two times the car
depth, or a minimum 2.4m.

10 _ Planning Guide Planning Guide _ 11


Four-Car Groupings Seven or Eight-Car Groupings
Two-Opposite-Two Arrangement
Three-opposite-four, or four-opposite-four arrangements provide passengers the minimum walking
This arrangement is the most efficient with the minimum walking distance. The alternative distance. All cars in a row arrangement makes the distance between elevators at both ends too
arrangement, four cars in a row, has some disadvantages because of the increased distance between long. If the two end cars arrive simultaneously, the passengers who could not board must run to the
elevators at both ends. other end and risk missing that car also. It is also hard to recognize which elevator is coming, and
The preferred two-opposite-two arrangement should have a lobby from one and one-half to two may miss the car without realizing it is arrived.
times the depth of an individual elevator but no less than 3m in consideration for those instances The lobby width should be about two times the depth of an individual elevator and never less than
3m and the maximum width of the lobby should never exceed 4.3m for those instance when all cars
Planning Guide

Planning Guide
when all cars arrive at the main lobby filled and passengers entering or leaving must pass each other.
For the four-car in a row arrangement, the lobby should be at least one and one-half times the depth arrive at the main lobby filled and passengers entering or leaving must pass each other. When the
of an individual elevator but no less than 2.4m. This width will allow a person to stand back far lobby is too wide, however, walking distance becomes too long and passenger may miss the arriving
enough to see the directional lantern of any elevator. car. With an excessively wide lobby, moreover, cars may not be recognized as one group and some
of them are mistaken as being in different groups serving different floors.

Five or Six-Car Groups


12 Positioning of More Than One Group
The arrangement of two-opposite-three, or three-opposite-three are preferred
with the minimum walking distance.
When elevators are zoned in two or more groups, each group must be arranged with the following
A six-car in a row arrangement makes distance between elevators at both ends too long. If the two in mind.
end cars arrive simultaneously, the passengers who could not board must run to the other end and
risk missing that car also. It is also hard to realize which elevator is coming, and may miss the car Border of groups must be distinct.
without realizing that it has arrived.
If the border is not distinct, passengers who intend to board low-zone elevators may ride in a high-
zone elevator. Specifically, the following arrangements are desirable :
The lobby width should be from one and three-fourths to two times the depth of an individual
elevator but no less than 3m. Set a passage between groups.
In case of face-to-face arrangements, have a wider lobby.
For those instance when all cars arrive at the main lobby filled and passengers entering or leaving
Arrange distinct face-to-face groups next to each other in the fashion of drawing below.
must pass each other. If the lobby is to be used as a passage for people other than elevator
passengers, its width should be no less than 3.6m.

12 _ Planning Guide Planning Guide _ 13


Entrance Details Entrance Details

Narrow Jamb without Transom Panel S-Type Wide Jamb with Transom Panel

Section B-B Section A-A Section B-B Section A-A


MID RISE

MID RISE
Front View of Entrance Front View of Entrance

Building Structure Plan (Normal Button) Building Structure Plan (Slim Type Button) Building Structure Plan (Normal Button) Building Structure Plan (Slim Type Button)

Note 1. Hdimension in building structure plan depends upon the type of hall indicator selected. Note 1. Hdimension in building structure plan depends upon the type of hall indicator selected.
2. Unit : mm 2. Unit : mm

14 _ Planning Guide Planning Guide _ 15


Entrance Details Entrance Details

T-Type Jamb with Transom Panel T-Type Jamb with Transom Panel (MUSE Top Floor)

Section B-B Section A-A Section B-B Section A-A


MID RISE

MID RISE
Front View of Entrance Front View of Entrance

Building Structure Plan Building Structure Plan (Slim Type Button) Building Structure Plan (Normal Button) Building Structure Plan (Slim Type Button)

Note 1. Hdimension in building structure plan depends upon the type of hall indicator selected. Note 1. Hdimension in building structure plan depends upon the type of hall indicator selected.
2. Unit : mm 2. Unit : mm

16 _ Planning Guide Planning Guide _ 17


Passenger Elevator MID RISE Passenger Elevator MID RISE

Elevator Layouts
Overhead, PitPit
Overhead, Depth
Depth
& Machine
& Machine
RoomRoom
HeightHeight
Hoistway & Machine Room Plan (Simplex) Hoistway Section
(Unit : mm)
MID RISE

MID RISE
Code / Country
Speed (m/s) Load (kg)
Standard EN Code Malaysia Singapore

L 1020 4550 4200 4200 4400


1.0
L 1020 4600 4250 4250 4400

L 1020 4750 4400 4400 4450


Overhead 1.5
L 1020 4800 4450 4450 4600

L 1020 4950 4600 4600 4600


1.75
L 1020 5000 4650 4650 4750

L 1020 1500 1450 1450 1450


1.0
L 1020 1600 1550 1600 1550

L 1020 1800 1600 1550 1500


Pit Depth 1.5
L 1020 1800 1700 1700 1600

L 1020 2100 1700 1800 1700


1.75
L 1020 2100 1850 1950 1950

L 1020 2200 2200 2500 2200


Machine Room Height 1.0, 1.5, 1.75
L 1020 2400 2400 2850 2400

Hoistway & Machine Room Plan (Duplex)


(Unit : mm)

Code / Country
Speed (m/s)
Standard EN Code Malaysia Singapore

2.0 5500 5200 5200 5200


Overhead
2.5 5700 5400 5400 5400

2.0 2100 2100 2100 2000


Pit Depth
2.5 2400 2500 2500 2400

2.0 2400 2400 2850 2400


Machine Room Height
2.5 2400 2400 2850 2400

Note

1. (Separating Beams) : By Others


2. Unit : mm

18 _ Planning Guide Planning Guide _ 19


Passenger Elevator MID RISE Passenger Elevator MID RISE

Layout Dimensions | Di1 (Speed : 1.0 m/s) Layout Dimensions | Di1 (Speed : 1.5, 1.75 m/s)

Standard (Unit : mm) Standard (Unit : mm)

Hoistway Size Machine Room Size Reaction Load(kg) Hoistway Size Machine Room Size Reaction Load(kg)
MID RISE

MID RISE
Capacity Entrance Car Size Capacity Entrance Car Size
Speed Speed
Opening Simplex Duplex Simplex Duplex Machine Room Pit Opening Simplex Duplex Simplex Duplex Machine Room Pit
(m/s) (m/s)
(mm) (mm)
Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4 Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4
6 450 800 1400 850 1800 1450 3750 1450 2100 3200 4050 3200 3600 2000 3800 3150 8 550 800 1400 1030 1800 1650 3750 1650 2100 3400 4050 3400 4200 2800 6550 4800
8 550 800 1400 1030 1800 1650 3750 1650 2100 3400 4050 3400 4050 2500 4550 3350 9 600 800 1400 1130 1800 1700 3750 1700 2100 3500 4050 3500 4500 3100 6850 5000
9 600 800 1400 1130 1800 1700 3750 1700 2100 3500 4050 3500 4100 2500 4700 3450 10 680 800 1400 1250 1800 1850 3750 1850 2100 3650 4050 3650 4900 3400 7450 5350
10 680 800 1400 1250 1800 1850 3750 1850 2100 3650 4050 3650 4200 2800 5000 3600 11 750 800 1400 1350 1800 1950 3750 1950 2100 3750 4050 3750 5250 3700 7850 5550
11 750 800 1400 1350 1800 1950 3750 1950 2100 3750 4050 3750 4550 2900 5200 3750 13 900 900 1600 1350 2000 1950 4150 1950 2300 3750 4450 3750 5750 4100 9000 6250
1.5
13 900 900 1600 1350 2000 1950 4150 1950 2300 3750 4450 3750 5100 3800 6300 4500 15 1000 900 1600 1500 2000 2100 4150 2100 2300 3900 4450 3900 6150 4600 9650 6650
~
1.0 15 1000 900 1600 1500 2000 2100 4150 2100 2300 3900 4450 3900 5450 4300 6600 4700 1000 1800 1500 2400 2200 4950 2200 2700 4000 5250 4000
1.75 17 1150 9400 7750 14100 10400
1000 1800 1500 2400 2200 4950 2200 2700 4000 5250 4000 1100 2000 1350 2600 2050 5350 2050 2900 3850 5650 3850
17 1150 8000 5200 9550 7150
1100 2000 1350 2600 2050 5350 2050 2900 3850 5650 3850 1000 1800 1700 2400 2400 4950 2400 2700 4200 5250 4200
20 1350 10000 8250 15400 11150
1000 1800 1700 2400 2400 4950 2400 2700 4200 5250 4200 1100 2000 1500 2600 2200 5350 2200 2900 4000 5650 4000
20 1350 8900 6000 10200 7500
1100 2000 1500 2600 2200 5350 2200 2900 4000 5650 4000 2000 1750 2600 2450 5350 2450 2900 4250 5650 4250
24 1600 1100 11550 8700 16950 12050
2000 1750 2600 2450 5350 2450 2900 4250 5650 4250 2150 1600 2750 2300 5650 2300 3050 4100 5950 4100
24 1600 1100 10200 7000 10950 8700
2150 1600 2750 2300 5650 2300 3050 4100 5950 4100

EN Code EN Code
6 450 800 1400 850 1800 1450 3750 1450 2100 3200 4050 3200 3600 2000 3800 3150 7 525 800 1400 1030 1800 1650 3750 1650 2100 3400 4050 3400 4200 2800 6550 4800
7 525 800 1400 1030 1800 1650 3750 1650 2100 3400 4050 3400 4050 2500 4550 3350 8 600 800 1400 1130 1800 1700 3750 1700 2100 3500 4050 3500 4500 3100 6850 5000
8 600 800 1400 1130 1800 1700 3750 1700 2100 3500 4050 3500 4100 2500 4700 3450 9 675 800 1400 1250 1800 1850 3750 1850 2100 3650 4050 3650 4900 3400 7450 5350
9 675 800 1400 1250 1800 1850 3750 1850 2100 3650 4050 3650 4200 2800 5000 3600 10 800 800 1400 1350 1800 1950 3750 1950 2100 3750 4050 3750 5250 3700 7850 5550
10 800 800 1400 1350 1800 1950 3750 1950 2100 3750 4050 3750 4550 2900 5200 3750 12 900 900 1600 1350 2000 1950 4150 1950 2300 3750 4450 3750 5750 4100 9000 6250
1.5
12 900 900 1600 1350 2000 1950 4150 1950 2300 3750 4450 3750 5100 3800 6300 4500 13 1000 900 1600 1500 2000 2100 4150 2100 2300 3900 4450 3900 6150 4600 9650 6650
~
1.0 13 1000 900 1600 1500 2000 2100 4150 2100 2300 3900 4450 3900 5450 4300 6600 4700 1000 1800 1500 2400 2200 4950 2200 2700 4000 5250 4000
1.75 16 1200 9400 7750 14100 10400
1000 1800 1500 2400 2200 4950 2200 2700 4000 5250 4000 1100 2000 1350 2600 2050 5350 2050 2900 3850 5650 3850
16 1200 8000 5200 9550 7150
1100 2000 1350 2600 2050 5350 2050 2900 3850 5650 3850 1000 1800 1700 2400 2400 4950 2400 2700 4200 5250 4200
18 1350 10000 8250 15400 11150
1000 1800 1700 2400 2400 4950 2400 2700 4200 5250 4200 1100 2000 1500 2600 2200 5350 2200 2900 4000 5650 4000
18 1350 8900 6000 10200 7500
1100 2000 1500 2600 2200 5350 2200 2900 4000 5650 4000 2000 1750 2600 2450 5350 2450 2900 4250 5650 4250
21 1600 1100 11550 8700 16950 12050
2000 1750 2600 2450 5350 2450 2900 4250 5650 4250 2150 1600 2750 2300 5650 2300 3050 4100 5950 4100
21 1600 1100 10200 7000 10950 8700
2150 1600 2750 2300 5650 2300 3050 4100 5950 4100

Malaysia, Singapore Malaysia, Singapore


6 450 800 1400 850 1800 1450 3750 1450 2100 3200 4050 3200 3600 2000 3800 3150 8 550 800 1400 1030 1800 1650 3750 1650 2100 3400 4050 3400 4200 2800 6550 4800
8 550 800 1400 1030 1800 1650 3750 1650 2100 3400 4050 3400 4050 2500 4550 3350 9 610 800 1400 1130 1800 1700 3750 1700 2100 3500 4050 3500 4500 3100 6850 5000
9 610 800 1400 1130 1800 1700 3750 1700 2100 3500 4050 3500 4100 2500 4700 3450 10 680 800 1400 1250 1800 1850 3750 1850 2100 3650 4050 3650 4900 3400 7450 5350
10 680 800 1400 1250 1800 1850 3750 1850 2100 3650 4050 3650 4200 2800 5000 3600 11 750 800 1400 1350 1800 1950 3750 1950 2100 3750 4050 3750 5250 3700 7850 5550
11 750 800 1400 1350 1800 1950 3750 1950 2100 3750 4050 3750 4550 2900 5200 3750 13 900 900 1600 1350 2000 1950 4150 1950 2300 3750 4450 3750 5750 4100 9000 6250
1.5
13 900 900 1600 1350 2000 1950 4150 1950 2300 3750 4450 3750 5100 3800 6300 4500 15 1020 900 1600 1500 2000 2100 4150 2100 2300 3900 4450 3900 6150 4600 9650 6650
~
1.0 15 1020 900 1600 1500 2000 2100 4150 2100 2300 3900 4450 3900 5450 4300 6600 4700 1000 1800 1500 2400 2200 4950 2200 2700 4000 5250 4000
1.75 17 1155 9400 7750 14100 10400
1000 1800 1500 2400 2200 4950 2200 2700 4000 5250 4000 1100 2000 1350 2600 2050 5350 2050 2900 3850 5650 3850
17 1155 8000 5200 9550 7150
1100 2000 1350 2600 2050 5350 2050 2900 3850 5650 3850 1000 1800 1700 2400 2400 4950 2400 2700 4200 5250 4200
20 1360 10000 8250 15400 11150
1000 1800 1700 2400 2400 4950 2400 2700 4200 5250 4200 1100 2000 1500 2600 2200 5350 2200 2900 4000 5650 4000
20 1360 8900 6000 10200 7500
1100 2000 1500 2600 2200 5350 2200 2900 4000 5650 4000 2000 1750 2600 2450 5350 2450 2900 4250 5650 4250
23 1565 1100 11550 8700 16950 12050
2000 1750 2600 2450 5350 2450 2900 4250 5650 4250 2150 1600 2750 2300 5650 2300 3050 4100 5950 4100
23 1565 1100 10200 7000 10950 8700
2150 1600 2750 2300 5650 2300 3050 4100 5950 4100

20 _ Planning Guide Planning Guide _ 21


Passenger Elevator MID RISE Passenger Elevator MID RISE

Layout Dimensions | Di2 (Speed : 2.0, 2.5 m/s, Geared) Power Supply Plan

Standard Di1 (Speed : 1 .0 ~ 1 .75 m/s)


MID RISE

MID RISE
(Unit : mm) (200~220 / 346~440V)

Hoistway Size Machine Room Size Reaction Load(kg) Motor MCCB Capacity of Power Supply Heat Starting
Entrance Speed Capacity Lead-in Wire Size() Earth Wire
Capacity Car Size Capacity Building(A) Capacity(kVA) Output Power
Speed (m/s) Size()
Opening Simplex Duplex Simplex Duplex Machine Room Pit
(m/s) Person Load(kg) (kW) Simplex Duplex Simplex Duplex Simplex Duplex (kcal/H) (kVA/set)
(mm)
Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4 6 450 5.5 50 30 100 60 4.2 8.4 8 5.5 14 5.5 5.5 3.5 700 13.1
8 550 5.5 50 30 100 60 5.1 10.2 8 5.5 14 5.5 5.5 3.5 850 16
13 900 900 1600 1350 2200 2150 4550 2150 2800 4100 5200 4100 11100 7550 10800 8550
9 600 7.5 50 30 100 60 5.5 11 8 5.5 14 5.5 5.5 900 17.5
10 680 7.5 75 50 150 100 6.3 12.6 14 5.5 22 8 5.5 1050 19.9
15 1000 900 1600 1500 2200 2300 4550 2300 2800 4200 5200 4200 11650 7850 11400 8950
2.0 11 750 8 75 50 150 100 6.9 13.8 14 5.5 22 8 5.5 1150 21.8
1.0 13 900 8 75 50 150 100 8.3 16.6 22 5.5 38 14 8 5.5 1350 26.2
~ 17 1150 1000 1800 1500 2400 2300 4950 2300 3000 4200 5600 4200 12300 8250 14150 11300
15 1000 8 75 50 150 100 9.2 18.4 22 5.5 38 14 8 5.5 1500 29.1
2.5
17 1150 15 75 50 150 100 10 19 22 5.5 38 14 8 5.5 1750 23
20 1350 1000 1800 1700 2400 2500 4950 2500 3000 4400 5600 4400 13100 8850 15200 11900
20 1350 15 100 50 125 100 8.9 17.8 22 5.5 38 14 8 5.5 2050 28.1
24 1600 11 100 50 200 100 10.5 21 22 8 60 22 8 5.5 2400 33.3
24 1600 1100 2000 1750 2600 2550 5350 2550 3200 4500 6000 4500 13900 9350 16900 13000
8 550 9.5 75 50 100 60 6.6 13.2 14 5.5 22 8 5.5 1250 20.7
9 600 9.5 75 50 100 60 7.1 14.2 14 5.5 22 8 5.5 1350 22.6
10 680 9.5 75 50 100 60 8.1 16.2 14 5.5 38 14 5.5 1550 25.6
11 750 11 75 50 150 100 8.9 17.8 14 5.5 38 14 5.5 1700 28.2
1.5 13 900 11 75 50 150 100 10.7 21.4 22 5.5 38 14 14 5.5 2050 33.8
EN Code 15 1000 13 75 50 150 100 11.9 23.8 22 5.5 38 14 14 5.5 2250 37.6
17 1150 15 100 60 200 100 11.3 22.6 22 8 60 22 14 5.5 2600 35.9
Hoistway Size Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size 20 1350 18 100 60 200 100 12.8 25.6 38 14 60 22 14 5.5 3050 40.7
Speed
Opening Simplex Duplex Simplex Duplex Machine Room Pit 24 1600 15 125 75 250 125 15.2 30.4 38 14 60 22 14 5.5 3600 48.2
(m/s)
(mm) 8 550 11 75 50 100 60 7.6 15.2 14 5.5 38 14 5.5 1450 24.1
Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4
9 600 11 75 50 100 60 8.3 16.6 14 5.5 38 14 5.5 1600 26.3
12 900 900 1600 1350 2200 2150 4550 2150 2800 4100 5200 4100 11100 7550 10800 8550 10 680 11 75 50 100 60 9.4 18.8 14 5.5 38 14 5.5 1800 29.8
11 750 11 75 50 150 100 10.4 20.8 14 5.5 38 14 5.5 2000 32.8
13 1000 900 1600 1500 2200 2300 4550 2300 2800 4200 5200 4200 11650 7850 11400 8950 1.75 13 900 15 100 50 150 100 12.5 25 22 8 60 22 14 5.5 2400 39.4
2.0 15 1000 15 100 50 150 100 13.8 27.6 22 8 60 22 14 5.5 2650 43.8
~ 16 1200 1000 1800 1500 2400 2300 4950 2300 3000 4200 5600 4200 12300 8250 14150 11300 17 1150 18 125 60 250 125 13.2 26.4 38 14 60 22 14 5.5 3050 41.8
20 1350 22 125 75 250 125 16 30.4 38 14 60 22 14 5.5 3550 47.4
2.5
18 1350 1000 1800 1700 2400 2500 4950 2500 3000 4400 5600 4400 13100 8850 15200 11900 24 1600 18 150 75 300 125 17.7 35.4 60 22 100 38 14 5.5 4200 56.2

21 1600 1100 2000 1750 2600 2550 5350 2550 3200 4500 6000 4500 13900 9350 16850 13000

Di2 (Speed : 2.0, 2.5 m/s, Geared) (200~220 / 346~440V)

Motor MCCB Capacity of Power Supply Earth Heat Starting


Speed Capacity Lead-in Wire Size()
Malaysia, Singapore (m/s)
Capacity Building(A) Capacity(kVA) Wire Output Power
Person Load(kg) (kW) Simplex Duplex Simplex Duplex Simplex Duplex Size() (kcal/H) (kVA/set)
Hoistway Size Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size 13 900 18 90 50 180 100 15 30 38 14 100 22 14 2750 35
Speed 15 1000 18 15 30 14 3000 35
Opening Simplex Duplex Simplex Duplex Machine Room Pit 90 50 180 100 38 14 100 22
(m/s)
(mm) 2.0 17 1150 20 105 60 205 115 17 34 50 14 100 30 14 3450 39
Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4
20 1350 22 125 75 250 140 20 40 50 14 125 38 14 4100 43
13 900 900 1600 1350 2200 2150 4550 2150 2800 4100 5200 4100 11100 7550 10800 8550 24 1600 24 150 85 295 165 23 46 60 22 150 38 14 4850 48
13 900 22 120 70 235 130 18 37 50 14 125 30 14 3400 46
15 1020 900 1600 1500 2200 2300 4550 2300 2800 4200 5200 4200 11650 7850 11400 8950 15 1000 22 120 70 235 130 18 37 50 14 125 30 14 3750 46
2.0 2.5 17 1150 24 130 80 260 145 21 42 60 14 150 38 14 4350 51
~ 17 1155 1000 1800 1500 2400 2300 4950 2300 3000 4200 5600 4200 12300 8250 14150 11300 20 1350 27 155 90 305 170 24 48 60 22 200 38 22 5100 57
24 1600 30 185 110 365 205 28 57 80 22 200 50 22 6000 64
2.5
20 1360 1000 1800 1700 2400 2500 4950 2500 3000 4400 5600 4400 13100 8850 15200 11900
Note The wire size should be calculated considering the voltage drop when travel exceeds 50m.
23 1565 1100 2000 1750 2600 2550 5350 2550 3200 4500 6000 4500 13900 9350 16850 13000

22 _ Planning Guide Planning Guide _ 23


Passenger Elevator HIGH RISE Passenger Elevator HIGH RISE

Elevator Layout Overhead, Pit Depth & Machine Room Height


Hoistway & Machine Room Plan (Simplex) Hoistway Section
(Unit : mm)
HIGH RISE

HIGH RISE
Code / Country
Speed
(m/s)
Standard EN Code ANSI Singapore Malaysia

2.0 5500 5200 5300 5200 5200

2.5 5700 5400 5500 5400 5400

3.0 6000 5700 5700 5700 5700

3.5 6400 6300 6300 6300 6300


Overhead
4.0 7100 6800 6900 6900 6800

5.0 7700 7500 7600 7600 7500

6.0 7700 7500 7600 7600 7500

7.0 8000 7800 7900 7900 7800

2.0 2100 2100 1950 2000 2100

2.5 2400 2500 2400 2400 2500

Hoistway & Machine Room Plan (Duplex) 3.0 2700 3000 2900 2900 2900

3.5 3200 3500 3400 3400 3450


Pit Depth
4.0 3800 4000 3900 3900 3950

5.0 4000 4400 4300 4300 4400

6.0 4000 4400 4300 4300 4400

7.0 6000 6200 6100 6100 6200

2.0 2400 2400 2400 2400 2850

2.5 2400 2400 2400 2400 2850

3.0 3000 3000 3000 3000 3500

3.5 3000 3000 3000 3000 3500


Machine Room Height
4.0 3000 3000 3000 3000 3500

5.0 3500 3500 3500 3500 3900

6.0 3500 3500 3500 3500 3900

7.0 3500 3500 3500 3500 3900

Hoistway & Machine Room Plan (Group control)

Note

1. (Separating Beams) : By Others


2. Unit : mm

24 _ Planning Guide Planning Guide _ 25


Passenger Elevator HIGH RISE Passenger Elevator HIGH RISE

Layout Dimensions | Ds4 (Speed : 2.0, 2.5 m/s, Gearless) Layout Dimensions | Ds4 (Speed : 3.0 m/s, Gearless)
HIGH RISE

HIGH RISE
Standard (Unit : mm) Standard (Unit : mm)

Hoistway Size Dimensions Machine Room Size Reaction Load(kg) Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size Capacity Entrance Car Size
Speed in Hoistway Machine Speed in Hoistway Machine
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit
(m/s) Room (m/s) Room
(mm) (mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
285 250
15 1000 900 1600 1500 2200 2300 4550 2300 6900 2300 255 255 455 150 2800 4200 5200 4200 7500 4800 11650 7850 14000 11450 15 1000 900 1600 1500 4600 2400 7000 2400 538 150 5300 4300 7700 4900 12000 8100 14650 12200
(355) (355)
285 250
2.0 17 1150 1000 1800 1500 2400 2300 4950 2300 7500 2300 255 255 455 150 3000 4200 5600 4200 8100 4800 12300 8250 14950 12050 17 1150 1000 1800 1500 Refer to 5000 2400 7600 2400 538 150 Refer to 5700 4300 8300 4900 12600 8500 15600 12850
(355) (355)
~ 3.0
285 250
2.5 20 1350 1000 1800 1700 2400 2500 4950 2500 7500 2500 255 255 455 150 3000 4400 5600 4400 8100 5100 13100 8850 15950 12650 20 1350 1000 1800 1700 Note 5000 2600 7600 2600 538 150 Note 5700 4600 8300 5200 13300 9000 16700 13500
(355) (355)
285 250
24 1600 1100 2000 1750 2600 2550 5350 2550 8100 2550 255 255 455 150 3200 4500 6000 4500 8700 5200 13900 9350 17300 13450 24 1600 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 14200 9600 18050 14350
(355) (355)

EN Code
Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size
EN Code Speed
Opening Simplex Duplex Triplex in Hoistway Simplex Duplex Triplex Machine Pit
(m/s) Room
(mm)
Hoistway Size Machine Room Size Reaction Load(kg) Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
Dimensions
Capacity Entrance Car Size
Speed in Hoistway Machine 285 250
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit 13 1000 900 1600 1500 4600 2400 7000 2400 538 150 5300 4300 7700 4900 12000 8100 14650 12200
(m/s) Room (355) (355)
(mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 285 250
16 1200 1000 1800 1500 Refer to 5000 2400 7600 2400 538 150 Refer to 5700 4300 8300 4900 12600 8500 15600 12850
(355) (355)
13 1000 900 1600 1500 2200 2300 4550 2300 6900 2300 255 255 455 150 2800 4200 5200 4200 7500 4800 11650 7850 14000 11450 3.0
285 250
18 1350 1000 1800 1700 Note 5000 2600 7600 2600 538 150 Note 5700 4600 8300 5200 13300 9000 16700 13500
(355) (355)
2.0 15 1200 1000 1800 1500 2400 2300 4950 2300 7500 2300 255 255 455 150 3000 4200 5600 4200 8100 4800 12300 8250 14950 12050
285 250
~ 21 1600 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 14200 9600 18050 14350
(355) (355)
2.5 18 1350 1000 1800 1700 2400 2500 4950 2500 7500 2500 255 255 455 150 3000 4400 5600 4400 8100 5100 13100 8850 15950 12650

21 1600 1100 2000 1750 2600 2550 5350 2550 8100 2550 255 255 455 150 3200 4500 6000 4500 8700 5200 13900 9350 17300 13450

Malaysia, Singapore
Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size
Speed in Hoistway Machine
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit
(m/s) Room
(mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
Malaysia, Singapore
285 250
15 1020 900 1600 1500 4600 2400 7000 2400 538 150 5300 4300 7700 4900 12000 8100 14650 12200
Hoistway Size Machine Room Size Reaction Load(kg) (355) (355)
Dimensions
Entrance Car Size 285 250
Speed Capacity in Hoistway Machine 17 1155 1000 1800 1500 Refer to 5000 2400 7600 2400 538 150 Refer to 5700 4300 8300 4900 12600 8500 15600 12850
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit (355) (355)
(m/s) Room 3.0
(mm) 285 250
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 20 1360 1000 1800 1700 Note 5000 2600 7600 2600 538 150 Note 5700 4600 8300 5200 13300 9000 16700 13500
(355) (355)
15 1020 900 1600 1500 2200 2300 4550 2300 6900 2300 255 255 455 150 2800 4200 5200 4200 7500 4800 11650 7850 14000 11450 285 250
23 1565 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 14200 9600 18050 14350
(355) (355)
2.0 17 1155 1000 1800 1500 2400 2300 4950 2300 7500 2300 255 255 455 150 3000 4200 5600 4200 8100 4800 12300 8250 14950 12050
~
2.5 20 1360 1000 1800 1700 2400 2500 4950 2500 7500 2500 255 255 455 150 3000 4400 5600 4400 8100 5100 13100 8850 15950 12650 Note
1. The dimensions in parentheses are for single Shaft
23 1565 1100 2000 1750 2600 2550 5350 2550 8100 2550 255 255 455 150 3200 4500 6000 4500 8700 5200 13900 9350 17300 13450
2. If Single Shaft will be applied, the follwing special designs shall be provided.
i) Air pressure effect relief holes shall be furnished at top and bottom of the hoistway, the net area for each hole shall not
be less than the car platform area/2.
ii) Car structure and hoistway shall be designed to reduce air pressure effects due to single shaft.
Please contact contract department for details.

26 _ Planning Guide Planning Guide _ 27


Passenger Elevator HIGH RISE Passenger Elevator HIGH RISE

Layout Dimensions | Ds4 (Speed : 3.5 m/s, Gearless) Layout Dimensions | Ds4 (Speed : 4.0 m/s, Gearless)

Standard Standard
HIGH RISE

HIGH RISE
(Unit : mm) (Unit : mm)

Hoistway Size Dimensions Machine Room Size Reaction Load(kg) Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size Capacity Entrance Car Size
Speed in Hoistway Machine Speed in Hoistway Machine
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit
(m/s) Room (m/s) Room
(mm) (mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
285 250 285 250
15 1000 900 1600 1500 4600 2400 7000 2400 538 150 5300 4300 7700 4900 12000 8100 17450 14800 17 1150 1000 1800 1500 5000 2400 7600 2400 538 150 5700 4300 8300 4900 17450 11850 18600 15550
(405) (405) (455) (455)
285 250 Refer to Refer to
17 1150 1000 1800 1500 Refer to 5000 2400 7600 2400 538 150 Refer to 5700 4300 8300 4900 12600 8500 18500 15500 285 250
(405) (405) 4.0 20 1350 1000 1800 1700 5000 2600 7600 2600 538 150 5700 4600 8300 5200 17800 13200 19700 16250
3.5 (455) (455)
285 250 Note Note
20 1350 1000 1800 1700 Note 5000 2600 7600 2600 538 150 Note 5700 4600 8300 5200 13300 9000 19600 16150 285 250
(405) (405)
24 1600 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 18100 13500 21150 17150
285 250 (455) (455)
24 1600 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 14200 9600 21050 17100
(405) (405)

EN Code EN Code
Hoistway Size Dimensions Machine Room Size Reaction Load(kg) Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size Capacity Entrance Car Size
Speed in Hoistway Machine Speed in Hoistway Machine
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit
(m/s) Room (m/s) Room
(mm) (mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
285 250 285 250
13 1000 900 1600 1500 4600 2400 7000 2400 538 150 5300 4300 7700 4900 12000 8100 17450 14800 16 1200 1000 1800 1500 5000 2400 7600 2400 538 150 5700 4300 8300 4900 17450 11850 18600 15550
(405) (405) (455) (455)
285 250 Refer to Refer to
16 1200 1000 1800 1500 Refer to 5000 2400 7600 2400 538 150 Refer to 5700 4300 8300 4900 12600 8500 18500 15500 285 250
(405) (405) 4.0 18 1350 1000 1800 1700 5000 2600 7600 2600 538 150 5700 4600 8300 5200 17800 13200 19700 16250
3.5 (455) (455)
285 250 Note Note
18 1350 1000 1800 1700 Note 5000 2600 7600 2600 538 150 Note 5700 4600 8300 5200 13300 9000 19600 16150 285 250
(405) (405)
21 1600 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 18100 13500 21150 17150
285 250 (455) (455)
21 1600 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 14200 9600 21050 17100
(405) (405)

Malaysia, Singapore Malaysia, Singapore


Hoistway Size Dimensions Machine Room Size Reaction Load(kg) Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size Capacity Entrance Car Size
Speed in Hoistway Machine Speed in Hoistway Machine
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit
(m/s) Room (m/s) Room
(mm) (mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
285 250 285 250
15 1020 900 1600 1500 4600 2400 7000 2400 538 150 5300 4300 7700 4900 12000 8100 17450 14800 17 1155 1000 1800 1500 5000 2400 7600 2400 538 150 5700 4300 8300 4900 17450 11850 18600 15550
(405) (405) (455) (455)
285 250 Refer to Refer to
17 1155 1000 1800 1500 Refer to 5000 2400 7600 2400 538 150 Refer to 5700 4300 8300 4900 12600 8500 18500 15500 285 250
(405) (405) 4.0 20 1360 1000 1800 1700 5000 2600 7600 2600 538 150 5700 4600 8300 5200 17800 13200 19700 16250
3.5 (455) (455)
285 250 Note Note
20 1360 1000 1800 1700 Note 5000 2600 7600 2600 538 150 Note 5700 4600 8300 5200 13300 9000 19600 16150 285 250
(405) (405)
23 1565 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 18100 13500 21150 17150
285 250 (455) (455)
23 1565 1100 2000 1750 5400 2650 8200 2650 538 150 6100 4600 8900 5200 14200 9600 21050 17100
(405) (405)

Note Note
1. The dimensions in parentheses are for single Shaft 1. The dimensions in parentheses are for single Shaft

2. If Single Shaft will be applied, the follwing special designs shall be provided. 2. If Single Shaft will be applied, the follwing special designs shall be provided.
i) Air pressure effect relief holes shall be furnished at top and bottom of the hoistway, the net area for each hole shall not i) Air pressure effect relief holes shall be furnished at top and bottom of the hoistway, the net area for each hole shall not
be less than the car platform area/2. be less than the car platform area/2.
ii) Car structure and hoistway shall be designed to reduce air pressure effects due to single shaft. ii) Car structure and hoistway shall be designed to reduce air pressure effects due to single shaft.
Please contact contract department for details. Please contact contract department for details.

28 _ Planning Guide Planning Guide _ 29


Passenger Elevator HIGH RISE Passenger Elevator HIGH RISE

Layout Dimensions | Di5 (Speed : 5.0, 6.0, 7.0 m/s, Gearless) Power Supply Plan

Standard Ds4 (Speed : 2.0 ~ 4.0 m/s, Gearless)


HIGH RISE

HIGH RISE
(Unit : mm) (200~220 / 346~440V)

Hoistway Size Machine Room Size Reaction Load(kg) Motor Power Supply Earth Heat Starting
Dimensions Speed Capacity MCCB Capacity of Building(A) Lead-in Wire Size()
Capacity Entrance Car Size Capacity(kVA)
Speed in Hoistway Machine Capacity Wire Output Power
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit (m/s)
(m/s) Room Person Load(kg) (kW) Simplex Duplex Triplex Simplex Duplex Triplex Simplex Duplex Triplex Size() (kcal/H) (kVA/set)
(mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4
15 1000 14 100 50 150 100 225 125 18 35 48 30 14 60 30 100 38 15 2900 36.6
17 1150 1000 1800 1500 5200 2450 7900 2450 305 305 583 200 6200 5800 9100 5800 18900 15400 20900 17750 17 1150 16 100 50 175 100 225 125 19 38 51 30 14 60 30 100 50 16 3300 39.0
2.0
5.0 20 1350 1000 1800 1700 5200 2650 7900 2650 305 305 583 200 6200 6000 9100 6000 19600 16100 22150 18550 20 1350 18 100 60 200 175 300 150 20 41 55 30 14 80 30 125 50 17 3900 39.9
24 1600 1100 2000 1750 5600 2700 8500 2700 305 305 583 200 6600 6300 9700 6300 21400 16400 23600 19450 24 1600 21 125 75 225 150 300 175 23 46 63 30 14 100 38 150 60 18 4600 45.1
17 1150 1000 1800 1500 5200 2450 7900 2450 305 305 583 200 6200 5800 9100 5800 18900 15400 25650 21600 15 1000 18 100 60 200 125 300 175 22 43 59 38 14 80 38 125 60 20 3600 48.0
Refer to Refer to
6.0 20 1350 1000 1800 1700 5200 2650 7900 2650 305 305 583 200 6200 6000 9100 6000 19600 16100 27150 22550 17 1150 20 125 75 225 125 300 175 23 46 62 38 14 100 38 150 60 21 4150 51.2
Note Note 2.5
24 1600 1100 2000 1750 5600 2700 8500 2700 305 305 583 200 6600 6300 9700 6300 21400 16400 28900 23650 20 1350 23 125 75 250 150 350 200 25 51 68 38 14 100 50 150 60 22 4850 52.8
17 1150 1000 1800 1500 5400 2500 7900 2500 355 355 633 200 6400 5850 9400 5850 22000 18000 33050 27900 24 1600 26 150 100 300 175 400 225 29 58 78 50 22 125 60 200 80 23 5750 59.6
7.0 20 1350 1000 1800 1700 5400 2700 7900 2700 355 355 633 200 6400 6050 9400 6050 23000 19000 34900 29050 15 1000 21 125 75 225 150 300 175 23 46 63 38 14 80 38 125 50 25 4300 56.6
24 1600 1100 2000 1750 5800 2750 8500 2750 355 355 633 200 6800 6350 10000 6350 24000 20100 37050 30350 17 1150 23 125 75 250 150 350 200 26 51 69 50 14 100 50 150 80 26 4950 61.5
3.0
20 1350 26 150 100 300 175 400 225 29 58 79 50 22 125 60 200 100 27 5800 69.3
EN Code 24 1600 30 175 100 350 200 500 250 33 67 90 60 22 150 80 250 100 28 6900 78.0
15 1000 24 125 75 250 150 350 200 27 54 73 50 22 100 50 200 80 30 5000 70.7
Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size 17 1150 27 150 100 300 175 400 225 30 60 81 60 22 125 60 200 100 31 5750 78.3
Speed in Hoistway Machine 3.5
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit 20 1350 32 175 100 350 200 500 250 34 68 91 60 22 150 80 250 125 32 6750 86.4
(m/s) Room
(mm)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 24 1600 36 200 125 400 225 500 300 39 77 104 80 30 200 80 325 125 33 8000 95.0
17 1150 31 175 100 350 200 500 250 34 68 92 80 22 150 80 250 125 36 6600 93.4
15 1200 1000 1800 1500 5200 2450 7900 2450 305 305 583 200 6200 5800 9100 5800 18900 15400 20900 17750
5.0 4.0 20 1350 36 200 125 400 225 500 300 39 77 105 80 30 200 80 325 125 37 7750 102.3
18 1350 1000 1800 1700 5200 2650 7900 2650 305 305 583 200 6200 6000 9100 6000 19600 16100 22150 18550
24 1600 41 225 125 450 250 600 350 44 89 120 80 38 250 100 400 150 38 9150 112.3
21 1600 1100 2000 1750 5600 2700 8500 2700 305 305 583 200 6600 6300 9700 6300 21400 16400 23600 19450
15 1200 1000 1800 1500 5200 2450 7900 2450 305 305 583 200 6200 5800 9100 5800 18900 15400 25650 21600
Refer to Refer to Note The wire size should be calculated considering the voltage drop when travel exceeds 50m.
6.0 18 1350 1000 1800 1700 5200 2650 7900 2650 305 305 583 200 6200 6000 9100 6000 19600 16100 27150 22550
Note Note
21 1600 1100 2000 1750 5600 2700 8500 2700 305 305 583 200 6600 6300 9700 6300 21400 16400 28900 23650
15 1200 1000 1800 1500 5400 2500 7900 2500 355 355 633 200 6400 5850 9400 5850 22000 18000 33050 27900
7.0 18 1350 1000 1800 1700 5400 2700 7900 2700 355 355 633 200 6400 6050 9400 6050 23000 19000 34900 29050
21 1600 1100 2000 1750 5800 2750 8500 2750 355 355 633 200 6800 6350 10000 6350 24000 20100 37050 30350

Malaysia, Singapore
Di5 (Speed : 5.0 ~ 7.0 m/s, Gearless) (200~220 / 346~440V)
Hoistway Size Dimensions Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size Motor MCCB Capacity of Power Supply Lead-in Wire Earth Wire
Speed in Hoistway Machine Capacity Heat Starting
Opening Simplex Duplex Triplex Simplex Duplex Triplex Pit Speed Building(A) Capacity(kVA) Size() Size()
(m/s) Room Capacity Output Power
(mm) (m/s)
Person Load(kg) AN BN AH BH AH BH AH BH A A BR S AM BM AM BM AM BM R1 R2 R3 R4 Person Load(kg) (kW) Simplex Duplex Triplex Simplex Duplex Triplex Simplex Duplex Triplex Simplex Duplex (kcal/hr) (kVA/set)

17 1155 1000 1800 1500 5200 2450 7900 2450 305 305 583 200 6200 5800 9100 5800 18900 15400 20900 17750 17 1150 36 175 100 300 175 250 42 77 108 120 50 240 70 120 70 25 120 35 5200 122.3
5.0 20 1360 1000 1800 1700 5200 2650 7900 2650 305 305 583 200 6200 6000 9100 6000 19600 16100 22150 18550 5.0 20 1350 43 200 125 350 200 300 48 87 122 150 50 240 95 185 95 25 120 50 6100 134.0
23 1565 1100 2000 1750 5600 2700 8500 2700 305 305 583 200 6600 6300 9700 6300 21400 16400 23600 19450 24 1600 51 225 125 400 225 350 55 100 140 150 50 300 120 240 95 25 150 70 7200 146.0
17 1155 1000 1800 1500 5200 2450 7900 2450 305 305 583 200 6200 5800 9100 5800 18900 15400 25650 21600 17 1150 43 200 125 350 250 300 50 92 129 150 50 300 120 185 95 25 150 70 6250 148.4
Refer to Refer to
6.0 20 1360 1000 1800 1700 5200 2650 7900 2650 305 305 583 200 6200 6000 9100 6000 19600 16100 27150 22550 6.0 20 1350 51 225 150 400 250 350 57 104 146 185 70 300 120 240 95 25 150 70 7300 162.0
Note Note
23 1565 1100 2000 1750 5600 2700 8500 2700 305 305 583 200 6600 6300 9700 6300 21400 16400 28900 23650 24 1600 61 250 150 500 300 400 66 119 167 185 70 400 185 300 95 35 240 95 8650 177.3
17 1155 1000 1800 1500 5400 2500 7900 2500 355 355 633 200 6400 5850 9400 5850 22000 18000 33050 27900 17 1150 51 225 150 400 250 350 59 107 149 185 70 300 120 240 95 35 150 70 7250 175.0
7.0 20 1360 1000 1800 1700 5400 2700 7900 2700 355 355 633 200 6400 6050 9400 6050 23000 19000 34900 29050 7.0 20 1350 61 300 150 500 300 400 66 121 169 185 70 400 185 300 95 35 240 95 8550 191.0
23 1565 1100 2000 1750 5800 2750 8500 2750 355 355 633 200 6800 6350 10000 6350 24000 20100 37050 30350 24 1600 71 300 175 600 350 500 76 139 194 240 70 400 240 400 120 35 240 120 10100 209.0

Note If the speed exceeds 5.0m/s, single shaft is not recommanded. Note The wire size should be calculated considering the voltage drop when travel exceeds 100m.

30 _ Planning Guide Planning Guide _ 31


Hospital Elevator Hospital Elevator

Elevator Layouts Layout Dimensions


(Unit : mm)

Hoistway & Machine Room Plan (Simplex) Hoistway Section Hoistway Size Dimensions in Machine Room Size Reaction(kg)
Capacity Entrance Car Size
Speed
Hospital

Hospital
Opening Simplex Duplex Hoistway Simplex Duplex Machine Room Pit
(m/s)
(mm)
Person Load(kg) AN BN AH BH AH BH AL AR S BR AM BM AM BM R1 R2 R3 R4

0.75 5850 3500 4950 3750

1.0 5900 3750 5650 4150


11 750 1100 1300 2300 2150 2900 4450 2900 225 575 150 230 2600 4200 4950 4200
1.5 5250 3700 8350 6150

1.75 5250 3700 10150 7500

0.75 6650 3900 6050 4450

1.0 6800 4100 7000 5050


15 1000 1100 1500 2300 2350 2900 4850 2900 225 575 150 230 2800 4200 5350 4200
1.5 6150 4600 9900 7050

1.75 6150 4600 11950 8650

Power Supply Plan


(200~220 / 346~440V)

(220V / 400V)
Motor MCCB Capacity of Power Supply Lead-in Wire Size
Speed Capacity Earth Wire Heat Output Starting Power
Capacity Building(A) Capacity(kVA) ()
(m/s) Size() (kcal/H) (kVA/set)
Person Load(kg) (kW) Simplex Duplex Simplex Duplex Simplex Duplex

0.75 8 75 / 50 100 / 75 10 17 30 / 14 38 / 14 5.5 850 37

1.0 11 75 / 50 100 / 75 10 17 14 / 5.5 38 / 14 5.5 1150 37


11 750
1.5 9.5 75 / 50 150 / 100 8.9 17.8 14 / 5.5 38 / 14 5.5 1700 28.2

1.75 11 75 / 50 150 / 100 10.4 20.8 14 / 5.5 38 / 14 5.5 2000 32.8


Hoistway & Machine Room Plan (Duplex)
0.75 8 75 / 50 125 / 100 11 19 34 / 14 60 / 38 8 / 5.5 1150 43

1.0 11 75 / 50 125 / 100 11 19 22 / 5.5 60 / 38 8 / 5.5 1500 20


15 1000
1.5 13 75 / 50 150 / 100 11.9 23.8 22 / 5.5 38 / 14 14 / 5.5 2250 37.6

1.75 15 100 / 50 150 / 100 13.8 27.6 22 / 5.5 60 / 20 14 / 5.5 2650 43.8

Overhead, Pit Depth & Machine Room Height


(Unit : mm)

Speed (m/s) Dimension (mm)

0.75 4400

1 4600
Overhead
1.5 4800

1.75 5000

0.75 1200

1 1500
Pit Depth
1.5 1800

1.75 2100

Machine Room Height 0.75 ~ 1.75 2300

32 _ Planning Guide Planning Guide _ 33


MUSE Machine Room-Less MUSE Machine Room-Less Standard / EN Code

Layout Dimensions
Elevator Layouts
Standard (Unit : mm)

Entrance Hoistway Size Pit Reation Load


Hoistway Plan (Simplex) Hoistway Section Speed Capacity Opening Car Size
Opening Simplex Duplex OH PIT (kg)
MUSE

MUSE
(m/s) Type
Passenger Load(kg) (mm) AN BN AH BH AH BH R1(Car) R2(Cwt)
8 550 800 1350 1050 2000 1600 4100 1600 3800 1200 5900 4700
9 600 800 1350 1130 2000 1650 4100 1650 3800 1200 6100 4900
10 680 800 1350 1280 2000 1800 4100 1800 3800 1200 6900 5400
11 750 800 1350 1350 2000 1850 4100 1850 3800 1200 7200 5600
1.0 13 900 900 1550 1350 2200 1850 4500 1850 3800 1200 8000 6100
15 1000 900 1600 1450 2250 1900 4600 1900 3800 1200 8500 6400
17 1150 1000 1800 1450 2450 1900 5000 1900 3800 1200 9500 7100
20 1350 1000 1800 1650 2610 2000 5320 2000 4100 1500 12400 9600
24 1600 1100 2000 1700 2810 2050 5720 2050 4100 1500 13700 10300
8 550 800 1350 1050 2000 1600 4100 1600 3900 1300 6800 5000
9 600 800 1350 1130 2000 1650 4100 1650 3900 1300 7000 5200
10 680 800 1350 1280 2000 1800 4100 1800 3900 1300 7900 5700
11 750 2 Panel 800 1350 1350 2000 1850 4100 1850 3900 1300 8200 5900
1.5 13 900 Center 900 1550 1350 2200 1850 4500 1850 3900 1300 9200 6400
15 1000 Opening 900 1600 1450 2250 1900 4600 1900 3900 1300 9700 6800
17 1150 1000 1800 1450 2450 1900 5000 1900 3900 1300 10900 7500
20 1350 1000 1800 1650 2610 2000 5320 2000 4250 1800 13500 9700
24 1600 1100 2000 1700 2810 2050 5720 2050 4250 1800 15000 10400
8 550 800 1350 1050 2000 1600 4100 1600 4000 1400 7000 5200
9 600 800 1350 1130 2000 1650 4100 1650 4000 1400 7300 5400
10 680 800 1350 1280 2000 1800 4100 1800 4000 1400 8200 5900
11 750 800 1350 1350 2000 1850 4100 1850 4000 1400 8600 6200
1.75 13 900 900 1550 1350 2200 1850 4500 1850 4000 1400 9500 6700
15 1000 900 1600 1450 2250 1900 4600 1900 4000 1400 10200 7000
17 1150 1000 1800 1450 2450 1900 5000 1900 4000 1400 11300 7800
20 1350 1000 1800 1650 2610 2000 5320 2000 4350 2100 16500 11800
24 1600 1100 2000 1700 2810 2050 5720 2050 4350 2100 18200 12800

Hoistway Plan (Duplex) EN Code


7 525 800 1350 1050 2000 1600 4100 1600 3800 1200 5900 4700
8 600 800 1350 1130 2000 1650 4100 1650 3800 1200 6100 4900
9 675 800 1350 1280 2000 1800 4100 1800 3800 1200 6900 5400
10 800 800 1350 1350 2000 1850 4100 1850 3800 1200 7200 5600
1.0 12 900 900 1550 1350 2200 1850 4500 1850 3800 1200 8000 6100
13 1000 900 1600 1450 2250 1900 4600 1900 3800 1200 8500 6400
16 1200 1000 1800 1450 2450 1900 5000 1900 3800 1200 9500 7100
18 1350 1000 1800 1650 2610 2000 5320 2000 4100 1500 12400 9600
21 1600 1100 2000 1700 2810 2050 5720 2050 4100 1500 13700 10300
7 525 800 1350 1050 2000 1600 4100 1600 3900 1300 6800 5000
8 600 800 1350 1130 2000 1650 4100 1650 3900 1300 7000 5200
9 675 800 1350 1280 2000 1800 4100 1800 3900 1300 7900 5700
10 800 2 Panel 800 1350 1350 2000 1850 4100 1850 3900 1300 8200 5900
1.5 12 900 Center 900 1550 1350 2200 1850 4500 1850 3900 1300 9200 6400
13 1000 Opening 900 1600 1450 2250 1900 4600 1900 3900 1300 9700 6800
16 1200 1000 1800 1450 2450 1900 5000 1900 3900 1300 10900 7500
18 1350 1000 1800 1650 2610 2000 5320 2000 4250 1800 13500 9700
21 1600 1100 2000 1700 2810 2050 5720 2050 4250 1800 15000 10400
7 525 800 1350 1050 2000 1600 4100 1600 4000 1400 7000 5200
8 600 800 1350 1130 2000 1650 4100 1650 4000 1400 7300 5400
9 675 800 1350 1280 2000 1800 4100 1800 4000 1400 8200 5900
10 800 800 1350 1350 2000 1850 4100 1850 4000 1400 8600 6200
1.75 12 900 900 1550 1350 2200 1850 4500 1850 4000 1400 9500 6700
13 1000 900 1600 1450 2250 1900 4600 1900 4000 1400 10200 7000
16 1200 1000 1800 1450 2450 1900 5000 1900 4000 1400 11300 7800
18 1350 1000 1800 1650 2610 2000 5320 2000 4350 2100 16500 11800
21 1600 1100 2000 1700 2810 2050 5720 2050 4350 2100 18200 12800

34 _ Planning Guide Planning Guide _ 35


MUSE Machine Room-Less Singapore / Malaysia MUSE Machine Room-Less

Layout Dimensions Layout Dimensions

Singapore (Unit : mm) Through Type (Unit : mm)

Entrance Hoistway Size Pit Reation Load Entrance Hoistway Size Pit Reation Load
Speed Capacity Opening Car Size Speed Capacity Opening Car Size
Opening Simplex Duplex OH PIT (kg) Opening Simplex Duplex OH PIT (kg)
MUSE

MUSE
(m/s) Type (m/s) Type
Passenger Load(kg) (mm) AN BN AH BH AH BH R1(Car) R2(Cwt) Passenger Load(kg) (mm) AN BN AH BH AH BH R1(Car) R2(Cwt)
8 545 800 1350 1050 2000 1600 4100 1600 3800 1200 5900 4700 11 750 800 1350 1300 2000 1810 4100 1810 3800 1200 8000 6400
9 610 800 1350 1130 2000 1650 4100 1650 3800 1200 6100 4900 13 900 900 1550 1300 2200 1810 4500 1810 3800 1200 8800 6900
10 680 800 1350 1280 2000 1800 4100 1800 3800 1200 6900 5400 15 1000 900 1600 1400 2250 1910 4600 1910 3800 1200 9300 7200
1.0 CO
11 750 800 1350 1350 2000 1850 4100 1850 3800 1200 7200 5600 17 1150 1000 1800 1400 2450 1910 5000 1910 3800 1200 10200 7800
1.0 13 885 900 1550 1350 2200 1850 4500 1850 3800 1200 8000 6100 20 1350 1000 1800 1630 2610 2140 5320 2140 4100 1500 13000 10200
15 1020 900 1600 1450 2250 1900 4600 1900 3800 1200 8500 6400 24 1600 1100 2000 1690 2810 2200 5720 2200 4100 1500 14300 10900
17 1155 1000 1800 1450 2450 1900 5000 1900 3800 1200 9500 7100 11 750 800 1350 1300 2000 1810 4100 1810 3900 1300 8000 6400
20 1360 1000 1800 1650 2610 2000 5320 2000 4100 1500 12400 9600 13 900 900 1550 1300 2200 1810 4500 1810 3900 1300 8800 6900
24 1630 1100 2000 1700 2810 2050 5720 2050 4100 1500 13700 10300 15 1000 900 1600 1400 2250 1910 4600 1910 3900 1300 9300 7200
1.5 CO
8 545 800 1350 1050 2000 1600 4100 1600 3900 1300 6800 5000 17 1150 1000 1800 1400 2450 1910 5000 1910 3900 1300 10200 7800
9 610 800 1350 1130 2000 1650 4100 1650 3900 1300 7000 5200 20 1350 1000 1800 1630 2610 2140 5320 2140 4250 1800 13000 10200
10 680 800 1350 1280 2000 1800 4100 1800 3900 1300 7900 5700 24 1600 1100 2000 1690 2810 2200 5720 2200 4250 1800 14300 10900
11 750 2 Panel 800 1350 1350 2000 1850 4100 1850 3900 1300 8200 5900 11 750 800 1350 1300 2000 1810 4100 1810 4000 1400 8000 6400
1.5 13 885 Center 900 1550 1350 2200 1850 4500 1850 3900 1300 9200 6400 13 900 900 1550 1300 2200 1810 4500 1810 4000 1400 8800 6900
15 1020 Opening 900 1600 1450 2250 1900 4600 1900 3900 1300 9700 6800 15 1000 900 1600 1400 2250 1910 4600 1910 4000 1400 9300 7200
1.75 CO
17 1155 1000 1800 1450 2450 1900 5000 1900 3900 1300 10900 7500 17 1150 1000 1800 1400 2450 1910 5000 1910 4000 1400 10200 7800
20 1360 1000 1800 1650 2610 2000 5320 2000 4250 1800 13500 9700 20 1350 1000 1800 1630 2610 2140 5320 2140 4350 2100 13000 10200
24 1630 1100 2000 1700 2810 2050 5720 2050 4250 1800 15000 10400 24 1600 1100 2000 1690 2810 2200 5720 2200 4350 2100 14300 10900
8 545 800 1350 1050 2000 1600 4100 1600 4000 1400 7000 5200
9 610 800 1350 1130 2000 1650 4100 1650 4000 1400 7300 5400
10 680 800 1350 1280 2000 1800 4100 1800 4000 1400 8200 5900
11 750 800 1350 1350 2000 1850 4100 1850 4000 1400 8600 6200
1.75 13 885 900 1550 1350 2200 1850 4500 1850 4000 1400 9500 6700
Power Supply Plan
15 1020 900 1600 1450 2250 1900 4600 1900 4000 1400 10200 7000
17 1155 1000 1800 1450 2450 1900 5000 1900 4000 1400 11300 7800 Electrical Data (Main Power : 380V)
20 1360 1000 1800 1650 2610 2000 5320 2000 4350 2100 16500 11800
24 1630 1100 2000 1700 2810 2050 5720 2050 4350 2100 18200 12800 Motor MCCB Capacity Power Supply Lead-in Wire Size Heat Starting
Speed Capacity Earth Wire
Capacity ofBuilding (A) Capacity (kVA) () Output Power
(m/s) Size()
(kW) (kcal/H) (kVA/set)
Malaysia Passenger Load(kg) Simplex Duplex Simplex Duplex Simplex Duplex
8 550 800 1350 1050 2000 1600 4100 1600 3800 1200 5900 4700 8 550 4.1 20 40 6.2 12.4 5.5 5.5 3.5 825 7.2
9 615 800 1350 1130 2000 1650 4100 1650 3800 1200 6100 4900 9 600 4.1 20 40 6.7 13.4 5.5 5.5 3.5 900 7.7
10 685 800 1350 1280 2000 1800 4100 1800 3800 1200 6900 5400 10 700 6.4 30 60 7.6 15.2 5.5 8 3.5 1050 9.3
11 750 800 1350 1350 2000 1850 4100 1850 3800 1200 7200 5600 11 750 6.4 30 60 8 16 5.5 8 3.5 1125 9.8
1.0 13 885 900 1550 1350 2200 1850 4500 1850 3800 1200 8000 6100 1.0 13 900 6.4 30 60 9 18 5.5 8 3.5 1350 11
15 1025 900 1600 1450 2250 1900 4600 1900 3800 1200 8500 6400 15 1000 6.4 30 60 9.8 19.6 5.5 8 3.5 1500 12
17 1160 1000 1800 1450 2450 1900 5000 1900 3800 1200 9500 7100 17 1150 6.4 40 80 11 22 5.5 8 5.5 1725 12.9
20 1365 1000 1800 1650 2610 2000 5320 2000 4100 1500 12400 9600 20 1350 18.7 50 100 10 20 5.5 14 5.5 2025 28.9
23 1635 1100 2000 1700 2810 2050 5720 2050 4100 1500 13700 10300 24 1600 18.7 50 100 12 24 8 14 5.5 2400 34.3
8 550 800 1350 1050 2000 1600 4100 1600 3900 1300 6800 5000 8 550 6.5 30 60 8.7 17.4 5.5 8 3.5 1240 12.9
9 615 800 1350 1130 2000 1650 4100 1650 3900 1300 7000 5200 9 600 6.5 30 60 9.3 18.6 5.5 8 3.5 1350 13.8
10 685 800 1350 1280 2000 1800 4100 1800 3900 1300 7900 5700 10 700 10.3 30 60 10.7 21.4 5.5 8 3.5 1575 16.2
11 750 2 Panel 800 1350 1350 2000 1850 4100 1850 3900 1300 8200 5900 11 750 10.3 40 80 11.3 22.6 5.5 14 5.5 1690 17.2
1.5 13 885 Center 900 1550 1350 2200 1850 4500 1850 3900 1300 9200 6400 1.5 13 900 10.3 40 80 12.7 25.4 5.5 14 5.5 2025 19.2
15 1025 Opening 900 1600 1450 2250 1900 4600 1900 3900 1300 9700 6800 15 1000 10.3 40 80 14 28 8 14 5.5 2250 20.9
17 1160 1000 1800 1450 2450 1900 5000 1900 3900 1300 10900 7500 17 1150 10.3 50 100 16 32 8 14 5.5 2560 22.6
20 1365 1000 1800 1650 2610 2000 5320 2000 4250 1800 13500 9700 20 1350 18.7 50 100 14 28 14 22 5.5 3040 43.4
23 1635 1100 2000 1700 2810 2050 5720 2050 4250 1800 15000 10400 24 1600 18.7 75 150 16 32 14 22 5.5 3600 51.4
8 550 800 1350 1050 2000 1600 4100 1600 4000 1400 7000 5200 8 550 6.5 30 60 9.9 19.8 5.5 8 3.5 1450 15.8
9 615 800 1350 1130 2000 1650 4100 1650 4000 1400 7300 5400 9 600 6.5 30 60 10.7 21.4 5.5 14 5.5 1575 16.9
10 685 800 1350 1280 2000 1800 4100 1800 4000 1400 8200 5900 10 700 10.3 40 80 12.3 24.6 5.5 14 5.5 1840 19.9
11 750 800 1350 1350 2000 1850 4100 1850 4000 1400 8600 6200 11 750 10.3 40 80 13.1 26.2 5.5 14 5.5 1970 21.1
1.75 13 885 900 1550 1350 2200 1850 4500 1850 4000 1400 9500 6700 1.75 13 900 10.3 50 100 14.6 29.2 8 22 5.5 2370 23.5
15 1025 900 1600 1450 2250 1900 4600 1900 4000 1400 10200 7000 15 1000 10.3 50 100 16.1 32.2 8 22 5.5 2625 25.7
17 1160 1000 1800 1450 2450 1900 5000 1900 4000 1400 11300 7800 17 1150 10.3 60 120 18.4 36.8 14 22 5.5 3020 27.7
20 1365 1000 1800 1650 2610 2000 5320 2000 4350 2100 16500 11800 20 1350 18.7 75 150 16 32 14 22 5.5 3550 50.6
23 1635 1100 2000 1700 2810 2050 5720 2050 4350 2100 18200 12800 24 1600 18.7 75 150 18 36 22 38 5.5 4200 60
Note The wire size should be calculated considering the voltage drop when travel exceeds 50m.

36 _ Planning Guide Planning Guide _ 37


IRIS Mini Machine Room IRIS Mini Machine Room

Elevator Layouts Layout Dimensions | Speed : 1.0 m/s

Hoistway & Machine Room Plan (Simplex) Hoistway Section Standard (Unit : mm)

Hoistway Size Machine Room Size Reaction Load(kg)


IRIS

IRIS
Capacity Entrance Car Size
Speed
Opening Simplex Duplex Simplex Duplex Machine Room Pit
(m/s)
(mm)
Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4
6 450 800 1400 850 1800 1500 3750 1500 1800 1500 3750 1500 3600 2000 3800 3150
8 550 800 1400 1030 1800 1700 3750 1700 1800 1700 3750 1700 4050 2500 4550 3350
9 600 800 1400 1100 1800 1750 3750 1750 1800 1750 3750 1750 4100 2500 4700 3450
10 680 800 1400 1250 1800 1900 3750 1900 1800 1900 3750 1900 4200 2850 5000 3650
11 750 800 1400 1350 1800 2000 3750 2000 1800 2000 3750 2000 4550 2900 5200 3750
13 900 900 1600 1350 2000 2000 4150 2000 2000 2000 4150 2000 5100 3800 6300 4500
1.0 15 1000 900 1600 1500 2000 2150 4150 2150 2000 2150 4150 2150 5450 4300 6600 4700
1000 1800 1500 2350 2200 4850 2200 2350 2200 4850 2200
17 1150 8000 5200 9550 7150
1100 2000 1350 2550 2050 5250 2050 2550 2050 5250 2050
1000 1800 1700 2350 2400 4850 2400 2350 2400 4850 2400
20 1350 8900 6000 10200 7500
1100 2000 1500 2550 2200 5250 2200 2550 2200 5250 2200
2000 1750 2550 2450 5250 2450 2550 2450 5250 2450
24 1600 1100 10200 7000 10950 8700
2150 1600 2700 2300 5550 2300 2700 2300 5550 2300

Hoistway & Machine Room Plan (Duplex) EN Code


6 450 800 1150 1030 1800 1700 3750 1700 1800 1700 3750 1700 3600 2000 3800 3150
7 525 800 1400 1030 1800 1700 3750 1700 1800 1700 3750 1700 4050 2500 4550 3350
8 600 800 1400 1100 1800 1750 3750 1750 1800 1750 3750 1750 4100 2500 4700 3450
9 680 800 1400 1250 1800 1900 3750 1900 1800 1900 3750 1900 4200 2850 5000 3650
10 800 800 1400 1350 1800 2000 3750 2000 1800 2000 3750 2000 4550 2900 5200 3750
12 900 900 1600 1350 2000 2000 4150 2000 2000 2000 4150 2000 5100 3800 6300 4500
1.0 13 1000 900 1600 1500 2000 2150 4150 2150 2000 2150 4150 2150 5450 4300 6600 4700
1000 1800 1500 2350 2200 4850 2200 2350 2200 4850 2200
16 1250 8000 5200 9550 7150
1100 2000 1350 2550 2050 5250 2050 2550 2050 5250 2050
1000 1800 1700 2350 2400 4850 2400 2350 2400 4850 2400
18 1350 8900 6000 10200 7500
1100 2000 1500 2550 2200 5250 2200 2550 2200 5250 2200
2000 1750 2550 2450 5250 2450 2550 2450 5250 2450
21 1600 1100 10200 7000 10950 8700
2150 1600 2700 2300 5550 2300 2700 2300 5550 2300

Malaysia
6 410 800 1400 820 1800 1500 3750 1500 1800 1500 3750 1500 3600 2000 3800 3150
8 545 800 1400 1030 1800 1700 3750 1700 1800 1700 3750 1700 4050 2500 4550 3350
Overhead, Pit Depth & Machine Room Height 9 615 800 1400 1100 1800 1750 3750 1750 1800 1750 3750 1750 4100 2500 4700 3450
(Unit : mm)
10 685 800 1400 1250 1800 1900 3750 1900 1800 1900 3750 1900 4200 2850 5000 3650
Speed (m/s) Load (kg) Travel (m) Overhead (mm) PIt Depth (mm) Machine Room Height (mm) Hook Load (kg) 11 750 800 1400 1350 1800 2000 3750 2000 1800 2000 3750 2000 4550 2900 5200 3750
450 ~ 1000 4200 1400 2300 3000 13 885 900 1600 1350 2000 2000 4150 2000 2000 2000 4150 2000 5100 3800 6300 4500
1.0
1150 ~ 1600 4400 1400 2000 4500 1.0 15 1025 900 1600 1500 2000 2150 4150 2150 2000 2150 4150 2150 5450 4300 6600 4700
450 ~ 1000 1450 2300 3000 1000 1800 1500 2350 2200 4850 2200 2350 2200 4850 2200
1.5 TR 100 4400 17 1160 8000 5200 9550 7150
1150 ~ 1600 1500 2000 4500 1100 2000 1350 2550 2050 5250 2050 2550 2050 5250 2050
450 ~ 1000 1600 2300 3000
1.75 4500 1000 1800 1700 2350 2400 4850 2400 2350 2400 4850 2400
1150 ~ 1600 1650 2000 4500 20 1360 8900 6000 10200 7500
1100 2000 1500 2550 2200 5250 2200 2550 2200 5250 2200
2.0 750 ~ 1600 5100 1900 2000 4500
TR 130 2000 1750 2550 2450 5250 2450 2550 2450 5250 2450
2.5 750 ~ 1600 5300 2200 2000 4500 24 1635 1100 10200 7000 10950 8700
2150 1600 2700 2300 5550 2300 2700 2300 5550 2300

38 _ Planning Guide Planning Guide _ 39


IRIS Mini Machine Room IRIS Mini Machine Room

Layout Dimensions | Speed : 1.5, 1.75 m/s Layout Dimensions | Speed : 2.0, 2.5 m/s

Standard (Unit : mm) Standard (Unit : mm)


IRIS

IRIS
Hoistway Size Machine Room Size Reaction Load(kg) Hoistway Size Machine Room Size Reaction Load(kg)
Capacity Entrance Car Size Capacity Entrance Car Size
Speed Speed
Opening Simplex Duplex Simplex Duplex Machine Room Pit Opening Simplex Duplex Simplex Duplex Machine Room Pit
(m/s) (m/s)
(mm) (mm)
Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4 Person Load(kg) AN BN AH BH AH BH AM BM AM BM R1 R2 R3 R4
8 550 800 1400 1030 1800 1700 3750 1700 1800 1700 3750 1700 4200 2800 7150 5300 11 750 800 1400 1350 1870 2050 4040 2050 1870 2850 4040 2850 2550 5100 10450 9700
9 600 800 1400 1100 1800 1750 3750 1750 1800 1750 3750 1750 4500 3100 7500 5500 13 900 900 1600 1350 2070 2050 4440 2050 2070 2850 4440 2850 2800 5500 11250 10250
10 680 800 1400 1250 1800 1900 3750 1900 1800 1900 3750 1900 4900 3400 8150 5900 15 1000 900 1600 1500 2070 2200 4440 2200 2070 3000 4440 3000 2950 5850 11850 10650
11 750 800 1400 1350 1800 2000 3750 2000 1800 2000 3750 2000 5250 3700 8600 6150 2.0 1000 1800 1500 2310 2200 4920 2200 2310 3000 4920 3000 3750 7450 14450 13200
17 1150
13 900 900 1600 1350 2000 2000 4150 2000 2000 2000 4150 2000 5750 4100 9850 6900 ~ 1100 2000 1350 2510 2050 5320 2050 2510 2850 5320 2850 3800 7500 14600 13350
1.5
15 1000 900 1600 1500 2000 2150 4150 2150 2000 2150 4150 2150 6150 4300 10550 7300 2.5 1000 1800 1700 2310 2400 4920 2400 2310 3200 4920 3200 4250 7600 15300 13750
~ 20 1350
1000 1800 1500 2350 2200 4850 2200 2350 2200 4850 2200 1100 2000 1500 2510 2200 5320 2200 2510 3000 5320 3000 4350 7600 15400 13900
1.75 17 1150 9400 7750 15450 11500
1100 2000 1350 2550 2050 5250 2050 2550 2050 5250 2050 2000 1750 2510 2450 5320 2450 2510 3250 5320 3250 4700 8400 16950 14850
24 1600 1100
1000 1800 1700 2350 2400 4850 2400 2350 2400 4850 2400 2150 1600 2660 2300 5620 2300 2660 3100 5620 3100 4800 8400 17000 14950
20 1350 10000 8250 16850 12300
1100 2000 1500 2550 2200 5250 2200 2550 2200 5250 2200
2000 1750 2550 2450 5250 2450 2550 2450 5250 2450
24 1600 1100 11500 8700 18550 13300
2150 1600 2700 2300 5550 2300 2700 2300 5550 2300

EN Code EN Code
7 525 800 1400 1030 1800 1700 3750 1700 1800 1700 3750 1700 4200 2800 7150 5300 10 800 800 1400 1350 1870 2050 4040 2050 1870 2850 4040 2850 2550 5100 10450 9700
8 600 800 1400 1100 1800 1750 3750 1750 1800 1750 3750 1750 4500 3100 7500 5500 12 900 900 1600 1350 2070 2050 4440 2050 2070 2850 4440 2850 2800 5500 11250 10250
9 680 800 1400 1250 1800 1900 3750 1900 1800 1900 3750 1900 4900 3400 8150 5900 13 1000 900 1600 1500 2070 2200 4440 2200 2070 3000 4440 3000 2950 5850 11850 10650
10 800 800 1400 1350 1800 2000 3750 2000 1800 2000 3750 2000 5250 3700 8600 6150 2.0 1000 1800 1500 2310 2200 4920 2200 2310 3000 4920 3000 3750 7450 14450 13200
16 1200
12 900 900 1600 1350 2000 2000 4150 2000 2000 2000 4150 2000 5750 4100 9850 6900 ~ 1100 2000 1350 2510 2050 5320 2050 2510 2850 5320 2850 3800 7500 14600 13350
1.5
13 1000 900 1600 1500 2000 2150 4150 2150 2000 2150 4150 2150 6150 4300 10550 7300 2.5 1000 1800 1700 2310 2400 4920 2400 2310 3200 4920 3200 4250 7600 15300 13750
~ 18 1350
1000 1800 1500 2350 2200 4850 2200 2350 2200 4850 2200 1100 2000 1500 2510 2200 5320 2200 2510 3000 5320 3000 4350 7600 15400 13900
1.75 16 1250 9400 7750 15450 11500
1100 2000 1350 2550 2050 5250 2050 2550 2050 5250 2050 2000 1750 2510 2450 5320 2450 2510 3250 5320 3250 4700 8400 16950 14850
21 1600 1100
1000 1800 1700 2350 2400 4850 2400 2350 2400 4850 2400 2150 1600 2660 2300 5620 2300 2660 3100 5620 3100 4800 8400 17000 14950
18 1350 10000 8250 16850 12300
1100 2000 1500 2550 2200 5250 2200 2550 2200 5250 2200
2000 1750 2550 2450 5250 2450 2550 2450 5250 2450
21 1600 1100 11500 8700 18550 13300
2150 1600 2700 2300 5550 2300 2700 2300 5550 2300

Malaysia Malaysia
8 545 800 1400 1030 1800 1700 3750 1700 1800 1700 3750 1700 4200 2800 7150 5300 11 750 800 1400 1350 1870 2050 4040 2050 1870 2850 4040 2850 2550 5100 10450 9700
9 615 800 1400 1100 1800 1750 3750 1750 1800 1750 3750 1750 4500 3100 7500 5500 13 885 900 1600 1350 2070 2050 4440 2050 2070 2850 4440 2850 2800 5500 11250 10250
10 685 800 1400 1250 1800 1900 3750 1900 1800 1900 3750 1900 4900 3400 8150 5900 15 1025 900 1600 1500 2070 2200 4440 2200 2070 3000 4440 3000 2950 5850 11850 10650
11 750 800 1400 1350 1800 2000 3750 2000 1800 2000 3750 2000 5250 3700 8600 6150 2.0 1000 1800 1500 2310 2200 4920 2200 2310 3000 4920 3000 3750 7450 14450 13200
17 1160
13 885 900 1600 1350 2000 2000 4150 2000 2000 2000 4150 2000 5750 4100 9850 6900 ~ 1100 2000 1350 2510 2050 5320 2050 2510 2850 5320 2850 3800 7500 14600 13350
1.5
15 1025 900 1600 1500 2000 2150 4150 2150 2000 2150 4150 2150 6150 4300 10550 7300 2.5 1000 1800 1700 2310 2400 4920 2400 2310 3200 4920 3200 4250 7600 15300 13750
~ 20 1360
1000 1800 1500 2350 2200 4850 2200 2350 2200 4850 2200 1100 2000 1500 2510 2200 5320 2200 2510 3000 5320 3000 4350 7600 15400 13900
1.75 17 1160 9400 7750 15450 11500
1100 2000 1350 2550 2050 5250 2050 2550 2050 5250 2050 2000 1750 2510 2450 5320 2450 2510 3250 5320 3250 4700 8400 16950 14850
23 1635 1100
1000 1800 1700 2350 2400 4850 2400 2350 2400 4850 2400 2150 1600 2660 2300 5620 2300 2660 3100 5620 3100 4800 8400 17000 14950
20 1360 10000 8250 16850 12300
1100 2000 1500 2550 2200 5250 2200 2550 2200 5250 2200
2000 1750 2550 2450 5250 2450 2550 2450 5250 2450
24 1635 1100 11500 8700 18550 13300
2150 1600 2700 2300 5550 2300 2700 2300 5550 2300

40 _ Planning Guide Planning Guide _ 41


IRIS Mini Machine Room Technical Data

Power Supply Plan Technical Features


Standard Option
Speed : 1.0, 1.5, 1.75 m/s (200~220 / 346~440V)
IRIS

Technical Data
Feature Description Remark
Motor MCCB Capacity of Power Supply Heat Starting
Speed Capacity Lead-in Wire Size() Earth Wire In case of substantial difference between the number of calls registered on the car operating
Capacity Building(A) Capacity(kVA) Output Power
(m/s) Size() Anti-nuisance Operation panel and actual load in the elevator, the elevator prevents unnecessary operation by
Person Load(kg) (kW) Simplex Duplex Simplex Duplex Simplex Duplex (kcal/H) (kVA/set)
cancelling all registered calls when it arrives at the nearest floor.
6 450 5.5 30 / 16 60 / 32 6 12 12 / 4 12 / 6 6 700 7.3
Allows cancellation of an incorrectly registered car call. If you push a wrong floor button in the
8 550 5.5 30 / 16 60 / 32 6 12 12 / 4 12 / 6 6 850 7.3 Car Call Cancellation
car, you can cancel it by pressing the same button one more time.

9 600 5.5 30 / 16 60 / 32 6.5 13 12 / 4 12 / 6 6 900 7.7
Automatic Turn Off of Car illumination and fan are turned off automatically in case there is no hall call or car call to
10 680 5.5 40 / 20 80 / 40 7 14 12 / 4 12 / 6 6 1050 8.7
Car Light and Fan save energy.
11 750 5.5 50 / 25 100 / 50 8 16 12 / 4 12 / 6 6 1200 10
1.0
13 900 6.7 50 / 25 100 / 50 8.5 17 12 / 4 12 / 6 6 1350 10.9 If the actual load comes to more than 80% of the allowable maximum load, the elevator will not
By Pass Operation (80%)
react to the calling signals from other passing floors.

15 1000 6.7 50 / 25 100 / 50 9.5 19 12 / 4 12 / 8 6 1500 11.9
17 1150 8 60 / 32 120 / 64 11 22 14 / 6 14 / 8 6 1650 14 When the load of passengers exceeds the maximum capacity, a buzzer sounds and the elevator
Over Load (110% of Rated
20 1350 9.4 75 / 40 150 / 64 12.5 25 16 / 6 30 / 16 6 1950 20.3 remains stopped at that floor. When the passengers get off, the buzzer will stop. Consequently
Load) Holding Stop elevator doors will close and operation continues.
24 1600 11 80 / 40 160 / 80 14.5 29 16 / 6 30 / 16 6 2300 24
8 550 8.3 50 / 25 100 / 50 8.5 17 12 / 4 12 / 8 6 1250 10.5 If landing door would not closed by a hall button s jamming and it is caused car can t start
9 600 8.3 50 / 25 100 / 50 9 18 12 / 4 12 / 8 6 1350 11.2 Anti Hall Button Jamming then, the floor will close in force by the command from controller so that the car service next
10 680 8.3 60 / 32 120 / 64 9.5 19 12 / 4 12 / 8 6 1550 12.6 calls.
11 750 8.3 60 / 32 120 / 64 11 22 14 / 6 14 / 8 6 1800 14.5 While the car door is closing, if a door reopen signal is occured the door will be reopened
1.5 Door Reopen Control
13 900 10 60 / 32 120 / 64 12 24 14 / 6 14 / 8 6 2050 15.7 immediately and after specified time expired the door will again close.
15 1000 10 75 / 40 150 / 80 13 26 16 / 6 38 / 16 6 2250 17.2
This device enables the doors to return to the fully open position, should the door encounter a
17 1150 12 100 / 50 200 / 100 15.5 31 16 / 8 30 / 16 6 2500 16 Car Door Safety Edge
person or obstacle while closing.

20 1350 13.9 100 / 50 200 / 100 17.5 35 16 / 8 30 / 16 6 2900 23.6
Automatic Adjustment of
24 1600 16.5 120 / 63 240 / 125 20 40 25 / 8 50 / 25 6 3450 26.8 Door closing time can be adjusted in order to improve the efficiency.
Door Time
8 550 9.7 60 / 32 120 / 64 10 20 14 / 6 14 / 8 6 1450 13.2
9 600 9.7 60 / 32 120 / 64 10.5 21 16 / 6 38 / 16 6 1600 14.1 In normal operation, if the serial communication between the controller and it
s terminal board
10 680 9.7 60 / 32 120 / 64 11.5 23 16 / 6 38 / 16 6 1800 15.6 have something malfunction, the car mode is changed to aBack-Up mode automatically, then
Back-up Operation the car checks itself by servicing every even floors and every odd floors until the car returns
11 750 9.7 75 / 40 150 / 80 13.5 27 16 / 6 38 / 16 6 2100 18
1.75 normal condition. By this operation, even though the car has something malfunction, passergers
13 900 11.7 75 / 40 150 / 80 14.5 29 16 / 6 38 / 16 6 2400 19.5 can be offered a limited service without shoutdown.
15 1000 11.7 100 / 50 200 / 100 15.5 31 16 / 8 38 / 16 6 2650 21.3
17 1150 14 17.5 35 6 2900 18.4 During normal operation, a malfunction is occurred suddenly but it s not serious, in this case, if
100 / 50 200 / 100 16 / 8 30 / 16
the car is not in a door zone, then the car starts to run to the nearest floor in slow speed. After
20 1350 16.2 125 / 63 250 / 125 20 40 25 / 8 50 / 25 6 3400 27.7 Safety Drive Operation stop at the nearest floor, the care remains stop with door fully open andOut of Servicelamp.
24 1600 19.4 125 / 63 250 / 140 23 46 30 / 16 50 / 25 6 4000 32.8 If the car condition is possible to return a normal condition itself then, the car can service
normal operation again.

An automatic two-way leveling device is provided to maintain the elevator car level with the
Micro Leveling
landing, regardless of elevator load or direction travel

Speed : 2.0, 2.5 m/s (200~220 / 346~440V) This system provides passengers with audio information about car operation such as direction
Voice Synthesizer
of travel, landing floor, etc.

Motor MCCB Capacity of Power Supply Heat Starting
Speed Capacity Lead-in Wire Size() Earth Wire The doors will return to fully open position if the light ray unit detects an obstacle when the
Capacity Building(A) Capacity(kVA) Output Power Door Photo Sensor
(m/s) Size() doors are closing.
Person Load(kg) (kW) Simplex Duplex Simplex Duplex Simplex Duplex (kcal/H) (kVA/set)

11 750 16.7 12.5 22.8 10 1350 20.8 When passengers are entering or getting out of the elevator, the multi-photo device will prevent
25 40 10 35 Multi-Photo
the door from closing.

13 900 16.7 32 50 14.4 26.1 16 35 16 1650 23.9
15 1000 16.7 32 60 15.4 28.1 16 50 16 1800 25.7 Forced Floor Stop After service on specific floor stop by car call, the car is operated normally.
2.0
17 1150 26 40 60 17.0 30.9 25 50 16 2100 28.3 This panel monitors elevator operations and conditions of emergency operations from the
20 1350 26 40 75 18.9 34.4 25 50 16 2450 31.5 Supervisory Panel
building
s control room

24 1600 26 50 100 21.7 39.4 35 70 16 2900 36.1
In order for park the elevator, if the parking key is on position the car stop at the specified floor
11 750 16.7 32 50 15.6 28.5 16 50 16 1700 26.0 after finish servicing of all of registered calls. After the car stops at the specified floor, the car
13 900 16.7 40 60 18.0 32.7 25 50 16 2050 29.9 Parking Operation
light and fan are off automatically and every buttons both on the car operating panel and hall

15 1000 16.7 40 75 19.3 35.1 25 50 16 2250 32.1 button box are no more available.
2.5
17 1150 26 50 75 21.2 38.6 35 70 16 2600 35.4
In case of fire every cars should be returned to the specified floor in order to evacuate
20 1350 26 50 100 23.6 43.0 35 70 16 3050 39.3 Fire Return Operation
passengers safety.

24 1600 26 60 120 27.1 49.3 35 70 16 3600 45.1
In case of fire, a firemen can use the elevator which is stopped at the specified floor in order to
Fireman Operation
support firemen for fire-fighting.

Note The wire size should be calculated considering the voltage drop when travel exceeds 50m.

42 _ Planning Guide Planning Guide _ 43


Technical Data

Work By Others

The works below are not included in the elevator installation work and should be carried out by building
Technical Data

contractors in accordance with our drawings, relevant international or local codes and regulations.

Hoistway

A properly framed and enclosed hoistway, including any ventilation as required by the governing code or authority.
A dry pit constructed to the elevator manufacturer's specifications to reinforce or sustain any vertical forces
on the guide rails and impacted loads from the car and counterweight buffers.
A metal sill angle or concrete haunch across the full width of the hoistway at each elevator landing.
Provision of steel bars to fix jamb around the entrance of each floor.
All cutting, including cutouts to accommodate hall singal fixtures, patching, painting of walls, floors, or
partitions, together with finish painting of entrance doors and frames, if required.
Provision of entrance or ladder for pit access
Supply and installation of fascia plate.
Installation of emergency exits and electric wiring in blind sections of hoistway where required.
The tolerance of perpendicular line over the whole hoistway height must not exceed 30mm.
A waterproof outlet and light fixture in the elevator pit area with the light switch being located adjacent to the
access door or ladder.
Suitable light fixture and convenience outlet in the pit with a light switch adjacent to the access door or ladder.
The receptacles shall have protection for ground fault circuit interrupter.

Machine Room

Provision of wiring between controller and building management system.


A construction hoisting beam or hook, if required, with the correct location and size as determined
by the elevator contractor for each hoistway.
Noise insulation should be installed between machine room and adjacent residential area.
A suitable machine room with legal access, ventilation and concrete floor.
The temperature in the machine room should be maintained between 5 and 40.
Relative humidity should not exceed 90%(monthly) and 95%(daily) non-condensing.
Ventilation fan or air conditioner should be provided as per heat dissipation by the elevator contractor.
The size of entrance shall be Min.1000mm(W) x 2000mm(H).
Installation of lead-in wire and earth wire between building main power board and machine room incoming
distribution board. However, machine room lighting source supply shall be installed separately.
Provision of suitable light fixture and convenience outlets in the machine room

Miscellaneous

Wiring and piping between monitoring system.


Machine room and hoistway shall be free of dust or harmful gas.
All electric power for lighting, tools, welding, etc during installation.
All single phase receptacles installed in machine room, pit, and machinery spaces shall have ground
fault circuit interrupter protection.
Fire detector for fire emergency operation.
A secured area for storage of elevator equipment and materials during installtion.

44 _ Planning Guide