Tier 1 1 224.809 1 20885.4 145.

038
Quick Checks KN lbf N/mm2 lbf/ft2 lbf/in2
1 Sesimic Forces
1.1 Pseudo Seismic Force 1 m2 1550 in2
V = CSaW

Sa = Sx/T section 4.5.2.3


Sx = FvS section 2.4.1.6
Designed SD1 2/3Sx1 section 2.5
S = 0.69 (According to ASCE 7-10, 11.4.1)
Fv = 1.5 Section 2.4.1.6 , Table 2-4 , (For S1 >/=0.5 and site class D)
Sx = 1.035
SD1 0.69 Note: to replace Sx1 by Sd1 by doing 2/3,section 2.5
T = Ct(hn)
Ct = 0.018 (For moment -resisting frames of reinforced concrete(Building Type C1)
hn = 29.52 ft
= 0.9 (For moment -resisting frames of reinforced concrete(Building Type C1)

T = 0.379
Sa = 1.822 Sa<=Sxs , Section 4.5.2.3
C 1 For Building type Moment Frame C1, Two and Half Storey
W 3895.11 KN
875655.33 lbf
V 1595162.99 lb-ft Sxs = FaSs section 2.4.1.6
7095.64 KN Ss 1.73
Fa 1.1 Table 2-3
Sxs 1.903

Storey Shear Calculation

K 1
Storey wx(KN) wx(lb-ft) hx(m) hx(ft) wxhx wxhxk V Fx Vj(lbf) Vj(KN)
3 918.752 206543.7184 9 29.52 6097170.5662 6097170.57 1595162.99 614090.53 614090.53 2731.6101
2 1427.044 320812.3346 6 19.68 6313586.7448 6313586.74 635887.38 1249978 5560.1774
1 1549.313 348299.5062 3 9.84 3427267.1412 3427267.14 345185.08 1595163 7095.6367
3895.109 875655.5592 15838024.5

Story Drift for Moment Frames (Sec 4.5.3.1)


Dr = ((kb+kc)/(kbkc))(h/12E)Vc

Storey Stress in Concrete Frame Columns ( Sec 4.5.3.2)


vjavg = (1/Ms)(nc/(nc-nf)(Vj/Ac) 9.81 29.53
Fck 15 Mpa m/s2 ft/s2
313281 lb-f/ft2 10608.9062 lb/ft2
2175.57 lb-f/in2 73.67321368 lb/in2
Ms = 2
vj avg
less than greater of 100 lb/in2 or 2f'c 17.1666204 lb/in2
Storey nc nf Ac (m ) 2
Ac (in2) Vj(lb) Vjavg Remarks
3 8 2 0.59 906.75 20795.48 15.29 OK
2 14 4 0.99 1534.5 42329.09 19.31 OK
1 14 4 0.99 1534.5 54018.39 24.64 OK
Column Axial Stress Caused by Overturning (Sec 4.5.3.6)
pot = 1/Ms(2/3)(Vhn/Lnf)(1/Acol)
Ms = 2
pot less than 0.30 f'c 652.671 lbf/in2
93984.3 lbf/ft2
Storey nfx Ac(ft2) hn(ft) V(lb-in) Lx(ft) pot Remarks
3 2 6.293664 29.52 1595162.99 39.7044 31407.1101 OK
2 4 10.650816 19.68 6186.24896 OK
1 4 10.650816 9.84 3093.12448 OK

Storey nfy Ac(ft2) hn(ft) V(lb-in) Ly(ft) pot Remarks


3 4 6.293664 29.52 1595162.99 44.034 14159.5184 OK
2 4 10.650816 19.68 5577.99208 OK
1 4 10.650816 9.84 2788.99604 OK

Check for overturning


Tier 1 1 224.8
Quick Checks KN lbf
1 Sesimic Forces
1.1 Pseudo Seismic Force
V = CSaW

Sa = Sx/T
Sx = FvS
S = 0.733 (According to ASCE 7-10, 11.4.1)
Fv = 1.5 (For S1 </=0.1 and site class D)
Sx = 1.0995
T = Ct(hn)b
Ct = 0.018 (For moment -resisting frames of reinforced concrete(Building Type C1)
hn = 29.52 ft
b = 0.9 (For moment -resisting frames of reinforced concrete(Building Type C1)

T = 0.379
Sa = 2.903
C 1 For Building type Moment Frame C1, Two and Half Storey
W 3895.11 KN
875620.28 lbf
V 2541755.79 lb-ft
11306.74 KN
d concrete(Building Type C1)

d concrete(Building Type C1)

and Half Storey


LOS ANGELES
ASCE 7 ASCE 41-30 From us Embassy
Ss 2.182 g Ss 20/50 0.852 g Ss 1.73
S1 0.733 g S1 " 0.303 g S1 0.69
Sns 2.182 g Ssx BSE-1E 0.988 g
Sn1 1.099 g Ss1 " 0.544 g
Sds 1.454 g
Sd1 0.733 g
g
g
ASCE 7

V CsW
Cs