Escolar Documentos
Profissional Documentos
Cultura Documentos
c 0MPRCR-1
ONE
OPTIMISED
NETWORK
EQUIPMENT Reactors and shunt capacitor banks
The worst case occurs when a capacitor bank is ener- In this case, with only some micro-henrys between the
gised close to a bank that is already connected. The banks, a peak current of more than 120 times nominal
inrush current into the newly connected bank (and out current, at a frequency of more than 8 kHz can be
of the connected bank) is determined by the size of expected.
the capacitor bank and the inductance between the
two banks. The larger the banks, and the smaller Capacitor standards such as IEC 60871 state that
the inductance between banks, the higher will be the capacitors should be able to withstand inrush currents
inrush current. up to 100 times nominal. The standards suggest a
lower value if banks are switched frequently.
The frequency of the inrush current is determined
Large and high frequency inrush current can dam-
by the ratio of capacitor bank reactance and the
age capacitors, circuit breakers and contactors. All
impedance between the banks. The smaller the
connected equipment, and even remote substations
impedance, the higher will be the frequency.
are subject to voltage transients and may result in
sporadic equipment malfunction or failure.
Consider the case shown in the following simplified
single line diagram. An 11 kV substation is supplied To avoid this problem, it is common practice to insert
via a 132 kV/11 kV transformer. At 11 kV, a load inrush limiting reactors in series with the capacitor
with moderately poor power factor is overloading the banks.
supply transformer. It is decided to compensate the
load by means of 8 Mvar of reactive power, in two In the diagram below, 150 H reactors have been
steps of 4 Mvar. inserted in series with each bank.
Optimised Network Equipment Pty Ltd 41/ 2 Benson Street Toowong QLD 4066
ABN 56 151 739 374 PO Box 1951 Toowong QLD 4066
www.onegrid.com.au info@onegrid.com.au
External grid When the first step is connected, the impedance trace
above predicts that resonance will occur at the seventh
harmonic. This is clearly seen in the chart below, with
total voltage distortion of 25%, mainly at the seventh
T1
20 MVA Dyn11 harmonic.
Similarly, when the second step is connected reso-
11 kV bus
Skss = 181 MVA
nance occurs at the fifth harmonic, resulting in voltage
distortion of more than 30%.
40
L1
P = 18 MW No PFC
C1, C2 20
4 Mvar at 11 kV
0.150 mH reactors
10
External grid
1
0.1 T1
0 500 1000 20 MVA Dyn11
Frequency (Hz)
11 kV bus
Skss = 181 MVA
2
In the single line diagram the series reactors have system impedance changes in network configura-
been described as 7% reactors. This shorthand ter- tion will not influence the performance of the bank
minology infers that the reactor reactance is 7% of itself.
the capacitor reactance at the fundamental frequency.
The resulting tuned frequency of the bank is 189 Hz The effect of the detuned bank on harmonic distortion
at this frequency, the reactor and capacitor have equal is indicated in the chart below. As before, the voltage
reactance. distortion with no capacitors connected is 4.3%.
100
One bank
Two banks
10 20
Impedance ()
Low distortion
Current distortion (%)
High distortion
15
1
189 Hz
10
0.1
5
0 500 1000 0
Frequency (Hz)
THD 5 7 11 13 17 19
Harmonic order
It is also clear that the natural frequency is not in-
fluenced by the number of capacitor steps that are
connected.
Given a total current distortion of 19%, the same net-
Not shown in this chart, but important to note is the work with 7% detuned capacitor banks would have
fact that the detuning frequency is independent of the voltage distortion as indicated in the chart below.
3
100
15 One bank
Voltage distortion (%) No PFC Two banks
One step Three banks
Impedance ()
Two steps 10
10
1
350 Hz
5
550 Hz
0.1
0 250 Hz
15
4 Reducing harmonic distortion No PFC
Voltage distortion (%)
One step
Two steps
10 Three steps
In the network below, the configuration of the capacitor
bank has been modified with the specific purpose of
reducing the amount of harmonic distortion at the 11
5
kV busbar.
0
THD 5 7 11 13 17 19
External grid Harmonic order
T1
20 MVA Dyn11 5 Conclusion
11 kV bus
Skss = 181 MVA
This application note describes in simple terms the
benefits of installing reactors in series with capacitor
banks.