Você está na página 1de 4

Important TRD Parameters of ACTM/IRSOD

Sr.No. Item Reference Value Remarks


(ACTM/SOD Para
etc)
1 Implantation
a Mast having single OHE (i)on ACTM correction 2.8 m
M/L slip No.20 dt
03.11.2010.
...do.. Min. 2.50 m without
approval
...do.. 2.36 m with approval of
CEE
(ii) In yard ...do.. 2.8 m
...do.. 2.36 min. without approval
b Mast carrying more than one ...do..
OHE
(i) Portal upright & ...do.. 3.0 m which may be
head span relaxed to 2.8 m with
personal approval of CEE
Note : For curves , Curve allowance and 150 mm slewing allowance to be
added.
c Mast on platforms ACTM Vol II Part II 4.75 m
, Appendix I,
20.4 (page-32)
IRSOD Chapter I, 4.72 m (for passenger PF)
item 8. 4.11 m (for goods PF)
d Obligatory mast RDSO SMI No. 3.00 m
TI/MI/0028 Rev-2
e CLS AT mast RDSO DRG No. 3.50 m
ETI/PSI/0036
2 Track centre
a Existing work IRSOD Sch-I, 4265 mm For both
Chapter I, 1 (pg-4) ML &
ACS No. 9.dt yard
16.10.12
b New works/Addition to ..do.. 5300 mm
existing work
3 Horizontal clearance
a Minimum distance from
centre of the track to any
structure except at platform
i) For new/addition ..do.. item 2360 mm
to existing work No.8(ii)
ii) DFCL RDSO letter No. 2825 mm
CT/DG/DFC dated
21/26.11.2007
b Horizontal clearance of IRSOD ACS 13,
mast/foundation from centre item 11-A of
of track below rail level and chapter I &II.
above formation level
For new works
On straight track 2575 mm
On curve more than 20 2725 mm
For existing 2360 mm
c Mini.Horizontal clearance of IRSOD ACS 13, For new structure : (H+6)m
Power line crossing mast item 11-(iv) of For existing str (H+2.135)m
from centre of track above chapter I. Where H height of mast
rail level above rail level
d Mini. Horizontal clearance of IRSOD ACS 10, 2360mm
tunnel/girder/bridge from item 13-(II) of
centre of track above rail chapter I.
level
3 Standard height of contact ACTM vol II part II
wire appendix I, para
7.1
a) Normal with 10 cm pre-sag ..do... 5.60 m
b) Old electrification works with ...do.. 5.55 m
5 cm pre-sag.
c Unregulated OHE ...do.. 5.75 m
Loco sheds/Inspection pits ..do.. 5.80 m
Level crossing . ..do.. 5.50 m
Height of height gauge ...do... 4.67 m
d Minimum height of contact IRSOD ACS 10, 4.80 m
wire from R.L to live Chapter V-A,
conductor under FOB/ROB/ para-2
Tunnel
Minimum height of contact ...do... 4.69 m
wire where loco/rolling stock
of higher than 4.42 are not
permitted
Minimum height of contact ...do... 4.54m
wire where loco/rolling stock
of higher than 4.27m are not
Permitted. ( Restriction
Board shall be provided at
the entrance of section)
Tolerance (Except on over ...do... +_20 mm
bridge)
4 Contact wire gradient
a Regulated OHE Main line ACTM Vol. II part 3mm/m
II appendix I, Para
7.4
Reg. OHE siding line 10 mm/m
Unregulated OHE Mumbai ACTM correction 10mm/m
suburban slip No.
5 stagger
a Contact wire -On tangent ACTM vol II part II +_200 mm
tracks appendix I, para
8.0
b On curved track ...do.. +_300 mm
c Cross over/turn out ...do... +_300 mm
c At section insulator ...do... +_100 mm
d At PTFE N/S ...do.. Zero at support
6 Normal Encumbrance 1.40 m
7 Height of ROB & FOB
a For new Over head structures
Height of FOB/light OLS IRSOD ACS No.13 6250 mm
Dt. 21.10.2013,
IRSOD Sch. I,
Chapter I, item
No. 10(c).
Height of ROB/heavy OLS ..do... 10(c) 5870 mm
c Existing over head structures ...do... Note (b)
FOB/Light OLS 5270 mm
ROB/Heavy OLS 5070 mm
8 Span length ACTM Vol. I, Para
10216
Maximum 72 m
Minimum 27 m
Maximum diff. between ACTM vol II, Part 18 m
consecutive span II , 5.5(i)
Max. Span for Cross type OHE ...do...5.5(vi) 54 m
Max span for Tramway type ACTM Vol. II, Part 63 m
regulated OHE II , 24.1.2

Max span for unregulated ..do.., 24.2.1 30 m


Tramway type OHE
9 Minimum Distance between
OHE mast and signal/LC
gate/bridges
If OHE mast is in front of the ACTM Vol. II, Part 30 m
signal II , 18.11
If OHE mast is in rear of the ...do... 10 m
signal
Distance between OHE mast ..do...,18.12 10 m
and end of level crossing/
abutment of bridge
10 Electrical clearance IRSOD ACS-7,
Item. No.1
Long duration 250 mm
Short duration 200 mm
11 Vertical clearance of power IRSOD ACS-10,
line crossing from Rail level Item. No.11
a Up to 33 KV
Existing non electrified ..do... 10160 mm
section
New crossing or proposed for ..do... By underground
alteration
Minimum clearance between ..do... 2440mm*
highest traction conductor &
lowest transmission line
conductor
b Above 66 KV & upto132 KV ..do...
Existing non electrified ..do... 11760 mm
section
New crossing or proposed for ..do... 15560 mm
alteration
Minimum clearance between ..do... 3050 mm*
highest traction conductor &
lowest transmission line
conductor
c Above 132 KV & upto220 KV ..do...
Existing non electrified ..do... 12660 mm
section
New crossing or proposed for ..do... 16460 mm
alteration
Minimum clearance between ..do... 4580 mm*
highest traction conductor &
lowest transmission line
conductor
* Note :- For new electrification work, existing crossing can continue, if dimension
(Minimum clearance between highest traction conductor & lowest transmission line
conductor) are as mentioned above
12 Earth resistance value ACTM Vol. II Pt. II
( combined) Appendix III
Traction substation Para 5 0.50 Ohms
Switching station -do- 2.0 Ohms
BT/AT stations -do- 10.0 Ohms

13 BDV values of Transformer ACTM Vol. II, Pt. I


oil Annex.2.03
a New Oil ( after filtration) IS;335 60KV
b Oil in service IS;1866 30kv for <72.5kv rating
transformer
40kv for <145kv rating
transformer
50kv for 145kv &above
145kv rating transformer
14 Tap Setting on traction ACTM Vol.II Pt. I
transformer Para 20206
At FP/TSS -do- 27.5KV ( Max.)
At farthest end - Do- 19KV (Min.)

Você também pode gostar