Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A

in the Eastern Province


@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

SPECIFICATION

FOR

ELECTRICAL INSULATING OIL

FOR LOW-PRESSURE, OIL-FILLED POWER CABLES

Approved by Engineering Standards Committee (ESC)


on 1418/0628 (1997/10/29)

]54SMSS2:DB:as] 0799 PAGE NO. 1 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

TABLE OF CONTENTS

1.0 SCOPE

2.0 CROSS REFERENCES

3.0 APPLICABLE CODES AND STANDARDS

4.0 PERFORMANCE REQUIREMENTS AND CHARACTERISTICS

5.0 TESTS

6.0 PACKING AND SHIPPING

7.0 DATA SCHEDULE

]54SMSS2:DB:as] 0799 PAGE NO. 2 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

1.0 SCOPE

1.1 This SCECO-East Material Standard Specification (SMSS) specifies the


minimum technical requirements for inspection, testing and performance of new
(unused) and uninhibited mineral insulating oil or synthetic oil intended for use
as an insulating and cooling medium for low-pressure, oil-filled (LPOF) power
cables installed in the system of Saudi Consolidated Electric Company in the
Eastern Province (SCECO-East), Saudi Arabia.

2.0 CROSS REFERENCES

This Material Standard Specification shall be read in conjunction with the SCECO-East
General Specification No. 01-SMSS-01, titled "General Requirements for All
Equipment/Materials" which shall be considered as an integral part of this SMSS.

This SMSS shall also be read in conjunction with SCECO-East Purchase Order or
Contract Schedules for project, as applicable.

3.0 APPLICABLE CODES AND STANDARDS

The latest revisions of the following Codes and Standards shall be applicable for the
equipment/material covered in this SMSS. In case of conflict, the vendor/manufacturer
may propose equipment/material conforming to one group of Industry Codes and
Standards quoted hereunder without jeopardizing the requirements of this SMSS.

3.1 IEC 60465 Specification for unused Insulating Mineral Oils for
Cables with Oil Ducts

3.2 IEC 60867 Specification for unused liquids based on synthetic


aromatic hydrocarbons

3.3 IEC 60475 Method of Sampling Liquid Dielectric

3.4 ASTM D-4059 Test Method for Analysis of PCBs in Mineral Insulating
Oils by Gas Chromatography.

]54SMSS2:DB:as] 0799 PAGE NO. 3 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

4.0 PERFORMANCE REQUIREMENTS AND CHARACTERISTICS

4.1 The oil shall be as follows :

4.1.1 Pure and unused hydrocarbon mineral oil or synthetic oil


(Alkylbenzene).

4.1.2 Clear and transparent.

4.2 The oil shall not contain the following :

4.2.1. Any additives such as anti-oxidants, pour point depressants and in


particular PCBs (Poly-chlorinated Biphenyls).

4.2.2 Any substance which may impart chromophoric characteristics


(darkening of color) to oil under normal operating conditions.

4.3 The oil shall maintain its functional characteristics in its application in the
LPOF power cables.

4.4 The mineral insulating oil shall generally conform to Class II, sheet 1 of IEC
60465.

4.6 The synthetic oil shall conform to class II, sheet 1 of IEC 60867.

4.7 Only one standard shall be followed in its entirety.

4.8 The oil shall comply with the specific requirements as indicated in Data
Schedule. The limiting values indicated apply only to unused oil as delivered
prior to its introduction into cable.

5.0 TESTS

All test results shall be provided for review and acceptance by SCECO-East.

5.1 All tests prescribed in IEC-60465 or IEC-60867 shall be performed on the first
of every new batch of oil to be supplied in drums or to be used in the new cable.

Insulating oil shall also be tested for PCB content per ASTM D-4059.

]54SMSS2:DB:as] 0799 PAGE NO. 4 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

5.2 Mineral insulating oil or synthetic oil complying with this specification shall
meet the limiting values specified in Data Schedule when tested in accordance
with the prescribed methods.

5.3 SCECO-East also reserves the right to request for a separately sealed sample
before delivery for own analysis.

5.4 Sampling of oil shall be carried out in accordance with the procedure described
in IEC 60475.

6.0 PACKING AND SHIPPING

6.1 Oil shall be supplied in non-returnable drums having capacity of 200/160 liters
especially cleaned and reserved for this purpose. The drums shall be abrasion
and/or corrosion resistant. Immediately after filling with oil the drums shall be
effectively sealed (weatherproof).

6.2 Each drum shall be permanently marked with the following information in
addition to those specified in 01-SMSS-01 :

6.2.1 Class of mineral insulating oil or synthetic oil along with reference to
industry standard

6.2.2 Supplier's designation of oil

6.2.3 Filling date and place

6.2.4 Oil capacity in each drum

6.3 Each oil delivery shall be accompanied by a document from the supplier
specifying at least the following information:

6.3.1 Total quantity of oil shipped

6.3.2 Total number of drums in the consignment

6.3.3 All other information as deemed necessary.

]54SMSS2:DB:as] 0799 PAGE NO. 5 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

7.0 DATA SCHEDULE

ELECTRICAL INSULATING OIL FOR LOW-PRESSURE, OIL-FILLED POWER CABLES

SCECO-East Enquiry No. Date :

SCECO-East Purchase Order No. Date :


or Contract No.

SCECO-East PTS No./Project Title with J. O. No.

REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'

3.0 APPLICABLE INDUSTRY *


STANDARD

4.0 PERFORMANCE REQUIREMENTS


AND CHARACTERISTICS

Class of oil *

Type of oil *

Manufacturer's Designation
of oil *

'A' - SCECO-EAST SPECIFIED DATA/PARAMETER


'B' - BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED
DATA/PARAMETERS
'C' - REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'
(*) - DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/
SUPPLIER/VENDOR/CONTRACTOR IN COLUMN 'B'

]54SMSS2:DB:as] 0799 PAGE NO. 6 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

7.0 DATA SCHEDULE

ELECTRICAL INSULATING OIL FOR LOW-PRESSURE, OIL-FILLED POWER CABLES

REFERENCE
SECTION NO. DESCRIPTION 'A' B' 'C'

4.0 (Cont'd) Mineral Synthetic


Oil (Per Oil (Per
(IEC60465) (IEC60867)

Appearance * *

Kinetic Viscosity, Max.


(mm/s) at + 40C 13 11

Flash point, Min. (C) 125 130


(Closed Cup)

Pour point, Max. (C) Minus 30 Minus 45

Cloud point, Max. (C) 20 N.A.

Density, Max, (Kg/m) 0.900 0.850


at 20C to
0.880

Breakdown Voltage
at 60Hz, Min. (kV)
As delivered 30 30

Volume resistivity at
90C, Min. (T.m)
As delivered N.A. 0.5

Dielectric Dissipation Factor


(Tan),at 90C and 0.002 0.002
60Hz, Max.

]54SMSS2:DB:as] 0799 PAGE NO. 7 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

7.0 DATA SCHEDULE


ELECTRICAL INSULATING OIL FOR LOW-PRESSURE, OIL-FILLED POWER CABLES
REFERENCE
SECTION NO. DESCRIPTION 'A' B' 'C'

4.0 (Cont'd) Mineral Synthetic


Oil (Per Oil (Per
(IEC60465) (IEC60867)

Neutralization value, 0.03 0.03


Max. (mg KOH/g)

Stability under electrical 2 20


stress and ionization
(gassing)(Method A),Min.
absorption(mm3/min)

Water content at delivery,


Max. (mg/Kg)
in Drum Supply < 40 75

Corrosive Sulphur Non- Non-


Corrosive Corrosive

Chlorine Content, Max. N.A. 30


(mg/Kg)

Presence of Anti-Oxidant
Additives(% by mass) Nil N.A.

P.C.B. Content Not Detectable


(per ASTM 4059)
6.0 MODE OF DELIVERY

Drums capacity * *

Number of drums * *

Weight of oil in each drum * *

]54SMSS2:DB:as] 0799 PAGE NO. 8 of 9


Saudi Consolidated Electric Company B@IZy{{ X@R}{A X@@la{A yZ@c{A
in the Eastern Province
@@@vZ@c{A @@@wi }{A s

SCECO MATERIALS STANDARD SPECIFICATION 54-SMSS-2, Rev.1

7.0 DATA SCHEDULE

ELECTRICAL INSULATING OIL FOR LOW-PRESSURE, OIL-FILLED POWER CABLES

A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED


BY SCECO-EAST

B. ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY


MANUFACTURER, VENDOR/BIDDER/CONTRACTOR :

C. OTHER PARTICULARS TO BE FILLED IN BY BIDDER/VENDOR/SUPPLIER/


CONTRACTOR :

Actual Manufacturer Vendor/Supplier/


of Material Contractor

Name of Company

Location and Office Address

Name and Signature of Authorized


Representative and Date

Official Seal/Stamp
of the Company

]54SMSS2:DB:as] 0799 PAGE NO. 9 of 9