Você está na página 1de 9

MAY05PUMPS&SYSp24-33 4/19/05 4:04 PM Page 24

It’s one of
the few
methods you
have to
control the
environment
outside a
mechanical
seal.

By Keith Schindler, PE,


Schindler Engineering, Inc.,
and Paul McMahan,
Flowserve Corporation

API Piping Plan 62:


A Reliable Quench System
For years, users and manufacturers have attempted to increase mechanical seal reliability. Focus often
has been placed on the seal flush arrangement and methods to control the parameters that affect the seal
environment. Engineering improvements have been made in seal design, face material combinations and
configurations to comply with EPA’s low-emissions regulations and the American Petroleum Institute’s (API)
recommendations. However, little attention has been given to the environment outside the mechanical seal
(atmospheric side) and how this environment affects seal reliability. This article discusses one of the few
methods used to control the environment external to the seal. An appendix beginning on page 28 outlines
guidelines for operation, shutdown and troubleshooting of these systems.

24 MAY 2005 www.pump-zone.com PUMPS & SYSTEMS


MAY05PUMPS&SYSp24-33 4/17/05 3:46 PM Page 25

the lowest possible point on sequent seal hang-up. For hydro-

A n external fluid quench


system (API Piping Plan
62) is designed to im-
merse the outside of a mechani-
cal seal assembly and the sec-
the seal gland to prevent a
dead spot where product
leakage can accumulate and
affect seal performance.
carbon product streams at or
near their auto-ignition point,
the steam helps cool the normal
leakage from the seal assembly
ondary seals with a clean non- below its auto-ignition tempera-
hazardous fluid [1, 2]. This fluid I The mechanical seal gland ture. It also reduces cooling of
serves multiple purposes. must be equipped with a the seal faces and the product in
close-clearance throttle bush- viscous or high freezing-point-
1) It occludes the atmosphere ing or other suitable device. temperature applications while
from the atmospheric side of Since the quench fluid is fed the pump is not running.
the mechanical seal assembly, to the gland under pressure, Damage can occur to the mech-
thereby reducing oxidation. the pressure forces the fluid anical seal at start-up, if the prod-
2) Since it is at a slightly higher out of the gland toward the uct thickens or freezes at the seal
pressure than atmospheric, it driver or bearings through the faces.
provides a low flow through space between the shaft and For a steam quench applica-
the area to assist in drainage gland ring bore. The close- tion with enough space in the
or removal of product leakage clearance bushing di-rects the pump, the mechanical seal gland
across the seal faces. quench flow and any product should be equipped with an anti-
leakage to the drain instead of coking baffle [2]. (Figure 1). The
3) Depending on temperature anti-coking baffle routes the
and solubility of the pump- along the shaft, and reduces
the amount of quench fluid steam to the area of the seal
age in the quench fluid, it where solids collect, then directs
helps to prevent solidification leakage from entering the
bearing housing and contam- the steam so that it carries the
product leakage until such material away from the seal and
leakage has exited the close inating the bearing lubrica-
tion. The bushing contains sealing faces to the outlet (drain)
clearances encountered in the connection [2].
gland. This build-up of prod- the quench fluid in the area
of the seal assembly where it The steam quench pressure
uct, if not removed, will oth- should be regulated between 1–3
erwise accumulate to cause is needed, by directing the
quench fluid to the atmo- PSIG at the inlet quench connec-
the seal assembly to hang up. tion to prevent any seal prob-
4) For hydrocarbon products at spheric side of the seal assem-
bly and the secondary seals. lems. Higher-than-recommend-
or near their auto-ignition ed steam pressures could affect
point, the quench fluid cools The bushing also acts as an
orifice to control the amount the performance of the seal—and
the normal leakage from the will cause the excess steam to
seal assembly to a tempera- of leakage to the atmosphere
in the event of a catastrophic exhaust out of the seal gland.
ture below the product auto- Excess steam will cause moisture
ignition temperature. seal failure.
to enter the pump bearing hous-
ing if the bearing housing is not
When considering an exter- Applications properly protected [3].
nal fluid quench system, certain In applications such as hot When steam is used as a
requirements must be incorpo- hydrocarbons and caustics, quench medium for high-tem-
rated in the design of the seal for where oxidation, coking or crys- perature applications, it is essen-
the quench system to be reliable. tal formation (crystallization) is a tial that the steam quench be
problem on the atmospheric side operated in a gaseous state and
I The mechanical seal gland of the mechanical seal, steam is liquid water must not be intro-
must be equipped with inlet typically used as the quench duced into the gland area. If con-
and outlet (drain) quench fluid. The steam is introduced densed steam is introduced to the
connections. The quench into the inlet quench connection atmospheric side of the seal
fluid must drain through the where it is directed around the assembly, it may result in flashing
outlet connection, making it sealing faces. of the steam in the seal face area,
necessary for the outlet con- The steam quench acts as a with the consequence of unstable
nection to be lower than the coolant for the mechanical seal in hydraulic forces affecting the
inlet connection. This ar- high temperature applications atmospheric side of the seal faces.
rangement will help wash (>300° F) [2]. The steam cools Another possible consequence is
away any product leakage at the leakage on the atmospheric damage to secondary graphite
the seal faces. The drain con- side of the sealing faces, which sealing members either through
nection should be located at reduces coke formation and sub- galvanic corrosion or damage

PUMPS & SYSTEMS www.pump-zone.com MAY 2005 25


MAY05PUMPS&SYSp24-33 4/17/05 3:49 PM Page 26

the equipment, or routing the


steam quench through a water
jacket on the equipment.
In applications where oxida-
tion or coking is a problem on
the atmospheric side of the
mechanical seal and steam is not
available or can’t be used, nitro-
gen is the second most common
quench fluid used (as shown in
Figure 3). Similar to the steam
quench application, a nitrogen
quench is introduced into the
quench inlet connection of the
Figure 1. Mechanical seal with anti-coking baffle seal gland where it is directed
under the sealing faces. The
that occurs when the condensa- across the controller, reducing nitrogen quench purges the oxy-
tion trapped in the secondary the initial steam pressure to a gen from the atmospheric side of
sealing member area flashes back usable level for the quench, addi- the seal to reduce oxidation and
to steam. tional measures to prevent con- the flow of fluid helps remove
Figure 2 shows the recom- densation in the steam quench any build-up from under the seal
mended piping system to ensure system may be needed. Insu- faces to prevent seal hang-up.
that “dry” steam is available as a lation and tracing of the steam The nitrogen quench also acts as
quench fluid. If the steam supply supply system is one option. a coolant for the seal in high-
line to the equipment is longer Others include using the heat of temperature applications by cool-
than 25 feet, or is taken from a the equipment to reheat the ing the leakage on the atmo-
high pressure source where there steam quench by wrapping a spheric side of the sealing faces,
is more than a 50-PSI drop short section of tubing around which reduces or prevents coke
Circle 112 on Reader Service Card

26 MAY 2005 www.pump-zone.com PUMPS & SYSTEMS


MAY05PUMPS&SYSp24-33 4/17/05 3:46 PM Page 27

formation and subsequent seal pad when there is minimal risk of


hang-up in hot services (>300°F) plugging or fouling of the addi-
[2]. Since nitrogen is a gas and tional drain piping.
the recommended flow rate is
low, there is no visible evidence Line-Up & Operating
at the seal gland that the nitrogen
quench system is in service [3]. For an external fluid quench
The only indication that the sys- system to be reliable, it must be
tem is working properly is a flow operated and maintained proper-
reading from a reliable flow ly. This includes establishing
meter. clear equipment line-up, operat-
The nitrogen quench flow ing, preventative maintenance,
rate should be controlled to shutdown and troubleshooting
approximately one (1) standard tasks for maintenance and oper-
cubic foot per minute (scfm). ating personnel. (A detailed
Higher-than-recommended description of each task is listed
nitrogen flow rates will not affect in the attached Appendix.)
the performance of the seal, but Remember that the main
will substantially increase the isolation valve on an external
operating cost of the external fluid quench line should never be
quench piping system [3]. opened after the equipment has
Water is a quench fluid used been prepared for service, or
in sour water, caustic soda and while it is in service. The external
saltwater brine applications, fluid quench system should be
where the product crystallizes on placed in service prior to lining
the atmospheric side of the up the equipment for opera-
mechanical seal. The water tion—and should not be isolated
quench fluid is introduced into until the equipment is removed
the inlet quench connection of
for maintenance. Opening the
the seal gland where it is directed
under the sealing faces (Figure fluid quench line while the
4). The flow of water washes equipment is in service (HOT)
away any build-up from under can seriously damage the
the sealing faces to prevent seal mechanical seal—and expose
hang-up. operating personnel to a serious
The quench pressure should safety risk.
be limited to prevent any seal
problems. The flush rate should Conclusion
be controlled so that a slow drip An external fluid quench sys-
appears at the back side of the tem (API Piping Plan-62) can
seal gland. This should be reliably control the environment
enough to keep any crystals from outside a mechanical seal if the
forming under the sealing faces system is installed and operated
to prevent seal hang-up. properly. Designed to immerse
A water quench typically
the seal faces and the secondary
becomes a housekeeping prob-
lem. The water drips on the seals with a clean, non-hazardous
fluid, this system will remove any
Circle 119 on Reader Service Card

pump bracket and the pump


baseplate, accelerating corrosion product leakage and build-up
[3]. In cold climates, the water from the atmospheric side of the
freezes and becomes a slipping seal to prevent seal hang-up, thus
hazard. For this reason, it is com- extending seal life. Depending
mon practice to pipe the outlet on the product or material being
of the drain connection on the sealed, the quench system can be
seal gland to a suitable drain tailored to fit the application.
location around the equipment

PUMPS & SYSTEMS www.pump-zone.com MAY 2005 27


MAY05PUMPS&SYSp24-33 4/19/05 4:01 PM Page 28

APPENDIX
Equipment Line-Up &
Operating Guidelines
The following steps are rec-
ommended when putting an
external fluid quench system
(API Plan-62) into service. This
line-by-line description can be
used to assist maintenance and
Figure 2. API Piping Plan-62 Steam Quench Piping Layout
operating personnel with their
daily line-up, operating and trou- piping is HOT and all from back of seal gland
bleshooting tasks. condensate is out of the and force condensate to
1. Open main valve isolating the system, close drain valve. enter bearing housing of
external quench system. iii. Note: the pump or driver.
2. Follow the procedure listed I A small amount of b. Nitrogen Quench: (Fig. 3.)
below for different quench condensate may drip i. Note:
mediums. from the seal flange. I Throttle needle valve
a. Steam Quench: (Fig. 2.) This is normal, but most (or adjust pressure
i. Open the drain valve to of it should be removed regulator) until flow
begin heating up the from the quench system meter reads one (1) stan-
steam quench line and by the steam trap. dard cubic foot per
to remove the conden- I Higher steam quench minute (scfm). There
sate from the system. pressure will cause the will be no other visual
ii. Once the steam quench excess steam to exhaust indicators at the seal
Circle 110 on Reader Service Card

28 MAY 2005 www.pump-zone.com PUMPS & SYSTEMS


MAY05PUMPS&SYSp24-33 4/19/05 2:32 PM Page 29

WARNING: Never open the main


isolation valve on an external fluid
quench line after the equipment
has been prepared for service or
while it is in service. The external
fluid quench system should be
placed in service prior to lining the
equipment up for operation and
should not be isolated until the
equipment is removed for mainte-
nance. Opening the fluid quench
line while the equipment is in ser-
vice (HOT) can seriously damage
the mechanical seal and places the
F i g u r e 3 . A P I P i p i n g P l a n - 6 2 N i t r o g e n Q u e n c h P i p i n g L ay o u t operating personnel at a serious
safety risk.
gland to show nitro- regulator) on quench
gen is flowing. The pres- line near the primary
sure gauge and flow me- seal gland to create I Proceed with opening
ter are the only indica- all process valves to place
recommended flow. (See
tors to show the system
Table 1.) the pump in service.
is operating properly.
I Nitrogen is expensive.
Excessive nitrogen flow
rates will not damage the
mechanical seal or affect
its performance, but will
increase operating cost
of the system [3].
c. Water Quench: (See Fig. 4.)
i. Open needle valve (or
block valve upstream of
pressure regulator) on
quench line near prima-
ry seal gland to create
recommended flow.
ii. Throttle needle valve
(or adjust pressure regu-
Circle 120 on Reader Service Card

lator) until a slow water


drip appears at back side
of seal gland.
I Open needle valve
controlling the quench
pressure (or block valve
upstream of the pressure

PUMPS & SYSTEMS www.pump-zone.com MAY 2005 29


MAY05PUMPS&SYSp24-33 4/19/05 2:32 PM Page 30

2. Proceed with closing all pro-


cess valves to isolate pump
from service.
3. Close main valve isolating the
external fluid quench system.
a. Steam Quench: Open
drain valve to remove
any condensate from
system. This step is
important to reduce risk
of freezing during cold
weather.
F i g u r e 4 . A P I P i p i n g P l a n - 6 2 Wa t e r Q u e n c h P i p i n g L ay o u t
b. Nitrogen Quench: No
I Check for leaks around ensure the system is per- additional steps are
any valves and connec- forming. required to isolate the
tions in the external fluid system for maintenance.
quench line. c. Water Quench: No addi-
I Start pump per nor-
Shutdown Guidelines tional steps are required
mal start-up procedure. The following steps are rec- to isolate the system for
ommended to safely isolate an maintenance.
I Once the pump is in
external fluid quench system for 4. The equipment is now isolat-
service, check the visual
maintenance. ed and ready for mainte-
indicator (exhausting
steam, water dripping 1. Shut down pump per normal nance.
and pressure reading) to shutdown procedure.
Circle 108 on Reader Service Card

30 MAY 2005 www.pump-zone.com PUMPS & SYSTEMS


MAY05PUMPS&SYSp24-33 4/19/05 4:03 PM Page 31

Table 1: Recommended flow rates and/or pressures

Preventative subsequent inspections, dripping from back of


the steam quench sys- the seal gland.
Maintenance Tasks tem should be more ii. Visually note reading
The external fluid quench thoroughly reviewed to on pressure gauge (if
system should be checked daily ensure it is operating applicable). The exter-
during normal operator rounds. properly. nal water quench pres-
The Preventative Maintenance b. Nitrogen Quench: sure should set be-
(PM) steps outlined below are set
i. Visually note reading tween 1 – 3 PSIG at the
up to assist operating personnel
on flow meter (if appli- inlet connection.
in troubleshooting the system.
cable). The flow meter
1. Verify that the main isolation should read ~ 1 scfm. Troubleshooting
valve for the external quench The typical failure mode for
ii. Visually note pressure
system is open. an external fluid quench system
gauge reading. It should
2. Follow the next steps for the be between 1 – 3 PSIG is a closed valve or clogged
different fluid quench appli- quench line. In the event the
at the inlet connection.
cations. Preventative Maintenance indi-
a. Steam Quench: c. Water Quench: cators show that the system is not
i. Visually note steam ex- i. Visually note water operating properly, shut down
hausting from back of
seal gland.
ii. Verify steam trap is
operating properly by
opening drain valve to
see if there is any con-
densate in the system.
iii. Visually note reading
on pressure gauge. The
external steam quench
pressure should set
between 1–3 PSIG.
iv. Visually note reading
on the flow meter (if
applicable). It should
read between 5 lbs/hr
and 10 lbs/hr.
v. Take a temperature
Circle 170 on Reader Service Card

reading at the interface


of the shaft and sec-
ondary sealing device
and note the tempera-
ture when the steam
quench is operating
properly. If the temper-
ature varies by more
than 10° F upon

PUMPS & SYSTEMS www.pump-zone.com MAY 2005 31


MAY05PUMPS&SYSp24-33 4/19/05 4:01 PM Page 32

the equipment according to the References


steps outlined previously.
1. Dura Seal Manual, The Sealing
The tips below are set up to
Technology Guidebook, Flow-
assist operating and maintenance
serve Corporation, Copyrighted
personnel in troubleshooting the
1994.
system.
2. API-682 Shaft Sealing Systems
1. Verify that main isolation valve for Centrifugal and Rotary
for the external fluid quench Pumps.
system is open. For an external
3. API Piping Plan, Training Man-
steam quench system, open
ual, Flowserve Corporation,
drain valve to see if there is ade-
quate pressure from the main Copyrighted 2000.
isolation valve.
2. Open and close needle valve (or Keith D. Schindler is a Rotating
Equipment Engineer with Schindler
block valve) to make sure it is
Engineering, Inc. The firm specializes
not plugged by debris. in machine repair, procedure writing,
3. If this proves successful, adjust Root Cause Failure Analysis on prob-
pressure and put equipment lem equipment and operator training.
back in service according to the Schindler holds a BS degree in
line-up procedure. Otherwise, Mechanical Engineering from the
University of Houston, and is a
isolate the equipment and pre-
Registered Professional Engineer in
pare to remove external fluid Michigan and Virginia. Contact him
quench line for inspection. directly at SchindlerInc@aol.com
4. Once the equipment is ready for
maintenance, remove external Paul McMahan is the Rotating
fluid quench line from seal Equipment Specialist Program Man-
gland. ager for Flowserve FSD Seal Group
in the Baton Rouge, LA, Service
a. Check needle valve (or Center. He has more than 30 years of
pressure regulator) for experience with mechanical seals and
pluggage. was one of the pioneers in the
b. Check main isolation valve mechanical seal alliance concept.
for pluggage. McMahan can be reached at pmcma-
han@-flowserve.com
5. If this proves successful:
a. Reconnect external fluid A piping plan pocket pal with a
quench piping. brief description of many of the stan-
b. Prepare external quench dard API piping plans, including
Plan 62, is available as a download
system for service accord-
in .PDF format or as a handy pocket
ing to line-up procedure.
reference. To obtain your piping plan
6. If the problem can’t be found, pocket pal, log on to www.Flowserve.-
contact your Mechanical Seal com/seals/literature and request “Me-
representative for assistance. chanical Seal Piping Plans” publica-
P&S tion FRA160.

32 MAY 2005 www.pump-zone.com PUMPS & SYSTEMS

Você também pode gostar