Você está na página 1de 15

APPENDIX A 2.2.

6 Stop Switch in Pits


There shall be installed in the pit of each elevator an
ASME A17.1 CODE
enclosed stop switch or switches meeting the requirements
The following material is reprinted with permission from the American of 2.26.2.7 and 2.2.6.1 through 2.2.6.3.
Society of Mechanical Engineers.
2.2.6.1 This switch shall be so located as to be acces-
sible from the pit access door. Where access to the pits of
SECTION 2.2 elevators in a multiple hoistway is by means of a single
PITS access door, the stop switch for each elevator shall be
2.2.4 Access to Pits located adjacent to the nearest point of access to its pit
Safe and convenient access shall be provided to all pits, from the access door.
and shall conform to 2.2.4.1 through 2.2.4.4. 2.2.6.2 In elevators where access to the pit is through
2.2.4.4 Separate pit door, when provided, shall be sub- the lowest landing hoistway door, a stop switch shall be
ject to the following requirements: located approximately 450 mm (18 in.) above the floor
(a) If the door swings into the pit, it shall be level of the landing, within reach from this access floor
located so that it does not interfere with moving and adjacent to the pit ladder, if provided. When the pit
equipment. exceeds 1 700 mm(67 in.) in depth, an additional stop
(b) If the door swings out, and the lowest structural or switch is required adjacent to the pit ladder and approxi-
mechanical part, equipment, or device installed beneath mately 1 200 mm (47 in.) above the pit floor.
the car platform, except guide shoes or rollers or safety 2.2.6.3 Where more than one switch is provided, they
jaw assemblies, projects below the top of the separate pit shall be wired in series.
access door opening when the car is level with the bottom
terminal landing
(1) an electric contact conforming to 2.26.2.26 shall SECTION 2.4
be provided to prevent operation of the elevator when the VERTICAL CLEARANCES AND RUNBYS
door is open; and FOR CARS AND COUNTERWEIGHTS
(2) the door shall be provided with a vision 2.4.1 Bottom Car Clearances
panel(s) that is glazed with clear wired glass not less than 2.4.1.1 When the car rests on its fully compressed
6 mm (0.25 in.) thick, will reject a ball 150 mm (6 in.) in buffers or bumpers, there shall be a vertical clearance of
diameter, and have an area of not more than 0.03 m 2 (47 not less than 600 mm (24 in.) between the pit floor and the
in.2). lowest structural or mechanical part, equipment, or device
(c) The door shall provide a minimum opening of installed beneath the car platform, except as specified in
750 mm (29.5 in.) in width and 1 825 mm (72 in.) in 2.4.1.2.
height.
(d) The door shall be equipped with a barrier con- 2.4.1.2 The 600 mm (24 in.) clearance does not apply
forming to 2.11.1.2(i), where the door sill is located more to the following:
than 300 mm (12 in.) above the pit floor. (a) any equipment on the car within 300 mm (12 in.)
(e) The door shall be self-closing and provided with a horizontally from any side of the car platform;
spring-type lock arranged to permit the door to be opened (b) any equipment located on or traveling with the car
from inside of the pit without a key. Such doors shall be located within 300 mm (12 in.) horizontally from either
kept closed and locked. The key shall be of Group 1 Secu- side of the car frame centerline parallel to the plane of the
rity (see 8.1). guide rails; and
(c) any equipment mounted in or on the pit floor
2.2.5 Illumination of Pits located within 300 mm (12 in.) horizontally from either
A permanent lighting fixture shall be provided and shall side of the car frame centerline parallel to the guide rail.
conform to 2.2.5.1 through 2.2.5.3. 2.4.1.3 In no case shall the available refuge space be
2.2.5.1 The lighting shall provide an illumination of less than the following:
not less than 100 lx (10 fc) at the pit floor and at a pit plat- (a) a horizontal area of 600 mm (24 in.) by 1 200 mm
form, when provided. (48 in.) with a height of 600 mm (24 in); or
(b) a horizontal area of 450 mm (18 in.) by 900 mm
2.2.5.2 The light bulb(s) shall be externally guarded to (35 in.) with a height of 1 070 mm (42 in.).
prevent contact and accidental breakage.
2.4.1.4 Trenches and depressions or foundation
2.2.5.3 The light switch shall be so located as to be encroachments permitted by 2.2.2.2 shall not be consid-
accessible from the pit access door. ered in determining these clearances.

42
21
2.4.1.5 When the car is resting on its fully compressed (1) 115% of the rated speed where oil buffers are
buffers or bumpers, no part of the car, or any equipment used, or 115% of the reduced striking speed when emer-
attached thereto or equipment traveling with the car, shall gency terminal-speed limiting devices meeting the
strike any part of the pit or any equipment mounted requirements of 2.25.4 are used and no compensating rope
therein. tie-down device in conformance with 2.17.17 is provided
(see 8.2.5 for gravity stopping distances); or
2.4.1.6 In any area in the pit, outside the refuge space,
(2) the governor tripping speed where spring buffers
where the vertical clearance is less than 600 mm (24 in.),
are used.
that area shall be clearly marked on the pit floor. Markings
(e) the distance to which the compensating rope tie-
shall not be required in the area under the platform guard
down device, if provided (see 2.17.17) limits the jump of
and guiding means if that is the only area in the pit where
the car when the counterweight strikes the buffers at
the vertical clearance is less than 600 mm (24 in.). The
speeds specified in 2.4.6.2(d).
marking shall consist of alternating 100 mm (4 in.) diago-
nal red and white stripes. In addition, a sign with the words
DANGER LOW CLEARANCE shall be prominently SECTION 2.11
posted on the hoistway enclosure and be visible from PROTECTION OF HOISTWAY OPENINGS
within the pit and the entrance to the pit. The sign shall
2.11.11 Entrances, Horizontal Slide Type
conform to ANSI Z535.2 or CAN/CSA-Z321, whichever
is applicable (see Part 9). The sign shall be of such mate- 2.11.11.5 Panels. Panels shall conform to 2.11.11.5.1
rial and construction that the letters and figures stamped, through 2.11.11.5.8.
etched, cast, or otherwise applied to the face shall remain 2.11.11.5.1 The panels shall overlap the top and sides
permanently and readily legible. of the opening, and each other, in the case of multispeed
entrances, by not less than 13 mm (0.5 in.).
2.4.6 Top Car Clearances for
Where entrances without frames are used, the overlap
Counterweighted Elevators
shall extend the thickness of the facing used to finish the
2.4.6.1 General Requirements. The top car clearance opening plus 13 mm (0.5 in.) or more.
shall be not less than the sum of the following:
(a) dimensions specified in 2.4.6.2(a) through (d); or 2.11.11.5.2 The clearance shall not exceed 10 mm
(b) dimensions specified in 2.4.6.2(a), (b), (c), and (e). (0.375 in.) between
(a) the panel and the frame;
2.4.6.2 Components of the Top Car Clearances. The (b) the panel and the wall, where entrances without
following shall be considered when calculating the mini- frames are used in masonry or concrete;
mum top car clearances: (c) related panels of multispeed entrances; and
(a) the designed maximum bottom counterweight (d) the panel and the sill measured vertically.
runby [see 2.4.4(b)];
(b) the stroke of the counterweight buffer, determined 2.11.11.5.3 The leading panel edge of side-opening
as follows: entrances shall not close into pockets in the strike jamb
(1) for full stroke buffers, the stroke of the buffer and shall be smooth and free of sharp projections.
used, or the remaining stroke when the buffer is com- 2.11.11.5.4 The meeting panel edges of center-opening
pressed with the car at the top terminal landing (see 2.4.2 entrances shall be smooth and free of sharp projection.
and 2.22.4.8); or The meeting panel edges of center-opening entrances
(2) for reduced stroke oil buffers (see 2.22.4.1.2), the shall be protected with not less than one resilient male
full stroke required by 2.22.4.1.1. member extending the full height of the panel. The
(c) 600 mm (24 in.) or the distance which any sheave resilient members shall be permitted to interlock by not
or any other equipment mounted in or on the car more than 10 mm (0.375 in.).
crosshead projects above the top of the car crosshead, When in the closed position, the distance between the
whichever is greater, but in no case shall there be less than metal parts of the meeting panels shall not exceed 13 mm
150 mm (6 in.) clearance above the equipment, exclusive (0.5 in.).
of guide-shoe assemblies or gate posts for vertically slid-
ing gates, mounted on the car top or in or on the car 2.11.11.5.5 No areas shall be depressed or raised more
crosshead when the car has reached its maximum upward than 3 mm (0.125 in.) from the adjacent area and edges
movement. shall be beveled at not more than 30 deg to the panel sur-
face.
NOTE [2.4.6.2(c)]: See also 2.4.12, requirements for refuge space on
top of car enclosure. 2.11.11.5.6 Where decorative material is applied to
(d) 1 2 the gravity stopping distance, based on: listed/certified panels it shall conform to the requirements
of the certifying organization.

43
22
2.11.11.5.7 The entrance assembly shall be capable of 2.12.7.2 Location and Design. Hoistway access
withstanding a force of 2 500 N (560 lbf) applied on the switches shall conform to 2.12.7.2.1 through 2.12.7.2.3.
landing side at right angles to and approximately at the
2.12.7.2.1 The switch shall be installed adjacent to
center of a panel. This force shall be distributed over an
the hoistway entrance at the landing with which it is iden-
area of approximately 100 mm by 100 mm (4 in. by 4 in.).
tified.
There shall be no appreciable permanent displacement or
deformation of any parts of the entrance assembly result- 2.12.7.2.2 The switch shall be of the continuous-
ing from this test. pressure spring-return type, and shall be operated by a
cylinder-type lock having not less than a five-pin or five-
2.11.11.5.8 Means shall be provided to prevent open-
disk combination, with the key removable only when the
ing of locked doors more than 20 mm (0.8 in.) per panel
switch is in the OFF position. The key shall be Group
at the farthest point from the interlock when a force of
1 Security (see 8.1).
135 N (30 lbf) is applied in the opening direction at the
leading edge of the door at the farthest point from the 2.12.7.2.3 The electric contacts in the switch shall
interlock. be positively opened mechanically; their openings shall
not be solely dependent on springs.
SECTION 2.12 2.12.7.3 Operating Requirements. The operation of
HOISTWAY-DOOR LOCKING DEVICES the switch shall permit movement of the car with the hoist-
AND ELECTRIC CONTACTS, AND way door at this landing unlocked or not in the closed
HOISTWAY ACCESS SWITCHES position, and with the car door or gate not in the closed
position, subject to the requirements of 2.12.7.3.1 through
2.12.5 Restricted Opening of Hoistway or Car
2.12.7.3.8.
Doors
Hoistway and car doors of passenger elevators shall 2.12.7.3.1 The operation of the switch shall not ren-
conform to 2.12.5.1 through 2.12.5.3. der ineffective the hoistway-door interlock or electric con-
tact at any other landing, nor shall the car move if any
2.12.5.1 When a car is outside the unlocking zone, the other hoistway door is unlocked.
hoistway doors or car doors shall be so arranged that the
hoistway doors or car doors cannot be opened more than 2.12.7.3.2 The car cannot be operated at a speed
100 mm (4 in.) from inside the car. greater than 0.75 m/s (150 ft/min).

2.12.5.2 When the car doors are so arranged that they 2.12.7.3.3 For automatic and continuous-pressure
cannot be opened when the car is outside the unlocking operation elevators, provided
zone, the car doors shall be openable from outside the car (a) car and landing operating devices shall first be
without the use of a special tool(s). made inoperative by means within the car. This means
shall enable the hoistway access switches and shall be
2.12.5.3 The doors shall be openable from within the key-operated or behind a locked cover. The key shall be
car (see 2.14.5.7) when the car is within the unlocking Group 1 Security (see 8.1); and
zone. (b) power operation of the hoistway door and/or car
NOTE (2.12.5): See also 2.12.1 and Appendix B, Unlocking Zone. door or gate is inoperative.

2.12.7 Hoistway Access Switches 2.12.7.3.4 Automatic operation by a car-leveling


device is inoperative.
2.12.7.1 General
2.12.7.3.5 Both top-of-car inspection operation (see
2.12.7.1.1 Hoistway access switches shall be pro- 2.26.1.4.2) and in-car inspection operation (see 2.26.1.4.3)
vided when the rated speed is greater than 0.75 m/s (150 are not in effect.
ft/min) at
(a) the lowest landing for access to the pit, when a sep- 2.12.7.3.6 The movement of the car initiated and
arate pit access door is not provided; and maintained by the access switch at the lowest landing, if
(b) the top landing for access to the top of the car. this landing is the normal means of access to the pit, shall
be limited in the up direction to the point where the bot-
2.12.7.1.2 For elevators with a speed of 0.75 m/s tom of the platform guard is even with hoistway entrance
(150 ft/min) or less, hoistway access switches shall be pro- header.
vided at the top landing when the distance from the top
of the car to the landing sill exceeds 900 mm (35 in.) when 2.12.7.3.7 The movement of the car initiated and
the car platform is level with the landing immediately maintained by the upper access switch shall be limited in
below the top landing. the down direction to a travel not greater than the height
of the car crosshead above the car platform, and limited in

44
23
the up direction to the distance the platform guard extends taken as the horizontal distance from a point 25 mm (1 in.)
below the car platform. away from the open jamb to a point 25 mm (1 in.) from the
center meeting point of the doors.
2.12.7.3.8 The access switch shall only control the
(c) The average closing speed shall be determined by
movement of the car within the zone specified in
measuring the time required for the leading edge of the
2.12.7.3.6 or 2.12.7.3.7. Control circuits related to, or
door to travel the code zone distance.
operated by, the hoistway access switches shall comply
with 2.26.9.3(c), (d), and (e) and 2.26.9.4. 2.13.4.2.3 Door Force. The force necessary to pre-
vent closing of the hoistway door (or the car door or gate
if power operated) from rest shall not exceed 135 N (30
SECTION 2.13 lbf) (see 2.13.3.1). This force shall be measured on the
POWER OPERATION OF HOISTWAY leading edge of the door with the door at any point
DOORS AND CAR DOORS between one third and two thirds of its travel.
2.13.4 Closing Limitations for Power-Operated
2.13.4.2.4 Data Plate. A data plate conforming to
Horizontally Sliding Hoistway Doors and
Horizontally Sliding Car Doors or Gates 2.16.3.3 shall be attached to the power door operator or to
the car crosshead and shall contain the following infor-
2.13.4.2 Closing Mechanism mation:
2.13.4.2.1 Kinetic Energy (a) minimum door closing time in seconds for the
(a) Where the hoistway door and the car door/gate are doors to travel the code zone distance as specified in
closed in such a manner that stopping either one manually 2.13.4.2.2 corresponding to the kinetic energy limits spec-
will stop both, the kinetic energy of the closing door sys- ified in 2.13.4.2.1(b)(2);
tem shall be based upon the sum of the hoistway and the (b) minimum door closing time in seconds for the
car door weights, as well as all parts rigidly connected doors to travel the Code zone distance as specified in
thereto, including the rotational inertia effects of the door 2.13.4.2.2 corresponding to the kinetic energy limits spec-
operator and the connecting transmission to the door pan- ified in 2.13.4.2.1(c)(2), if applicable [see 2.27.3.1.6(e)];
els. (c) where heavier hoistway doors are used at certain
(b) Where a reopening device conforming to 2.13.5 is floors, the minimum door closing time in seconds corre-
used, the closing door system shall conform to the fol- sponding to the kinetic energy limits specified in
lowing requirements: 2.13.4.2.1(b)(2) and 2.13.4.2.1(c)(2), if applicable, for
(1) The kinetic energy computed for the actual clos- the corresponding floors shall be included on the data
ing speed at any point in the code zone distance defined by plate.
2.13.4.2.2 shall not exceed 23 J (17 ft-lbf); and
(2) The kinetic energy computed for the average
SECTION 2.14
closing speed as determined in accordance with 2.13.4.2.2
CAR ENCLOSURES, CAR DOORS AND
shall not exceed 10 J (7.37 ft-lbf).
(c) Where a reopening device is not used, or has been
GATES, AND CAR ILLUMINATION
rendered inoperative (see 2.13.5), the closing door system 2.14.1 Passenger and Freight Enclosures,
shall conform to the following requirements: General
(1) The kinetic energy computed for the actual clos- 2.14.1.5 Top Emergency Exits. An emergency exit
ing speed at any point in the code zone distance defined by with a cover shall be provided in the top of all elevator
2.13.4.2.2 shall not exceed 8 J (6 ft-lbf). cars, except cars in partially enclosed hoistways (see
(2) The kinetic energy computed for the average 2.14.1.5.2).
closing speed within the code zone distance (see
2.14.1.5.1 Top emergency exits shall conform to the
2.13.4.2.2), or in any exposed opening width, including
following requirements:
the last increment of door travel, shall not exceed 3.5 J (2.5
(a) The top emergency exit opening shall have an area
ft-lbf).
of not less than 0.26 m 2 (400 in.2 ) and shall measure not
2.13.4.2.2 Door Travel in Code Zone Distance less than 400 mm (16 in.) on any side.
(a) For all side sliding doors using single or multiple (b) The top emergency exit and suspended ceiling
speed panels, the code zone distance shall be taken as the opening, if any, shall be so located as to provide a clear
horizontal distance from a point 50 mm (2 in.) away from passageway, unobstructed by fixed equipment located in
the open jamb to a point 50 mm (2 in.) away from the or on top of the car. Equipment is permitted directly above
opposite jamb. the exit opening, provided that
(b) For all center-opening sliding doors using single or (1) it is not less than 1 070 mm (42 in.) above the top
multiple speed panels, the code zone distance shall be of the car; or

45
24
(2) the exit is located to allow unobstructed passage (3) must be manually reset from the top of the car
of a parallel piped volume measuring 300 mm by 500 mm and only after the cover is within 50 mm (2 in.) of the fully
by 1 500 mm (12 in. by 20 in. by 59 in.) at an angle not less closed position; and
than 60 deg from the horizontal (see Appendix C). (4) shall be protected against mechanical damage.
(c) The top emergency exit cover shall open outward.
2.14.1.5.2 On elevators in partially enclosed hoist-
It shall be hinged or securely attached with a chain when
ways, means shall be provided to facilitate emergency
in both the open and closed positions. If a chain is used,
evacuation of passengers. Such means shall not require a
it shall be not more than 300 mm (12 in.) in length and
top emergency exit. A top emergency exit shall be permit-
have a factor of safety of not less than 5. The exit cover
ted.
shall only be openable from the top of the car, where it
shall be openable without the use of special tools. The exit 2.14.4 Passenger and Freight Car Doors and
cover of the lower compartment of a multideck elevator Gates, General Requirements
shall be openable from both compartments. On elevators
2.14.4.11 Closed Position of Car Doors or Gates.
with two compartments, if the emergency exit of the lower
Car doors or gates shall be considered to be in the closed
compartment does not open directly into the upper com-
position under the following conditions:
partment, a guarded passageway shall be provided
(a) for horizontally sliding doors or gates, when the
between the lower compartment roof and the upper com-
clear open space between the leading edge of the door or
partment floor.
gate and the nearest face of the jamb does not exceed 50
(d) The movable portion (exit panel) of the suspended
mm (2 in.) except where car-doors are provided with a car
ceiling that is below the top exit opening shall be
door interlock(s), 10 mm (0.375 in.);
restrained from falling. It shall be permitted to be hinged
(b) for vertically sliding counterweighted doors or
upward or downward, provided that the exit will permit a
gates, when the clear open space between the leading edge
clear opening with the top exit opening.
of the door or gate and the car platform sill does not
(1) A minimum clear headroom of 2 030 mm (80
exceed 50 mm (2 in.); and
in.) above the car floor shall be maintained when down-
(c) for horizontally sliding center-opening doors, or
ward-swinging suspended ceiling exit panels are used.
vertically sliding biparting counterbalanced doors, when
(2) Upward-opening suspended ceiling exit panels
the door panels are within 50 mm (2 in.) of contact with
shall be restrained from closing when in use and shall not
each other, except where horizontally sliding center open-
diminish the clear opening area of the corresponding top
ing car doors are provided with a car door interlock(s), 10
exit opening.
mm (0.375 in.).
(3) The movable portion and the fixed portion of a
suspended ceiling shall not contain lamps that could be
shattered by the rescue operation using the top emergency SECTION 2.17
exit. The movable portion of the suspended ceiling shall CAR AND COUNTERWEIGHT SAFETIES
be permitted to contain light fixtures connected to the sta- 2.17.3 Function and Stopping Distance of
tionary portion of the suspended ceiling wiring by means Safeties
of a plug and socket or by flexible armored wiring. Flexi-
ble wiring shall not be used to support or restrain the exit The safety device, or the combined safety devices
opening in the suspended ceiling in the open position. where furnished, shall be capable of stopping and sustain-
(e) Where elevators installed in enclosed hoistways ing the entire car with its rated load from governor tripping
are provided with special car top treatments such as speed (see also 2.16.8).
domed or shrouded canopies, the exit shall be made Type B safeties shall stop the car with its rated load
accessible, including the car top refuge space as specified from governor tripping speed within the range of the max-
in 2.4.12. imum and minimum stopping distances as determined by
(f) Immediately adjacent to the top emergency exit the formulas in 8.26. Table 2.17.3 and Figs. 8.2.6-1
there shall be a space available for standing when the through 8.2.6-3 show the maximum and minimum stop-
emergency exit cover is open. This space shall be permit- ping distances for various governor tripping speeds, when
ted to include a portion of the refuge area (see 2.4.12). All tested in conformance with 8.10 and 8.11.
exit covers shall be provided with a car top emergency exit 2.17.5 Identification and Classification of
electrical device (see 2.26.2.18) that will prevent opera- Types of Safeties
tion of the elevator car if the exit cover is open more than
50 mm (2 in.), and the device shall be so designed that it Car safety devices (safeties) are identified and classi-
(1) is positively opened; fied on the basis of performance characteristics after the
(2) cannot be closed accidentally when the cover is safety begins to apply pressure on the guide rails. On this
removed; basis, there are three types of safeties.

46
25
2.17.5.1 Type A Safeties. Safeties that develop a rap- 2.17.11 Maximum Permissible Movement of
idly increasing pressure on the guide rails during the stop- Governor Rope to Operate the Safety
ping interval, the stopping distance being very short due Mechanism
to the inherent design of the safety. The operating force is For all Type B safeties, the movement of the governor
derived entirely from the mass and the motion of the car rope, relative to the car or the counterweight, respectively,
or the counterweight being stopped. These safeties apply required to operate the safety mechanism from its fully
pressure on the guide rails through eccentrics, rollers, or retracted position to a position where the safety jaws begin
similar devices, without any flexible medium purposely to exert pressure against the guide rails, shall not exceed
introduced to limit the retarding force and increase the the following values based on rated speed:
stopping distance. (a) for car safeties:
2.17.5.2 Type B Safeties. Safeties that apply limited (1) 1 m/s (200 ft/min) or less: 1 070 mm (42 in.);
pressure on the guide rails during the stopping interval, (2) 1.01 m/s (201 ft/min) to 1.9 m/s (375 ft/min):
and which provide stopping distances that are related to 915 mm (36 in.); and
the mass being stopped and the speed at which application (3) over 1.9 m/s (375 ft/min): 756 mm (30 in.).
of the safety is initiated. Retarding forces are reasonably (b) for counterweight safeties, all speeds: 1 070 mm
uniform after the safety is fully applied. Continuous ten- (42 in.).
sion in the governor rope may or may not be required to Drum-operated car and counterweight safeties, requir-
operate the safety during the entire stopping interval. Min- ing continual unwinding of the safety drum rope to fully
imum and maximum distances are specified on the basis apply the safety, shall be so designed that not less than
of governor tripping speed (see 2.17.3). three turns of the safety rope will remain on the drum after
the overspeed test of the safety has been made with rated
2.17.5.3 Type C Safeties (Type A With Oil Buffers). load in the car.
Safeties that develop retarding forces during the com-
pression stroke of one or more oil buffers interposed 2.17.12 Minimum Factors of Safety and Stresses
between the lower members of the car frame and a gov- of Safety Parts and Rope Connections
ernor-operated Type A auxiliary safety plank applied on 2.17.12.4 Rope used as a connection from the safety to
the guide rails. The stopping distance is equal to the effec- the governor rope, including rope wound on the safety-
tive stroke of the buffers. rope drum, shall be not less than 9.5 mm (0.375 in.) diam-
2.17.7 Governor-Actuated Safeties and Car-
eter, shall be made of metal, and shall be corrosion resist-
Safety-Mechanism Switches Required ant. The factor of safety of the rope shall be not less than
5. Tiller-rope construction shall not be used.
2.17.7.1 Counterweight safeties, where provided for
rated speeds over 0.75 m/s (150 ft/min), and car safeties,
shall be actuated by separate speed governors. SECTION 2.18
Counterweight safeties for rated speeds of not over 0.75 SPEED GOVERNORS
m/s (150 ft/min) may be operated as a result of the break- 2.18.2 Tripping Speeds for Speed Governors
ing or slackening of the suspension ropes and shall be per-
2.18.2.1 Car Speed Governors. Speed governors for
mitted to be of the inertia or other approved type without
car safeties shall be set to trip at car speeds as follows:
governors.
(a) at not less than 115% of the rated speed; and
Where counterweight safeties are furnished to provide
(b) at not more than the tripping speed listed oppo-
ascending car overspeed protection in accordance with
site the applicable rated speed in Table 2.18.2.1. Maxi-
2.19.1.1, they shall be actuated by a counterweight speed
mum tripping speeds for intermediate rated speeds shall
governor (see 2.17.4).
be determined from Figs. 8.2.5-1 and 8.2.5-2. For rated
2.17.7.2 Every car safety shall be provided with a speeds exceeding 10 m/s (2,000 ft/min), the maximum
switch, operated by the car safety mechanism (see tripping speeds shall not exceed 120% of the rated
2.26.2.9). speed.
A switch operated by the safety mechanism is not
required on counterweight safeties. 2.18.6 Design of Governor Rope-Retarding
Means for Type B Safeties
2.17.7.3 The car-safety mechanism switch shall oper-
ate before or at the time of application of the safety. Type B car and counterweight safeties shall be activated
by a speed governor with a governor-rope-retarding
2.17.7.4 Switches operated by the car-safety mecha- means conforming to 2.18.6.1 through 2.18.6.5.
nism shall be of a type that cannot be reset until the car-
safety mechanism has been returned to the unapplied posi- 2.18.6.1 Upon activation at the tripping speeds given
tion. by 2.18.2, the means shall retard the rope with a force that

47
26
is at least 67% greater than the force required to activate 2.27.3.1 Phase I Emergency Recall Operation
the safety or to trip the governor-rope releasing carrier,
2.27.3.1.1 A three-position key-operated switch
where used (see 2.17.15).
shall be
2.18.6.2 The means shall be set to allow the governor (a) provided only at the designated level for each sin-
rope to slip through the speed governor at a rope tension gle elevator or for each group of elevators;
(the governor pull-through tension) higher than required (b) labeled FIRE RECALL and its positions marked
to activate the safety or to trip the releasing carrier as spec- RESET, OFF, and ON (in that order), with the
ified in 2.17.15. The maximum tension in the rope shall OFF position as the center position. The FIRE
not exceed one-fifth of the rated ultimate strength of the RECALL letters shall be a minimum of 5 mm (0.25 in.)
rope. high in red or a color contrasting with a red background;
(c) located in the lobby within sight of the elevator or
2.18.6.3 The means shall be designed to prevent appre-
all elevators in that group and shall be readily accessible.
ciable damage to or deformation of the governor rope
resulting from its application (stopping action). 2.27.3.1.2 An additional key-operated FIRE
RECALL switch, with two-positions, marked OFF
2.18.6.4 The means shall provide a continuous tension
and ON (in that order), shall be permitted only at the
in the governor rope as required to operate the safety dur-
building fire control station.
ing the entire stopping interval in accordance with
2.17.5.2. 2.27.3.1.3 The switch(es) shall be rotated clockwise
to go from the RESET (designated level switch only),
2.18.6.5 The governor shall be arranged to be tripped
to OFF to ON positions. Keys shall be removable
by hand to facilitate the tests specified in 8.10.
only in the OFF and ON positions.
2.27.3.1.4 Only the FIRE RECALL switch(es) or
SECTION 2.20 fire alarm initiating device located at floors that are served
SUSPENSION ROPES AND THEIR by the elevator, or in the hoistway, or in the elevator
CONNECTIONS machine room (see 2.27.3.2) shall initiate Phase I Emer-
2.20.9 Suspension Rope Fastening gency Recall Operation.
2.20.9.8 Anti-Rotation Devices. Following the com- 2.27.3.1.5 All FIRE RECALL switches shall be
pletion of the rope socketing and any adjustments of indi- provided with an illuminated visual signal to indicate
vidual shackle rods as provided for in 2.20.9.2, means when Phase I Emergency Recall Operation is in effect.
shall be provided to prevent the rotation of the suspension
ropes without restricting their movement horizontally or 2.27.3.1.6 When a FIRE RECALL switch is in the
vertically. ON position all cars controlled by the switch shall oper-
ate as follows:
(a) A car traveling towards the designated level shall
SECTION 2.27 continue nonstop to the designated level and power-oper-
EMERGENCY OPERATION AND ated doors shall open and remain open.
SIGNALING DEVICES On cars with two entrances, if both entrances can be
NOTE (2.27): Additional requirements may be found in the building opened at the designated level, only the doors serving the
code. lobby where the FIRE RECALL switch is located shall
open and remain open.
2.27.3 Firefighters Emergency Operation (b) A car traveling away from the designated level shall
Automatic Elevators reverse at or before the next available landing without
Firefighters Emergency Operation shall apply to all opening its doors and proceed to designated level.
automatic elevators except (c) A stopped car shall have the in-car stop switch (see
(a) where the hoistway or a portion thereof is not 2.26.2.21) and the emergency stop switch in the car (see
required to be fire-resistive construction (see 2.1.1.1), the 2.26.2.5) when provided, rendered inoperative as soon as
travel does not exceed 2 000 mm (80 in.), and the hoist- the car moves away from the landing. A moving car shall
way does not penetrate a floor; have the in-car stop switch and the emergency stop switch
(b) in jurisdictions enforcing the NBCC where the in the car when provided, rendered inoperative without
NBCC does not require Firefighters Emergency Opera- delay. Once the emergency stop switch in the car and the
tion. in-car stop switch have been rendered inoperative, they
Where Firefighters Emergency Operation is provided shall remain inoperative while the car is on Phase I Emer-
voluntarily these requirements shall also apply. gency Recall Operation. All other stop switches required
by 2.26.2 shall remain operative.

48
27
(d) A car standing at a landing other than the desig- (k) To remove the elevator(s) from Phase I Emergency
nated level, with the doors open and the in-car stop switch Recall Operation, the FIRE RECALL switch shall be
and the emergency stop switch in the car when provided, rotated first to the RESET, and then to the OFF posi-
in the run position, shall conform to the following: tion, provided that
(1) Elevators having automatic power-operated hor- (1) the additional two-position FIRE RECALL
izontally sliding doors shall close the doors without delay switch, where provided, is in the OFF position; and
and proceed to the designated level. (2) no fire alarm initiating device is activated (see
(2) Elevators having power-operated vertically slid- 2.27.3.2).
ing doors provided with automatic or momentary-pressure (l) Means used to remove elevators from normal oper-
closing operation per 2.13.3.4 shall have the closing ation, other than as specified in this Code, shall not pre-
sequence initiated without delay in accordance with vent Phase I Emergency Recall Operation.
2.13.3.4.1, 2.13.3.4.2, 2.13.3.4.3, and 2.13.3.4.5, and the (m) No device, which measures load, shall prevent
car shall proceed to the designated level. operation of the elevator at or below the capacity and load-
(3) Elevators having power-operated doors provided ing required in 2.16.
with continuous pressure closing operation (see 2.13.3.2),
2.27.3.2 Phase I Emergency Recall Operation by
or elevators having manual doors, shall be provided with
Fire Alarm Initiating Devices
a visual and audible signal system [see 2.27.3.1.6(h)] to
alert an operator to close the doors and shall, when the 2.27.3.2.1 In jurisdictions not enforcing the NBCC,
doors are closed, proceed to the designated level. fire alarm initiating devices shall be installed in confor-
Sequence operation, if provided, shall remain effective. mance with the requirements of NFPA 72, and shall be
(e) Door reopening devices for power-operated doors located
that are sensitive to smoke or flame shall be rendered inop- (a) at each floor served by the elevator;
erative without delay. Door reopening devices not sensi- (b) in the associated elevator machine room; and
tive to smoke or flame (e.g., mechanically actuated (c) in the elevator hoistway, when required.
devices) are permitted to remain operative. Door closing 2.27.3.2.2 In jurisdictions enforcing the NBCC,
for power-operated doors shall conform to 2.13.5. automatic Emergency Recall Operation shall be permitted
(f) All car and corridor call buttons shall be rendered when the following devices, complying with the require-
inoperative. All call registered lights and directional ments in the NBCC, initiate the operation:
lanterns shall be extinguished and remain inoperative. Car (a) smoke detectors installed in each elevator lobby, or
position indicators, where provided, shall remain opera- the building fire alarm system;
tive. Where provided, landing position indicators shall be (b) smoke detectors installed in the elevator lobby at
extinguished and remain inoperative, except at the desig- the designated level, if that floor area is not sprinklered
nated level and the building fire control station, where throughout; and
they shall remain operative. (c) smoke detectors installed in the machine room if
(g) Where provided on elevators with vertically slid- the machine room is sprinklered.
ing doors, corridor door open and close buttons shall
remain operative. 2.27.3.2.3 Phase I Emergency Recall Operation to
(h) All cars shall be provided with an illuminated the designated level shall conform to the following:
visual and audible signal system which shall be activated (a) The activation of a fire alarm initiating device spec-
to alert the passengers that the car is returning nonstop to ified in 2.27.3.2.1 or 2.27.3.2.2(a) at any floor, other than
the designated level. The visual graphic shall be as shown at the designated level, shall cause all elevators that serve
in Fig. 2.27.3.1.6(h). The signals shall remain activated that floor, and any associated elevator of a group auto-
until the car has returned to the designated level. matic operation, to be returned nonstop to the designated
(i) A car stopped at a landing shall have the in-car door level.
open button rendered inoperative as soon as the car moves (b) The activation of a fire alarm initiating device
away from the landing The in-car door open button shall specified in 2.27.3.2.1(b) or 2.27.3.2.2(c) shall cause all
remain inoperative when a car stops to reverse direction. elevators having any equipment located in that machine
Once the in-car door open button has been rendered inop- room, and any associated elevators of a group automatic
erative, it shall remain inoperative until the car has operation, to be returned nonstop to the designated level.
returned to the designated level. If the machine room is located at the designated level,
( j) Where an additional FIRE RECALL switch is the elevator(s) shall be returned nonstop to the alternate
provided, both FIRE RECALL switches shall be in the level.
ON position to recall the elevator to the designated level (c) The activation of a fire alarm initiating device
if the elevator was recalled to the alternate level (see specified in 2.27.3.2.1(c) shall cause all elevators having
2.27.3.2.4). any equipment in that hoistway, and any associated ele-

49
28
vators of a group automatic operation, to be returned SECTION 8.11
non-stop to the designated level, except that initiating PERIODIC INSPECTIONS AND TESTS
device(s) installed at or below the lowest landing of Requirement 8.11 covers periodic inspections and tests
recall shall cause the car to be sent to the upper recall of existing installations.
level. NOTE (8.11): Compliance with certain requirements is verifiable through
(d) The Phase I Emergency Recall Operation to the review of design documents, engineering, or type tests.
designated level shall conform to 2.27.3.1.6(a) through
(m). 8.11.2 Periodic Inspection and Tests of
Electric Elevators
2.27.3.2.4 Phase I Emergency Recall Operation to
an alternate level (see 1.3) shall conform to the following: All references to Items are to Items in ASME A17.2.1,
(a) the activation of a fire alarm initiating device spec- Inspectors Manual for Electric Elevators.
ified in 2.27.3.2.1(a) or 2.27.3.2.2(a) that is located at the 8.11.2.2 Periodic Test Requirements Category
designated level, shall cause all elevators serving that level One
to be recalled to an alternate level, unless a FIRE NOTE (8.11.2.2): For test frequency, see 8.11.1.3.
RECALL switch is already in the ON position;
(b) the requirements of 2.27.3.1.6(f), (j), and (m); 8.11.2.2.1 Oil Buffers. Car and counterweight
(c) the requirements of 2.27.3.1.6(a), (b), (c), (d), (e), buffers shall be tested to determine conformance with the
(g), (h), (i), (k), and (l), except that all references to the applicable plunger return requirements (Item 5.3.2).
designated level shall be replaced with alternate 8.11.2.2.2 Safeties
level. (a) Examinations. All working parts of car and coun-
2.27.3.2.5 The recall level shall be determined by terweight safeties shall be examined to determine that they
the first activated fire alarm initiating device for that group are in satisfactory operating condition and that they con-
[see 2.27.3.2.1 or 2.27.3.2.2, see also 2.27.3.1.6(j)]. form to the applicable requirements and 8.7.2.14 through
8.7.2.28 (see 2.17.10 and 2.17.11; Division 112). Check
2.27.3.2.6 When activated, a fire alarm initiating the level of the oil in the oil buffer and the operation of the
device in the machine room shall cause the visual signal buffer compression-switch on Type C safeties.
[see 2.27.3.1.6(h) and Fig. 2.27.3.1.6(h)] to illuminate (b) Tests. Safeties shall be subjected to the following
intermittently only in car(s) with equipment in that tests with no load in the car.
machine room. When activated, a fire alarm initiating (1) Type A, B, or C governor-operated safeties shall
device in the hoistway shall cause the visual signal be operated by tripping the governor by hand with the car
[see 2.27.3.1.6(h) and Fig. 2.27.3.1.6(h)] to illuminate operating at the slowest operating speed in the down direc-
intermittently only in car(s) with equipment in that hoist- tion.
way. In this test, the safety shall bring the car to rest
promptly.
SECTION 8.6 In the case of Type B safeties, the stopping distance
MAINTENANCE, REPAIR, AND is not required to conform to 2.17.3.
REPLACEMENT In the case of Type C safeties, the oil buffer may or
Requirement 8.6 applies to maintenance, repairs, and may not compress its full stroke.
replacements. In the case of Type A, B, or C safeties employing
rollers or dogs for application of the safety, the rollers or
NOTE: See 8.7 for alteration requirements.
dogs are not required to operate their full travel [Item
8.6.4 Maintenance of Electric Elevators 2.29.2(c)].
(2) Governor-operated wood guide-rail safeties shall
The maintenance of electric elevators shall conform to be tested by tripping the governor by hand with the car at
8.6.1 through 8.6.4. rest and moving the car in the down direction until it is
8.6.4.2 Governor Wire Ropes brought to rest by the safety and the hoisting ropes slip on
traction sheaves or become slack on winding drum
8.6.4.2.1 The ropes shall be kept clean. sheaves [Item 2.29.2(d)].
8.6.4.2.2 Governor wire ropes shall not be lubricated (3) Type A and wood guide-rail safeties without
after installation. If lubricants have been applied to gov- governors which are operated as a result of the breaking or
ernor ropes, they shall be replaced, or the lubricant slackening of the hoisting ropes shall be tested by obtain-
removed, and the governor and safety shall be tested as ing the necessary slack rope to cause it to function [Item
specified in 8.11.2.3.2(b) and 8.11.2.2.2. 2.29.2(d)].

50
29
8.11.2.2.3 Governors. Governors shall be operated A metal tag shall be attached to the safety-releasing car-
manually to determine that all parts, including those which rier in a permanent manner, giving the date of the safety
impart the governor pull-through tension to the governor test, together with the name of the person or firm who per-
rope, operate freely [Item 2.28.2(a)]. formed the test.
8.11.2.2.4 Slack-Rope Devices on Winding Drum 8.11.2.3.2 Governors
Machines. Slack-rope devices on winding drum (a) The tripping speed of the governor and the speed at
machines shall be operated manually and tested to deter- which the governor overspeed switch, where provided,
mine conformance with the applicable requirements (Item operates shall be tested to determine conformance with the
2.18). applicable requirements and the adjustable means shall be
sealed [Item 2.28.2(b)].
8.11.2.2.5 Normal and Final Terminal Stopping
(b) The governor rope pull-through and pull-out forces
Devices. Normal and final terminal stopping devices shall
shall be tested to determine conformance with the appli-
be inspected and tested to determine conformance with the
cable requirements, and the adjustment means shall be
applicable requirements (2.25) (Items 3.8.2 and 3.7.2).
sealed [Item 2.28.2(b)].
8.11.2.2.6 Firefighters Emergency Operation.
8.11.2.3.3 Oil Buffers
Firefightersemergency operation shall be tested to deter-
(a) Car oil buffers shall be tested to determine confor-
mine conformance with the applicable requirements
mance with the applicable requirements by running the car
(Division 6).
with its rated load onto the buffer at rated speed, except as
8.11.2.2.7 Standby or Emergency Power Opera- specified in 8.11.2.3.3(b) and (c) [Item 5.3.2(b)(1)]. Coun-
tion. Operation of elevators equipped with standby or terweight oil buffers shall be tested by running the coun-
emergency power shall be tested to determine confor- terweight onto its buffer at rated speed with no load in the
mance with the applicable requirements (Item 1.17.2). car, except as specified in 8.11.2.3.3(b) and (c) [Item
Tests shall be performed with no load in the car. 5.3.2(b)(2)].
(b) For reduced stroke buffers, this test shall be made
8.11.2.2.8 Power Operation of Door System. The
at the reduced striking speed permitted [Item
closing forces of power operated hoistway door systems
5.3.2(b)(1)(b)].
shall be tested to determine conformance with the appli-
(c) This test is not required where a Type C safety is
cable requirements (Item 1.8.2).
used (see 8.11.2.3.1).
8.11.2.2.9 Broken Rope, Tape, or Chain Switch. (d) In making these tests, the normal and emergency
Where a rope, tape, or chain is used to connect the motion terminal stopping devices shall be made temporarily inop-
of the car to the machine room normal limit, the switch erative. The final terminal stopping devices shall remain
that senses failure of this connection shall be tested for operative and be temporarily relocated, if necessary, to
compliance with 2.26.2.6 (Item 3.9.2). permit full compression of the buffer during the test.
8.11.2.3 Periodic Test Requirements Category (e) After completion of the test, a metal tag, indicating
Five the date of the test, together with the name of the person or
firm who performed the test, shall be attached to the buffer
NOTE (8.11.2.3): For test frequency, see 8.11.1.3.
[Item 5.3.2(b)].
8.11.2.3.1 Car and Counterweight Safeties. 8.11.2.3.4 Braking System. For passenger elevators
Types A, B, and C car safeties, except those operating on and all freight elevators, the brake shall be tested for com-
wood guide rails, and their governors, shall be tested with pliance with applicable requirements. Place the load as
rated load in the car. Counterweight safety tests shall be shown in Table 8.11.2.3.4 in the car and run it to the low-
made with no load in the car. Tests shall be made by trip- est landing by normal operating means. The driving
ping the governor by hand at the rated speed. The fol- machine shall safely lower, stop, and hold the car with this
lowing operational conditions shall be checked [Item load. Freight elevators of class C-2 loading shall sustain
2.28.2(b)]: and level the elevator car.
(a) Type B safeties shall stop the car with the rated load
within the required range of stopping distances for which 8.11.2.3.5 Emergency and Standby Power Oper-
the governor is tripped [Item 2.29.2(e)]. ation. Operation of elevators equipped with emergency or
(b) For Type A safeties and Type A safety parts of Type standby power shall be inspected and tested for confor-
C safeties, there shall be sufficient travel of the safety mance with the applicable requirements (Item 1.17.2).
rollers or dogs remaining after the test to bring the car and Passenger elevators and freight elevators permitted to
its rated load to rest on safety application at governor trip- carry passengers (see 2.16.4) shall be tested with 125% of
ping speed. rated load [see 2.16.8(f)].

51
30
8.11.2.3.6 Emergency Terminal Stopping and
Speed Limiting Devices. Emergency terminal speed lim-
iting devices, where provided, shall be tested for confor-
mance with applicable requirements (2.25.4) [Item
5.3.2(b)].
For static control elevators, emergency terminal stop-
ping devices, when provided, shall be tested for confor-
mance with applicable requirements (2.25.4) [Item
2.26.2(b)].
8.11.2.3.7 Power Opening of Doors. Determine
that power opening of car and hoistway doors only occurs
when the car is at rest at the landing, or in the landing zone,
except, in the case of static control, check that power shall
not be applied until the car is within 300 mm (12 in.) of the
landing (Item 1.10.2).
8.11.2.3.8 Leveling Zone and Leveling Speed.
Check that the leveling zone does not exceed the maxi-
mum allowable distance. Check that the leveling speed
does not exceed 0.75 m/s (150 ft/min). For static control
elevators, the person or firm installing or maintaining the
equipment shall provide a written checkout procedure and
demonstrate that the leveling speed with the doors open is
limited to a maximum of 0.75 m/s (150 ft/min) and that
the speed limiting (or speed monitor) means is independ-
ent of the normal means of controlling this speed [Item
1.10.2(b)].
8.11.2.3.9 Inner Landing Zone. For static control
elevators, check that the zone in which the car can move
with the doors open is not more than 75 mm (3 in.) above
or below the landing [Item 1.10.2(c)].
8.11.2.3.10 Emergency Stopping Distance. Coun-
terweight traction elevators shall be tested for traction
drive limits to ensure that
(a) During an emergency stop initiated by any of the
electrical protective device(s) listed in 2.26.2 (except
2.26.2.13), (except buffer switches for oil buffers used
with Type C car safeties) at the rated speed in the down
direction, with passenger elevators and freight elevators
permitted to carry passengers carrying 125% of their rated
load, or with freight elevators carrying their rated load,
cars shall stop and safely hold the load; and
(b) if either the car or the counterweight bottoms on its
buffers or becomes otherwise immovable:
(1) the ropes shall slip in the drive sheave and not
allow the car or counterweight to be raised; or
(2) the driving system shall stall and not allow the
car or counterweight to be raised.

52
31
TABLE N1 RECOMMENDED INSPECTION AND TEST INTERVALS IN MONTHS
Periodic Tests

Reference Periodic Inspections Category One Category Three Category Five


Section Equipment Type Requirement Interval Requirement Interval Requirement Interval Requirement Interval

8.11.2 Electric elevators 8.11.2.1 6 8.11.2.2 12 N/A N/A 8.11.2.3 60


8.11.3 Hydraulic elevators 8.11.3.1 6 8.11.3.2 12 8.11.3.3 36 8.11.3.4 60
8.11.4 Escalators and moving walks 8.11.4.1 6 8.11.4.2 12 N/A N/A N/A N/A
8.11.5.1 Sidewalk elevators 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.2 Private residence elevators 8.11.2.1, 12 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.3 Hand elevators 8.11.2.1 6 8.11.2.2 12 N/A N/A 8.11.2.3, 60
8.11.3.4
8.11.5.4 Dumbwaiters 8.11.2.1, 12 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.5 Material lifts and dumbwaiters 8.11.2.1, 12 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60

32
with automatic transfer devices 8.11.3.1 8.11.3.2 8.11.3.4

53
8.11.5.6 Special purpose personnel 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
elevators 8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.7 Inclined elevators 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.8 Shipboard elevators 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.9 Screw-column elevators 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.10 Rooftop elevators 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.12 Limited-use/limited-application 8.11.2.1, 6 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
elevators 8.11.3.1 8.11.3.2 8.11.3.4
8.11.5.13 Elevators used for construction 8.11.2.1, 3 8.11.2.2, 12 8.11.3.3 36 8.11.2.3, 60
8.11.3.1 8.11.3.2 8.11.3.4

GENERAL NOTE: The intervals specified in this Table are recommended for periodic tests and inspections. Factors such as the environment, frequency and type of
usage, quality of maintenance, etc., related to the equipment should be taken into account by the authority having jurisdiction prior to establishing the inspection
and test intervals.

ASME A17.1 APPENDIX N


Table N1 Recommended Inspection and Test Intervals in Months
APPENDIX B speed should not exceed 125% of the rated speed or the
governor tripping speed.
ASME A17.2 CODE
1.17.2.2 Hydraulic Elevators
The following material is reprinted with permission from the American
Society of Mechanical Engineers.
(a) Yearly Test (for A17.1d2000 and Earlier Editions);
Category 1 Test (for A17.12000 and Later Editions).
Have the elevator(s) taken out of normal service and
ITEM 1.17 placed at the floor where the standby power switch is
STANDBY POWER OPERATION located. Have the system transferred to standby power and
1.17.2 Periodic Test operate the elevator(s) with no load in the car. Check the
switch that overrides automatic sequence operation, if pro-
1.17.2.1 Electric Elevators vided. Make several trips and stops checking for proper
(a) Yearly Test (for A17.1d2000 and Earlier Editions); operation. If more than one elevator is operated simulta-
Category 1 Test (for A17.12000 and Later Editions). neously from the same power supply, test the simultane-
Have the elevator(s) taken out of normal service and ous operation.
placed at the floor where the standby power switch is (b) 5-Year Test, Only One Elevator on Standby Power
located. Have the system transferred to standby power and Supply (for A17.1d2000 and Earlier Editions); Category
operate the elevator(s) with no load in the car. Check the 5 Test, Only One Elevator on Standby Power Supply (for
switch that overrides automatic sequence operation, if pro- A17.12000 and Later Editions). Have the elevator placed
vided. Make several trips and stops checking for proper on standby power as outlined in Item 1.17.2(a). Place the
operation. From the machine room use a tachometer to rated load on the elevator and operate the elevator observ-
verify that the elevator is running at normal speed espe- ing for safe operation.
cially in the up direction (speed must not exceed 125% of (c) 5-Year Test, More Than One Elevator Operating
rated speed). If a separate power absorption means such as Simultaneously on Standby Power Supply (for
a resistor bank is used to absorb regenerative power, it A17.1d2000 and Earlier Editions); Category 5 Test,
must be connected on the load side of the elevator discon- More Than One Elevator Operating Simultaneously on
nect switch. If more than one elevator is operated from the Standby Power Supply (for A17.12000 and Later Edi-
same power source simultaneously, test the simultaneous tions). Have the elevators placed on standby power sup-
operation. ply operation and loaded with the rated load and operate
(b) 5-Year Test, Only One Elevator on Standby Power all of the elevators simultaneously observing that they
Supply (for A17.1d2000 and Earlier Editions); Category operate normally.
5 Test, Only One Elevator on Standby Power Supply (for
A17.12000 and Later Editions). Have the elevator placed
on standby power as outlined in Item 1.17.2(a). Place the
rated load on the elevator (125% rated load for passenger
elevators and freight elevators that are permitted to carry
passengers) and operate the elevator observing for safe
operation. Use a tachometer in the machine room to ver-
ify that the overhauling load does not cause a speed
increase in excess of 125% of rated speed or the gover-
nor tripping speed.
(c) 5-Year Test, More Than One Elevator Operating
Simultaneously on Standby Power Supply (for
A17.1d2000 and Earlier Editions); Category 5 Test,
More Than One Elevator Operating Simultaneously on
Standby Power Supply (for A17.12000 and Later Edi-
tions). Have the elevators placed on standby power sup-
ply operation and loaded with the rated load (125% rated
load for passenger elevators and freight elevators that are
permitted to carry passengers) and operate all of the ele-
vators simultaneously observing that they operate nor-
mally and will safely lower, stop, and hold. Use a
tachometer to check the speed of each elevator when oper-
ating simultaneously in the down direction. Verify that
each elevator stops at or near the terminal landing and
before the final terminal stopping device is operated. The

54
33
TABLE 2.29.2(b) MINIMUM AND MAXIMUM TABLE 2.29.2(c) GRADUAL WEDGE CLAMP
STOPPING DISTANCES FOR TYPE B CAR SAFETY
SAFETIES WITH RATED LOAD, AND TYPE B Maximum
COUNTERWEIGHT SAFETIES WITH NO LOAD Stopping
IN THE CAR Distance Minimum Stopping Distance

Stopping Distances Governor Car + Rated Car + Rated


Tripping Load or for Load or for
Rated Speed, Minimum, Maximum, Speed, Counterweight, Car + 150 lb, Counterweight,
ft/min ft-in. ft-in. ft/min ft-in. ft-in. ft-in.
0 to 125 0-1 1-0 175 6-2 1-5 1-11
150 0-1 1-1 200 6-3 1-5 2-0
175 0-2 1-3 300 6-11 1-6 2-4
200 0-2 1-4 400 7-10 1-8 2-7
225 0-3 1-6 500 8-10 1-11 2-11
250 0-3 1-7 600 9-11 2-1 3-4
300 0-5 1-11 700 11-1 2-4 3-10
350 0-7 2-4 800 12-4 2-7 4-6
400 0-9 2-10 900 13-6 3-0 5-4
450 0-11 3-4 1,000 14-8 3-6 6-1
500 1-1 3-11 1,100 16-0 4-0 7-0
600 1-7 5-3 1,200 17-4 4-7 8-0
700 2-2 6-10 1,300 18-6 5-1 9-0
800 2-9 8-9 1,400 19-8 5-8 10-1
900 3-6 10-10 1,500 21-1 6-2 11-1
1,000 4-4 13-2
1,100 5-2 15-9 GENERAL NOTES:
1,200 6-2 18-7 (a) For elevators installed prior to A17.11955.
1,300 7-3 21-8 (b) 1 ft /min = 5.08 E 03 m/s
1,400 8-5 25-0 (c) 1 in. = 25.4 mm
1,500 9-8 28-7
1,600 11-0 32-5
1,700 12-5 36-5
1,800 13-11 40-9

GENERAL NOTES:
(a) This table is for rated load, rated speed test only. Use Table 2.17.3
in the Code for rated load, overspeed test only.
(b) Use Table 2.17.3 of the A17.1 Code when performing acceptance
tests.
(c) 1 ft /min = 5.08 E m/s
(d) 1 in. = 25.4 mm

55
34
APPENDIX C
NEC
Reprinted with permission from NFPA 70-1999, The National Electrical
Code , Copyright 1998, National Fire Protection Association, Quincy,
MA 02269. This reprinted material is not the complete and official posi-
tion of the National Fire Protection Association, on the referenced sub-
ject which is represented only by the standard in its entirety.

ARTICLE 620
ELEVATORS, DUMBWAITERS,
ESCALATORS, MOVING WALKS,
WHEELCHAIR LIFTS, AND
STAIRWAY CHAIR LIFTS
E. Traveling Cables
620-41. Suspension of Traveling Cables. Traveling
cables shall be suspended at the car and hoistways ends,
or counterweight end where applicable, so as to reduce the
strain on the individual copper conductors to a minimum.
Traveling cables shall be supported by one of the fol-
lowing means:
(1) By its steel supporting member(s)
(2) By looping the cables around supports for unsup-
ported lengths less than 100 ft (30.5 m)
(3) By suspending from the supports by a means that auto-
matically tightens around the cable when tension is
increased for unsupported lengths up to 200 ft (61 m)
FPN: Unsupported length for the hoistway suspension means is
that length of cable as measured from the point of suspension in
the hoistway to the bottom of the loop, with the elevator car
located at the bottom landing. Unsupported length for the car sus-
pension means is that length of cable as measured from the point
of suspension on the car to the bottom of the loop, with the ele-
vator car located at the top landing.

620-43. Location of and Protection for Cables. Travel-


ing cable supports shall be located so as to reduce to a
minimum the possibility of damage due to the cables com-
ing in contact with the hoistway construction or equip-
ment in the hoistway. Where necessary, suitable guards
shall be provided to protect the cables against damage.

J. Grounding
620-85. Ground-Fault Circuit-Interrupter Protection
for Personnel. Each 125-volt, single-phase, 15- and 20-
ampere receptacle installed in pits, on elevator car tops,
and in escalator and moving walk wellways shall be of the
ground-fault circuit-interrupter type.
All 125-volt, single phase, 15- and 20-ampere recepta-
cles installed in machine rooms and machinery spaces
shall have ground-fault circuit-interrupter protection for
personnel.
A single receptacle supplying a permanently installed
sump pump shall not require ground-fault circuit-inter-
rupter protection.

56
35

Você também pode gostar