NESTE OIL - SINGAPORE HVAC TECHNICAL DATA

Pr.071973C - ENOC - Jebel Ali Refinery expansion Project - Dubai (UAE)

HVAC SYSTEMS : Technical data rev. 31.05.17

BUILDINGS LIST:
SUBSTATION AND RACK ROOM 42-R-101
SUBSTATION AND RACK ROOM 44-R-101
SATELLITE OPERATOR BUILDING 44-R-105

REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)


Offer XXXXX dated XXXXXXXX

as per 071973C-G00-JSD-3400.01 (hereafter


1. General Design Criteria
referred to as "JSD") NOTED

as per 071973C-G00-JSS-3480.01 (hereafter


2. Minimum Requirements for Fabrication
referred to as "JSS") NOTED

3. EQUIPMENT

3.1. General requirements


Applicable Stds. as per JSD, sect.2. and JSS, sect.2. NOTED
Electric data 380 VAC / 3ph./ 50 Hz NOTED

3.2. Protection against harsh environment


as per JSS, sect. 3.1., EDS-B-3 "GENERAL
SPECIFICATION FOR COATING AND
General PAINTING" and 071973C-G00-JSD-2300-01
"JOB DESIGN SPECIFICATION FOR
PAINTING" NOTED
tin coated copper piping with copper fins shall be
Air cooled condensers and AHUs cooling in general selected, or other well-proven
coils (if not protected by a chemical filtration equivalent coating provisions (world-main
system) Brands patented/guaranteed) such as Heresite,
High silver coating, or others NOTED

3.3. Air cooled water chillers

3.3.1. Common features


Brand name & model carrier &30XA aquaforce
Construction features as per JSS sect. 3.2.2.
Compressors type scroll or semi-hermetic type NOTED
R134a or other ozone friendly type, complying
Refrigerant with the local phase-out policy NOTED
Minimum performance as per JSS sect. 3.2.1. NOTED
Notes

3.3.2. Service SUBSTATION AND RACK ROOM 42-R-101


Acronym ACWC-ES-42-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Cooling capacity (each unit) 398 kW 402 KW
Electrical power input (each unit) 200 kW 172 KW

10/09/2017 - page 1 of 6 file name:368203201.xls


NESTE OIL - SINGAPORE HVAC TECHNICAL DATA

REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)


Offer XXXXX dated XXXXXXXX
Working unit weight 6300 kg 4313 KG
Overall dimensions (lxwxh) 5 x 2,5 x 2,5 m 4798x2253x2295 mm

3.3.3. Service SUBSTATION AND RACK ROOM 44-R-101


Acronym ACWC-ES-44-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Cooling capacity (each unit) 618 kW 702 kw
Electrical power input (each unit) 310 kW 278 kw
Working unit weight 7600 kg 6640 kg
Overall dimensions (lxwxh) 6 x 2,5 x 2,5 m 7186x2253x2297mm

3.4. Chemical filtration units

3.4.1. Common features


Brand name & model
Construction features as per JSS sect. 3.2.5.
level G1 according to ISA S71.04 (outdoor: H2S
Values of pollutants at outlet of filter
levels 5 ppm - level GX )
Fans no. 2 (1 duty, 1 stand-by)
Notes fans motors provided with VFD

3.4.2. Service SUBSTATION 42-R-101 WE WILL PROVIDE LATER


Acronym PFU-ES-42-01
Quantity no.1
Fresh air flow rate 1950 l/s
Full load input power 3 kW
Working unit weight
Overall dimensions (lxwxh) 3,0 x 2,0 x 2,0 m

3.4.3. Service RACK ROOM 42-R-101


Acronym PFU-RR-42-01
Quantity no.1
Fresh air flow rate 524 l/s
WE WILL PROVIDE LATER
Full load input power 1,5 kW
Working unit weight
Overall dimensions (lxwxh) 2,5 x 1,0 x 1,2 m

3.4.4. Service SUBSTATION 44-R-101


Acronym PFU-ES-44-01
Quantity no.1
Fresh air flow rate 2961 l/s
WE WILL PROVIDE LATER
Full load input power 4 kW
Working unit weight
Overall dimensions (lxwxh) 4,0 x 2,5 x 2,0 m

3.4.5. Service RACK ROOM 44-R-101


Acronym PFU-RR-44-01
Quantity no.1
Fresh air flow rate 784 l/s
WE WILL PROVIDE LATER
Full load input power 1,5 kW
Working unit weight
Overall dimensions (lxwxh) 3,0 x 1,5 x 1,5 m

10/09/2017 - page 2 of 6 file name:368203201.xls


NESTE OIL - SINGAPORE HVAC TECHNICAL DATA

REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)


Offer XXXXX dated XXXXXXXX

3.4.6. Service SATELLITE OPERATOR BUILDING 44-R-105


Acronym PFU-SOB-01
Quantity no.1
Fresh air flow rate 136 l/s
WE WILL PROVIDE LATER
Full load input power 0,75 kW
Working unit weight
Overall dimensions (lxwxh) 2,5 x 0,6 x 1,2 m
Notes chemical filter section to be included

3.5. Air handling units

3.5.1. Common features


Brand name & model carrier &39 HQM SERIES-KSA
Construction features as per JSS sect. 3.2.4. and 3.2.8.

3.5.2. Service SUBSTATION 42-R-101


Acronym AHU-ES-42-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Supply air flow rate (each unit) 11027 l/s 11470 L/S
Fresh air flow rate (each unit) 1950 l/s WE WILL PROVIDE LATER
Cooling coil capacity (each unit) 324 kW WE WILL PROVIDE LATER
Full load input power (each unit) 22 kW WE WILL PROVIDE LATER
Working unit weight
Overall dimensions (lxwxh) 5,0 x 2,4 x 2,2 m WE WILL PROVIDE LATER

3.5.3. Service RACK ROOM 42-R-101


Acronym AHU-RR-42-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Supply air flow rate (each unit) 2664 l/s 2800 L/S
Fresh air flow rate (each unit) 524 l/s WE WILL PROVIDE LATER
Cooling coil capacity (each unit) 74 kW WE WILL PROVIDE LATER
Full load input power (each unit) 7,5 kW WE WILL PROVIDE LATER
Working unit weight
Overall dimensions (lxwxh) 3,5 x 1,2 x 1,2 m WE WILL PROVIDE LATER
n.1 self-contained steam humidifier to be
Notes
provided NOTED

3.5.4. Service SUBSTATION 44-R-101


Acronym AHU-ES-44-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Supply air flow rate (each unit) 17432 l/s 17118 L/S
Fresh air flow rate (each unit) 2961 l/s WE WILL PROVIDE LATER
Cooling coil capacity (each unit) 506 kW WE WILL PROVIDE LATER
Full load input power (each unit) 35 kW WE WILL PROVIDE LATER
Working unit weight
Overall dimensions (lxwxh) 7,0 x 3,0 x 3,0 m WE WILL PROVIDE LATER

3.5.5. Service RACK ROOM 44-R-101


Acronym AHU-RR-44-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Supply air flow rate (each unit) 4096 l/s 3798 L/S

10/09/2017 - page 3 of 6 file name:368203201.xls


NESTE OIL - SINGAPORE HVAC TECHNICAL DATA

REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)


Offer XXXXX dated XXXXXXXX
Fresh air flow rate (each unit) 784 l/s WE WILL PROVIDE LATER
Cooling coil capacity (each unit) 112 kW WE WILL PROVIDE LATER
Full load input power (each unit) 11 kW WE WILL PROVIDE LATER
Working unit weight
Overall dimensions (lxwxh) 4,0 x 1,5 x 1,5 m WE WILL PROVIDE LATER
n.1 self-contained steam humidifier to be
Notes
provided NOTED

3.6. Electric driven water pumps

3.6.1. Common features


Brand name & model
Construction features as per JSS sect. 3.2.10. NOTED

Chilled water distribution - SUBSTATION AND


3.6.2. Service
RACK ROOM 42-R-101
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Water flow rate (each unit)
Full load input power (each unit)
Notes included in the hydronic module of chillers NOTED

Chilled water distribution - SUBSTATION AND


3.6.3. Service
RACK ROOM 44-R-101
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Water flow rate (each unit)
Full load input power (each unit)
Notes included in the hydronic module of chillers NOTED

3.7. Exhaust air fans

3.7.1. Common features


Brand name & model
Construction features as per JSS sect. 3.2.9. NOTED

3.7.2. Service All Bldgs NOTED


Quantity
Air flow rate (each unit)
Full load input power (each unit)
fans for battery rooms shall be suitable for
Notes
local hazardous area characteristics NOTED

3.8. Electrical type duct heaters

3.8.1. Common features


Brand name & model
Construction features as per JSS sect. 3.2.7. NOTED

3.8.2. Service All Bldgs NOTED


Quantity
Heating capacity

10/09/2017 - page 4 of 6 file name:368203201.xls


NESTE OIL - SINGAPORE HVAC TECHNICAL DATA

REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)


Offer XXXXX dated XXXXXXXX
Reversible heat pump split-system air
3.9.
conditioners

3.9.1 Common features


Brand name & model
Construction features as per JSS sect. 3.2.6. and 3.2.8. NOTED
Minimum performance as per JSS sect. 3.2.1. NOTED
n.1 self-contained steam humidifier to be
Notes
provided NOTED

SATELLITE OPERATOR BUILDING 44-R-105 -


3.9.2. Service
Operator room
Acronym SSAC-SOB-01 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Overall cooling capacity (each unit) 11 kW NOTED
Electrical power input (each unit) 5 kW NOTED
Working unit weight
External unit: overall dimensions (lxwxh) 1,0 x 0,4 x 1,5 m WE WILL PROVIDE LATER
N.2 indoor units: overall dimensions -each
1,2 x 0,3 x 0,4 m
(lxwxh) WE WILL PROVIDE LATER
Notes dual split-type: n.2 indoor units NOTED

SATELLITE OPERATOR BUILDING 44-R-105 -


3.9.3. Service
Dining room
Acronym SSAC-SOB-02 A/B
Quantity no. 2 (1 duty, 1 stand-by) NOTED
Cooling capacity (each unit) 4 kW NOTED
Electrical power input (each unit) 2 kW NOTED
Working unit weight
External unit: overall dimensions (lxwxh) 1,0 x 0,4 x 1,0 m WE WILL PROVIDE LATER
Indoor unit: overall dimensions (lxwxh) 1,2 x 0,3 x 0,4 m WE WILL PROVIDE LATER

4. Electric power & control panels

4.1. Common features


Brand name & model as per Project Vendor List NOTED
Construction features as per JSS sect. 3.5.2. NOTED

4.2. Service All Bldgs NOTED


Quantity n.3 NOTED
Overall dimensions (lxwxh)

5. Electric power & control cables and cable trays/conduits

5.1. Common features


Brand name & model as per Project Vendor List NOTED
Construction features as per JSS sect. 3.5.1. NOTED

5.2. Service All Bldgs NOTED


Quantity
Notes

10/09/2017 - page 5 of 6 file name:368203201.xls


NESTE OIL - SINGAPORE HVAC TECHNICAL DATA

REQUIREMENTS PROPOSAL (DATA BY SUPPLIER)


Offer XXXXX dated XXXXXXXX
6. Ductwork and insulation
Quantity
Construction features as per JSS sect. 3.4. NOTED
Notes

7. Diffusers, dampers, grilles, louvers, fire dampers, blast valves


Brand name
Construction features as per JSS sect. 3.4. NOTED
Notes

8. Piping, insulation, valves, pressurized tanks, water treatment systems


Brand name
Construction features as per JSS sect. 3.2., 3.3. and 3.6. NOTED
Notes

9. Regulation & control systems


Brand name
Construction features as per JSS sect. 3.7. NOTED
Notes

10. Services