Você está na página 1de 5

Danger

High voltage

DISCLAIMER

THE END USER IS RESPONSIBLE FOR


ENSURING THAT AN EARTHING
ARRANGEMENT THAT IS COMPLIANT
WITH LOCAL CONDITIONS IS
ESTABLISHED AND TESTED BEFORE
THE EQUIPMENT IS USED.

TRANSPORTATION - WARNING
THE GENERATOR SET DOOR(S) MUST BE LOCKED
BEFORE TRANSPORTATION, AND MUST REMAIN LOCKED
DURING TRANSPORTATION AND SITING.
BEFORE ANY TRANSPORTATION,
THE FLUID CONTAINMENT AREA MUST BE INSPECTED
AND EMPTIED OF ANY SPILLAGE OR ENGINE WASTE.

For Additional Assistance: Decal for Rental Sets


Tel: E-mail:
A041F701 Issue 01 12-2011
Sheet 1 of 5
Fax: Web Site: English - Original Instructions
C1250 D2R Gensets with PowerCommand 3.3

Start-up and General Information Ear


Danger Protection
High voltage
for Rental Sets MUST be used

This machine MUST be installed and connected by a competent person


! according to local codes and regulations. !
Initial Start-up:
! Set-up, calibration, and adjustment must be performed by technically qualified personnel only.
Improper Set-up, calibration, or adjustments can cause equipment malfunction or damage.
!
! WARNING: All checks must only be carried out on a switched off, isolated, and cold generator set!
! Personnel working on generator plant must be familiar with normal operating procedures and hazards!
! Failure to observe safety precautions may result in severe personal injury or death!
! Ear protection must be used at all times!
! The generator set door(s) MUST be locked before transportation, and MUST remain locked during siting.

Manual Start-up 10 seconds


maximum

Performance?

Sound?

Breaker Open

DD
Engine
Appearance? Close
Breaker

Manual Stop

Breaker Open

Auto Start-up
L

D
WARNING: Set may start automatically as soon as Auto Mode is selected.
! In Auto Mode, the set is started or stopped with a Remote Signal.

Genset Engine Model Oil (Premium Blue) Coolant Air Filter Fuel Filter
Qty Filter Qty Part No.
Litres Imp. Gall Part No. Litres Imp. Gall Primary Secondary Part No.
C1250 D2R KTA50G3 203 53.6 LF777/LF3325 555 146.6 AF25544 AF25545 FS19870

For Additional Assistance: Decal for Rental Sets


Tel: E-mail: A041F701 Issue 01 12-2011
Sheet 2 of 5
Fax: Web Site: English - Original Instructions
C1250 D2R Gensets with PowerCommand 3.3

Generator Control Panel Layout Ear


Danger Protection
High voltage
for Rental Sets MUST be used

! Personnel working on generator plant must be familiar with normal operating procedures and hazards!
! Failure to observe safety precautions may result in severe personal injury or death!
! Ear protection must be used at all times!

Control Panel
EMERGENCY STOP
Push to
Display Module -
Front Panel ! STOP THE GENERATOR SET
IMMEDIATELY !
To Reset:
Investigate and correct the fault.
Pull the activated Emergency Stop Switch
to unlatch it.
Press the Off Mode button.
Press the Manual Run or Auto Mode
button as required.
WARNING
DO NOT
use the Emergency Stop b u t t o n
for a Normal generator set shutdown.

Display Module Genset Running - LED


Remote Start - LED

MANUAL RUN: Not In Auto - LED


Provides power to the unit, and Shutdown - LED
will start the generator set if the Graphic Display
Start button is pressed within ten Warning - LED
seconds.
Selection Buttons
Four
START: Lamp Test Button
Must be pressed with ten seconds
of the Manual button to start the Home Button Reset Button
generator set.

AUTO:
Generator set is started Stop Button
automatically Four Change Auto Button
via a remote start signal. Selection Buttons
Start Button
Circuit Breaker Closed Button
OFF: Item Select Button
Circuit Breaker Open Button
Initiates the shutdown of the
generator set. Manual Run Button
Previous Screen Button

For Additional Assistance: Decal for Rental Sets


Tel: E-mail: A041F701 Issue 01 12-2011
Sheet 3 of 5
Fax: Web Site: English - Original Instructions
C1250 D2R Gensets with PowerCommand 3.3
Ear
Danger General Safety for Rental Sets Protection
High voltage
MUST be used

! WARNING: All checks must only be carried out on a switched off, isolated and cold generator set!
! Personnel working on generator plant must be familiar with normal operating procedures and hazards!
! Failure to observe safety precautions may result in severe personal injury or death!
! Ear protection must be used at all times!

OK
Com Gas
bus
tible

DAILY MAINTENANCE

TO IMMOBILISE THE SET FOR SAFE WORKING


Press the STOP button.
Stop Engage the Emergency Stop button and hold for 30 seconds, before
disconnecting the starter and control system batteries.

Check for Loose or Damaged Electrical and Mechanical Parts. If in doubt, contact your Rental Company.

Electrical Connections

Visual System Check (with system running)

For Additional Assistance: Decal for Rental Sets


Tel: E-mail: A041F701 Issue 01 12-2011
Sheet 4 of 5
Fax: Web Site: English - Original Instructions
C1250 D2R Gensets with PowerCommand 3.3

Routine Daily Maintenance Checks Ear


Danger Protection
High voltage
for Rental Sets MUST be used

! WARNING: All checks must only be carried out on a switched off, isolated, and cold generator set!
! Personnel working on generator plant must be familiar with normal operating procedures and hazards!
! Failure to observe safety precautions may result in severe personal injury or death!
! Ear protection must be used at all times!

Note: The Hirer is responsible for the Daily checks of the system.
Further, more extensive, monthly and yearly checks must be carried out by the Rental Company.

TO IMMOBILISE THE SET FOR SAFE WORKING


Press the STOP button.
Stop Engage the Emergency Stop button and hold for 30 seconds, before
disconnecting the starter and control system batteries.

1. Check Hoses, Fuel Lines, and 2. Check Oil Level: Use Premium Blue or Equivalent
Exhaust System for Leaks

3. Check Coolant Level: 4. Check Fluid


Use Fleetguard E.S.Compleat or Equivalent Containment Area

Drain any liquid and dispose


Maintain Coolant Concentration Level - 25% or 50% of according to local health
(Refer to your Distributor if in Doubt) and safety regulations

5. Check Fuel Level 6. Check Fuel-Water Separator 7. Check Air Inlet/Outlet 8. Check
Air Restriction Indicator

! !
WARNING
Do NOT refill fuel tank
if the set is running

CAUTION: The set must not be run off-load for more than fifteen minutes.
For Additional Assistance: Decal for Rental Sets
Tel: E-mail: A041F701 Issue 01 12-2011
Sheet 5 of 5
Fax: Web Site: English - Original Instructions