Você está na página 1de 18

HVAC Clinic

Duct Design
Table Of Contents

Introduction ............................................................................................................................................ 3
Fundamentals Of Duct Design .............................................................................................................. 3
Pressure Changes In A System ............................................................................................................ 8
Example 1 ............................................................................................................................................. 13
Duct Design Methods .......................................................................................................................... 15
Example 2 ............................................................................................................................................. 15
HVAC Clinics Draft - Not For Distribution
Introduction

The purpose of air conditioning ductwork is to deliver air from the fan to the diffusers which distribute air to the room.
This air that is distributed is ultimately delivered in response to a pressure difference created by one or several fans.
The required pressure differential required by the fan(s) is a function of duct design. The objective of duct design is to
size the duct such that:

Minimize pressure drop


Minimize noise
Minimized cost
Simplify Balancing

Proper duct design required a knowledge of the factors that affect pressure drop and velocity in the duct.

Fundamentals Of Duct Design


Pressure is the force per unit area applied in a direction perpendicular to the surface of an object. Pressure in a duct
system is the sum of two components, static pressure and velocity pressure. Static Pressure is equal in all directions.
Static pressure is a perpendicular outward component and is analogous to the pressure which pushes against the walls
of a balloon (figure 1).

Figure 1. Static Pressure

Velocity pressure is due to the momentum of the air. Velocity pressure is directional. Imagine a ribbon tied to the outlet
of a common prop fan. When the fan is off, the ribbon remains slack, even though subjected to an atmospheric static
pressure of 14.7 lb/sq-in. As the fan starts and begins producing airflow, the ribbon begins to deflect in the direction of
airflow. As the airflow increases, the ribbon becomes more taught in the direction of airflow (figure 2).

Figure 2. Velocity Pressure


WN Mechanical Systems Duct Design Page 3 of 18
HVAC Clinics Draft - Not For Distribution
Velocity pressure plus static pressure is equal to total pressure. In a duct system, velocity pressure and static pressure
can be demonstrated using a flat plate suspended from a hinge. The plate and hinge are located downstream of a fan
connected to a duct system. Directly downstream of the hinged plate, the duct system is fitted with discharge dampers.
When the fan is off and the dampers are open, the plate does not deflect (figure 3). The fan is not producing any static
or velocity pressure.

Figure 3. Duct Pressure Measurement System

With the fan turned on and the discharge dampers closed, pressure is produced in the duct system. All of pressure
produced is static pressure (otherwise known as block tight static pressure). Static pressure is equal in all directions.
Thus, the hinged plated does not deflect (figure 4). Total pressure is equal to static pressure.

Figure 4. Dampers Closed

With the fan turned on and the discharge dampers partially opened, the duct system experiences a combination of both
static and velocity pressure. The velocity pressure component is directional in the direction of the airflow. This
pressure impedes on the plate causing it to deflect (figure 5). The magnitude of the deflection is a function of the
magnitude of the velocity pressure. Total pressure is equal to the velocity pressure plus the static pressure.

Figure 5. Dampers Partially Open

Finally, with the fan on, the discharge dampers are fully opened. Assuming the length of the duct system is very short,
the static pressure in the duct system approaches zero. The majority of the pressure in the duct system is velocity
pressure. The hinged plate will deflect to its maximum position (figure 6).

WN Mechanical Systems Duct Design Page 4 of 18


HVAC Clinics Draft - Not For Distribution

Figure 6. Dampers Fully Ope

One method for measuring pressure in a duct system is a u-tube manometer. A u-tube manometer is a u shaped tube
filled with some water. When one end of a u-tube manometer is closed to a vacuum and the other is open to
atmosphere, the water will deflect. The magnitude of the deflection is equal to atmospheric pressure. Atmospheric
pressure at sea level will cause the water to deflect 407.1 or 33.97 ft (figure 7).

Figure 7. U-Tube Manometer

Pressures measured in duct system are ordinarily in the order of 0-5 in-wg. This makes the use u-tube manometers in
duct systems impractical. The variations in duct pressure are too small to make out accurately within the vertical tubes.
To solve this problem, a similar device called an inclined manometer is used. An inclined manometer is sloped at 1:10
ratio (horizontal to vertical axis respectively). Knowing this ratio, we can more accurately determine changes within a
duct system (figure 8).

Figure 8. Inclined Manometer


WN Mechanical Systems Duct Design Page 5 of 18
HVAC Clinics Draft - Not For Distribution

Before we can measure pressure in a duct system, we must first understand how pressure varies with cross section. A
fan creates kinetic energy by imparting velocity to air particles. At the discharge of a housed centrifugal fan, the velocity
is greatest at top of the duct and falls off sharply as we approach the bottom of the duct. Generally speaking, it takes
5-10 duct diameters before the pressure in a duct system becomes uniform (figure 9).

Figure 9. Velocity Profile in Ductwork

After 5-10 duct diameters, we have an even flow distribution profile with the velocity achieving its maximum magnitude
at the center of the duct. As we approach the walls of the duct, the air velocity approaches zero. When measuring
pressure in a duct, it is important that the readings are taken in a section of duct where the velocity profile is uniform.

Note from the cross sectional velocity profiles that the air velocity is zero at the edge of the duct. Thus, any pressure
measurement taken at the edge of the duct is going to be measuring static pressure only (figure 10).

Figure 10. Static Pressure

Recalling that static pressure plus velocity pressure is equal to total pressure, placing the positive port of the inclined
manometer at the center of the duct is going measure total pressure (figure 11).

WN Mechanical Systems Duct Design Page 6 of 18


HVAC Clinics Draft - Not For Distribution

Figure 11. Combination Velocity + Static Pressure

Finally, manipulating the equation for total pressure yields:

Velocity Pressure = Total Pressure Static Pressure

Taking into account the equation above, velocity pressure can be found by measuring total pressure with the positive
port and static pressure with the negative port of the inclined manometer. The total water displacement would then be
equal to velocity pressure (figure 12).

Figure 12. Measuring Velocity Pressure

Knowing the velocity pressure, the actual velocity in the duct can be determined.

WN Mechanical Systems Duct Design Page 7 of 18


HVAC Clinics Draft - Not For Distribution
Pressure Changes In A System
The first principle to understand when describing pressure changes in a duct system is the interaction between static
pressure and velocity pressure. Earlier, we found that:

If we have a frictionless system and velocity pressure increases, then static pressure must then decrease by the exact
same amount. Said another way, in a frictionless system, total pressure does not change. That being the case, if
velocity pressure is equal to

If we increase the velocity in a duct system, the corresponding velocity pressure will increase. Assuming a frictionless
system, this must come at the expense of static pressure. This can be demonstrated with an airplane wing. The Upper
surface of the wing has a greater area than the lower surface. Thus the velocity of the air particles flowing along the
upper surface will be greater than the velocity of the particles flowing along the lower surface. This velocity differential
causes a pressure differential, which in turn causes lift (figure 13).

Figure 13. Airplane Wing Analogy

To begin our analysis of pressure changes in a duct system, we will assume a frictionless duct transition. Recall that :

If the outlet area is larger than the inlet area, the velocity pressure at the outlet must decrease. With a frictionless
system where total pressure remains constant (Pt), static pressure (Ps) must increase at the same rate that velocity
pressure (Pv) decreases. This phenomenon is known as static regain (figure 14).

WN Mechanical Systems Duct Design Page 8 of 18


HVAC Clinics Draft - Not For Distribution

Figure 14. Static Regain in Lossless Duct System

However, both ductwork and fittings introduce friction. In straight duct, friction losses are due to fluid viscosity and are
the result of momentum exchange between molecules in laminar flow. In fittings, friction losses are caused by the
individual particles of adjacent fluid layers moving at differing velocities in turbulent flow. Friction losses are irreversible
and are the conversion of mechanical energy into heat.

Generally speaking, friction losses per unit length of straight duct are less severe than friction losses in fittings.
Frictional losses occur at the expense of static pressure. Frictional losses do not impact velocity pressure.

Examining the same duct system with two lengths of straight duct connected by a transition, but accounting for friction
losses, results in pressure profile similar to that of figure 15. Note that that the magnitude of the velocity pressure at any
point of the duct system does not change. However, as the air travels down the first section of straight duct, the static
pressure drops at a consistent rate to due frictional losses in the duct. As the airflow travels through the transition, it
experiences frictional losses due to turbulence which increases the rate of static pressure loss. Finally, as the airflow
travels down the last section of straight duct, the static pressure loss again experiences at constant rate of change per
unit length due to frictional losses. The sum of the static pressure plus velocity pressure at any point equals the total
pressure in the duct system. The loss in total pressure is a direct result of the loss in static pressure due to frictional and
turbulence losses.

WN Mechanical Systems Duct Design Page 9 of 18


HVAC Clinics Draft - Not For Distribution

Figure 15. Friction Losses in

As mentioned previously, frictional losses in a section of straight duct are due to momentum exchange between the air
particles (for laminar flow) and duct particles, which in turn produce heat. Those variables would include the velocity in
the section of duct, air density and the type of material used for the duct. ASHRAE has plotted the relationship between
those variable and created graphical chart for various roughness of duct (figure 16).

Note that figure 16 is applicable only at sea level (.075 lb/ft3 air density). Figure 16 should be corrected for altitudes
other than sea level.

WN Mechanical Systems Duct Design Page 10 of 18


HVAC Clinics Draft - Not For Distribution

Figure 16. Friction Chart For Round Duct (density = .075 lb/ft3 and =.0003 ft)

WN Mechanical Systems Duct Design Page 11 of 18


HVAC Clinics Draft - Not For Distribution
Using this chart, we can find the frictional loss per 100 feet of duct. Another method which simplifies the use of the
ASHRAE chart is a ductilator. Either method provides an accurate representation of duct losses due to friction. The
output is generally given as in-wg pressure drop per 100 feet of duct.

The second type of duct loss is referred to as dynamic losses. Dynamic losses result from flow disturbances caused by
duct mounted equipment or fittings that change the airflow path direction or area. The local loss coefficient C is a
measure of the fittings efficiency. The loss coefficient is the ratio of total pressure loss to velocity pressure at the
referenced cross section. The pressure drop through a fitting is calculated as:

Recalling that velocity pressure is

Substituting the equation for velocity pressure, the pressure drop through a fitting becomes

ASHRAE gives the local loss coefficient for various types and sizes of duct fittings. For example, a common duct fitting
is the 45 degree branch. ASHRAE table SR5-13 (figure x) gives the loss coefficients for a 45 degree entry branch
diverging tee. Note that two loss coefficients are given; Cb and Cs. ASHRAE defines the subscripts:

c = Common
b = Branch
s = Straight

Figure 17. ASHRAE Fitting Table

WN Mechanical Systems Duct Design Page 12 of 18


HVAC Clinics Draft - Not For Distribution

Example 1
Determine the straight and branch pressure drops through a tee.

Example one assumes a 45 degree branch diverging tee with 2000 CFM entering the common duct and 1000 CFM
leaving both the straight and branch legs of the tee. The upstream connection is 20 wide x 10 high and the straight and
branch outlets are both 10 wide x 10 high. Find the straight and branch pressure drop (figure 17).

Figure 18. Example One

Solution:

First we must find the areas of the common inlet, and straight and branch outlet. The area of the common inlet, straight
outlet and branch outlet respectively are:

Next, we find the area ratio of the straight outlet to common inlet and the branch outlet to common inlet.

WN Mechanical Systems Duct Design Page 13 of 18


HVAC Clinics Draft - Not For Distribution

Finally, we find the ratio of airflow of the straight outlet to common inlet and the branch outlet to common inlet.

Given these values, we enter ASHRAE table SR5-13 and find that Cb = .73 and Cs = .04. The velocity at both the branch
and straight outlets is

Finally, the pressure drop through the straight common leg is:

And the pressure drop through the branch common leg is:

WN Mechanical Systems Duct Design Page 14 of 18


HVAC Clinics Draft - Not For Distribution

Duct Design Methods

Three common methods of duct design are the velocity method, equal friction method and static regain method.

The velocity method assumes a constant duct velocity for main ducts and branch ducts. Typical duct velocities for low
pressure duct design are:

Rectangular Duct Recommended Velocities (fpm):

Duct Type Residence Theaters, Libraries Office Buildings Industrial Buildings


Main 700 1000 2200 3000
Branch 500 500 1600 2500

Round Duct Recommended Velocities (fpm):

Duct Type Residence Theaters, Libraries Office Buildings Industrial Buildings


Main 900 1200 2400 4000
Branch 600 600 2000 3000

The procedure for the velocity method is to pick a constant velocity for the main trunk and branch ducts. At the selected
velocity enter the ASHRAE charts or use a common ductilator to find the nearest size common duct. Having found the
duct size, the friction loss per 100 feet can be determined from the chart/ductilator. Multiply the friction loss per 100 feet
times the actual duct length to find the pressure drop through all the sections of main trunk duct and branch duct. Add
the pressure drops through each path. The total static pressure drop through the duct system is the sum of the worst
case path. The fan external static pressure is the sum of the worst case path.

The procedure for the equal friction method is very similar to the velocity method. With the equal friction method, we
select a constant friction loss per 100 feet for all main trunk ducts and branch ducts. Then using a common ductilator or
the ASHRAE charts, find the nearest practical duct size. Based on the actual duct size, determine the actual friction loss
per 100 feet. Add the pressure drops through each path and sum the worst case path. The sum of the worst case path
is equal to the fan external static pressure.

Example 2.
Determine round duct size and fan external static pressure of system shown in figure 18. Assume a design friction loss
of 0.1/100 and all fittings will have a pressure drop of 0.1 w.g. (figure 18).

Figure 19. Example Two

WN Mechanical Systems Duct Design Page 15 of 18


HVAC Clinics Draft - Not For Distribution
Solution:

Create a chart assigning the duct segments and corresponding airflow.

Segment Airflow (CFM) Round Duct Friction Loss Duct Length (ft) Pressure Drop
Size (in) per 100
AB 2000 100
BE 500 40
BC 1500 50
CF 1000 75
CD 500 40
DG 500 50

Starting at segment AB, find the nearest duct size that (rounding to the larger size) that gives us 0.1/100 ft of friction
loss. Entering the ASHRAE chart, we find that the nearest duct size (rounding up) is 18. The friction loss for 18 duct at
2000 CFM is .09/100. Knowing the length of segment AB is 10 ft, we can calculate the actual static pressure drop
through the segment as:

Filling in the chart for segment AB


Segment Airflow (CFM) Round Duct Friction Loss Duct Length (ft) Pressure Drop
Size (in) per 100 (in)
AB 2000 18 .09 100 .09
BE 500 40
BC 1500 50
CF 1000 75
CD 500 40
DG 500 50

Next, we repeat the process for each of the remaining segments and complete the chart.
Segment Airflow (CFM) Round Duct Friction Loss Duct Length (ft) Pressure Drop
Size (in) per 100 (in)
AB 2000 18 .09 100 .09
BE 500 12 .055 40 .022
BC 1500 16 .085 50 .0425
CF 1000 14 .09 75 .0675
CD 500 12 .055 40 .022
DG 500 12 .055 50 .0275

Finally, we add each of the paths in order to determine the worst case path. The three possible paths are:

Adding the static pressure losses for the three passes above, we get:

WN Mechanical Systems Duct Design Page 16 of 18


HVAC Clinics Draft - Not For Distribution

The worst case path is the required external static pressure of the fan. In the case of example 2, path 3 is the worst case
path. The fan should be sized to an external static pressure of 0.585 in-wg. Typically, the worst case path can be
identified without adding each and every path of the duct system. However, if the worst case path is not obvious, it is
necessary to examine several of the worst case paths in order to determine the exact amount of external static pressure
required for fan sizing. Note that in order for the duct system to properly balance, each of the branches will need to have
the same static pressure as worst case branch. It is for this reason we install balancing dampers in all of the duct
branches.

The procedure for determining rectangular duct sizes is very similar. After having determined the round duct size,
AHRAE tables can be used to find the equivalent round duct sizes based on duct aspect ratio. An alternate method is to
identify the equivalent rectangular duct size using a common ductilator.

The static regain friction duct design method uses the principal of static regain. Recall that static regain is the
conversion of velocity pressure to static pressure by increasing duct cross sectional area and thus decreasing velocity
pressure (figure 19).

Figure 20. Static Regain

WN Mechanical Systems Duct Design Page 17 of 18


HVAC Clinics Draft - Not For Distribution
The static regain duct design method employs the use of fittings that decrease the airstream velocity downstream of a
branch takeoff. This decrease in velocity is used to compensate the loss in static pressure upstream of the takeoff. The
goal is to keep the static pressure constant via static regain at each takeoff. If done correctly, the duct system is literally
self-balances and requires no balancing dampers. The downside to the static regain method is that is requires a
computer analysis tool and often requires more duct material (figure 20).

Figure 21. Static Regain Duct Design

WN Mechanical Systems Duct Design Page 18 of 18

Você também pode gostar