Its increasingly popular to team a centrifugal pump with a variable speed drive (VSD) rather than couple a
constant speed pump with a control valve on the discharge. However, many engineers dont understand a
VSDs impact on flow and how that affects control.
A pump/control-valve combination provides smooth flow even at very small valve openings, although in some
cases protection against low flow is required. However, with variable speed pumping, flow isnt always
Figure 1. As the valve closes, friction head increases, leading to lower flow.
drop below the minimum, the controller will quickly open the control valve to provide the necessary flow.
A control valve also is required in the line to the process to provide appropriate flow. In some configurations,
this flow loop is the inner loop for a level-to-flow cascade, a temperature-to-flow cascade or other cascade
arrangement. In some cases, the flow isnt measured; instead the output of the level, temperature or other
controller is connected directly to the control valve.
Often some modifications are made to reduce costs. Well assume a flow controller here, but the points
generally apply to all configurations.
Because pressure measurements are less expensive than flow ones, a measurement of either discharge pressure
or pump differential pressure is substituted for the pump flow measurement. The success of this approach
depends on the nature of the pump performance curves; it only works if the pressures significantly change with
pump flow.
The control valve can be avoided by inserting a fixed orifice into the recirculation piping. This provides some
recirculation at all times, even when the process flow exceeds the minimum necessary for low flow protection.
It requires extra energy and, possibly, a larger pump.
Variable speed pumping
Figure 3. Only pump speeds greater than 2,370 rpm provide flow.
In contrast, with a VSD a flow measurement is used to adjust a speed or torque controller included with the
drive electronics.
Vendors always stress possible energy savings with a VSD. However, especially in industries such as specialty
chemicals, few drives are large enough to provide sufficient energy savings to justify their additional cost.
However, a VSD offers other potential benefits. It may make the following equipment unnecessary:
1. sensor/transmitter for pump flow
2. recirculation piping
3. control valve in the recirculation piping
4. control valve in the line to the process
The controller for pump flow also is eliminated but this component is likely to be in the software of the digital
HP = HS + HD (QP/QD)2 (1)
where QP is process flow, gal/min; HP is head at process flow QP, ft; HS is static head, ft; QD is design flow,
gal/min; and HD is friction head at flow QD, ft.
The operating point is always where the pump curve intersects the system curve.
Control valves regulate flow by varying friction head that is, they work entirely through the system curve,
as illustrated in Figure 1. It presents system curves for a fully open control valve and a control valve that is
75% open. For the fully open valve, flow is 177 gal/min. As the control valve closes, resistance to flow
increases. This raises the friction head component of the system curve, which makes that curve intersect the
pump curve at a lower flow at 75% open, flow is 127 gal/min.
Small variations in both static and friction head occur in any pumping installation. These head variations cause
flow variations, which also can be determined from the performance curves.
Suppose the static head is 60 1 ft. Figure 2 shows system curves for 59 ft. and 61 ft. and where they intersect
with the pump curve. For the fully open control valve, flow is 177 2 gal/min; for the 75% open control valve,
flow is 127 2 gal/min. In each case, a head variance of 1 ft. leads to a flow variance of 2 gal/min.
Closing the control valve doesnt significantly affect the propagation of variance from head to flow. But as we
shall see, this isnt necessarily the case for variable speed pumping.
Flow regulation with a VSD
With variable speed pumping, the system curve is fixed but the pump curve shifts with pump speed. Some
vendors provide pump curves for certain selected speeds; others provide a pump curve only for the rated speed
of a constant speed drive. In either case, the affinity laws can be applied to obtain pump curves at other speeds:
Q(N) = QC (N/NC) (2)
H(N) = HC (N/NC)2 (3)
where N is speed, rpm; NC is speed for the pump curve supplied by the manufacturer, rpm; Q(N) is volumetric
flow at speed N, gal/min; QC is volumetric flow at speed NC (from the pump curve), gal/min; H(N) is head at
speed N, ft.; and HC is head at speed NC (from the pump curve), ft.
Flow decreases in proportion to the pump speed; head decreases in proportion to the square of the pump speed.
The affinity laws also state that power decreases with the cube of the pump speed, which strengthens the
energy savings arguments by VSD manufacturers.
Figure 3 illustrates regulating flow by varying pump speed. The system curve is fixed. For a pump speed of
3,450 rpm, the flow through the pump is 177 gal/min; for 2,850 rpm, 98 gal/min; and for 2,370 rpm, 0 gal/min.
In fact, 2,370 rpm is the minimum pump speed for flow that is, flow occurs only for speeds above 2,370
rpm.
The minimum speed to obtain flow is easily computed. When theres no flow, the system head is the static
head. The pump curve shows the head delivered by a pump with no flow and running at speed NC. The
minimum pump speed to obtain flow is computed using the affinity laws:
Nmin = NC (HS/HC0) (4)
where Nmin is minimum pump speed for flow, rpm; HS is static head (from the system curve); and HC0 is
head at speed NC and zero flow (from the pump curve), ft.
For our example, NC is 3,450 rpm, HS is 60 ft., and HC0 is 127 ft. The minimum pump speed is 2,370 rpm.
So, the VSD must operate over the range of 2,370 rpm to 3,450 rpm. The minimum speed is 69% of the
maximum speed; the turndown ratio is 1.46:1. VSDs are easily capable of this.
Figure 7. More linear relationship better matches the PID control equation.
Figure 4 illustrates propagation of variance from static head to flow for pump speeds of 3,450 rpm and 2,450
rpm. At 3,450 rpm, a static head of 60 1 ft. gives a flow of 127 2 gal/min (just like for the fully open control
valve). However, at 2,450 rpm, a static head of 60 1 ft. gives a flow of 19 6 gal/min. As the pump speed
decreases, the variance in flow increases by a factor of three.
Even with this increase in variance, the pump probably would still perform satisfactorily. At low flows, the
pump curve in Figure 4 exhibits a significant sensitivity of head to flow. This isnt the case for all pumps. For
some, the pump curve at low flows is essentially flat (slope is zero) that is, at low flows, pump head is
independent of flow. For such pump curves, the propagation of variance from static head to pump flow would
be much larger.
Pumps with a flat pump curve at low flows likely will experience cycling between no flow and some positive
flow. Avoid them if you want a VSD to perform smoothly at low flows. Pumps with pump curves such as in
Figure 6 probably wouldnt exhibit the cycling.
Sensitivity of flow to pump speed
Figure 8. Value remains relatively constant over the entire operating range.
Its also important to understand the change in flow produced by a given change in pump speed.
Figure 5 presents the sensitivity of flow to pump speed for the range of speeds over which the pump could
operate. (The somewhat erratic nature of the graph is the result of digitizing the pump curve.) It shows that the
sensitivity increases as the pump speed decreases that is, at low pump speeds, a change in speed has a larger
effect on flow than the same change at high speeds.
Such a change in sensitivity affects the performance of the control loop (flow, level, temperature or other)
whose output determines the pump speed. As the sensitivity increases, more oscillations can be expected in
that loop. So, to use the same tuning at low flows and at high flows, either tune the loop under a low flow
condition or conservatively tune the loop at high flows. The results are essentially the same the controller is
tuned with a lower gain. For the controller to function at low flows, performance is sacrificed at high flows.
While techniques such as scheduled tuning could address this problem, conservative tuning usually can
accommodate a change in sensitivity of 3:1. But its possible that the change in sensitivity could far exceed
3:1. At low flows, the pump curve in our example exhibits a significant sensitivity of head to flow. However,
the pump curve for some pumps is basically flat. For such pumps, the increase in sensitivity would be much
larger than 3:1 and could even lead to instabilities in the loop that outputs to the pump speed.
Figure 9. High sensitivity of flow to speed at low rpm could lead to cycling.
Torque
Pump curves traditionally are drawn with pump speed as a parameter. This might imply that the flow through
the pump is best controlled by varying the pump speed, but it isnt necessarily the case. Changing the torque
may make more sense. VSDs can control either of these variables.
When the input signal to the drive electronics adjusts pump speed, the relationship between flow through the
pump and pump speed is important. This can be computed from the pump curve and system curve (Figure 6).
The departure from linearity is noticeable and is consistent with the changes in the sensitivity of flow to
speed (Figure 5).
When the input signal to the drive electronics adjusts torque, the relationship between flow through the pump
and torque is important. This also can be computed from the pump curve and system curve (Figure 7). The
graph exhibits only a slight departure from linearity, making it preferable for PID control as that control
equation is linear.
Figure 10. Nearly linear relationship offers advantage for control.
Figure 8 presents the sensitivity of flow to torque for the range over which the pump could operate. The
somewhat erratic nature of the graph is the result of digitizing the pump curve. The sensitivity changes only
slightly over the operating range.
These graphs were computed from the pump curve (Figure 5), which exhibits significant sensitivity of head to
flow at low pump flows. As already mentioned, for some pumps the pump curve is flat at low flows that is,
the head is almost constant at such flows.
Figure 9 shows flow as a function of speed for a pump with a flat pump curve. The departure from linearity is
much greater. At low flows this graph is almost vertical, so the sensitivity of flow to speed at low flows will be
very large, which could lead to cycling in the flow.
However, even for a pump with a flat pump curve, the relationship between flow and torque is nearly linear
(Figure 10). Generally linear behavior leads to better performance from the controls.
So, for a centrifugal pump with a VSD its usually preferable to use torque to control flow. This also seems
consistent with the future directions for VSD technology.
Cecil L. Smith is president of Cecil L. Smith, Inc., Baton Rouge, La. E-mail him at cecilsmith@cox.net.