CHILLED WATER SUPPLIED BY EACH PUMP

(MAIN PUMP STATION BUILDING)


P
PLAN TRANE
I
P
E
SI No. EQUIPMENT AREA QTY DUTY
S
I
Z
A. SUPPLIED BY SECONDARY PUMP SCHP-B2-01 E
1 Transmission Pumps SS-3B 4
1 VFD 4
Total Supplied by Secondary Pump SCHP-B2-01
Secondary Pump Capacity SCHP-B2-01
Remaining Available Chilled Water Flow

B. SUPPLIED BY SECONDARY PUMP SCHP-B2-02


1 FRESH AIR HANDLING UNIT FAHU-B2-01 PUMP / MCC RM. 1 1 ###
2 FRESH AIR HANDLING UNIT FAHU-B2-02 CONTROL RM. / SERVER RM. 1 1 ###
3 FRESH AIR HANDLING UNIT FAHU-B2-03 VFD ROOM 2 1 1 ###
4 FRESH AIR HANDLING UNIT FAHU-B2-04 VFD ROOM 1 1 1 ###
5 AIR HANDLING UNIT AHU-B2-06 CABLE BASEMENT 1 1 ###
6 AIR HANDLING UNIT AHU-B2-07 CABLE BASEMENT 1 1 ###
7 AIR HANDLING UNIT AHU-B2-08 CABLE BASEMENT 1 1 ###
8 FAN COIL UNIT FC-B2-13 ELEC. ROOM 2 1 ###
9 FAN COIL UNIT FC-B2-14 CONTROL ROOM 2 1 ###
10 FAN COIL UNIT FC-B2-15 ELEC. ROOM 2 1 ###
11 FAN COIL UNIT FC-B2-17 VFD ROOM 1 4 3 ###
12 FAN COIL UNIT FC-B2-18 MCC ROOM 4 3 ###
13 FAN COIL UNIT FC-B2-19 VFD ROOM 2 4 3 ###
14 FAN COIL UNIT FC-B2-20 PUMP ROOM 4 3 ###
15 COMPUTER COIL AIR CONDITIONING CRAC B2-1A / 1B SERVER ROOM 2 1 ###
Total Supplied by Secondary Pump SCHP-B2-02 ###
Secondary Pump Capacity SCHP-B2-02
Remaining Available Chilled Water Flow

C. SUPPLIED BY SECONDARY PUMP SCHP-B2-03


1 FRESH AIR HANDLING UNIT FAHU-B2-05 OFFICES 1 1 ###
2 FAN COIL UNIT FC-B2-1 MALE CHANGING ROOM 1 1 ###
3 FAN COIL UNIT FC-B2-2 CORRIDOR 1 1 ###
4 FAN COIL UNIT FC-B2-3 FEMALE CHANGING ROOM 1 1 ###
5 FAN COIL UNIT FC-B2-4 PRAYER ROOM 1 1 ###
6 FAN COIL UNIT FC-B2-5 FIRST AID ROOM 1 1 ###
7 FAN COIL UNIT FC-B2-6 PRINT RECORDS 1 1 ###
8 FAN COIL UNIT FC-B2-7 COMMON ROOM 1 1 ###
9 FAN COIL UNIT FC-B2-8 OFFICE 1 1 ###
10 FAN COIL UNIT FC-B2-9 MEETING ROOM 1 1 ###
11 FAN COIL UNIT FC-B2-10 LOBBY 1 1 ###
12 FAN COIL UNIT FC-B2-11 OFFICE 1 1 ###
13 FAN COIL UNIT FC-B2-12 OFFICE 1 1 ###
14 FAN COIL UNIT FC-B2-16 MAIN HALLWAY 2 2 ###
Total Supplied by Secondary Pump SCHP-B2-03 ###
Secondary Pump Capacity SCHP-B2-03
Remaining Available Chilled Water Flow

D. SUPPLIED BY SECONDARY PUMP SCHP-B2-04


1 COOLING COIL CC-B2-01 to 02 MAIN PUMP HALL 4 4 ###
2 FAN COIL UNIT FC-B2-21 ELEC. ROOM 8 4 ###
Total Supplied by Secondary Pump SCHP-B2-04 ###
Secondary Pump Capacity SCHP-B2-04
Remaining Available Chilled Water Flow

1
S.I. Item Size Quantity Length Temp. Flow

mm mm C lps

MAIN PUMP PCHP-B2-01


1 Pipe 200 46000 6 90.75
2 Elbow 90 200 1 6 90.75
3 Tee (run) 200 5 6 90.75
4 Pipe 200 10100 6 72.72
5 Elbow 90 200 2 6 72.72
6 Tee (run) 200 1 6 72.72
7 Pipe 200 6200 6 54.69
8 Tee (run) 200 1 6 54.69
9 Pipe 150 7300 6 36.66
10 Tee (run) 150 1 6 36.66
11 Pipe 150 10000 6 18.03
12 Elbow 90 150 2 6 18.03
13 CHILLER 18.03
14 Pipe 200 13200 10 90.75
15 Elbow 90 200 2 10 90.75
16 Tee (branch) 200 2 10 18.03
17 Tee (run) 200 1 10 90.75
18 Pipe 200 4300 10 81.59
19 Tee (run) 200 1 10 81.59
20 Pipe 200 4850 10 37.75
21 Tee (run) 200 1 10 37.75
22 Pipe 200 4400 10 27.44
23 Pipe 200 7100 10 24.46
24 Elbow 90 200 2 10 24.46
25 Tee (branch) 200 1 10 24.46
26 Tee (run) 200 1 10 27.44
SUB-TOTAL PRESSURE DROP, kPa
MARGIN, 15%
TOTAL PRESSURE DROP, kPa
Velocity Press. Drop

m/s kPa

2.89 15.46
2.89 1.13
2.89 2.09
2.31 2.23
2.31 1.45
2.31 0.27
1.74 0.80
1.74 0.15
2.07 1.86
2.07 0.26
1.02 0.67
1.02 0.30
22.40
2.89 4.39
2.89 2.25
0.57 0.19
2.89 0.42
2.60 1.17 less pump 1
2.60 0.34
1.20 0.31 less pump 1, 2
1.20 0.07
0.87 0.15 less pump 1, 2, 3
0.78 0.20 branch to pump 4
0.78 0.16
0.78 0.18
0.87 0.04
58.92
8.84
67.76
K factor (from ASHRAE Fundamentals 2009 Chapter 22 Table 1 & 2; Butterfly Valves from CR

Nominal Pipe Dia. 10 15 20 25 32 40


(mm)
Angle Valve 6.1 4.6 3.6 2.9
Butterfly Valve
Elbow 45 0.38 0.37 0.35 0.34 0.33 0.32
Elbow 90 2.5 2.1 1.7 1.5 1.3 1.2
Elbow 90 LR 0.92 0.78 0.65 0.54
Gate Valve 0.4 0.33 0.28 0.24 0.22 0.19
Globe Valve 20 14 10 9 8.5 8
Return Bend 2.5 2.1 1.7 1.5 1.3 1.2

Swing Check Valve 8 5.5 3.7 3 2.7 2.5

Tee (branch) 2.7 2.4 2.1 1.8 1.7 1.6


Tee (run) 0.9 0.9 0.9 0.9 0.9 0.9

SCREWED FITTINGS

friction factor (fT), 0.027 0.025 0.023 0.022 0.021


Crane 1982

WATER PROPERTIES Pipe Roughness


Dynamic
TEMPERATURE Density (Absolute) =
Viscosity
C kg/m3 Pa*s
2 999.9429 0.0016735 1.6735
3 999.9672 0.001619 1.619
4 999.975 0.0015673 1.5673
5 999.9668 0.0015182 1.5182
6 999.9432 0.0014715 1.4715
7 999.9045 0.0014271 1.4271
8 999.8512 0.0013847 1.3847
9 999.7838 0.0013444 1.3444
10 999.7026 0.0013059 1.3059
11 999.6018 0.0012692 1.2692
12 999.5004 0.001234 1.234
13 999.3801 0.0012005 1.2005
14 999.2474 0.0011683 1.1683
15 999.1026 0.0011375 1.1375
16 998.946 0.0011081 1.1081
17 998.7779 0.0010798 1.0798
18 998.5986 0.0010526 1.0526
19 998.4082 0.0010266 1.0266
20 998.2071 0.0010016 1.0016
21 997.9955 0.0009775 0.9775
22 997.7735 0.0009544 0.9544
23 997.5415 0.0009321 0.9321
24 997.2995 0.0009107 0.9107
25 997.0479 0.00089 0.89

Formula Used (According to ASHRAE HANDBOOK - FUNDAMENTALS, 2009)


Reference Chapters: 3, 22, 33

Darcy-Weisbach Equation

p = Pressure Drop, Pa
f= friction factor (from Moody or equations), dimensionless
L= length, m
D= hydraulic diameter, m
= density at mean temp, kg/m3
V= average velocity, m/s

Churchill Equation for friction factor (f)

where:
f= friction factor, dimensionless
Re = Reynold's number, dimensionless
Dh = hydraulic diameter, m
= absolute roughness of pipe wall, m

K FACTOR FOR FULLY OPEN BUTTERFLY VALVES:


from CRANE Technical Paper 410: Flow of Fluids Through Valves, Fittings & Pipes Metric Edition 1982)

Size 50mm (2") to 200mm (8") : K = 45 fT


Size 250mm (10") to 350mm (14") : K = 35 fT
Size 400mm (16") to 600mm (24") : K = 25 fT
able 1 & 2; Butterfly Valves from CRANE Technical Paper 410 Metric Edition 1982)

50 65 80 100 150 200 250 300

2.1 2.3 2.2 2.1 2.1 2.1 2.1 2.1


0.855 0.81 0.81 0.765 0.675 0.63 0.63 0.585
0.31 0.19 0.18 0.18 0.17 0.17 0.16 0.16
1 0.35 0.34 0.31 0.29 0.27 0.25 0.24
0.42 0.28 0.25 0.22 0.18 0.16 0.14 0.13
0.17 0.27 0.22 0.16 0.1 0.08 0.06 0.05
7 8 7 6.5 6 5.7 5.7 5.7
1 0.35 0.34 0.31 0.29 0.27 0.25 0.24

2.3 2 2 2 2 2 2 2

1.4 0.79 0.76 0.7 0.62 0.58 0.53 0.5


0.9 0.18 0.17 0.15 0.12 0.1 0.09 0.08

FLANGED WELDED FITTINGS

0.019 0.018 0.018 0.017 0.015 0.014 0.014 0.013

Pipe Roughness

0.000046 m

Steel Pipe (ASHRAE Fundamentals Chapter 3, 2009)


Pressure Loss in Valves & Fittings

p = Pressure Drop, Pa
K= geometry & size dependent coefficient, dimensionless (see table above)
= density at mean temp, kg/m3
V= average velocity, m/s
Edition 1982)
see table above)