Contents Page
1 General...........................................................................................................4
1.1 Purpose ..................................................................................................................................4
1.2 General information on the use of the PC program..........................................................4
1.3 Other relevant documents...................................................................................................4
1.4 Danger symbols ....................................................................................................................5
1.5 Software .................................................................................................................................5
6 Application menu.......................................................................................12
6.1 General.................................................................................................................................12
6.2 "Project" menu....................................................................................................................12
6.2.1 General ........................................................................................................................... 12
6.2.2 New project, .............................................................................................................. 13
6.2.3 Open project, ............................................................................................................. 13
6.2.4 Close project, ............................................................................................................ 13
6.2.5 Save project, .............................................................................................................. 13
6.2.6 Save project as ............................................................................................................... 14
9 Further documents....................................................................................42
1 General
1.1 Purpose
The operating software of Transafe ADW 511 contains fixed basic settings for various applications. These
can be individually selected by means of a program selector switch so that most applications are thus
generally covered.
In applications where there may be extreme ambient conditions or different response behaviour is re-
quired, the Transafe ADW 511 can be programmed in a customer-specific manner with the aid of the PC
programming software.
All necessary operating parameters of the ADW 511 are programmable on the PC and can be transmitted
to the ADW. It is also possible to load standard configurations and transmit them to the ADW 511. The
projects (data) generated can be saved as a file with a recognizable name (e.g. system number). With the
PC Tool, it is also possible to perform tests, recordings and long-term data acquisition and to document all
data generated (measured data and programming data).
This documentation describes the handling of this PC program.
Information
All adaptations or modifications to ADW 511 via the PC may be made only by the
manufacturer or by persons instructed by the manufacturer.
This documentation is only valid for the following SW versions:
Operating software (Firmware) ADW 511 from Version 02.01.00
PC program Version 02.03.01
Danger information
If the danger information is not observed, the product and possibly other system parts
may constitute a danger to persons and/or property or may be damaged or may lead to
malfunctions so that there is a possible danger for persons and property.
Description of possible dangers
Measures and precautions
How dangers can be avoided
Any further safety-relevant information
Safety information
Failure to observe the safety information may result in damage to the product.
Description of possible damage
Measures and precautions
How the dangers can be avoided
Any further safety-relevant information
Information
If the information is not observed, the product may cause a malfunction.
Description of expected malfunctions
Measures and precautions
Any further safety-relevant information
1.5 Software
Danger information
The ADW 511 may be operated only with the suitable original operating software from
the manufacturer.
Any unauthorized intervention in the software or the use of non-original software may
lead to malfunction of the unit or damage to the unit. Furthermore, all guarantee and li-
ability rights with respect to the manufacturer of the Transafe ADW 511 shall become
null and void as a result.
Copyright by SECURITON
All software of the ADW 511 and of the PC program are subject to the manufacturer's copyright. Any unauthorized
intervention in the software, any misuse, copying or unauthorized trade in the software constitutes an infringement of
the copyright and and would be subject to prosecution.
Information
A change of version or extension of the ADW 511 software (operating software, incl.
PC program) does not imply any right to an update or release for existing Transafe
ADW 511 systems.
2.2 PC software
The software for the customer-specific programming
of the ADW 511 is available on a 3.5" diskette. All
necessary setup files for installing the program on a INDEX
WRITE ENABLE
WRITE PROTECT
Main directory
Application file
bmp 1
The following password dialogue then appears (only at first program start):
bmp 2
By inputting a user name and a password, the PC program can be protected from unauthorized access.
The password must be confirmed in the third line. The dialogue window should then be closed by clicking
on "OK". On restarting, the program can be started only with the user name and the password (also see
Section 5.1.2 "Log in").
However, if you only click on "Cancel" instead of making inputs in the dialogue field, the following window
appears.
bmp 3
If you confirm now by clicking on "OK", the program can be started in future without a password. A
code can if required also be specified later on by means of the function "Set password" (see Section
5.1.3).
5 Main menu
5.1 Menu bar
The program contains two menu bars (main menu and application menu), under which the main functions
are available.
The further actions are triggered by clicking with the mouse, by means of a hotkey (icon) or with the cur-
sor keys. Further actions are calling up submenus, dialogues or editing.
When the program is started, the following menu appears:
bmp 4
5.1.1 Project
All menu options under "Project" relate to file handling. The data set up for an ADW 511 system can be
saved. For a 'system' which was stored, the data can be loaded and changed.
On the basis of the currently loaded file, the data can be prepared so that they can be used for sending a
configuration to the ADW 511 and for creating the documentation.
The "Project" menu contains the following submenus and functions:
bmp 5
Documents: A project is opened with predefined settings. The settings are based on empirical val-
ues, and a document can thus be used without changes for programming an applica-
tion (to be implemented in the future).
Open: An existing project is loaded from the hard disk into the program.
5.1.2 GoOn
The only two actions which can be executed even without opening a project or logging on correctly are
listed under "GoOn".
bmp 6
LogIn: Possible only if the procedure was terminated with "Cancel" in the password win-
dow on starting the PC program.
When "LogIn" is selected, the password window appears. Logging in is no longer
possible after an incorrect entry for the password or cancellation (3 attempts) the
PC program must be newly installed.
System state: The state of the ADW 511 is displayed graphically (also see under Section 6.4.8).
5.1.3 Setup
Under "Setup", it is possible to make system settings, such as interface configuration, scanning cycles,
directory structure and password change.
bmp 7
Interface: The interface can be configured. Only the specification of the port is possible (also
see under Section 6.5.2).
Polling time: Under this menu option, it is possible to input the cycle in which the data of the
ADW 511 are to be scanned and transmitted to the PC. The default setting is
0.5 second (500 ms). Changes in the range from 0.5 to 5 seconds are possible (also
see under Section 6.4.8.1 and 6.5.3).
Index: This option gives a list of the various index under which the generated data are
stored. The occupation corresponds to the assignment according to Section 3.1, Fig.
4 (also see under Section 6.5.4).
bmp 8
Set If no password was specified during
password: the installation of the PC program, a
user name and a password can be
allocated by means of this option.
The password must be repeated in
the last line for confirmation.
bmp 9
5.1.4 View
Under "View", the toolbar and the state bar can be displayed.
b a
bmp 10
Toolbar (a): The hotkeys (icons) at the top edge of the screen can be switched on and off.
Status bar (b): The status bar at the bottom edge of the screen can be switched on and off.
5.1.5 Help
bmp 11
6 Application menu
6.1 General
To be able to work in the application menu, the user must be correctly logged on (password input, if pres-
ent) and must have opened an existing or a new project.
If these preconditions were fulfilled, the following menu appears (opened below with "Project" > "New" or
)
bmp 12
6.2.1 General
All actions which are performed under Project relate only to projects with the extension "___.ADW". All
other files with other formats cannot be edited directly.
Before an action is performed, the extension and the format are always checked. In the event of any er-
rors, the user is informed.
bmp 13
Documents: A project is opened with predefined settings. The settings are based on empirical val-
ues, and a document can thus be used without changes for programming an applica-
tion (to be implemented in future).
Open: An existing project is loaded from the hard disk into the program (also see Section
6.2.3).
Close: Exit the application menu. The main menu is displayed (also see Section 6.2.4).
Save: An edited project is saved under the current (opened) name (also see Section 6.2.5).
Save as: An edited project is saved under any new name (also see Section 6.2.6).
Delete: An existing project on the hard disk can be deleted (also see Section 6.2.7).
Exit: Exits the PC program (also see Section 6.2.8).
bmp 14
bmp 16
bmp 17
bmp 18
Selection:
Yes: Next window appears with the ques-
tion: "Overwrite existing project? Yes /
No / Cancel".
No: The system will exit from the PC pro-
gram without saving the changes.
Cancel: The window will be discarded. The file
will not be saved and the system will
not exit from the PC program.
bmp 20
Selection:
Yes: The changes will be saved under the
opened project name.
No: The system will exit from the PC pro-
gram without saving the changes.
Cancel: The window will be discarded. The file
will not be saved and the system will
not exit from the PC program.
bmp 21
6.3.1 General
All functions under the "Edit" menu are for configuring the connected ADW 511. The programmed data
are written to the main memory and are backed up on the PC's storage medium only during saving.
The individual functions can be opened and edited as masks (dialogues) at the same time.
Information
The relay allocation can be changed only by the manufacturer.
bmp 22
Project data: Input of system data (customer, project, remarks, etc.) (also see Section 6.3.2).
System parameter: Input of the general trigger criteria of the ADW 511 (also see Section 6.3.3).
Relay allocation: The relay allocation can be changed only by the manufacturer (also see
Section 6.3.4).
The data can be loaded from any project, edited and transmitted to the ADW 511.
bmp 23
The system parameters are divided into "Test criteria" and "Trigger criteria".
6.4.1 General
All menu options under "ADW 511" relate to the online operation - PC ADW 511. i.e. each subfunc-
tion can be executed only if there is a connection from the PC to the ADW 511.
Information
The event memory can be cleared only by the manufacturer.
bmp 25
Send The system data defined in Section 6.3.2 (customer, project, remarks, etc.) are
project data: transmitted to the ADW 511 and stored there (also see Section 6.4.2).
Send The system parameters defined in Section 6.3.3 (test and trigger criteria) are
configuration data: transmitted to the ADW 511 and stored there (also see Section 6.4.3).
Load config. and The system data and system parameters stored/defined in the ADW 511 - the
project data: latter according to the selector switch position in the ADW 511 - are loaded onto
the PC for further editing (also see Section 6.4.4).
System test: The ADW 511 starts a test procedure (also see Section 6.4.5).
Various tests: In the ADW 511, LEDs, relays and test motor can be individually actuated (trig-
gered). The operating software version of the ADW 511 can be displayed (also
see Section 6.4.6).
Information
Actuation of the relays results in corresponding triggering of the
FACP. Depending on the system parameters, actuation of the test
motor may put the ADW 511 in the alarm state.
Alarm, fault, fire control installations!
System state The current state of the ADW 511 is shown in the form of a table (faults, alarms,
(general): general state) (also see Section 6.4.7).
System state The current state of the ADW 511 is displayed graphically (curve of maximum
(graphic): and differential pressure). The recording for long-term data acquisition can be
started (also see Section 6.4.8).
Measured value: The last three events (from original reset) can be called up. The event memory
can be cleared only by the manufacturer (also see Section 6.4.9).
Reset ADW 511: Existing alarms/faults in the ADW 511 can be reset (also see Section 6.4.10).
bmp 26
bmp 27
Information
Before the data transmission, one of the two programs 8 or 9 must be selected in the
"Program selection" field. The programs correspond to the freely configurable selector
switch positions in the ADW 511.
bmp 29
Information
To enable the ADW 511 to function with the transmitted system parameters, the corre-
sponding selector switch position must be set in the ADW 511.
bmp 31
bmp 33 bmp 34
In the field "Results of measurement", the positive and negative pressure components of the test per-
formed and the positive and negative pressure components of the original reset (commissioning) appear.
A comparison of the values takes place in the ADW 511. The result is shown in the field "Error evalua-
tion".
With a correct run (no leak, no crushing of the sensor tube), the message "No errors found" appears in
the field "Error evaluation".
If, for example, a leak is found in the sensor tube, a message "[1] Pressure too low (leak)" "[2] Positive-
negative ratio not OK" appears in the field "Error evaluation".
Depending on the result, the ADW 511 remains in the standby state or triggers a fault.
Information
Actuation of the relay results in corresponding triggering of the FACP. Depending on
the system parameters, actuation of the test motor can put the ADW 511 in the alarm
state.
Alarm, fault, fire control installations!
bmp 35
bmp 36
bmp 37
Legend:
A Current date (from PC)
B Current time (from PC)
C Order number (according to entry in "Project data", see Section 6.3.2)
D Set selector switch position in ADW 511
E State of the connection from PC to ADW 511
F State of the ADW 511
G Maximum pressure window, display range +/- 200 mbar
H Red line, set alarm threshold of maximum pressure = 120 mbar (corresponds to field "X")
I Black line, measured maximum pressure curve (corresponds to field "K" at "J")
J Instantaneous time of continuous maximum pressure display
K Current maximum pressure in mbar (corresponds to curve value "I" at time "J")
L Highest measured maximum pressure in mbar (max. value memory)
M Lowest measured maximum pressure in mbar (min. value memory)
N Time window (the differential pressure must be above the alarm threshold for this time before an alarm is trig-
gered)
O Maximum positive pressure value (generated by original reset test procedure)
P Maximum negative pressure value (generated by original reset test procedure)
Q Differential pressure window, display range +/- 100 mbar/min
R Red line, set alarm threshold of differential pressure = 10 mbar/min (corresponds to field "Y")
S Black line, measured differential pressure curve (corresponds to the field "U" at "T")
T Instantaneous time of continuous differential pressure display
U Current differential pressure in mbar (corresponds to curve value "S" at time "T")
V Highest measured differential pressure in mbar (max. value memory)
W Lowest measured differential pressure in mbar (min. value memory)
X Alarm threshold for maximum alarm in mbar
Y Alarm threshold for differential alarm in mbar/min
Z Start and definition of long-term data acquisition (see Section 6.4.8.1)
Information
The setting in the "Polling" window (polling
time) should always be chosen to be equal
bmp 38 to or less than the time setting in the "Log-
ger" window it is preferable to leave the
default setting of 500 ms.
bmp 39
bmp 42
B H
E I
G
K
bmp43
Legend:
A Shows the number of elapsed events (unlimited).
B Reading of the processor timer when the event occurred
C Event state
D Computer failure associated with the event
E Info window for alarm events. The arrow reveals further info texts.
F Info window for fault events. The arrow reveals further info texts.
G Loading of the measured values associated with the event:
PH = Pressure value in mbar, only used internally for test procedure.
PL = Effective pressure value in total pneumatic loop in mbar.
TE = Temperature in C, used only for temperature compensation.
DP = Differential pressure value (gradient) in mbar/min.
H Display of the set system parameters.
I Display of the triggered reserve relay actuations associated with the event (only when programmed by the
manufacturer).
J Window for inputting the filename under which the event is to be saved in the "Events" directory. If no other entry
is made, the three events automatically receive the names "LAST.EVE" / "SE_LAST.EVE" / "TH_LAST.EVE".
K Button for saving the event in the "Events" directory
Further procedure:
1. Click on the buttons "PH", "PL", "TE" and "DP" in suc-
cession the adjacent window appears between the
individual inputs.
bmp 44
2. If desired, overwrite the default entry "LAST.EVE" with
the desired filename. The extension "___.EVE" should be left or entered again. The filename may be
max. 8 characters long (without extension).
3. To save the event in the "Events" directory, click on the "Save data" button.
4. The procedure is ended with the "Cancel" button.
5. In the "Events" directory, the file can be opened using various application programs (Excel, Word,
WordPad, etc.).
bmp 45
bmp 46
6.5.1 General
Under "Setup", it is possible to make system settings, such as port configuration, polling time, directory
structure and printer setup.
bmp 47
Interface: The interface can be configured. Only the determination of the interface is possible
(also see Section 6.5.2).
Polling time: Under this option, you can specify in which cycle the ADW 511 data are to be polled
and transmitted to the PC. The default setting is 0.5 second (500 ms). Changes in the
range from 0.5 to 5 seconds are possible (also see Section 6.4.8.1 and 6.5.3).
index: This option displays a list of the various directories under which the data generated
are stored. The allocation corresponds to the assignment according to Section 3.1,
Fig. 4 (also see Section 6.5.4).
Printer setup The printer driver can be installed and various printer settings made (also see Section
6.5.5).
6.5.2 Interface
The port is set via the path "Setup" > "Interface".
Only the interface assignment (Com 1 to Com 4) can be
changed here.
The other settings are fixed and cannot be changed.
bmp 48
Information
In the case of long-term data acquisition, the "Polling Time" setting should always be
chosen to be equal to or less than the time setting in the "Logger" window prefera-
bly, the default setting of 500 ms should be left (also see Section 6.4.8.1).
6.5.4 Directories
The menu option "Setup" > "Index" displays a
list of various directories under which the data
generated are stored.
Assignment of the directories is automatically
generated in the installation of the PC program
(also see Section 3.1, Fig. 4).
The "Program directory" is fixed during the
installation. The path cannot be changed in
this menu option. If it is intended to establish a
different program directory (for example an-
bmp 50 other drive), this must be done by means of
the installation procedure (also see Section
3.1).
The other Index (Project, Log data and Event data) can if required be adapted by an appropriate correc-
tion in the menu "Setup" > "Index". On confirming with "OK", these are automatically generated.
bmp 51
6.6.1 General
The current project can be documented under "Documentation". The display of the current print image
and the print command are available.
bmp 52
Print Preview: The current print image of the loaded project is displayed (also see Section 6.6.2).
Print project Printing of the loaded project can be started. A window with options for selecting page
data: number, number of copies, etc. first appears (also see Section 6.6.3).
bmp 53
bmp 43
"Window" menu
Under "Window", a list of the opened projects can be called up. The project displayed on the screen has
a mark before the project name (3). By clicking on one of the project names in the list, the corresponding
project is brought into the foreground and can be edited.
bmp 55
bmp 56
6.8.1 General
Under "Help", you can call up various help functions and information on the PC program.
bmp 57
Index: Outputs help messages for the user (not yet implemented, also see Section 6.9.2).
Using Help: Explains the use of the Help (not yet implemented, also see Section 6.9.3).
About ADW511: Shows information on the PC program (also see Section 6.9.4).
6.8.2 Index
The Index help option "Help" > "Index" for
the PC program has not yet been imple-
mented. A corresponding information mes-
sage therefore appears when you click on it.
bmp 58
6.8.3 Using Help
The Using Help option "Help" > "Using
Help" for the PC program has not yet been
implemented. A corresponding information
message therefore appears when you click
bmp 59 on it.
bmp 60
7.2.1 Procedure
1. Establish a connection from the PC to the ADW 511 and start the PC program according to Section 4.
The ADW 511 must be switched on (FAS zone on).
2. Select "Project" > "New" ( button).
3. Select "Edit" > "System Parameter" ( button).
4. Make the required settings in the "System Pa-
rameter" window (example) and confirm with
"OK":
bmp 61
bmp 62
bmp 63
8. Select "ADW511" > "Send project
data". In the "Send project data to
ADW511", click on the "Send" button to
start the data transmission. On correct
transmission, the information window
"Send data" appears. Confirm with "OK".
bmp 64
9. Select "ADW511" > "Send configura-
tion data". Select the desired free se-
lector switch position in the "Send data to
ADW511" window (in this case = 8) and
click on the "Send" button to start the
data transmission. On correct transmis-
sion, the information window "Send data"
appears. Confirm with "OK".
bmp 65
10. Information
To enable the ADW 511 to operate with the transmitted system parameters, the appro-
priate selector switch position must be set in the ADW 511 at the end (in this case = 8).
7.3.1 Procedure
1. Establish connection from PC to ADW 511 and start PC program according to Section 4. The
ADW 511 must be switched on (FAS zone on).
2. Determine which of the selector switch positions with fixed configuration are to be loaded from the
ADW 511 to the PC and set this selector switch position on the ADW 511 (for example = position 8).
3. Select "Project" > "New" ( button).
4. Select "ADW511" > "Load config. and
project data". Click on the "Load" button
in the "Load data from ADW511" window
to start the data transmission. On correct
transmission, the information window
"Load data" appears. Confirm with "OK".
bmp 67
bmp 68
bmp 69
10. Select "ADW511" > "Send project data".
Click on the "Send" button in the "Send
project data to ADW511" to start the data
transmission. On correct transmission, the
information window "Send data" appears.
Confirm with "OK".
bmp 70
12. Information
To enable the ADW 511 to operate with the transmitted system parameters, the appro-
priate selector switch position must be set in the ADW 511 at the end (in this case =
8).
A previously defined project is opened on the PC (with defined project data and system parameters).
These data should then be sent to one of the free selector switch positions 8 or 9 on the ADW 511. This
method is recommended if several ADW 511 are to be equipped with identical customer-specific pro-
gramming in a system.
7.4.1 Procedure
Define project: The project can be defined on the PC without an ADW 511 having to be connected to the
PC for this purpose.
1. Start PC program according to Section 4.
2. Select "Project" > "New" ( button).
3. Select "Edit" > "System Parameters" ( button).
4. Make the required settings in the "System Parame-
ters" window (example) and confirm with "OK":
bmp 72
5. Select "Edit" > "Project Data" ( button).
6. Make the project-specific entries in the "Project
Data" window (example) and confirm with "OK".
bmp 73
bmp 74
Program ADW: The previously defined project data and system parameters can now be loaded locally
onto several ADW 511.
8. Establish connection from PC to ADW 511. The ADW 511 must be switched on (FAS zone on).
9. Select "Project" > "Open" ( button). In
the "Open project" window, select the filename
of the previously defined project under "Proj-
ect" (in this case = "TEST2.adw") and confirm
with "Open".
bmp 75
bmp 76
11. Select "ADW511" > "Send configura-
tion data". Select the desired free se-
lector switch position (in this case = 8) in
the "Send data to ADW 511" window and
click on the "Send" button to start the
data transmission. On correct transmis-
sion, the information window "Send data"
appears. Confirm with "OK".
bmp 77
12. Information
To enable the ADW 511 to operate with the transmitted system parameters, the appro-
priate selector switch position must be switched on in the ADW 511 at the end (in this
case = 8).
8.3 Warnings
Occur when:
cable is connected to wrong port
wrong port has been selected (setup).
Solution:
Check port connection or correct setup.
bmp 80 bmp 81
Occur on:
unsuccessful attempt to input user name or password.
Solution:
Enter correct user name and password (three tries possible).
bmp 82
Occur after:
third unsuccessful attempt to input user name or password.
Solution:
Input correct user name and password (last try).
bmp 83
Occur on:
unsuccessful reset attempt, during timeout (port error).
Solution:
Check port (connection, cable, setup).
bmp 84
4 Occur when:
User tries to change the relay allocation.
Solution:
Consult the manufacturer.
bmp 85
Occur when:
User tries to delete the event memory.
Solution:
Consult the manufacturer.
bmp 86
Occur when:
There are no events in the polled event memory, i.e. no alarm or faults have
occurred since commissioning or since the event memory has been
cleared by the manufacturer.
bmp 87
Occur when:
a temporary file was opened with "Project" > "New"
and an attempt was then made to save this with
"Project" > "Save".
Solution:
bmp 88
Save with "Project" > "Save as" (input of new file-
name).
Occur when:
an attempt is made to send a temporary file opened under
"Project" > "New" to the ADW 511 and to save it there.
Solution:
First save "NONAME" file on the PC under "Project" > "Save
as" (input of new filename) and then send to the ADW 511.
bmp 89
Occur when:
an attempt is made to save an opened file under an existing file-
name with "Project" > "Save as".
Solution:
If existing file is to be overwritten = "Yes"
Cancel with "No", input new filename and then save.
bmp 90
Occur when:
No program selection (selector switch position 8 or 9) was made in
"ADW511" > "Send configuration data".
Solution:
Click on program 8 or 9 in the window "Send data to ADW 511" program
selection, and then click on "Send".
bmp 91
Occur when:
Possible input value in the window "System Parameters",
"Polling Time", "Logger Time" is exceeded or not reached.
Solution:
Input the desired value within the range stated in the warn-
ing window (according to adjacent example).
bmp 92
Occur when:
Dialogues which are still open are displayed on the screen when
you click on "Documentation" > "Print Preview" ("Edit" > "Project
Data" menu).
Solution:
Close "Project Data" window with "OK" or "Cancel" and input
"Print Preview" command again.
bmp 93
Occur when:
Dialogues which are still open are displayed on the screen when
you click on "Documentation" > "Print Project Data" ("Edit" > "Proj-
ect Data" menu).
Solution:
Close "Project Data" window with "OK" or "Cancel" and input "Print
Project Data" command again.
bmp 94
8.4 Information
Occurs when:
the ADW 511 was successfully reset to the standby state after input
of "ADW 511" > "Reset ADW 511" (no alarm/fault).
bmp 95
Occurs when:
the data stored in the ADW 511 were successfully transmitted to
the PC with the command "ADW 511" > "Load config. and project
data". The program number with the associated system parame-
ters (configuration data) is displayed (set selector switch position
in ADW 511).
bmp 96
Occurs when:
the newly defined system configurations were successfully
transmitted to the ADW 511 with the command "ADW 511" >
"Send configuration data". The selector switch position (pro-
gram number) to be set in the ADW 511 is displayed.
bmp 97
Occurs when:
the defined project data were successfully transmit-
ted to the ADW 511 with the command "ADW 511" >
"Send project data".
bmp 98
8.5 Inquiries
Occur when:
edited projects which had not been saved are still open on
exiting the program with "Project" > "EXIT".
Solution:
bmp 99
"Yes" second window appears, "Yes" the change
is saved under the name shown in the window
"No" the change is discarded and not saved
"Cancel" the system does not exit from the PC pro-
gram and the change can be saved under a new name
before "EXIT" is input again ("Save project as").
bmp 100
Occur when:
open projects (dialogues) are present on exiting the pro-
gram with the input "Project" > "EXIT".
bmp 101
Occur when:
changes which have not yet been saved are open on
inputting "Project" > "Close".
Solution:
"Yes" the change is saved under the name shown in
the window
bmp 102
"No" the change is discarded and not saved
"Cancel" the project is not closed and the change
can be saved under a new name before inputting
"Project" > "Close" again ("Save project as").
Occur after:
the input of "Project" > "Delete", before the data are
finally deleted.
Attention:
Clicking on "Yes" causes the project shown in the win-
bmp 103
dow to be finally deleted!!
Occur on:
input of "Help" > "Index" or "Help" > "Using Help".
These two help options have not yet been imple-
mented.
bmp 104
9 Further documents
Art. No. HEKATRON Art. No. SECURITON
Data Sheet for Transafe ADW 511 7001856 T 138 004
Technical Documentation for Transafe ADW 511 7001855 T 138 005