5, SEPTEMBER/OCTOBER 1981
power, and spike voltage depend on the amount of delay and (b)
the capacitance value; also, the optimum control of the delay Fig. 1. Two typical current-source inverters. (a) Autosequential com-
under various operating conditions seems to be not so simple. mutated inverter. (b) Third harmonic auxiliary commutated inverter.
In addition, the allowable range of load variation and its oper-
ating frequency in THACI are about one-third those of ASCI. In contrast, the current through the commutating capacitor
In a specific or limited range operation, however, THACI may in ASCI delivers power to the load, which occurs smoothly
be a good choice for its simplicity in configuration. even in the consecutive commutation where a new commuta-
The wide difference in the operating range between THACI tion starts at the end of one. A wide range of operation is
and ASCI is caused mainly by the difference of the paths of thus possible in ASCI. However, in this case, the operating
the dc current flowing through the capacitor during commuta- range as well as the spike voltage are also functions of load
tion; namely, this current passes through the load in ASCI and capacitance value, since commutation and phase-to-phase
while it bypasses the load in THACI. Therefore, the operating current changes occur at the same time while the commutating
range becomes narrow in THACI due to the capacitor charging capacitors are discharged and charged by the dc current. These
time in addition to the delayed gating. This may be the com- situations necessitate some compromise in the choice of the
mon problem in all circuit configurations where the current capacitance value among the various factors involved. Another
through the commutating capacitor bypasses the load. shortcoming is that it requires a number of commutating
capacitors and high power diodes and/or high voltage silicon
Paper IPCSD 80-8, approved by the Static Power Converter Com- controlled rectifiers (SCR's).
mittee of the IEEE Industry Applications Society for publication in In the inverter scheme proposed in this paper, the operating
this TRANSACTIONS. Manuscript released for publication May 19, range, which is limited in ASCI and THACI for the reason
1981. described above, is extended by employing a different com-
The authors are with the Department of Science, Korea Advanced
Institute of Science, P. 0. Box 150, Chongryangni, Seoul, Korea. mutating scheme, namely the dc side commutating (dc-sc)
Line
F i e i
method. In the new dc-sc circuit, not only the polarity of the Complete and In- Voltage Limit and
commutating capacitor reverses at high speed for turning off complete Controlled Energy Rebound Circuit:
the main SCR's and eliminating the time of capacitor recharg- Rectifier
ing, but also the regenerative capability of the inverter is pre-
served. Also employed in the new inverter is a novel energy ~P1 JrlP b zP5 Li *
rebounding method, the main purpose of which is to limit the
peak voltage, making possible the use of low voltage SCR's. 3+ o
Combining the dc-sc and the energy rebound circuits in Line
Power
such a way that their respective functions be kept independ-
ently, a novel six-step CSI is obtained, which allows both rh FP
motoring and regenerating operations. A new and economic
twelve-step CSI will then be presented in which one auxiliary
inverter with a power requirement of about one-half that of (a)
the main inverter is added while the dc-sc circuit and the en- DC- side
ergy rebound (ER) circuit operate for both inverters. Proto- Commutating Circuit nverter Load
types of both six-step and twelve-step inverters have been de-
signed, constructed, and tested; oscillograms of the experimen-
tal results are shown.
II. A NEW SIX-STEP CURRENT SOURCE INVERTER
A. General
It is not a new idea in commutating circuits to reverse a
capacitor voltage at high speed and thereby turn off associated
SCR's; actually this method is employed in the McMurray (b)
inverter, chopper, and other circuits. However, several con-
siderations must be made to apply this scheme to CSI's with- Fig. 3. New six-step current-source inverter circuit. (a) Controlled
rectifiers and energy rebound circuit. (b) DC side commutating cir-
out loss of their advantages. Fig. 2 shows the block diagram of cuit and inverter.
the new six-step CSI, while Fig. 3 shows its complete circuit
diagram. The distinctive features of the new inverter are, as the dc-sc method is applied to CSI's. In order to limit the spike
can be seen from these figures, employment of the dc-sc, and voltage and at the same time increase the inverter efficiency,
addition of the peak voltage limit and ER circuit. The dc-sc the spike energy must be fed back to the source. This and the
method has relative merits and demerits as compared with the connection of free-wheeling diodes have to be done without
branch commutating method [5] -[6]. In the conventional affecting the regenerative mode operation of the motor. For
dc-sc inverters a free-wheeling diode is simply connected back- this purpose a new ER circuit has been devised. With this
to-back to each main SCR. This simple connection may fail circuit and a simple control, it is possible to increase the in-
when applied directly to the CSI, since regenerative capability, verter efficiency using low voltage SCR's.
one of its advantages, will then be lost. However, the free-
wheeling diodes can not be eliminated, since they play a cru- B. Operation
cial role in the commutating transient, during which phase- Fig. 4 shows the sequence of topology modes starting with
to-phase change of the motor current occurs right after the a state where SCR's T1 and T2 are conducting. Typical wave-
main SCR's are blocked by the operation of the commutating forms of voltages across capacitors C1, C2, and C4, as well
circuit. Also, the associated high spike voltage is inevitable. as currents through C2, diode D 1 , and phase currents are
This necessitates some means to limit the spike voltage when shown in Fig. 5, in which the various intervals correspond to
526 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-17, NO. 5, SEPTEMBER/OCTOBER 1981
(a) (b)
(c) (d)
(e) (f)
(g) (h)
(i)
Fig. 4. Sequence of topology modes of six-step CSI.
CHO AND PARK: CURRENT-SOURCE INVERTERS 527
Specifically, the phase-to-phase current, which has kept
almost constant until the end of interval G, starts changing as
it charges capacitor C4. Thus, the capacitor voltage continues
to rise very slowly, if C4 is sufficiently large, until the phase A
current becomes zero and the phase B current reaches Id.
After the end of the transition state, T3 maintains a constant
conduction current as T2 does; this state continues until the
next commutation begins.
For convenience, S3 is turned on during interval H to sup-
ply any energy loss (from the dc source consisting of D1 6,
D1 7, D1 8, and C3) to capacitor C2 in order to insure stable
and continuous operation. The control sequence for the above
cycle is S1 turned on (interval B); S2 turned on (interval C);
T2 turned on again (interval F); T3 turned on (interval G);
and S3 turned on in any interval G to I.
Figs. 6 and 7 show the sketches and oscillograms, respec-
tively, of the voltage and current waveforms during the com-
plete cycle of operation for the six-step inverter. As is seen
Fig. 5. Voltage and current waveforms for each mode. Intervals A, B, from Fig. 7, the voltage spikes are limited but still relatively
* -, I corresponds to modes (a), (b), , (i) in Fig. 4. high because the experiment was done at low voltage. This
fact will further be examined later in connection with the ER
respective topology modes. (The operation of the ER circuit, circuit operation.
which is included in Fig. 4 as a block, will be described later in
connection with Fig. 8.) C. Distinctive Features of the DC-SC Circuit
The initial state with T1 and T2 conducting is shown as
interval A. Interval B starts with SI turned on. The voltage The dc-sc circuit as described in the above has several
across C2 reverses polarity and SI turns off before the end of advantages over the conventional ones. First, a wide range of
interval B. S2 is turned on at the start of interval C, which operating frequency is possible due to the fact that the com-
places C1 and C2 in series with L1 and S2. When voltage mutating interval is determined mainly by the SCR turn-off
across C1 becomes zero, interval D begins. The new conduc- time and is almost independent of the load current, since the
ting paths from the main and commutating buses are now voltage on C2 reverses at high speed and a small capacitance
formed with diodes D4, D5, D7 -D1 turned on.
0 suffices for C1 .
The forward drops of diodes D7 and D8 determine the Second, a very wide range of load variation is allowed.
cutoff of T1 and T2 which is the start of interval E when all This can be explained as follows. The voltage on C2, which is
diodes D1 to D6 conduct through the commutating bus and necessary for commutation, is determined by the voltage on
D7 and D8. The current flowing through L1 in interval E C3 due to the role of S3. The voltage on C3 is maintained al-
consists of the dc current from the main bus and the current most always at a maximum level, with a slight variation de-
from the commutating bus which contains the load current. pending on the converter output voltage, since it is supplied
Therefore, the commutating circuit must be capable of hand- by the incomplete bridge rectifier consisting of diodes D1 6-
ling twice the dc current. The voltage across C2 becomes posi- D1 8 and SCR's P2, P4, and P6. Thus for simplicity, C3 is re-
tive again by the inductive current through L1, which then de- placed by a dc source in Fig. 4. As a result, stable operation
creases with the commutating bus current. As the bus current is secured even at low voltage and high current such as in the
decreases to the load current, T2 turns on again and interval motor starting. Even in the extreme load conditions, open or
F starts. In interval F, the current through the commutating shorted load, the commutating circuit operates independently,
bus continues to decrease. After it becomes zero, Cl begins and temporary failure such as caused by noise turn-on of the
charging as the L1 current decreases below the load current, main SCR's can be immediately recovered.
when interval G starts. In interval G, T3 is newly turned on The third distinctive feature of the proposed dc-sc circuit
and the sum of the current through C1 and L1 is almost equal is that it does not affect the regenerative operation of the in-
to Id, where the maximum rate of dv/dt is given by Id/Cl. verter. Specifically, the commutating circuit is isolated from
This value can be large as long as it does not exceed the the rest of the system when the motor operates as a generator,
dv/dt rating of the main SCR's at full load. Actually, C1 can since then the voltage polarity of the p side in Fig. 3 becomes
be much smaller than C2 but the value must be determined minus while that of the n side becomes plus. Hence, diodes Dg
considering some other factors involved. When the voltage on and D1 0 are turned off. In other words, by the presence of Dg
Cl equals the voltage on C4, D8 and Dg stop conducting, then and D10, both motoring and generating operations are pos-
D3 and D1 start conducting and charging capacitor C4 in sible; at commutating operation they are conducted to turn
interval H. off the main SCR's, and at regenerative operation they are
528 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. IA-17, NO. 5, SEPTEMBER/OCTOBER 1981
tors can even be wound on the same core due to the actioni of
the bridge diodes, as described above.
Both the main and the auxiliary SCR's, which have been
in the conducting state, are turned off simultanieously by the
31' operation of tlhe commutatinig circuit. Diodes Da1-DDa6 can
AC -
be of a very small capacity, since they are used only to secure
stable turn-off of the auxiliary SCR's. They do this by forming
a demagnetizing current path during the commutating initerval
for the current balancing inductor, which has been nmagnetized
(a) by the motor EMF during the operation of the auxiliary in-
verter. Also, the power rating required for the auxiliary SCR's
is about one-half that for the main SCR's, since as can be seen
from Fig. 14, the ratio of conduction intervals is one to three,
3, while the conduction current magnitudes are the same in the
AC two sets of SCR's. Finally, the power rating required for the
bridge diodes is one-half that for the auxiliary SCR's, since the
current through the auxiliary SCR is bisected in the bridge
arms. Fig. 16 shows the oscillograms of the phase voltage and
the line current obtained with an experimental twelve-step
Fig. 11. Two typical configurations of twelve-step CSI. CsI.
C. Distinctive Features
The auxiliary inverter, which is added to the six-step CSI
in order to obtain a twelve-step waveform, does not require
a separate commutating circuit; one dc side commutating cir-
cuit controls simultaneously both the main and the auxiliary
inverters. The current balancing inductor in the auxiliary in-
verter can be of a very small size compared with the one of
DSCI. Power rating required for the auxiliary SCR's is about
one-half that for the main SCR's, and that for the bridge
diodes is further reduced. Furthermore, all components can
be low voltage devices due to the particular peak voltage
Fig. 12. Block diagram of new twelve-step CSI. limit and energy rebound method employed. Firing control of
the SCR's in the proposed twelve-step CSI is simple, since only
verter part consists of a main inverter, which has the same con- the alternating ON time durations for the main and auxiliary
figuration as in the six-step CSI, and an auxiliary inverter, SCR's need to be considered in timing the firing pulses. This
which has quite a different configuration. Fig. 14 shows the is different from the situation in DCSI where a rather elabo-
firing sequence of the proposed twelve-step CSI, from which rate firing control is needed, taking into account the difference
we see that the main SCR's and the auxiliary SCR's are turned of the power delivered by two CSI's.
on and off altemately and a half-current step is formed in the In all, the proposed twelve-step CSI has an economic ad-
line current in the conducting state of each auxiliary SCR. vantage and can be used for low and medium power appli-
Fig. 15 shows the conducting state at the positive half- cations as well as for higher power applications, where the
current step for one branch of the auxiliary inverter. Each harmonics content is the main concern.
branch of the auxiliary inverter consists of a set of bridge By slightly modifying the firing sequence, namely, by send-
diodes and a pair of inductors. As can be seen from Fig. 15, ing the gating pulses only to the main inverters, the twelve-step
the role of the bridge diodes is twofold; it makes a current CSI can be smoothly converted to a six-step CSI. This is ad-
path through B2 I and B22 when A1 is ON and through B2 3 vantageous at high frequency operation of the motor, since
and B24 when A4 is ON, while is isolates points A and B, the commutation frequency is halved. Fig. 17 shows smooth
causing no magnetization of L2 1 and L2 2, when both AI and transition of twelve-step to six-step conversion and vice versa.
A4 are OFF. In this way L21 and L22 play the same role as
the current balancing inductor in Fig. 11 (b) when one of the V. CONCLUSION
auxiliary SCR's is ON. L21 and L22 are wound on the same Novel six-step and twelve-step inverters with dc side com-
core with no air gap, as are (L1 1, L 2) and (L31 ,L32). Thus mutation and energy rebound features were designed, con-
one more core is required compared with Fig. 1 1(b). However, structed, and tested in the laboratory with the expected
the core size can be considerably reduced, since in Fig. 14 results obtained. The proposed inverters have improved re-
current flows through the current balancing inductor during liability and capability of very wide range operations in terms
only one-sixth of the period, while in Fig. 1 l(b) current flow of load variation and operating frequency, and they can be im-
continues through the whole period. The three sets of induc- plemented with low voltage SCR's and hence at a lower over-
CHO AND PARK: CURRENT-SOURCE INVERTERS 53
Load
Fig. 13. Circuit diagram of new twelve-step CSI.
FE I/I// A/
(a)