Escolar Documentos
Profissional Documentos
Cultura Documentos
3.1 Introduction
Nowadays, electric power systems are under growing stress, more complex to
operate, and more unstable with unscheduled/uncontrolled power flows and higher losses
[49]. The reason behind is higher demand and less generation as well as constraints on
the construction of new lines. On the other hand, a number of high-voltage power
systems are operating below their thermal ratings because of voltage and stability limits.
Conventional electric power delivery systems, in most cases, are not designed to handle
the control requirements of complex, highly interconnected power systems [50]. This
situation necessitates the review of traditional power delivery methods and practices and
the creation of new concepts. These steps would allow the use of existing lines up to their
full capabilities without reduction in system stability and security [51], [52]. Another
reason that is forcing the review of conventional power transfer methods is the tendency
of modern power systems to follow the changing global economy [53]. Leading trend of
Deregulation of electric power industry requires flexible control of power flow that
equipment that may be used in high voltage systems [55]. The power electronics
39
involvement in power system has a long tradition. It has been in use for high voltage
converters allow the power flows as per operator actions. Hence HVDC line can be used
to its thermal capacity. However, HVDC is expensive for general use, and is only
economical when power systems in different regions separated by long distances are
interconnected.
The parameters and configuration of network are approximately fixed and the
network is slow in response to unforeseen events and is difficult to deal with system load
flow control required in terms of speed and versatility [56]. Energy Management Systems
require fast on-line decision making ability from power system equipment. However, the
mechanical switched equipment in power system can not perform this job. In this
scenario, concept of flexible ac transmission system (FACTS) was presented for the long
term development of power systems of the future [57]. This power electronics based
concept involving switching equipment and controllers was introduced by the electric
power research institute (EPRI) in the late 1980 [58], [59]. The main purpose of FACTS
is to bring a system under control and to transfer power in required network configuration
[60], [61]. It proposes that power in a transmission line can be controlled by varying
three parameters namely impedance, voltage magnitude and voltage angle difference
between the ends of the line [55], [62]. Maximum power flow can then be limited to
transmission line rated thermal limit capacity if less power flows on it or under
contingency conditions when this line is expected to carry more power due to the loss of
parallel line.
40
Just like the use of FACTS devices to solve voltage stability problem and attain cheap
power transfer, the application of power electronic devices can also be effective for the
power distribution systems to enhance the quality and the reliability of power delivered
to the consumers. A compact solution to the present issues that are seen by the utilities
and power distributors can be offered by custom power technology that offers fast
response for the benefit of a customer or group of customers. Custom power (CP)
reliability of electrical energy supplied to consumers in the form of less interruptions and
small voltage variations [52]. Hence if this technology is appropriately applied then all
the industrial, commercial and domestic customers may benefit from it.
The term power quality involves all possible circumstances in which the waveform of
the supply voltage (or load current) differs from the sinusoidal waveform at rated
frequency with amplitude corresponding to the rated rms value for all three-phases of a
three-phase system [63]. The PQ disturbances involve sudden, short duration deviations,
e.g. impulsive and oscillatory transients, voltage dips, voltage swells, short interruptions,
as well as steady-state deviations, such as harmonics and flicker [18]. However, survey
results pointed out that interruptions of more than 90% in the industries are due to
voltage sags [64]. Generally, PQ issues are either related to the quality of supply voltage
and those related to the quality of the current drawn by the load.
Besides the other causes, voltage dips and interruptions are the main reasons related
to supply voltage issue. These are usually caused by faults in the power system and may
41
industrial plants, where tripping of critical equipment can bear the stoppage of the whole
production with associated high costs [65]. One can claim that in this situation, it is the
source that disturbs the load. The second issue is related with low quality of the current
drawn by the load. In this situation, it is the load that disturbs the source. Due to these
two reasons, there is an increasing trend to utilize the devices that serves to compensates
PQ events, particularly that are based on power electronics called Custom Power
Devices [66], [67]. These devices have the ability to provide remedial measures to PQ
problems. Hence, load voltage can be regulated which results in smooth and clean power
Fig. 3.1 shows basic types and commonly used configurations of custom power
devices (CPDs). Main categories of CPDs are compensating type and network
reconfiguring type.
Compensating type CPDs include the static series compensator (SSC), reactive
power and harmonic compensation devices and backup stored energy devices.
42
Fig. 3.2 Schematic diagram of a DVR with its main components.
Fig. 3.2 shows series connection of DVR between the utility bus and the load bus. It is
connected in series between the utility bus and the load bus as shown in Fig. 3.2. This
converter (VSC), passive filter and a series connected transformer. The VSC utilizes
insulated gate bipolar transistors (IGBTs). It is supplied from an energy source, and
provides compensated AC voltage with the help of PWM modulator. A passive filter is
used to suppress the switching harmonics and corrects the shape of injected voltage.
Connection of DVR with the distribution line is made through an injection transformer
that is connected in series with the line. The main purpose of it is to mitigate sag/swell,
reducing harmonic and transient voltages in the supply and protecting critical loads from
43
compensate for the variations in the supply voltage. As DVR is series connected device,
hence it may serve as an active series filter [69], [70]. The basic function of a controller
sag/swell etc; computation of the correcting voltage; generation of trigger pulses to the
anomalies in the series voltage injection; and termination of the trigger pulses when the
Even though this device has same structure as that of static synchronous series
compensator (SSSC), the operating principles of the two devices differ significantly.
While the SSSC injects a balanced voltage in series, the DVR may have to inject
unbalanced voltage to maintain the load voltage at the rated value in case of an
unbalanced sag in the supply voltage. Moreover, when there is a distortion in the source
voltage, the DVR may also have to inject a distorted voltage to offset the harmonic
voltage.
A. V. Jouanne and his colleagues pointed out that short-duration shallow voltage sag
duration, deep sag can be avoided by changing structure and/or operation of the power
system [73]. Usually, industrial customers do not normally have access to system or
equipment is in general the only solution left to attain the desired quality of supply
J. G. Nielson and his colleagues have reported experimental test results that were
obtained on a medium voltage (10 kV) level using a series compensator (DVR) at a
44
distribution test facility [75]. A feed forward and feed back approach has been combined
in the control circuit of the DVR to obtain good responses in case of transient and steady-
state disturbances in the supply voltage, for different types of loads. Fig. 3.3 shows the
(MV) DVR. On the experimental results, authors proposed implementation of the DVR at
both a low-voltage (LV) level, as well as a medium voltage (MV) level for the protection
of sensitive load from disturbances in the voltage. Control structure of the DVR shows
that d-q technique is used for the detection of sag. However, in this technique, the
selection of the parameters for the low pass filter (LPF) and order of the filter play a vital
role in the filter performance. Hence filtration process gets better with the increase of
filter order, but the response time gets worse and the phase-shift of the output signal
becomes bigger. Also the d-q technique takes at least one-cycle time to track the sagged
voltage [76]. Moreover, this technique indicates some differences in voltage magnitudes
and phase-shifts in the non-faulted phases. In addition, this technique does not provide
45
S.S. Choi and his colleagues have proposed a voltage sag/swell mitigation strategy in
source side voltage [23]. Authors have shown that, in case of sag in voltage energy
injection from the DVR to external system (load) takes place so that load voltage can be
restored to its rated value. However, energy is absorbed by the DVR during voltage swell
from the external system that increases the DC-link voltage of inverter. With the
strategy was illustrated using numerical examples. Simulation results have shown that
constant voltage across DC-link can be maintained only by using the zero-power
injection strategy. But, this limits the DVR capability to mitigate deep and long sags.
Moreover, dip (sag) mitigation demands injection of active power as well when load has
Fig. 3.4 Block diagram of the DVR system with proposed controller [77].
the DVR with closed-loop load voltage and current-mode control [77], [78]. They
compared their proposed multiloop control scheme with the existing open-loop control
46
scheme used in the DVR to regulate load voltage. Fig. 3.4 shows block diagram of the
proposed control system of the DVR. Authors have shown through simulation studies
and experimental tests that the suggested control technique is better than the existing
closed-loop load voltage and current-mode control has been also applied by the authors
to IDVR (Interline DVR). Mostly, the voltage-restoration process by the DVR requires
active power injection into the distribution system. The ability of a specific DVR
topology, particularly for mitigating long-duration voltage sag, depends on the energy
storage capacity of the DVR. The interline DVR (IDVR) considered in the work restock
47
The IDVR consists of numerous DVRs that are connected to different distribution
feeders in the power distribution system. The DVRs in the IDVR system have common
DC-link energy storage. When one of the DVR mitigates voltage sag appearing in that
feeder, the other DVRs restock the DC-link energy dynamically. The control strategy for
the IDVR consists of a multiloop feedback control system that uses closed-loop load
voltage and current-mode-control techniques in the two modes of operation. Hence, one
DVR in the IDVR system operates in voltage-sag compensation mode while the other
DVR in the IDVR system work in power-flow control mode. Proposed control system for
DVR-1 in voltage sag compensation mode is similar to that as shown in Fig. 3.4 except
addition of one gain block after voltage error signal. The proposed IDVR system work
efficiently when several DVRs in the system are electrically far apart. The analysis and
experimental results obtained for a laboratory prototype of the IDVR have been presented
to show performance of a two-line IDVR system that can compensate about 40% voltage
M.R. Banaei and his colleagues have also utilized IDVR for their proposed control
strategy to restore load voltage with minimum energy injection to mitigate sag [79]. Fig.
3.6 shows the proposed control strategy. However, the presented IDVR systems by M. R.
Banaei et al. and M. Vilathgamuwa et al. require at least one parallel healthy feeder that
limits the application of this system to a typical situation due to increased cost.
Chi-Seng Lam and his colleagues have addressed voltage swell and over voltage
DVR [24]. Existing DVR voltage boosting method results in a rapid rise in DC-link
voltage in case voltage swell or over voltage occurs. This may damage the storage
48
capacitors and switching devices, and raise the switching loss. This paper shows that the
minimum energy injection strategy cannot handle these problems during unbalanced
situation. A unidirectional power flow control algorithm was proposed with DVR
Fig. 3.6 The suggested control strategy for the DVR [79].
rotating speed and DC-link safe operating voltage, the proposed control algorithm can
solve reverse power flow problems in both balanced and unbalanced swell or overvoltage
situations, while the compensated load output voltage remains balanced, sinusoidal and at
a nominal value. Simulation and experimental results for unbalanced voltage swell
compensation have been presented to verify the accuracy and improved performance of
49
the proposed algorithm over existing minimum energy scheme. However, results
obtained from experimental prototype show that the swell or overvoltage is mitigated
after 50 ms by using the suggested control algorithm. This slow response by the series
device for the proposed control algorithm against swell or overvoltage phenomenon may
damage rectifier unit of rectifier supported DVR. Moreover, it affects sensitive load as
well.
Fig. 3.7 Block diagram of proposed controller for DVR system [80].
H. Kim and S. K. Sul have suggested a method to control DVR compensation voltage
[80]. In order to define tasks for the control of compensation voltage, power circuit of the
DVR has been analyzed. A control structure for the DVR has been proposed by authors
utilizing a feed-forward and state feedback based scheme. Digital control systems (DCSs)
have time delay concern. This issue in DCS of a DVR has been also discussed in the
paper. Usually, control delay in DCSs results from the sampling period, transmission
time of the sensor and the inverter switching frequency, etc. This paper has analyzed and
presented some important design guidelines for the control gains and the inverter
switching frequency of DVRs proposed controller related with the control delay and filter
cut off frequency. Fig. 3.7 shows control system block diagram for the DVR with control
50
delay. An experimental setup with complete DCS has been utilized to validate the
analysis and simulation results for the suggested theory. Simulations for the proposed
controller for DVR system show that output voltage after compensation becomes stable
and shows good dynamics only at the higher switching frequencies. The reason for is that
M. J. Newman and his colleagues have proposed feedback control strategy based on
selective harmonics elimination. It has been suggested by authors that this strategy can be
incorporated with great ease to MV DVR systems to counter voltage harmonics with
negligible effect on the dip mitigation ability of the DVR [81]. In the suggested control
scheme, harmonics in load voltage are eliminated using resonant feedback controller. The
controller is designed by adding resonant control filters to the existing PI control scheme.
verify the proposed controller for various situations, including distortion in supply
voltage, nonlinear load, and operation during voltage sag. These results show that
existing sag compensator. However, the main problem with the proposed DVR structure
in above mentioned study is that it requires separate filter to eliminate each harmonic, if
P. R. Snchez and his colleagues have presented two control systems for the DVR to
mitigate various PQ problems such as sag, voltage harmonics, and imbalance in voltage
[82], [83]. The proposed control system uses repetitive controller. Only one controller
has been used to deal with all three disturbances, simultaneously. Proposed closed loop
control scheme is shown in Fig. 3.8. Proposed repetitive controller has been claimed to
51
have a fast transient response and zero steady-state error for any sinusoidal reference
input and for any sinusoidal disturbance whose frequencies are integral multiple of the
50/60 Hz. The PSCAD/EMTDC environment has been utilized to perform the modeling
aspects required for the repetitive controller and test system. Results of simulation have
been included only to show that the DVR control approach yield excellent voltage
The other system proposed by P. R. Sanchez is based on the repetitive control for a
medium-voltage (MV) applications and offer advantages, such as the flexibility in the
converters find its application in DVR to ameliorate voltage sags as well as other PQ
DVR require more versatile control system than the classical controller, such as the PI
regulator. The developed control system consists of three subsystems: the first one
eliminates the resonance peak of the filter used in the converter output voltage; while the
second one is the repetitive control, which improves the transient response and zero-
52
tracking error in steady-state for any sinusoidal reference and for any sinusoidal
disturbance whose frequencies are integral multiples of the 50/60 Hz.. The third
subsystem maintains constant, balanced voltages in the five level flying capacitors.
PSCAD/EMTDC environment has been used to implement the control system, together
with the DVR. Detailed simulation results with an MV test system shows that the control
scheme developed in this paper performs very effectively and provides excellent voltage
regulation. However, the proposed control scheme is complex and its hardware
implementation is difficult.
B. J. Quirl and his colleagues have addressed DVR control strategies that eliminate
propagation of voltage sag or phase-shift to the load [84]. Voltage sag with phase jump is
in some situations more apt to load tripping. Two open loop control methods that protect
the load from voltage sag with phase jump have been explored through simulation in
SIMULINK. Space vector control has been used in the control scheme of the DVR. Fig.
3.9 outlines the control methodology for the DVR. The first method is described as pre-
sag to in-phase compensation and monitors the supply such that initial pre-sag conditions
are used, but it adjusts approximately after 25 ms to inject a voltage that is in phase with
the new supply voltage. This method includes compensation during the sag and after the
sag has left the system. The second method makes use of the condition before sag.
Ideally, with this approach, the load voltage remains same as before voltage sag. These
compensation methods are very effective in keeping the load voltage at the correct level
and phase-shift free. The benefit of the pre-sag to in-phase compensation is that the
magnitude of injected DVR voltage is finally minimized for constant load voltage
53
magnitude. This can be beneficial; however, in case of deep sag, the voltage rating of the
DVR is a concern.
In case of the simulated sag, both methods need active power injection, but the pre-
sag to in-phase compensation involve the development of less instantaneous active power
towards the end of the sag than that of the pre-sag compensation. However, the pre-sag to
in-phase compensation also includes active power injection after the sag, while the pre-
sag method only requires compensation during the sag. The important advantage of the
pre-sag method is that phase-shift is not seen by the load. However, this would be the
best method if the sag duration is relatively small and power drain on the DVR is not a
concern.
Fig. 3.9 Open loop control methodology for the DVR [84].
filters to operate a DVR for improving quality of power delivered to load has been
presented by S. A. Saleh and his colleagues [85]. These passive filters are used to detect
any disturbance which can affect the smooth power flow to critical loads in an electric
54
distribution system. Detection of disturbance in system voltage is sensed by extracting
frequency components (high and low) by using filters (high and low pass). It has been
shown that third-order Butterworth passive filters (BWFs) can provide the response
comparable to DWT- associated filters. Simulations studies using the proposed DVR
system have been performed to show mitigation of transient voltage sag as well as
experimental test results have confirmed the simulated features. The simplicity and
response time simulated features make the proposed DWT-operated DVR system feasible
to enhance the quality of power delivered to load under various types of disturbances.
The proposed DVR system collects the energy from the healthy feeder of utility to
compensate load voltage in case of a disturbance in the system voltage. So, the authors
have to analyze the voltage swell and overvoltage phenomena in utility voltage for their
system as well, otherwise these PQ events will damage the rectifier unit in rectifier
supported DVR.
H. K. Al-Hadidi and his colleagues have introduced a design of a DVR that is based
thyristor-switched inductor [86]. Sag mitigation usually demands active power injection
from the DC storage energy capacitors for high power factor loads. In contrast, for
sufficiently low power factor loads, the zero or minimum active power injection
technique can be utilized to compensate long duration sags. Proposed DVR topology has
explored this feature by using an additional branch that includes an inductor in the
55
decrease the power factor during sags. In this way, operating limit of DVR and its sag
mitigation duration is increased. This inturn increases the DVR operating limit and
mitigation interval. Fig. 3.10 shows the proposed control structure of DVR. The proposed
DVR control system has the ability to reduce the active power injection and, thus,
increases the sag mitigation limit in situations where sag mitigation also requires active
power injection. Operation of the new device for the DVR proposed strategy has been
the feasibility and the practicality of the suggested DVR control system, however,
presented simulation results show that load voltage after sag mitigation takes 3-5 cycles
to reach steady-state value. Hence settling time for the load voltage after sag mitigation
E. K. Kenneth Sng and his colleagues have presented the control of a transformerless
and self-charging DVR using a capacitor bank for energy storage to mitigate voltage sag
[87]. The proposed DVR works without an isolation transformer for series injection.
Moreover, it is capable of self charging under normal supply conditions, without the need
for a separate charging circuit and transformer. The voltage recovery and self-charging
processes of the new restorer have been explained in detail and validated through
simulation. The study of the DC-link voltage regulation dynamics has revealed the
existence of a nonlinear element in the form of magnetic energy of the filter inductor.
This affects stability for high feedback gains. Verification of this aspect on regulator
performance and closed loop stability problem has been carried out and a cancellation
technique has been proposed. The proposed controller is simple to implement using
56
either digital or analog devices. This allows flexibility of choice in the face of device cost
or robustness constraints. Simulation and experimental results have been provided for a 1
kVA prototype to show the usefulness of the restorer design on series compensation and
the self-charging process, the effects of the nonlinear element in regulator dynamics, and
effective in enhancing stability when higher feedback gains are used. But, if uncertain
parameters are present in the nonlinear term then higher feedback gains in proposed
57
A. K. Jindal and his colleagues have investigated a rectifier supported DVR to
regulate voltage at a critical load bus of a distribution system under system frequency
variation [89]. A voltage waveform that is sinusoidal and balanced is required by the
critical load at fundamental frequency of 50 Hz. Source voltage frequency has been
assumed to change and differs from the nominal frequency of electric power distribution
system. Rectifier supported DVR has been operated such that it maintains constant
voltage at the critical load bus at system nominal frequency irrespective of the frequency
of the source voltage. Authors in their simulation results have shown that when load
voltage frequency differs from source frequency, then the critical load active power
demand is met by the DVR. Active power requirement of DC-link of the DVR is served
with the help of an uncontrolled rectifier. This rectifier takes active power from the
distribution feeder itself. To compensate for frequency mismatch, this rectifier also
provides a path for the real power required by the critical load to flow. A simple
frequency estimation technique has been presented that makes use of a moving average
process with zero-crossing detector. Analysis and simulation studies have been carried
out using PSCAD/EMTDC. Simulation results have shown that, when frequency of the
injected voltage is identical to that of the source voltage, the DVR voltage injection
decreases significantly and voltage is fully controlled across the critical load. However,
in the proposed scheme some variations in the zero-crossing of the average voltage
continue for some cycles. But, if frequency is permitted to adjust with the change in the
estimated frequency during this period, the load side voltage will by no means be able to
obtain steady-state value and the average will also not turn to zero.
58
A new reference voltage generation algorithm for a DVR has been presented by A.
Ghosh and A. Joshi. It uses the method of instantaneous symmetrical components [90].
Series injection of reference voltage in distribution feeder is made by a VSC. It has the
ability to regulate load voltage at its rated value against harmonics or imbalance in the
to facilitate the DVR to produce balance steady-state voltage within a half-cycle. The
proposed algorithm does not require injection of active power from the series
algorithm has been investigated and verified using computer simulation studies. In it,
dynamic voltage restorer has been assumed as an ideal voltage source which tracks the
reference voltage. The DVR algorithms discussed in this work are suitable only for
systems with balanced and linear loads. However, the authors in another work have
presented the operating principles, structure, and control of a DVR that is supplied by a
DC capacitor to protect sensitive but unbalanced and/or distorted loads [91]. Harmonics
components in the source and load currents for the desired task have been reduced by
allowing them to pass through a low impedance path. This path is provided by a shunt
capacitor filter in the proposed hybrid structure of an ideal DVR. Three different DVR
configurations have been examined for performing the desired task. However, best
performance is obtained when series device is connected with the shunt capacitor.
simulation results. However, it has revealed that DVR success depends on the choice of
shunt capacitor and DC-link capacitor. Their values must be chosen carefully. Also, the
proposed algorithm for the reference voltage generation allows variation in phase-angle
59
of load voltage; hence above DVR system cannot be used for the loads that are sensitive
to phase-angle shifts.
Il. Y. Chung and his colleagues have proposed a new method of voltage restoration
that is based on load voltage tolerance to inject minimum energy during DVR
compensation period [92]. Generally, voltage tolerance range of almost all the
distribution system load varies. However, capability of DVR to inject real power to
mitigate voltage sag is limited. Usually, phase advance technique is used for the DVR to
supply minimum energy during sag compensation. In this technique, load voltage phase-
angle serves as a control parameter in phase advance technique. However, this technique
has limited capability to optimize energy injection to mitigate deep voltage sag. The
proposed method utilizes phase advance angle as well as magnitude of load voltage in the
voltage tolerance area in order to optimize injected active power of DVR. In addition,
authors have also proposed objective function, equality constraints, and inequality
constraints in order to have control parameter. Simulation for the proposed method for
several cases is performed using EMTDC/PSCAD package to verify that the proposed
technique has a merit to optimizing injected real power compared with existing methods,
especially, during deep sag. However, load voltage phase still varies as is the case in
phase advance method which restricts its applications to locations where load is not
of a DVR model for use within distribution system to provide ride-through capability for
an AC variable speed drive under voltage sag conditions [71]. It has been suggested that
presented closed loop control system can be utilized as a potentially promising design
60
method for efficient regulation and control of the DVR. Fig. 3.11 shows the presented
control scheme for the DVR. However, only simulations for the proposed DVR model
and its control system have been presented using electromagnetic transients simulation
program (EMTDC). It does not guarantee that integrated power electronics environment
can be used for successful implementation of the DVR. Experimental investigations are
required to validate the proposed DVR model and its control system.
Literature review reveals that there are numerous methods to inject DVR
These methods are: pre-sag compensation, in-phase compensation, and phase advance
method [93]-[96]. A brief description of these methods is also provided in chapter IV.
The worlds first DVR was installed in August 1996 at a 12.47 kV substation in
61
However, it was first installed at the Waltz test facility near Pittsburgh for full power
tests [97]. Florida Power Corporations 2 MVA VSC-based DVR provides protection to
one of the six 12.47 kV feeders at the Econ substation (230/12.5 kV) of Orlando, Florida.
This DVR is placed in service in 1996 in a high density residential and commercial area
system at Stanhope, Victoria, Australia [99]. This project was carried out to protect the
diary milk processing plant. Another installation of a DVR was done in April 1997 at the
Sappi Limited, Stanger Mill in South Africa that provides pulp to Sappis paper making
process. The DVR is supplied by superconducting magnetic energy storage (SMES) [98].
Two DVRs, each having rating of 6 MVA, 12.47 kV have been installed in July 1998 at
an important industrial place on the Salt River Project system at Phoenix metropolitan
area in Arizona. Each of these DVRs can boost a 20 MVA load as much as 30% [98]. In
April 1998 a 4 MVA series compensator is installed by Scottish Power at the Caledonian
Paper Mill at Irvine, Scotland [98]. The power to the mill is supplied by a South African
electricity public utility ESKOM. Platform mounted DVR was first installed in 1999 to
provide protection to Northern Lights Community College and several other loads in
Fig. 3.1 shows that second type of compensating CPDs are called Reactive
power and harmonic compensation devices. Generally, these devices are connected
in shunt at the load bus, with the objective of injecting a current to the load.
62
compensator (SVC), distribution static compensator (D-STATCOM) and passive or
PQ problems may arise from nonlinear customer loads such as, arc furnaces, welding
operations. Voltage flicker and harmonic problems can affect the entire distribution
feeder. Various devices have been considered to reduce the impact of these variations.
The main concept is to use dynamic capacitance and reactance to have steady-state
operation of the power system. This is particularly achieved by using static switching
devices to control the capacitance and reactance to stabilize the power system. SVC and
the D-STATCOM are the mostly used flicker mitigation devices [63]. However, series
capacitor and series line reactors are also used for this purpose. Moreover, literature
studies show that reactive power and harmonic devices have been also investigated for
flicker mitigation [101]. A capacitor in series with the arc furnace with a suitable value
of capacitance has the ability to cancel the reactance between the source and the arc
furnace. In spite of this, the risk of sub-synchronous resonance (SSR) for series
line voltage drop. They can be bypassed in order to change the compensation degree of
the line reactance [102]. Normally, it is assumed that only circuit breakers can be
bypassing devices, but nowadays thyristor-controlled series capacitors (TCSCs) are also
63
installed in distribution networks. Although they were initially intended for installation in
transmission grids but only a few of them has been applied. They increase the voltage
stability limit through reduction in the line reactance and maintaining constant voltage
irrespective of quick load changes. Hence, they can decrease power losses and line
voltage drop in a distribution feeder. However, constant voltage can be maintained only
in a certain range of power change, depending upon the equivalent reactance of series
By inserting a linear reactor in series with the arc furnace, the short-circuit current of
the furnace is reduced owing to the higher total impedance. Moreover, increased
reactance in the circuit results in larger phase-shift between voltage and current and
hence a more stable electric arc in the furnace. But, the selection of series reactor must be
done carefully as high value of the series impedance will decrease the furnace power and
thereby the steel production rate. Saturatable reactors in series have also been used to cut
current peak due to for instance short-circuit in the arc furnace [103]. It has been
observed that independent usage of series capacitors and series line reactors without
thyristor control have no effect on voltage sag, swell or phase jumps mitigation.
However, Thyristor controlled series capacitors and reactors can be used for voltage sag
mitigation as discussed in section 3.2.2.1 under heading Solid State Current Limiter and
The SVC can be used for AC voltage control by generation and absorption of reactive
power through passive elements. It can also be used for balancing unsymmetrical loads.
64
number of thyristor switched capacitor (TSC) branches as shown in Fig. 3.12 [52]. In
addition to TCR and TSCs branches, VSC circuit also contains tuned filters to suppress
harmonic current from flowing into the AC system. Moreover, there are firing and
The SVC is connected in shunt to an AC line through a step down transformer. Due
to this arrangement, the SVC has the ability to generate continuously variable reactive
power in a specific range, and the size of the TCR is limited to the rating of one TSC
branch. Evidently, the reactor size limits the power that can be absorbed in the inductive
range. SVCs placed closed to load can be very effective in providing voltage support,
thereby avoiding voltage instability [5]. Although, electrically switched shunt capacitors
(TSCs) in SVC branch can supply variable reactive power to the system, however,
65
reactive power output of a capacitor is proportional to the square of the system voltage
The SVC has been found in applications such as power line compensation [104],
compensation of traction system [105], reducing disturbance from rolling mills [106] and
arc furnace compensation [107]. The potential to absorb changes in reactive power makes
to some extent the SVC appropriate for flicker reduction. In this situation, the SVC
usually consists of a TCR branch with a filter. An SVC installed together with an arc
furnace not only reduces the flicker, but also, increases the steel production and its
quality due to stabilized AC voltage [108]. However, SVC has a low control update rate.
Therefore, the capability of the SVC to mitigate flicker is limited. Also, it has been
advanced static VAR compensator (ASVC) [109]. The results of this investigation have
shown that the ASVC can completely compensate shallow sag, and considerably lift the
sagged voltage during deep sag. However, due to opted sag mitigation strategy, post sag
voltage overshoots. Response time of ASVC for sag mitigation has been measured about
two and half cycles of the power frequency. This shows that response of the device is
quite slow and some of the sags cant be mitigated in this time frame according to
was further investigated that phase-angle jumps can disturb the working of the ASVC,
SVC sag mitigation capability is strongly dependent on its ability to provide variable
reactive power to the system. However, in case of a sag mitigation for high power factor
66
loads where active power contribution is also required to compensate sag then SVC lacks
in its operation to achieve the desired sag mitigation task. Hence, due to the pitfalls
associated with SVCs, the D-STATCOM was introduced into the market as an alternate
for it.
required for flicker mitigation purpose. A PWM operated VSC utilizing IGBTs and
shunt-connected synchronous machine has some similarities with the STATCOM, but
does not contain power electronics. The capability of the synchronous machine to supply
large reactive currents enables this system to lift the voltage by 60% for at least 6 s.
used in the context of FACTS at the transmission level [110], custom power controllers
at the distribution level and in end users electrical installations [111]. A typical
STATCOM has emerged as a promising CPD to provide not only for voltage sag
voltage regulation, load balancing, power factor correction, harmonic filtering, and
C. K. Sao and his colleagues have provided a bench mark D-STATCOM that
67
it has offered DC-bus voltage control, power factor correction, and AC voltage
correction mode and AC voltage regulation mode has been analyzed through
excellent match between the experimental and simulated results. This provide a
(PLL) technique is used for voltage sag detection and mitigation. However, this
technique provides good results only if voltage sag is not coupled with phase-angle
jump.
Fig. 3.13 Schematic representation of the D-STATCOM as a custom power Device [112].
68
Fig. 3.14 Complete D-STACOM control system [114].
STATCOM for the voltage or current control mode, load compensation at a weak AC
bus, and voltage regulation for a mini custom power park [113], [115]-[116]. In the
voltage control mode D-STATCOM has forced the voltage of a distribution bus to be
balanced sinusoids. Moreover, it has cancelled distortion caused by the load, such that
current drawn by the compensated load is pure balanced sinusoid in the current control
adopted and its suitability has been verified through simulations for the voltage and
69
weak AC buses will result in distortions in the line current or the voltage at the point of
common coupling. The line current distortion has been eliminated using the fundamental
voltage of the PCC, but the distortion in voltage cannot be eliminated without adding a
filter capacitor in parallel with the D-STATCOM. However, the addition of the filter
capacitor generates control issues and complicates the tracking problem, as standard
controls are not appropriate to be used in this situation. A switching control scheme was
then proposed that depends on the extraction of the reference signals to solve the tracking
problem. The reference current generation scheme along with extraction of fundamental
simulation studies have been carried out to validate the performance of the proposed
scheme. However, the employed reference signal generation method also suffers from the
have used only capacitors to filter the harmonics produced due to VSC switching,
A configuration of the mini custom power park in which the voltage inside the park is
Ledwich. Fig. 3.15 shows the layout of the mini custom power park. It has been shown
maintain the custom power park (CPP) voltage for as long as 10 s when both (preferred
and alternate) feeders are lost due to any catastrophic failure. Moreover, the D-
STATCOM, backed by a diesel generator, will supply the most sensitive loads during the
total line outages, thereby nearly making them both transient and interruption free.
Simulation studies have been carried out to verify the proposed operation of the custom
70
power park, which shows satisfactory results. The above discussion clearly demonstrates
that the D-STATCOM can hold the custom power park bus voltage during moderate
voltage sag. However, for a very deep sag or fault in the preferred feeder, the supply has
to be switched to the AF through the static transfer switch (STS). Moreover simulation
results show that CPP voltage bus is regulated after 20 ms. This shows that controller
side.
storage capacitors. Three filter capacitors, one for each phase; have been connected in
control scheme realized by a dead-beat controller for the VSC has been used to control
the voltage across the filter capacitor to maintain the AC bus voltage [118]. The control
scheme consists of an outer DC capacitor voltage control loop and an inner load angle
71
control loop. Block diagram of closed loop voltage control is shown in Fig. 3.16. The
load bus voltage magnitude is chosen as nominal value, i.e., 1.0 p.u., while its phase-
angle is attained through a feedback loop that regulates the voltage across the DC storage
capacitors. It has been shown through detailed simulation and experimental results, that
the D-STATCOM is capable of regulating the PCC voltage against any unbalance and
distortion in either on the load or supply side. However, the employed dead-beat control
scheme for the VSC to maintain the AC bus voltage is very sensitive to system
parameters and it must be carefully used even if it has a very fast convergence property.
W. Freitas and his colleagues have presented a dynamic study about the simultaneous
shown in Fig. 3.17. The controllers impact on the stability performance and protection
Simulation results have shown that a D-STATCOM voltage controller can improve the
power factor controller may adversely affect the stability performance of synchronous
72
generators. Moreover, simulation results shows that although load bus is maintained at
constant value but D-STATCOM response to stabilize load voltage is poor and it took 35
cycles to attain steady-state value. This shows that D-STATCOM controller performance
needs to be improved.
Elnady and his colleagues have introduced a unified approach for the mitigation of
the voltage sag and voltage flicker by the D-STATCOM using Kalman filter [KF] and its
derivatives [120]. Also, the authors of the paper have shown the advantage of using the
Kalman filter instead of the existing tools for tracking and extracting voltage
disturbances. The Kalman filter is an algorithm used as a tool to extract both the
instantaneous envelope of the voltage sags, and to extract the instantaneous flicker level
(IFL) of the voltage flicker. The proposed modular D-STATCOM has been investigated
73
to show its ability to mitigate voltage sags and voltage flicker, even if the voltage
fast and accurate for the tracking and extraction of the voltage disturbance. Therefore,
Control block diagram of proposed algorithm is shown in Fig. 3.18. Different levels
of voltage sags and a voltage swell has been compensated simultaneously. Also, the
cyclic voltage flicker is mitigated efficiently and the IFL is reduced by approximately
60% of its value before the compensation. Consequently, voltage flicker that occurs due
to an arc furnace is transferred from the irritation region to lower than the observable
region, based on IEEE Std. 141-1993, and does not disturb the other customers.
Simulation results have been shown to demonstrate the mitigation of unbalanced voltage
sags and the compensation of the voltage flicker by employing the proposed algorithm.
74
However, the presented mitigation approach is complex and its hardware implementation
is difficult.
configuration with IGBT has been designed and the graphic based models of the D-
STATCOM have been developed using the PSCAD/EMTDC. The reactive power control
strategy for the D-STATCOM has been employed for load compensation. PI controller is
used to control the flow of reactive power to and from the DC capacitor. Phase-locked
loop (PLL) has been used to generate the switching signals for the VSC. The D-
STATCOM has been developed using DSP controller to achieve excellent overall
mitigating voltage sag caused by three phase balanced fault. However, as PLL is used for
detection and mitigation of sag in the control strategy, it provides good results only if sag
B. Blazic and I. Papic have proposed a new D-STATCOM control algorithm that
control of d- and q-axes current components [122]. The proposed control algorithm is
operating under unbalanced conditions. The problem of DC-side voltage ripple and AC-
overrated. The proposed control scheme is also suitable for high-power applications
75
using multipulse VSCs. The algorithm has been tested by carrying out detailed
simulation using PSCAD. Simulation results have shown good dynamic performance
especially in the case of unbalanced load compensation. However, as the d-q method is
used for sag detection in the control algorithm, it provides good results for balanced
voltage sag. Also use of d-q approach takes 2 cycles to detect the magnitude or envelop
of sag with a little oscillations. This shows that if voltage sag magnitude is more than
50% of nominal load voltage then according to SEMI-F47 standard, sensitive load will be
tripped as voltage magnitude should be 50% of rated load voltage from 1st cycle to 10th
cycle of supply voltage. Hence sag detection and mitigation time for the proposed control
(FCMLI) is a multiple voltage level inverter scheme that has been designed for high
voltage and power operations with low distortion. Capacitors, called flying capacitors
have been used in FCMLI for clamping the voltage across the power semiconductor
devices. A current control technique has been derived for controlling the injected current
by the FCMLI-based D-STATCOM. A new scheme has been proposed for controlling
the flying capacitor voltage such that their voltage remains constant and at the same time
produces the required output line currents under the current control operation.
the effectiveness of the proposed control scheme and the FCMLI-based DSTATCOM.
The simulation results show that the proposed D-STATCOM provides acceptable
76
performance. However, by using the proposed current control scheme, needless
switching occurs, that raises the losses in the system. Consequently the switching
The idea of using multilevel inverters or VSCs for D-STATCOM by the same authors
was then extended to load compensation with reduced switching frequency. The D-
multilevel inverter topologies are used to realize the two different structures of D-
STATCOM. They are diode-clamped multilevel inverter (DCMLI) and flying capacitor
multilevel inverter (FCMLI). A compensating technique has been derived, which uses the
feedback switching controller uses linear quadratic regulator (LQR) design that tracks the
reference state trajectories. State feedback control with a nonlinear element in the
forward path is shown in Fig. 3.19. It has been assumed that the D-STATCOM is
load through a long feeder. A switching strategy for the multilevel inverters has been
presented that ensures utilization of all output voltage states of the inverter for efficient
tracking of references. A flying capacitor voltage control scheme for the FCMLI-based
D-STATCOM has been proposed and used. It provides balanced flying capacitor
voltages and at the same time the required output voltage level of the inverter is
topologies have been carried out through simulation of a distribution network having
unbalanced and nonlinear loads. The simulation studies have been performed using
PSCAD/EMTDC environment and simulation results have shown that the proposed D-
77
STATCOMs works satisfactorily. But, performance of the FCMLI-based compensator is
DC capacitor voltage and in case, the load contains a DC part, the neutral point of the
Fig. 3.19 State feedback control with a nonlinear element in the forward path [124].
authors have investigated the effects of different loading conditions on the DC capacitor
DCMLI-based DSTATCOM have been presented. However, authors of this paper have
utilized a five-level inverter circuit configuration with DC-DC converter circuit for
equalization. Two new control circuits have been proposed for equalizing the capacitor
voltages under all loading conditions. The first equalizing circuit requires two extra
power semiconductor devices, while the other one demands the existing devices of a
equations of the proposed equalizing controller. Different control techniques have been
analyzed and compared and the performances of the two controllers are investigated.
PSCAD/EMTDC simulation environment have been used to test and validate the efficacy
of the proposed equalizing controller circuits. Simulation results have shown that both
control techniques for D-STATCOM using multilevel inverters shows that these
techniques for voltage and power operations with low distortion are complex and their
78
hardware implementation is a hard task to be carried out. Moreover, FCMLI topology
requires a large number of high voltage capacitors and full load current passes through
these capacitors at least for the part of the switching cycle. This necessitates the use of
capacitors having high capacitance and dielectric strength. But, this inturn makes them
expensive.
B. Singh and his colleagues have made a detailed investigation into the causes,
standards, and remedies of the excessive neutral current in the VSC based D-STATCOM
[126]. A reduced rating three leg voltage-source converter with a zig-zag transformer as a
D-STATCOM has been proposed for power-quality enhancement in the three-phase four-
wire distribution system. Synchronous reference frame theory (SRFT) based control for
the proposed D-STATCOM configuration has been utilized for the compensation of
reactive power, harmonic current, neutral current, load balancing and the voltage
stabilization at the point of common coupling (PCC). Fig. 3.20 shows the SRFT based
control of D-STATCOM. The zig-zag transformer is used for providing a path to the
zero-sequence current. The performance of the D-STATCOM has been validated through
SimpowerSystemsTM toolbox. Fig. 3.20 shows that d-q technique is used for driving the
reference control signals, but this technique does not provide good results for unbalanced
voltage sags. Also three phase PLL is used to synchronize load current in dqo frame with
the source voltage. However, PLL approach provides good results if voltage sag is not
STATCOM) protects the utility system from the ill effects of customer loads with the
79
assumption that supply is balanced. However, series compensator protects a sensitive
load from the distortion and unbalance in the supply side voltage. In addition, the DVR is
Fig. 3.20 Synchronous reference frame theory (SRFT) based control of D-STATCOM [126].
Current harmonics from the grid are removed by installing, passive or active shunt-
filters. Passive filters for harmonic minimization provide low impedance paths for current
harmonics. Hence, the current harmonics are fed into the shunt filters and they do not
return to the supply. Construction wise passive filter consists of series LC filters tuned
for specific harmonics, usually associated with a high pass filter used to wipe out the rest
of the higher-order current harmonics. Passive filters have the drawbacks that they are
strongly dependent on the system impedance, which depends on the distribution network
80
configuration and the loads [63]. Consequently, the system impedance, which changes
can take place between the filter and the system in the worst case. This may compel the
passive filter to act as a sink for harmonic currents from other sources in the grid.
Hence, the passive filter can be overloaded by a current higher than the rated value.
Ultimately, the capacitors of the passive filter generate reactive power that may not
necessarily be needed for power factor correction. Literature studies show that when
passive filters are used independently then they are unable to mitigate voltage sag.
Active filters or active power filters (APFs) can have connection configuration either
in series or shunt. But, a shunt active power filter configuration is preferred over series
behind a reactance acting as a current source. The VSC based shunt active filter is mostly
includes a DC-link capacitor, power electronic switches and filter inductors between the
can be used in the context of D-STATCOM [127]. However, a shunt active filter is
dependent on injection of current harmonics in phase with the load current harmonics,
hence removing the harmonic content of the line current. Active filters provide an
opportunity to choose the current harmonics to be filtered and the degree of attenuation.
The VSC size can be reduced by using selective filtering and eliminating only those
current harmonics that violate the limits given in IEEE Std. 519-1992 [128]. Active
filtering also provides a control on the power factor by injecting or absorbing reactive
power from the load. Moreover, APF can be also used to compensate nonlinear as well as
unbalanced load [129]. Unified form of series and shunt APFs is also called as active
power line conditioner (APLC) [130]. These APLCs were invented in Westinghouse
H. Fujita and H. Akagi have examined the dynamic behavior of a shunt active filter
that performs both harmonic compensation and voltage regulation within a micro-grid
[131]. S. Puengsungwan and his colleagues have presented the compensation of voltage
sag and current harmonics simultaneously using the hybrid series active filter (HSAF)
[132]. HSAF is a combination of a pure series active filter and LC passive filter.
Although, authors of the paper have investigated the use of adaptive prediction method to
detect and mitigate sag using HSAF, but no constructive theory and mathematical
modeling is presented to support the proposed concept. Moreover, only two simulation
results have been shown by the authors to support their idea that is not enough to validate
the proposed adaptive prediction system. However literature studies revealed that both
82
active shunt and series filters have not been investigated to compensate voltage swell and
phase jumps.
The literature survey shows that the D-STATCOM is proposed for compensating PQ
problems in the current whereas DVR is used for mitigating PQ problems in the voltage.
However, when D-STATCOM and DVR are combined to provide a multi purpose
compensator for solving current and voltage PQ problems then this concept has been
given the name of unified power-quality conditioner (UPQC) [63]. Although, literature
studies reveal that APLCs were rebranded as UPQC. Schematic block diagram of single-
phase UPQC is shown in Fig. 3.22. A UPQC is a device that is similar in construction to
a unified power flow controller (UPFC) [133]. The concept of UPFC, as the combination
of STATCOM and a SSSC, was first introduced in 1991 by Gyugi [134]. The UPQC like
energy storage capacitor. Out of these two VSCs, one is connected in series with AC line
while the other is connected in shunt with the AC system. A UPFC is used in a power
transmission system to provide shunt and series compensation at the same time. In the
similar analogy, a UPQC can also be utilized to provide shunt and series compensation in
a power distribution system. But, operating principles resemblance of these two devices
balanced, distortion (harmonic) free environment. Hence, a UPFC must only offer
balanced shunt or series compensation. On the other hand, a power distribution system
may have unbalance, distortion and even DC components in the load bus voltage. Hence
83
UPQC have to function with all these aspects so as to provide shunt or series
compensation [135]. However, due to its high cost, it is rarely used in its combined form.
V. Khadkikar and A. Chandra have explored a new idea to balance the load-reactive
power demand using a three-phase UPQC [136]. Usually shunt converter of the UPQC is
employed for load-reactive power compensation, whereas the series converter handles
UPQC in which both the series and shunt APFs provide the load-reactive power demand.
This property facilitates the UPQC APFs not only to share the load-reactive power
demand, but also helps to reduce the shunt APF rating, and hence, the overall cost of
UPQC. In this way series converter is effectively utilized during normal operating
condition. Power angle control (PAC) concept has been utilized to achieve the desired
objectives. Fig. 3.23 shows the block diagram that has been used to determine
84
instantaneous power angle (). MATLAB/Simulink environment has been used to
perform simulations to validate the proposed PAC theory. The proposed approach has
been also validated through scaled UPQC laboratory prototype. However, PAC approach
relies upon the extraction of power angle in real time. In order to achieve this purpose,
the instantaneous power angle () determination is carried out by extracting load active as
well as instantaneous load reactive power demand utilizing single-phase p-q theory.
However, p-q theory provides correct results for only pure sinusoidal waveforms for its
voltage and current. Hence, if load voltage or current or both, waveforms are distorted
then final results will not be according to the proposed PAC theory.
A. Ghosh and G. Ledwich have discussed the operation and control of a UPQC that
system [137]. The series component of the UPQC called DVR forces the voltage of a
distribution bus to be balanced sinusoids and free of distortion in the voltage control
mode. At the same time shunt component of UPQC called D-STATCOM performs load
distribution system bus in the current control mode. Both these objectives have been
85
attained irrespective of unbalance and harmonic distortions either in source voltage or
load current. A UPQC structure having six single-phase H-bridge converters connected to
DC storage capacitor has been examined that allows the tracking of reference current and
voltage generated to meet the objective as stated above. The generated UPQC current and
components using half cycle running (moving) averaging. Authors have also presented a
linear quadratic regulator (LQR) based switching controller scheme that tracks a
reference using the proposed compensator. Results of simulation studies have been
presented to validate the proposed structure and control of UPQC. However, working of
LQR will be stable only if the effective gain of the input nonlinearity is bounded between
and 2 [138].
operation of the UPQC with the DG [139]. The proposed UPQC system with DG consists
DC-link through rectifier is shown in Fig. 3.24. Two operation modes have been used in
the proposed system; interconnected mode and islanding mode. In the interconnected
mode of operation, DG with shunt converter of UPQC is used to supply power to the
source and load while in islanding mode, DG supplies power to the load only within its
power rating. The proposed system is capable of compensating voltage sag and swell,
voltage interruption, harmonics, and reactive power in both interconnected mode and
islanding mode. The proposed system performance has been explored using simulations
86
have verified the simulation results. The proposed UPQC system with DG has the ability
to enhance the power quality at the point of installation on power distribution system or
industrial power system. However, if the diesel generator is replaced with PV source and
STATCOM and its cost would be further increased if Diesel generator is connected as
DG with DC-link through rectifier. Hence, cost versus benefit analysis should be carried
out first to opt the proposed UPQC configuration with DG for the required application.
M. Basu and his colleagues have explained two control scheme models for UPQC, for
improving PQ of sensitive nonlinear loads [140]. Designed control schemes are based on
87
two different kinds of voltage compensation strategy for series converter (SEC) of
UPQC. These schemes are termed as UPQC-Q and UPQC-P. UPQC-Q has the benefit of
VAR sharing between the two compensators. The SEC, while injecting voltage to
mitigate the supply voltage sag, shares a part of VAR of the load and does not consume
voltage sag. But for situations where reactive power requirement is very high UPQC-Q
could be a potential control scheme for action. Besides voltage sag compensation, the
SEC control scheme of UPQC-P has the ability to mitigate the supply voltage unbalance
problem as well. But, this control scheme utilizes d-q technique to generate reference
signals for unbalanced sag mitigation that suffers from the drawback that it does not
provide satisfactory results for unbalanced voltage sag mitigation. The reason is that the
and q). These components oscillate with twice the frequency of the fundamental
frequency [141]. These oscillations in d-q components are not suitable for control
purpose. It has been observed that under balanced voltage sag condition, the load voltage
angle after compensation is not altered. Hence, the shunt converter (SHC) of the UPQC-P
does not require compensating any additional VAR created due to SEC control action. A
comparative analysis of VA loading of SEC, SHC and total loading of UPQC has been
carried out. The performance of the two control schemes has been shown through
extensive simulation using the software SABER. Since the power circuit design of UPQC
remains same for both the model, the usage of UPQC can be optimized depending upon
88
Y. Y. Kolhatkar and S. P. Das have presented an optimized UPQC, which aims at the
integration of series active and shunt active power filters with minimum volt-ampere
(VA) loading of the UPQC [142]. The series active filter is a DVR, which regulates the
voltage at the load end with minimum VA loading of the overall UPQC by injecting the
STATCOM in the proposed scheme are shown in Fig. 3.25 and Fig. 3.26 respectively.
The D-STATCOM has been activated in the current control mode to stabilize the DC-
link voltage, supply the load reactive power, and eliminate harmonics from the supply
current. The control scheme flexibility for the sudden load change during the sag
condition has also been investigated with the help of simulation as well as through single-
phase experimental setup in the laboratory at 120 V, 0.6 kVA. It has been shown that
voltage can be restored in 12 cycles after the occurrence of the sag. However, angle
closed loop may take another 23 cycles to match with calculated voltage value.
89
Fig. 3.26 Closed loop block diagram of D-STATCOM [142].
A. K. Jindal and his colleagues have illustrated the operation and control of a new
connection for a UPQC to enhance the PQ of two feeders in a distribution system [143].
Connection of this device between two independent feeders originating from different
substations has been explained in this paper. As UPQC is connected between two
different lines, hence the device has been given the name interline UPQC (IUPQC) as
shown in Fig. 3.27. The proposed configuration of UPQC serves to control the bus
voltage of one of the feeders while regulating the voltage across a sensitive load in the
other feeder. Different case studies have been carried out to verify the efficacy of the
proposed configuration of UPQC always requires two parallel feeders to be present. This
restricts its application to specific situations that have two, side by side running parallel
feeders.
Fig. 3.1 shows that third type of compensating CPDs are backup stored energy
devices. Usually, a D-STATCOM is used for flicker mitigation and active filtering
90
purposes in a distribution system. However, when it is provided with an isolation switch
for disconnection from the distribution feeder, it results in a backup source, and also
called as backup stored energy system/device (BSES) as shown in Fig. 3.28 [67].
Sensitive load is isolated from the power system by a static switch on sensing a
disturbance and is fed by the VSC. As mentioned in chapter II, there are several devices
for storing the necessary electrical energy e.g. DC storage capacitors, batteries
and superconducting coils [145]. These backup energy storage devices can manage to
supply up to seconds or even minutes of backup power. This permits sensitive loads to
continue operation during complete power interruptions. TBESS have the capability to
compensate short term PQ variations and enhance reliability provided they are configured
with longer-term backup generation. The above mentioned storage devices are shortly
described in a Table 3.1 along with their merits and demerits [146]:
91
Fig. 3.28 Backup power source [67].
92
Table 3.1
Backup storage devices and their merits and demerits [146].
Sr. Type of backup stored
Merits and demerits
No. energy devices
1 DC storage capacitors Store energy in their capacitance.
Useful for short ride through times.
Require DC/DC converter between the constant voltage
bus and the capacitance.
Cost increases with the increase in ride through time.
2 Batteries Most common method of storing energy.
Do not require DC/DC converter as they are directly
connected to VSC.
Capacitor can compete with batteries but only for short
ride through times.
Utilize environmentally unfriendly materials.
Have limited life time.
Require regular maintenance.
Some new types of batteries do not have above mentioned
limitations but have higher cost.
3 Supercapacitors Energy densities comparable to batteries.
Improve equipment voltage tolerance.
Have much longer lifetime than batteries.
Require much less maintenance than batteries.
Discharge time is not less than 1 minute.
Faster than batteries but much slower than capacitors.
Only available for voltages of a few volts.
4 Flywheels Store energy in fast-spinning flywheels.
Stored energy cannot be extracted fully.
Require an additional DC/DC converter.
5 Superconducting coils Energy is stored in superconducting magnetic energy
storage (SMES) coils.
Most cost attractive solution for high power short time ride
through applications.
Fast extraction of energy as compared to batteries.
Have reduced size and lower maintenance cost as
compared to batteries.
Can be quickly and easily installed with short lead times.
Have modular design to meet future load growth and are
portable [145], [148], [149].
Require an additional DC/DC converter between SMES
and constant voltage bus (Fig. 3.29).
M. Moschakis and his colleagues have presented some of the operational and design
[146]. The main parts that a D-SMES includes: VSC, D-SMES system, DC-DC
operational techniques for D-SMES have been discussed in the paper. The merits and
93
demerits of SMES compared to other solutions have been provided. The issues that a D-
SMES can deal with have been listed and discussed. However, authors in the present
work have focused only on the ability of a D-SMES to compensate voltage fluctuations
and sags (dips) and support a sensitive load during power system outages or
interruptions. Simulations results have been shown using the EMTDC simulation
package that demonstrates the ability of D-SMES to mitigate voltage fluctuations caused
by load variations. Moreover, it has been shown that D-SMES can safeguard a sensitive
load from faults on the distribution or the transmission system when it is accompanied
with a static switch. Hence, the load faces no voltage sag during the fault. However,
without the uses of static switch upstream the D-SMES system, the D-SMES would
sensitive load [18]. But, the use of static switch requires an alternate feeder as well.
Moreover simulations in the paper have been performed with the assumption that DC
side of the SMES system is replaced by a DC voltage source. Hence amount of energy
that is available in SMES is not taken into consideration and the response in the demand
for real power is instantaneous. However, this response in a real D-SMES unit would not
Two possible functions of flywheel energy storage systems (FESS) are voltage
support and the uninterruptible power supply. These applications are helpful to protect
sensitive loads on distribution feeders. Robert S. and his colleagues have looked at the
possibility of combining voltage support and the uninterruptible power supply functions
by considering a flywheel energy storage system (FESS) [147]. Authors have proposed
FESS system that performs the above mentioned functions by adopting a new control
94
scheme using both sinusoidal pulse-width modulation (SPWM) as well as a boost
converter to regulate the critical load voltage on the feeder. Dynamic voltage
compensation has been attained by injecting voltage using series transformers rather than
by connecting the system in shunt, to minimize the amount of kVA required by the
flywheel system. Electromagnetic transients program (EMTP) has been used to perform
simulations to validate the proposed control scheme. However, for voltage dips of 50%,
the load voltage simulation plot shows load voltage is stabilized after 3 cycles. Moreover
if voltage dip exceeds 50% then boost converter tends to become unstable and FESS
enters into UPS mode by isolating load from main supply. The load voltage simulation
plot for this case also shows that, although rated load voltage magnitude is obtained after
sag mitigation but waveform is distorted and contains noise. Also, FESS is suitable to
mitigate voltage sag if sag duration is smaller than the hold-up time of the flywheel.
Normally, Backup energy stored devices available in the market can be considered
modification of UPS. These devices can be classified on the basis of three different
factors [150]:
95
In a conventional online energy storage system, the protection unit supplies the load.
Protection unit consists of a diode rectifier followed by a VSC as shown in Fig. 3.30. The
batteries or some of the other energy storage mediums. This DC power is then converted
into AC power to feed the load. If the incoming AC power fails, the VSC is fed from the
batteries and continues to supply the load. Generally, UPS systems are designed to
outages, an online UPS system provides isolation of the critical load from all power-line
disturbances.
An offline energy-storage system allows the utility to power the protected loads until
a disturbance is detected and a static or a mechanical switch transfers the load to the
during the time it takes to detect a mains failure, start the VSC and transfer the load to
battery power. A load with some inherent ride-through capability is required for the
mechanical switch can provide nearly seamless transfer from utility power to battery
which the design includes some means of load voltage regulation. This can be
static voltage regulator [150]. In theory, installing an uninterruptible power supply (UPS)
is the easiest way to protect sensitive processes against all sags. However, these battery-
dependent devices are often expensive and energy insufficient and they require
96
maintenance that may exceed the owners available in-house resources. Hence, due to its
basis only in places where the damage resulting from power supply problems is very
high, such as in hospitals etc. Amongst the CPDs, UPS and DVR have the ability to inject
a voltage waveform to the distribution line. However, DVR costs less as compared to
UPS. While evaluating the UPS and DVR; the UPS is constantly providing the full
voltage to the load irrespective of whether the waveform is distorted or not. As a result,
the UPS is always working at its full power. In contrast, the DVR injects only the
difference between the pre-sag and the sagged voltage and that too is only during the
sagged period. Hence operating losses of the DVR and the power rating are very small as
compared to the UPS. Hence DVR is deemed as a power efficient device as compared to
the UPS.
In Fig. 3.1, second type of CPDs called network reconfiguring type is shown.
These devices are series-connected devices. A. Ghosh and G. Ledwich have described
that network reconfiguring type equipment are gate turn-off (GTO) based or thyristor
based switches [1]. Network reconfiguring devices include solid state current limiter
(SSCL), solid state circuit breaker (SSCB) and solid state transfer switch (SSTS).
However, most popular network reconfiguring device is SSTS. The solid state transfer
switch or static source transfer switch (SSTS) uses solid-state switches to provide an
from momentary interruptions and voltage sag/swell or fault in the supplying feeder. The
transfer time can be as low as quarter of the rated frequency cycle [22].
97
3.2.2.1 Solid State Current Limiter
SSCL used to limit fault current in power system have two types.
GTO-Switched
Thyristor- Controlled
In the GTO based switched device, fault current-limiting impedance is shunted across a
pair of anti-parallel GTO switches. It comes in series with a faulted circuit as soon as the
fault is sensed. In this way large fault current is interrupted by turning off the GTO
switches during fault. However, this leads to high transient overvoltage and nuisance
oscillations initiated by the operation of GTO based switched SSCL excite LC circuits
formed by the customer step down transformers and the low-voltage power factor
correction capacitors at the customer vicinities. This phenomenon gives rise to voltage
magnification at the customer vicinities [152]. Hence it can be concluded that GTO based
switched SSCL is not suitable for use on power system if voltage quality is a critical
issue.
system as soon as fault occurs. In contrast to GTO switched SSCL the switches of this
device turn on during fault. In this way, fault current interruption during fault is avoided
and system does not suffer from transient complication. There are two types of thyristor-
controlled SSCL devices. Thyristor controlled series capacitors (TCSCs) and thyristor
reactor (TCR). This allows continuous control of the TCSC reactance. When TCSC is
98
used to limit fault current, it is consequently improving the quality of the supply by
mitigating sag severity [153]. However these devices are not able to completely mitigate
sag as desired and hence have limited capacity to compensate voltage sag.
TCSR have been also investigated for voltage sag mitigation by the researches but
they were found to have limited capacity to ride through AC power line dips [154].
Moreover, value of inductance in TCSC and TCSR design should not be kept large in
order to gain higher voltage level, smaller phase-angle jump and lower fault current;
SSCL has been initially proposed for the limitation of large fault current. However,
literature studies reveal that, through the correct selection of circuit configuration, SSCL
can also be operated for the mitigation of voltage sag. In contrast to UPS and DVR that
are installed on the feeder supplying sensitive loads, a SSCL requires to be installed on
every potentially faulty line. Hence, due to the large number of SSCLs required, this
It has the ability to intrude a fault current very rapidly and can also perform auto-
reclosing function. It is a lot faster than its mechanical equivalent and is therefore an
ideal device for custom power application. However, according to above discussion,
SSCL and SSCB are not commonly used for voltage sag, swell and phase-angle jump
mitigation.
Fig. 3.31 shows a device that is obtained by series combination of STS and static
series compensator (SSC) [22]. This arrangement can manage total protection against
99
interruptions and voltage dips, with the STS taking care of interruptions and dips
originated by faults in the distribution system, which are long and deep and would
deplete the energy storage of the SSC. In this case, the responsibility of the SSC would
be to compensate for the voltage dips originated by faults in the transmission systems,
which the STS cannot handle. It is reported by Bollen that transmission system dips are
normally short and shallow [63]. The combined series configuration of SSC and STS will
reduce the size of the energy storage of the SSC, with a consequent reduction of the cost
of the device. However, this arrangement is bounded with availability of alternate feeder.
A. Bagginii pointed out that most commonly used solid-state device in SSTS is the
configuration then transfer time may be half-cycle as SCR cannot turn off until the
current crosses zero. Fig. 3.32 shows a common static switch configuration.
100
Fig. 3.32 Schematic representation of the SSTS as a CPD [22].
T.A. Short mentioned another fast transfer technology that can be used in the same
applications as static switches [15]. High-speed mechanical source transfer switches use
two sources are not parallel during the transfer; therefore, the load experiences an
interruption of approximately 1.5 cycles. The authors also pointed out that this
interruption may trip some sensitive equipment. These switches have the
cost of a static switch), and small. Both pole-mounted and pad-mounted versions
are available. For most loads, the fast transfer switch provides significant benefit.
Relays and contactors, though, can drop out for an l.5-cycle interruption.
application as shown in Fig. 3.33. This configuration offers better performance for
101
voltage sags, momentary interruptions, and long duration interruptions for the
customers at the end of the circuit that normally get the worst power quality [15].
The SSTS performance concerning transfer time has been analyzed by [99, 151].
Simulation results conclude that in general the speed of SSTS operation is high enough to
attain a seamless transfer for sensitive loads. However, the transfer time increases even
Fig. 3.33 Fast transfers switch to enhance power quality to a downstream section
of circuit [15].
electromagnetic transient studies for the following three custom power controllers in
PSCAD/EMTDC: the SSTS, the DVR, and the D-STATCOM [112]. For the SSTS,
authors described that each time a fault condition is detected in the preferred feeder, the
control system swaps the firing signals to the thyristors in both switches, i.e., SS1 in the
preferred feeder is deactivated and SS2 in the alternate feeder is activated as shown in
Fig. 3.32. The peak value of the voltage waveform is measured by the control system at
102
every half-cycle. This checks whether or not load voltage is within a prescribed range. In
case it is found outside the allowed limit, an abnormal condition is sensed and the firing
signals to the SSTS thyristors are changed to shift the load to the healthy feeder. The
main reason for the success of the SSTS is its rather low cost compared with other
solutions. Although, the SSTS has been proved to be a suitable CPD for screening
selected load points against faulted conditions, but it does require an alternate feeder
being available that has high cost. Therefore, this solution is particularly attractive for
installations that already have mechanical transfer systems, where upgrading to a static
system does not require major changes in the layout of the distribution system. In
addition, SSTS cannot protect against dips originating in the transmission system that
also affects the alternative supply. However, a significant improvement can be attained in
the performance of the industrial system against faults at distribution level, that usually
regulating transformer in which the voltage of the regulated circuit is controlled in steps
by means of taps, without interrupting the load. This transformer can boost or buck the
voltage supplied to a load with a delay on the order of seconds. In contrast, electronic tap
changers (ETC) as shown in Fig. 3.34 can be mounted on a dedicated transformer for the
sensitive load, in order to rapidly change its turns ratio according to changes in the input
voltage [159]. This device, also called static voltage regulator, provides voltage boost
during voltage sags by using thyristor switches that rapidly change taps on three single-
103
phase transformers [67]. Generally, this type of device is limited in design to provide up
to 50% boost [150]. The rating of an ETC needs to be the same as the full rating of the
load that it will protect, because the ETC will carry the entire load during sag or swell
events. An ETC is not effective during voltage interruptions because there is no voltage
transformer. During voltage sags in which the ETC switches to full 50% boost, the
current drawn by the unit can be twice as high as normal. Therefore, upstream protection
devices need to be coordinated with the ETC so that they do not operate in response to
the higher current levels. Solid state tap changer system does not compensate for the
change in the voltage wave shape that occurs during voltage sags. If the load is sensitive
to changes in wave shape, such as phase-angle jump, then it may still malfunction during
the event, even though the magnitude of the voltage is within design requirements.
104
J. Faiz and B. Siahkolah have presented the ability of a distribution transformer
equipped with electronic tap changer for sag mitigation [160]. Authors of this paper have
also investigated sum of cost of the sag reduction devices (UPS, DVR, constant-voltage-
transformers (CVT), motor-generator set (MG), ETC) for a typical application. Result of
this investigation have revealed that due to low cost, high efficiency and very low
maintenance cost of electronic tap changers, the total cost of ETC is lower in first year of
application. However, in the second year and later, the DVR has been found to have
lower cost as compared to the other devices; the reason is larger compensation range of
the DVR.
3.3 Summary
CPDs are used in the power distribution systems to improve the quality and reliability
of power delivered to the consumers. Compensating type CPDs include DVR, reactive
power and harmonic compensation devices and backup stored energy devices. SSTS is
most commonly used for network reconfiguring. An overview of each CPD has been
included in this chapter for voltage sag, swell and phase jump mitigation. Specific
There are various CPDs for protecting industrial processes against voltage sags like
and UPQC, etc. Although these CPDs work efficiently with some constraints to protect
sensitive load from voltage sags, but the most efficient and robust voltage restoration is
possible by the use of DVR. The main reason for extensive use of DVR is its simple
control, fast response, and fewer transients. The DVR is a CPD that provides technically
105
advanced and economical solution to voltage sags, swells and phase jumps as compared
to other CPDs.
DVRs are now a matured option in industry to reduce the impact of voltage sags to
sensitive loads. The use of DVR in PQ-related applications is increasing. Although, the
most popular application of DVR is to control voltage sags (swells) but the harmonics
and power factor correction may also be achieved through robust control schemes. DVR
customers. Decrease in shut down time of process industries, small losses in the
power irregularities, and smooth operation of sophisticated electronic equipments are few
of them. Proliferation of sensitive load has opened the venues for DVR application in all
consumer categories.
106