CONTENTS
1. GENERAL ..................................................................................................................................... 5
1.1. SCOPE.................................................................................................................................... 5
8. APPENDICES ............................................................................................................................. 53
1. GENERAL
1.1. SCOPE
This calculation defines the requirements for detail design and construction of Heating,
Ventilating and Air Conditioning (hereinafter referred to as HVAC) system and plumbing
system, which shall be applied to Control Building for Saudi Aramco Third Party
Cogeneration Project in the Ras Tanura, Kingdom of Saudi Arabia(Red Sea).
1.2. OBJECTIVE
To determine the cooling and heating loads in Control Building and to size HVAC
equipment to provide the suitable environmental conditions for personnel and
equipments
1.3. REFERENCES
This calculation is performed in accordance with the following codes, standards and
project specifications. Their latest editions at time of contract award shall be applied
Language : English
Unit : S.I Unit
2. DESIGN CONDITIONS
Note ; 1) Selection for Air Cooled Condensing Units (ACCU) and Split System Air
Conditioning Units (SAC) shall be as per 106 F (41 C) DB.
F03 Engineering
222 5010 222 5010 62 Pa -
Room
F05 Central
222 5010 222 5010 62 Pa -
Control Rm.
1) HVAC System load calculation shall be done in accordance with ASHRAE handbook
methods and computer generated using Carrier E20-II used calculation software. A
psychometric analysis shall be provided for each system with cooling and/or heating
load calculations. A 10% safety margin shall be applied for HVAC load calculation.
This analysis shall be include but not limited to:
A. Mixing temperature of outside and return air
B. Entering air temperature and enthalpy at coil
C. Leaving air temperature and enthalpy at coil
D. Outside air design condition
E. Building R and U values
F. Internal heat gains for installed equipment
G. Internal heat gain basis for Lighting and other miscellaneous equipment
H. Supply air volumes
I. Ventilation air volumes
2) Heat load calculation shall be carried out in accordance with good engineering
practice and Carrier E20-II, HAP ver. 4.4.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Minimum ventilation rates shall be as per table below or latest issue of ASHRAE 62 and
SBC-501.
Ventilation and Exhaust Rates
Application Minimum Air Flow Rate
Toilets 72 cfm (36 l/s) per water closet/urinal
Shower Rooms 48 cfm (24 l/s) per shower head
Locker rooms, Pantry,
Ablution, Janitor Room,
Normal storage areas,
0.5 cfm per ft2 (2.6 l/s per m2) floor area
Dressing room, Lunch room,
Water heater rooms, Fire
truck bay
Trash Storage, Workshop,
1.5 cfm per ft2 (7.5 l/s per m2) floor area
Chemical Storage
Office areas and similar 20 cfm (10 l/s) per person
rooms
Kitchen (General Area) 0.7 cfm per ft2 (3.5 l/s per m2) floor area
Minimum ventilation for Battery Rooms shall be 10 air changes per hour.
Heat Emission
Typical Application Remarks
(Watts/ m2)
Based on ASHRAE Fundamentals
Office 12
Handbook 2013
Chapter 18 Table 2
Electrical / Mechanical 16
Laboratory 15
Restroom 10
Corridor 5
Workshop 20
Warehouse 15
Conference / Meeting /
15
Training
3.3. HEAT DISSIPATION FROM CONTROL & ELECTRICAL PANEL AND EQUIPMENTS
F03 Engineering
- 8762 Watts -
Room
F05 Central Control
- 10088 Watts -
Room
F06 Telecom room 690 Watts - -
Notes : 1) Heat Emission from Electrical Panel and Equipment are informed from Electric
division.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
d/ 0.53
U (W / m2K) 1.887
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
d/ 0.378
2
U (W / m K) 2.645
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
4.4. FLOOR
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
d/ 0.911
U (W / m2K) 1.098
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)
d/ 0.424
2
U (W / m K) 2.358
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Notes: 1. Total Fresh air volume shall be larger than the fresh air volume according
to occupant. (QF > QFO ) : 4370 LPS > 160 LPS
- Centrial System Total Fresh air volume (QF)
QF = Exhaust Air + Pressurization Air = 3140 + 1230 = 4370 LPS
- Requirement Minimum Fresh air volume according to occupant (QFO)
QFO = A x 10 LPS/Person = 16 x 10 LPS/Person = 160 LPS
- A : Total occupant
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
G03 FF Room - 25 - - - - 25 -
Notes: 1. Total Fresh air volume shall be larger than the fresh air volume according
to occupant. (QF > QFO ) : 296 LPS > 130 LPS
- Centrial System Total Fresh air volume (QF)
QF = Exhaust Air + Pressurization Air = 283 + 13 = 296 LPS
- Requirement Minimum Fresh air volume according to occupant (QFO)
QFO = A x 10 LPS/Person = 13 x 10 LPS/Person = 130 LPS
- A : Total occupant
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Air Outlet 30 1 30
Blast Protection Damper 100 1 100
Air Intake Stack 30 1 30
Sand Trap Louver 100 1 100
Filter Box 100 1 100
Supply duct (m) 0.6 70 42
Supply duct fitting - - 32
Fresh air duct (m) 1.0 25 25
Fresh air duct fitting - - 19
Sub Total 858
Safety Factor 86 1
Total(b) 944
Total (a)+(b) 1549 1600
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Refer to Appendix 1
Cooling capacity Sensible capacity : 345.4 kW
Air System Size 1
(qCA) Total Capacity : 475.0 kW
Summary
Cooling Coil
Type : Direct expansion 1
(qCA)
Sensible capacity : 172.7 kW
Total Capacity : 237.5 kW
Entering Air Temperature : 30.4 DB, 20.8 WB
Leaving Air Temperature : 12.0 DB, 11.7 WB
Static Pressure
Air
Volume Unit Remarks
Pressure
(L/s) Part Name Pressure Qty
Drop(Pa)
Drop(Pa)
1741 Internal Mixing Box 50 1 50 Pressure
Pre Filter 100 1 100 drop of fittings
Static are estimated
Pressure Final Filter 250 1 250
75% of total
Cooling Coil (DX Type) 100 1 100 duct pressure
Supply plenum 50 1 50 drop.
Sub Total 550
Safety Factor
Safety Factor 55
: 10 %
Total(a) 605
External Dampers 20 7 140 Internal static 1
Air Outlet 30 1 30
Blast Protection Damper 100 1 100
Air Intake Stack 30 1 30
Sand Trap Louver 100 1 100
Filter Box 100 1 100
Supply duct (m) 0.6 45 27
Supply duct fitting - - 21
Fresh air duct (m) 1.0 54 54
Fresh air duct fitting - - 41
Sub Total 783
Safety Factor 78 1
Total(b) 861
Total (a)+(b) 1466 1500
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1
Refer to Appendix 1
Cooling capacity Sensible capacity : 35.3 kW
Air System Size
(qCA) Total Capacity : 48.3 kW
Summary
Cooling Coil
Type : Direct expansion
(qCA)
Sensible capacity : 35.3 kW
Total Capacity : 48.3 kW
Entering Air Temperature : 28.0 DB, 19.2 WB
Leaving Air Temperature : 11.5 DB, 11.0 WB
Total Input
25.2 kW 1
Power for unit
Ventilation 1) Ventilation Fan volume by room sensible heat load (QS) A : Area of the
Airflow Ventilation Fan volume for this room by sensible related room,
Rate (Q) heat load [Unit : m2]
a) Heat emission (qs)
Safety Factor: 10 %
- Electrical Heat emission (qe) : 24000 W(24.0 kW)
- Fabric and Solar (qf) : 9091 W (9.1 kW) Specific heat (Cp)
: 1005 J/kg.C
- Total : qs = qe+qf
= 24.0 + 9.1 = 33.1 kW Air density (p)
: 0.0011 kg/liter
b) Outside Air Temperature (To) : 41.0 CDB (Density of air at 41 C)
c) Room Temperature (Tr1) : 46.0 CDB
qe : Refer to 3.3
d) Electrical Room Temperature (Tr2) : 27.0 CDB Heat Dissipation
e) Temperature difference (dT= Tr1 - Tr2) : 19.0 CDB from Control &
Q s = qs/(Cp x x dT) x S.F Electrical Panel and
Equipments
= 33.1 x 1000 / ( 1005 x 0.0011 x 19.0 ) x 1.1
qf : Refer to
= 1733 L/s 1740 L/s
APPENDIX 2.
2) Therefore, ventilation airflow rate (Q) : 1740 L/s Space Design Load
Pressure Drop Part Pressure Drop Summary
Static Part Name
(Pa/Part) Qty (Pa)
Pressure BPD : Blast Protection
(SP) Air device 30 2 60 Damper
Damper 30 2 60
Duct 1.0 35 35
Fitting - - 26
Fan
Specificatio Equip. No. : R0TBA-JE001
ns Quantity : 1 Set
Location : B01-Cable Room
Type : Centrifugal, Duct In-Line
Capacity : 1740 L/s 200 Pa x 1.50 kW
1
Kitchen Sink 75 1 75
Faucet 22 - -
Total 427
Shower 110 - -
Kitchen Sink 75 - -
Faucet 22 - -
Total 44
8. APPENDICES
CONTROL BUILDING
APPENDIX 1
HVAC LOAD CALCULATION OUTPUT DATA (E20-II)
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS
CONTROL BUILDING
TECHNICAL AREA
(R0TBA-JA001A/B/C/D)
Air System Sizing Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING
Zone L/s ................................Sum of space airflow rates Calculation Months ........................................... Jan to Dec
Space L/s ............................Individual peak space loads Sizing Data ....................................................... Calculated
Total coil load ............................................................ 475.0 kW Load occurs at ...................................................... Jul 1500
Sensible coil load ...................................................... 345.4 kW OA DB / WB ...................................................... 41.0 / 27.0 C
Coil L/s at Jul 1500 ................................................... 14122 L/s Entering DB / WB .............................................. 30.4 / 20.8 C
Max block L/s ........................................................... 14761 L/s Leaving DB / WB ............................................... 12.0 / 11.7 C
Sum of peak zone L/s .............................................. 14761 L/s Coil ADP ...................................................................... 10.1 C
Sensible heat ratio .................................................... 0.727 Bypass Factor ........................................................... 0.100
m/kW ............................................................................ 2.7 Resulting RH .................................................................. 45 %
W/m .......................................................................... 368.5 Design supply temp. .................................................... 12.0 C
Water flow @ 5.6 K rise .............................................. N/A Zone T-stat Check ..................................................... 3 of 3 OK
Max zone temperature deviation ................................... 0.0 K
Max coil load ............................................................... 67.9 kW Load occurs at ...................................................... Des Htg
Coil L/s at Des Htg ..................................................... 6752 L/s W/m ............................................................................ 52.7
Max coil L/s ................................................................ 6752 L/s Ent. DB / Lvg DB ............................................... 17.3 / 25.6 C
Water flow @ 11.1 K drop........................................... N/A
Actual max L/s .......................................................... 14762 L/s Fan motor BHP.......................................................... 39.59 BHP
Standard L/s ............................................................. 14732 L/s Fan motor kW .............................................................. 22.0 kW
Actual max L/(s-m) ................................................... 11.45 L/(s-m) Fan static .................................................................... 1600 Pa
1. Summary
Ventilation Sizing Method ........................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ....................................................................... 5100 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CCB-F01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.3 C / 26.4 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 74 m 587 - 74 m 357 -
Roof Transmission 210 m 1245 - 210 m 593 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 112 - 6 m 112 -
Floor Transmission 28 m 62 - 28 m 0 -
Partitions 86 m 438 - 86 m 201 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3629 W 3629 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 15580 W 15579 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2165 0 10% 126 0
>> Total Zone Loads - 23818 0 - 1390 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CCB-F01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 74 0.439 - 587 - 357
DOOR 6 1.703 - 112 - 112
H EXPOSURE
ROOF 210 0.257 - 1245 - 593
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' CCB-G01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 292 m 1980 - 292 m 1409 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 128 - 6 m 112 -
Floor Transmission 480 m 14145 - 480 m 12450 -
Partitions 38 m 181 - 38 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 8294 W 8294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 97987 W 97983 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 12271 0 10% 1397 0
>> Total Zone Loads - 134982 0 - 15369 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' CCB-G01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 144 0.439 - 936 - 696
NE EXPOSURE
WALL 77 0.439 - 577 - 371
SW EXPOSURE
WALL 71 0.439 - 467 - 342
DOOR 6 1.703 - 128 - 112
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' CCB-F02-RACK ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 148 m 1453 - 148 m 845 -
Roof Transmission 180 m 1039 - 180 m 534 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 170 - 6 m 133 -
Floor Transmission 180 m 1882 - 180 m 849 -
Partitions 36 m 101 - 36 m 34 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3110 W 3110 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 12378 W 12377 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2013 0 10% 239 0
>> Total Zone Loads - 22146 0 - 2634 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' CCB-F02-RACK ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 86 0.439 - 843 - 488
NE EXPOSURE
WALL 62 0.439 - 610 - 356
DOOR 6 1.703 - 170 - 133
H EXPOSURE
ROOF 180 0.228 - 1039 - 534
TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' CCB-F05-CONTROL ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 138 m 1327 - 138 m 786 -
Roof Transmission 210 m 1179 - 210 m 623 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 210 m 2296 - 210 m 990 -
Partitions 49 m 730 - 49 m 439 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3402 W 3402 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10088 W 10088 - 0 0 -
People 10 700 450 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1972 45 10% 284 0
>> Total Zone Loads - 21693 495 - 3122 0
TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' CCB-F05-CONTROL ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 80 0.439 - 775 - 456
SE EXPOSURE
WALL 15 0.439 - 143 - 86
SE EXPOSURE
WALL 43 0.439 - 409 - 244
H EXPOSURE
ROOF 210 0.228 - 1179 - 623
TABLE 2.3.A. COMPONENT LOADS FOR SPACE '' CCB-F03-ENGINEERING ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 44 m 247 - 44 m 131 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 44 m 481 - 44 m 208 -
Partitions 12 m 105 - 12 m 45 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 713 W 713 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8762 W 8762 - 0 0 -
People 4 280 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1059 18 10% 38 0
>> Total Zone Loads - 11646 198 - 422 0
TABLE 2.3.B. ENVELOPE LOADS FOR SPACE '' CCB-F03-ENGINEERING ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 44 0.228 - 247 - 131
TABLE 2.4.A. COMPONENT LOADS FOR SPACE '' CCB-F06-TELECOM ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 40 m 400 - 40 m 228 -
Roof Transmission 14 m 76 - 14 m 41 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 6 m 45 - 6 m 12 -
Partitions 9 m 149 - 9 m 104 -
Ceiling 12 m 170 - 12 m 46 -
Overhead Lighting 238 W 238 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 690 W 690 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 177 0 10% 43 0
>> Total Zone Loads - 1946 0 - 475 0
TABLE 2.4.B. ENVELOPE LOADS FOR SPACE '' CCB-F06-TELECOM ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 13 0.439 - 123 - 71
SE EXPOSURE
WALL 28 0.439 - 277 - 157
H EXPOSURE
ROOF 14 0.228 - 76 - 41
TABLE 2.5.A. COMPONENT LOADS FOR SPACE '' CCB-F04-MANAGER ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 23 m 220 - 23 m 130 -
Roof Transmission 16 m 89 - 16 m 47 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 16 m 176 - 16 m 75 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 207 W 207 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 480 W 480 - 0 0 -
People 2 140 90 0 0 0
Infiltration - 171 218 - 152 6
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 148 31 10% 41 1
>> Total Zone Loads - 1631 339 - 446 7
TABLE 2.5.B. ENVELOPE LOADS FOR SPACE '' CCB-F04-MANAGER ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 23 0.439 - 220 - 130
H EXPOSURE
ROOF 16 0.228 - 89 - 47
TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' CCB-F11-BATTERY ROOM '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.3 C / 26.4 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.5 C OCCUPIED T-STAT 21.5 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 137 m 1377 - 137 m 811 -
Roof Transmission 135 m 956 - 135 m 468 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 135 m 1201 - 135 m 796 -
Partitions 86 m 609 - 86 m 403 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 2333 W 2333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 865 W 865 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 734 0 10% 248 0
>> Total Zone Loads - 8075 0 - 2727 0
TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' CCB-F11-BATTERY ROOM '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 86 0.439 - 867 - 507
SW EXPOSURE
WALL 51 0.439 - 510 - 304
H EXPOSURE
ROOF 135 0.257 - 956 - 468
CONTROL BUILDING
NON-TECHNICAL AREA
(R0TBA-JA002A/B)
Air System Sizing Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING
Zone L/s ................................Sum of space airflow rates Calculation Months ........................................... Jan to Dec
Space L/s ............................Individual peak space loads Sizing Data ....................................................... Calculated
Total coil load .............................................................. 48.3 kW Load occurs at .................................................... Aug 1500
Sensible coil load ........................................................ 35.3 kW OA DB / WB ...................................................... 41.0 / 27.0 C
Coil L/s at Aug 1500 ................................................... 1615 L/s Entering DB / WB .............................................. 28.0 / 19.2 C
Max block L/s ............................................................. 1741 L/s Leaving DB / WB ............................................... 11.5 / 11.0 C
Sum of peak zone L/s ................................................ 1741 L/s Coil ADP ...................................................................... 10.6 C
Sensible heat ratio .................................................... 0.731 Bypass Factor ........................................................... 0.100
m/kW ............................................................................ 9.9 Resulting RH .................................................................. 45 %
W/m .......................................................................... 100.8 Design supply temp. .................................................... 12.0 C
Water flow @ 5.6 K rise .............................................. N/A Zone T-stat Check ..................................................... 3 of 3 OK
Max zone temperature deviation ................................... 0.0 K
Max coil load ................................................................. 9.1 kW Load occurs at ...................................................... Des Htg
Coil L/s at Des Htg ....................................................... 927 L/s W/m ............................................................................ 19.0
Max coil L/s .................................................................. 927 L/s Ent. DB / Lvg DB ............................................... 18.9 / 27.1 C
Water flow @ 11.1 K drop........................................... N/A
Actual max L/s ............................................................ 1741 L/s Fan motor BHP............................................................ 4.67 BHP
Standard L/s ............................................................... 1737 L/s Fan motor kW .............................................................. 5.5 kW
Actual max L/(s-m) ..................................................... 3.64 L/(s-m) Fan static .................................................................... 1500 Pa
1. Summary
Ventilation Sizing Method ....................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 296 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CCB-G07-FIRST AID '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 43 m 440 - 43 m 246 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 21 m 241 - 21 m 80 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 193 W 193 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 224 W 223 - 0 0 -
People 2 140 90 0 0 0
Infiltration - 131 165 - 128 7
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 137 26 10% 45 1
>> Total Zone Loads - 1505 281 - 498 8
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CCB-G07-FIRST AID '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 18 0.439 - 183 - 104
SW EXPOSURE
WALL 25 0.439 - 257 - 142
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' CCB-F07-MEETING ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 28 m 275 - 28 m 157 -
Roof Transmission 26 m 139 - 26 m 77 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 26 m 284 - 26 m 122 -
Partitions 28 m 390 - 28 m 104 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 420 W 420 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 389 W 388 - 0 0 -
People 5 350 225 0 0 0
Infiltration - 249 289 - 222 12
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 250 51 10% 68 1
>> Total Zone Loads - 2745 565 - 750 13
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' CCB-F07-MEETING ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 28 0.439 - 275 - 157
H EXPOSURE
ROOF 26 0.228 - 139 - 77
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' CCB-G05-PRAYER ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 26 m 260 - 26 m 151 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 33 m 361 - 33 m 123 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 295 W 295 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 273 W 273 - 0 0 -
People 6 420 270 0 0 0
Infiltration - 168 203 - 156 8
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 178 47 10% 43 1
>> Total Zone Loads - 1954 520 - 473 9
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' CCB-G05-PRAYER ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 26 0.439 - 260 - 151
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' CCB-G02-HVAC ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 111 m 821 - 111 m 536 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 11 m 225 - 11 m 197 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 132 m 1037 - 132 m 524 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 4709 W 4709 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4088 W 4087 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 3432 3765 - 3515 -89
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1431 376 10% 477 -9
>> Total Zone Loads - 15742 4141 - 5249 -98
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' CCB-G02-HVAC ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 45 0.439 - 305 - 216
DOOR 11 1.703 - 225 - 197
SE EXPOSURE
WALL 66 0.439 - 517 - 320
TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' CCB-G06-KITCHEN AREA '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 21 m 160 - 21 m 101 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 11 m 49 - 11 m 0 -
Ceiling 13 m 85 - 13 m 80 -
Overhead Lighting 143 W 143 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 396 W 396 - 0 0 -
People 4 280 180 0 0 0
Infiltration - 88 103 - 96 -2
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 120 28 10% 28 0
>> Total Zone Loads - 1321 311 - 305 -3
TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' CCB-G06-KITCHEN AREA '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 0.439 - 160 - 101
TABLE 2.3.A. COMPONENT LOADS FOR SPACE '' CCB-G11-LOCKER ROOM(M) '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 20 m 168 - 20 m 112 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 147 W 147 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 96 106 - 99 -2
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 41 11 10% 21 0
>> Total Zone Loads - 453 116 - 232 -3
TABLE 2.3.B. ENVELOPE LOADS FOR SPACE '' CCB-G11-LOCKER ROOM(M) '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' CCB-G03-FF ROOM '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 10 m 60 - 10 m 47 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 2 m 36 - 2 m 41 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 251 W 251 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 143 139 - 187 -5
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 49 14 10% 28 0
>> Total Zone Loads - 539 153 - 303 -5
TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' CCB-G03-FF ROOM '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 10 0.439 - 60 - 47
DOOR 2 1.703 - 36 - 41
TABLE 3.2.A. COMPONENT LOADS FOR SPACE '' CCB-G04-Corridor '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 22 m 142 - 22 m 106 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 21 m 176 - 21 m 213 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 275 W 275 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1530 W 1530 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 212 0 10% 32 0
>> Total Zone Loads - 2336 0 - 351 0
TABLE 3.2.B. ENVELOPE LOADS FOR SPACE '' CCB-G04-Corridor '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 22 0.439 - 142 - 106
TABLE 3.3.A. COMPONENT LOADS FOR SPACE '' CCB-F08,F10-Corri,Stair1 '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 20 m 129 - 20 m 97 -
Roof Transmission 49 m 176 - 49 m 124 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 12 m 105 - 12 m 127 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 267 W 267 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 275 267 - 358 -9
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 95 27 10% 71 -1
>> Total Zone Loads - 1047 294 - 776 -10
TABLE 3.3.B. ENVELOPE LOADS FOR SPACE '' CCB-F08,F10-Corri,Stair1 '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 20 0.439 - 129 - 97
H EXPOSURE
ROOF 49 0.228 - 176 - 124
TABLE 3.4.A. COMPONENT LOADS FOR SPACE '' CCB-G08-Air Lock '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 10 m 65 - 10 m 48 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 2 m 36 - 2 m 41 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 30 W 30 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 83 W 82 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 21 0 10% 9 0
>> Total Zone Loads - 234 0 - 98 0
TABLE 3.4.B. ENVELOPE LOADS FOR SPACE '' CCB-G08-Air Lock '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 10 0.439 - 65 - 48
DOOR 2 1.703 - 36 - 41
CONTROL BUILDING
B01-CABLE ROOM
(Space Design Load Summary)
Space Design Load Summary for CCB-Cable Room
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CCB-B01-CABLE ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 48.5 C OCCUPIED T-STAT 6.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 48 m -30 - 48 m 0 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 8294 W 8294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 826 0 10% 0 0
>> Total Zone Loads - 9091 0 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CCB-B01-CABLE ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 27 0.414 - -50 - 0
SW EXPOSURE
WALL 21 0.414 - 21 - 0
CONTROL BUILDING
APPENDIX 2
PRESSURIZATION AIR VOLUME CALCULATION
CALCULATION EXAMPLE OF FLOW RATE OF SUPPLY AIR FOR PRESSURIZATION
(Based on ASHRAE Application, Chapter 53, Equation 8 & 9, edition on 2011)
The air flow rate, through a construction crack, door gap, or other flow path is proportional to the pressure
difference across that path raised to the power n.
For a flow path of fixed geometry, n is theoretically in the range of 0.5 to 1.
However, for all flow paths, except extremely narrow cracks, n = 0.5, and the flow can be expressed as ;
Q = CA(2p/)
where,
Q = volumetric air flow rate
C = flow coefficient
A = flow area (called leakage area)
p = pressure difference across the flow path
= density of air entering the flow path
The flow coefficient depends on the geometry of the flow path, as well as on turbulence and friction.
In the present context, the flow coefficient is generally in the range of 0.6 to 0.7.
For = 1.2 kg/, and C = 0.65, the flow equation above can be expressed as ;
Q = 0.8392 Ap
where,
Q = volumetric air flow rate (/s)
A = flow area (called leakage area) ()
p = pressure difference across the flow path (Pa)
Total leakage area should be summed with data of each architectural component as below ;
Room name : G01-ELECTRICAL ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 135.0 25.7
Cast-in-place concrete cm2/m2 0.50 297.6 148.8
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40 480 192.0
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 366.5
Leakage air volume to be maintain 62Pa (m /hr) 1,040.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1
CONTROL BUILDING
APPENDIX 3
PSYCHROMETRIC CHART
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS
CONTROL BUILDING
TECHNICAL AREA
(R0TBA-JA001A/B/C/D)
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS
CONTROL BUILDING
NON-TECHNICAL AREA
(R0TBA-JA002A/B)