Power Cogeneration Plant Company

SAUDI ARAMCO THIRD PARTY COGENERATION PROJECTS


Owner Power Cogeneration Plant Company
Contractor Samsung Engineering Company Ltd.
Plant Location Ras Tanura
Contract No. Document No. SECL-R0-HV-CA-TBA-0001

HVAC & PLUMBING CALCULATION


FOR
CONTROL BUILDING

SECL DISTRIBUTION
PROJECT V
CIVIL V
ARCH. V
ELEC. V
INST.&CONT. V
FIRE FIGHTING V
HVAC O
MECH. V
PIPING V
PROCESS V
VIBRATION V
NOISE V
MATERIAL V
PERPORMANCE
V
GROUP
PROCURE. V
CONST. V
QA/QC V
HSE V
PRECOMM.-
V
COMM.

1 23-FEB-2015 Issued for Construction Y.H.Jeong D.H.Noh A.J.W S. Choi


0 08-OCT-2014 Issued for Construction Y.H.Jeong D.H.Noh S.J.Chun C.H. Shin
A 27-JUN-2014 Issued for Review Y.H.Jeong D.H.Noh S.J.Chun C.H. Shin
Rev. Date Description Prepared by Checked by Approved by PD
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 2 of 53

CONTENTS

1. GENERAL ..................................................................................................................................... 5

1.1. SCOPE.................................................................................................................................... 5

1.2. OBJECTIVE .......................................................................................................................... 5


1.3. REFERENCES ...................................................................................................................... 5
1.3.1 International Codes and Standards ..................................................................................................... 5
1.3.2 Local Codes and Standards .................................................................................................................... 6
1.3.3 Project Specifications ................................................................................................................................. 6
1.4. LANGUAGE AND UNIT...................................................................................................... 6

2. DESIGN CONDITIONS ............................................................................................................... 6


2.1. OUTDOOR DESIGN CONDITION .................................................................................... 6
2.2. INDOOR DESIGN CONDITION ........................................................................................ 6
2.3. DESIGN CALCULATIONS ................................................................................................. 8
2.4. DESIGN VENTILATION RATES ...................................................................................... 9

3. HEAT GAIN FROM OCCUPANTS, LIGHTING FIXTURE AND EQUIPMENT .......................................... 9


3.1. HEAT GAIN FROM OCCUPANTS .................................................................................... 9
3.2. HEAT GAIN FROM LIGHTING FIXTURES ................................................................. 10
3.3. HEAT DISSIPATION FROM CONTROL & ELECTRICAL PANEL AND EQUIPMENTS................... 10

4. THERMAL TRANSMITTANCE CALCULATION SHEET ................................................. 11


4.1. EXTERNAL ROOF ............................................................................................................ 11
4.1.1 Concrete Roof (With Ceiling) ................................................................................................................11
4.1.2 Concrete Roof (Without Ceiling) .........................................................................................................12
4.2. EXTERNAL WALL ............................................................................................................ 13
4.2.1 Concrete Block Wall ..................................................................................................................................13
4.2.2 Reinforced Concrete Wall .......................................................................................................................14
4.3. PARTITION WALL (INTERNAL WALL) ...................................................................... 15
4.3.1 Concrete Block Wall ..................................................................................................................................15
4.3.2 Reinforced Concrete Wall .......................................................................................................................16
4.4. FLOOR ................................................................................................................................. 17
4.4.1 Concrete Slab Floor (With Ceiling) .....................................................................................................17
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 3 of 53

4.4.2 Concrete Slab Floor (Without Ceiling) ..............................................................................................18

5. AIR BALANCE SUMMARY ..................................................................................................... 19


5.1. TECHNICAL AREA (R0TBA-JA001A/B/C/D) ............................................................... 19
5.2. NON-TECHNICAL AREA (R0TBA-JA002A/B) ............................................................. 20

6. HVAC EQUIPMENT SELECTIONS ....................................................................................... 21


6.1. AIR HANDLING UNIT ...................................................................................................... 21
6.1.1 Technical Area (R0TBA-JA001A/B/C/D) ...........................................................................................21
6.1.2 Non-Technical Area (R0TBA-JA002A/B) ..........................................................................................24
6.2. ELECTRIC DUCT HEATER ............................................................................................ 27
6.2.1 Technical Area - Electrical Zone (R0TBA-JH001)........................................................................27
6.2.2 Technical Area - Control Zone (R0TBA-JH002) ............................................................................29
6.2.3 Technical Area - Rack Room (R0TBA-JH003) ...............................................................................31
6.2.4 Technical Area - Battery Room (R0TBA-JH004) ..........................................................................33
6.2.5 Non-Technical Area - Office Zone (R0TBA-JH005).....................................................................35
6.2.6 Non-Technical Area - Service Zone (R0TBA-JH006) .................................................................37
6.3. ELECTRIC HUMIDIFIER ................................................................................................ 39
6.3.1 Technical Area (R0TBA-JG001) ...........................................................................................................39
6.3.2 Non-Technical Area (R0TBA-JG002) .................................................................................................40
6.4. VENTILATION FAN.......................................................................................................... 41
6.4.1 F11-Battery Room (R0TBA-JF001A/B) ..............................................................................................41
6.4.2 Kitchen & Shower (M) (R0TBA-JF002) ..............................................................................................42
6.4.3 1st FL. F09-Toilet (M) (R0TBA-JF003) ...............................................................................................43
6.4.4 B01-Cable Room Supply Air (R0TBA-JE001) ................................................................................44
6.4.5 B01-Cable Room Exhaust Air (R0TBA-JF004) ..............................................................................45
6.5. SMOKE EXTRACTION FAN ........................................................................................... 46
6.5.1 G01-Electrical Room (R0TBA-JF005) ................................................................................................46
6.5.2 F01-Electrical Room (R0TBA-JF006) .................................................................................................47
6.5.3 F05-Central Control Room (R0TBA-JF007) ....................................................................................48

7. PLUMBING SYSTEM CALCULATION ................................................................................. 49


7.1. POTABLE WATER DEMAND CALCULATION .......................................................... 49
7.1.1 CONTROL BUILDING ................................................................................................................................49
7.2. ELECTRIC WATER HEATER CALCULATION .......................................................... 51
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 4 of 53

7.2.1 G06-Kitchen, G10-Shower Room (M) (R0TBA-JJ001) ...............................................................51


7.2.2 F09-Toilet (M) (R0TBA-JJ002) ...............................................................................................................52

8. APPENDICES ............................................................................................................................. 53

Appendix 1 HVAC Load Calculation Output data (E20-II)

Appendix 2 Pressurization Air Volume Calculation

Appendix 3 Psychrometric Chart


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 5 of 53

1. GENERAL

1.1. SCOPE

This calculation defines the requirements for detail design and construction of Heating,
Ventilating and Air Conditioning (hereinafter referred to as HVAC) system and plumbing
system, which shall be applied to Control Building for Saudi Aramco Third Party
Cogeneration Project in the Ras Tanura, Kingdom of Saudi Arabia(Red Sea).

1.2. OBJECTIVE

To determine the cooling and heating loads in Control Building and to size HVAC
equipment to provide the suitable environmental conditions for personnel and
equipments

1.3. REFERENCES

This calculation is performed in accordance with the following codes, standards and
project specifications. Their latest editions at time of contract award shall be applied

1.3.1 International Codes and Standards

ASHRAE American Society of Heating, Refrigeration and Air Conditioning


Engineer
SMACNA Sheet Metal and Air Conditioning Contractors National Association
Low Pressure Duct Construction Standards
ARI American Refrigeration Institute
NFPA National Fire Protection Association
NFPA 70 National Electrical Code
NFPA 90A Installation of Air Conditioning and Ventilation System
IEC International Electro-technical Commission
ASTM American Society for Testing and Materials
ASTM B280 Seamless Copper Tube for Air Conditioning and Refrigeration Field
Service
ASTM A653 Standard Specification for Steel Sheet, Zinc-Coated (Galvanized)
or Zinc-Iron Alloy-Coated (Galvannealed) by Hot-Dip Process
ASTM A924 General Requirements for Steel Sheet, Metallic-Coated by the Hot-
Dip Process
ASTM E84 Standard Test Method for Surface Burning Characteristics of
Building Materials
ASTM A53 Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-
Coated, Welded and Seamless
IBC International Building Code
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 6 of 53

1.3.2 Local Codes and Standards


Local regulation about building design and environmental protection
Saudi Building Codes (SBC 401, 501, 601, 701 & 801)

1.3.3 Project Specifications


Section 4.7.6 of SFR Part A Engineering & Supply
Section 4.7.9 of SFR Part A Construction
Section 8.11 of SFR Part B Engineering & Supply
Section 8.11 of SFR Part B Construction
Section 4.7 of Contractors Proposal
SECL-A0-HV-SP-YYY-0001 (General Specification For HVAC & Plumbing System)

1.4. LANGUAGE AND UNIT


The following language and unit will be used for specifications, calculation sheets and
drawings throughout the project.

Language : English
Unit : S.I Unit

2. DESIGN CONDITIONS

2.1. OUTDOOR DESIGN CONDITION


( Location : Ras Tanura, Saudi Arabia )
Outdoor Dry Bulb Wet Bulb Relative
Enthalpy
Temperature Temperature Humidity Remarks
(kJ/kg)
Seasons (C DB) (C WB) (% RH)

Summer 41.0 27.0 34.6 84.68

Winter 8.0 3.4 45.2 15.51

Note ; 1) Selection for Air Cooled Condensing Units (ACCU) and Split System Air
Conditioning Units (SAC) shall be as per 106 F (41 C) DB.

2.2. INDOOR DESIGN CONDITION

Summer Winter Room Minimum


Rm. Room
Pressure Ventilation Remark
No. Name
DB(C) RH(%) DB(C) RH(%) (Pa) Rate (ACH)

B01 Cable N.R N.R N.R N.R - Note.5


Room
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 7 of 53

Summer Winter Room Minimum


Rm. Room
Pressure Ventilation Remark
No. Name
DB(C) RH(%) DB(C) RH(%) (Pa) Rate (ACH)

G01 Electrical 272 5020 192 5020 62 Pa -


Room

G02 HVAC 272 5020 192 5020 - -


Room

G03 FF Room 302 N.R 192 N.R - -

G04 Corridor 302 N.R 192 N.R - -

G05 Prayer 222 5010 222 5010 - Note.2


Room

G06 Kitchen 272 5020 192 5020 - Note.2


Area

G07 First Aid 222 5010 222 5010 - Note.2

G08 302 N.R 192 N.R - Non-


Air Lock recycling

G10 Shower N.R N.R N.R N.R - Note.2


Room (M)

G11 Locker 272 5020 192 5020 - Note.2


Room (M)

F01 Electrical 272 5020 192 5020 62 Pa -


Room

F02 Rack Room 222 5010 222 5010 62 Pa -

F03 Engineering
222 5010 222 5010 62 Pa -
Room

F04 Manager 222 5010 222 5010 62 Pa -


Room

F05 Central
222 5010 222 5010 62 Pa -
Control Rm.

F06 Telecom 222 5010 222 5010 62 Pa -


Room

F07 Meeting 222 5010 222 5010 - Note.2


Room
F08 Corridor/ 302 N.R 192 N.R - -
/F10 Stair-1

F09 Toilet (M) N.R N.R N.R N.R - Note.2


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 8 of 53

Summer Winter Room Minimum


Rm. Room
Pressure Ventilation Remark
No. Name
DB(C) RH(%) DB(C) RH(%) (Pa) Rate (ACH)

F11 Battery 22.52.5 5010 22.52.5 5010 - Note.2


Room
Notes : 1) DB: Dry Bulb, RH: Relative Humidity, N.R: No Requirement
2) Minimum ventilation rate shall be according to paragraph 2.4.
3) Any temperature, humidity and air filtration requirements of installed equipment to be met.
4) Toilets and showers to take make-up air from air conditioned areas.
5) Ventilation flow rate for Cable Rooms and other ventilated industrial areas to be designed so
that the temperature is no more than 5C above ambient temperature.

2.3. DESIGN CALCULATIONS

1) HVAC System load calculation shall be done in accordance with ASHRAE handbook
methods and computer generated using Carrier E20-II used calculation software. A
psychometric analysis shall be provided for each system with cooling and/or heating
load calculations. A 10% safety margin shall be applied for HVAC load calculation.
This analysis shall be include but not limited to:
A. Mixing temperature of outside and return air
B. Entering air temperature and enthalpy at coil
C. Leaving air temperature and enthalpy at coil
D. Outside air design condition
E. Building R and U values
F. Internal heat gains for installed equipment
G. Internal heat gain basis for Lighting and other miscellaneous equipment
H. Supply air volumes
I. Ventilation air volumes

2) Heat load calculation shall be carried out in accordance with good engineering
practice and Carrier E20-II, HAP ver. 4.4.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 9 of 53

2.4. DESIGN VENTILATION RATES

Minimum ventilation rates shall be as per table below or latest issue of ASHRAE 62 and
SBC-501.
Ventilation and Exhaust Rates
Application Minimum Air Flow Rate
Toilets 72 cfm (36 l/s) per water closet/urinal
Shower Rooms 48 cfm (24 l/s) per shower head
Locker rooms, Pantry,
Ablution, Janitor Room,
Normal storage areas,
0.5 cfm per ft2 (2.6 l/s per m2) floor area
Dressing room, Lunch room,
Water heater rooms, Fire
truck bay
Trash Storage, Workshop,
1.5 cfm per ft2 (7.5 l/s per m2) floor area
Chemical Storage
Office areas and similar 20 cfm (10 l/s) per person
rooms
Kitchen (General Area) 0.7 cfm per ft2 (3.5 l/s per m2) floor area
Minimum ventilation for Battery Rooms shall be 10 air changes per hour.

3. HEAT GAIN FROM OCCUPANTS, LIGHTING FIXTURE AND EQUIPMENT

3.1. HEAT GAIN FROM OCCUPANTS


Sensible Heat Latent Heat
Typical
Degree of Activity Calor sensible Calor latente Remarks
Application
(Watts/Person) (Watts/Person)
Control Seated, very light Based on
70 45 ASHRAE
Room & work
Office Room Fundamentals
Moderate active Handbook
Areas 75 55
office work 2013
Chapter 18
Light bench work 80 140
Table 1
Factory
Light machine work 110 185
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 10 of 53

3.2. HEAT GAIN FROM LIGHTING FIXTURES

Heat Emission
Typical Application Remarks
(Watts/ m2)
Based on ASHRAE Fundamentals
Office 12
Handbook 2013
Chapter 18 Table 2
Electrical / Mechanical 16

Laboratory 15

Restroom 10

Corridor 5

Workshop 20

Warehouse 15
Conference / Meeting /
15
Training

3.3. HEAT DISSIPATION FROM CONTROL & ELECTRICAL PANEL AND EQUIPMENTS

Room Heat emission (W)


Room Name Remarks
No. Electrical Electronic Miscellaneous

B01 Cable Room 24000 Watts - -

G01 Electrical Room 97987 Watts - -

F01 Electrical Room 15580 Watts - - 1

F02 Rack Room - 12378 Watts -

F03 Engineering
- 8762 Watts -
Room
F05 Central Control
- 10088 Watts -
Room
F06 Telecom room 690 Watts - -

F11 Battery room 865 Watts - - 1

Notes : 1) Heat Emission from Electrical Panel and Equipment are informed from Electric
division.
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 11 of 53

4. THERMAL TRANSMITTANCE CALCULATION SHEET

4.1. EXTERNAL ROOF

4.1.1 Concrete Roof (With Ceiling)

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Outside surface - - 0.044


R1
Fully Adhered Single Ply
2 0.00152 0.150 0.0367
EPDM Membrane
3 Fiberboard (Mechanically Fixed) 0.025 0.250 0.1
4 Rigid Polystyrene Insulation 0.1 0.029 3.448
5 Vapor Barrier (P.E Film) - - Neglect
6 Concrete Slab 0.15 1.450 0.104
7 Air space - - 0.170
8 Acoustic Ceiling 0.019 0.060 0.317
9 Inside surface - 0.160

Total resistance (d/) 4.38


U (W / m2K) 0.228
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 12 of 53

4.1.2 Concrete Roof (Without Ceiling)

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Outside surface - - 0.044


R2
Fully Adhered Single Ply
2 0.00152 0.150 0.0367
EPDM Membrane
3 Fiberboard (Mechanically Fixed) 0.025 0.250 0.1
4 Rigid Polystyrene Insulation 0.1 0.029 3.448
5 Vapor Barrier (P.E Film) - - Neglect
6 Concrete Slab 0.15 1.450 0.104
7 Inside surface - 0.160

Total resistance (d/) 3.893


2
U (W / m K) 0.257
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 13 of 53

4.2. EXTERNAL WALL

4.2.1 Concrete Block Wall

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Outside surface - - 0.044


W1
2 Enamel Paint - - Neglect
3 Cement Mortar 0.015 0.970 0.015
4 Concrete Block 0.2 0.768 0.260
5 Vapor Barrier - - 0.150
6 Rigid Polystyrene Insulation 0.05 0.029 1.724
7 Gypsum Board 0.016 0.160 0.1
8 Emulsion Paint - - Neglect
9 Inside surface - - 0.120

Total resistance (d/) 2.413


2
U (W / m K) 0.414
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 14 of 53

4.2.2 Reinforced Concrete Wall

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Outside surface - - 0.044


W2
2 Enamel Paint - - Neglect
3 Reinforced Concrete 0.2 1.450 0.138
4 Vapor Barrier - - 0.150
5 Rigid Polystyrene Insulation 0.05 0.029 1.724
6 Gypsum Board 0.016 0.160 0.1
7 Emulsion Paint - - Neglect
8 Inside surface - - 0.120

Total resistance (d/) 2.276


2
U (W / m K) 0.439
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 15 of 53

4.3. PARTITION WALL (INTERNAL WALL)

4.3.1 Concrete Block Wall

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Inside surface - - 0.120


P1
2 Emulsion Paint - - Neglect
3 Cement Plaster 0.015 0.970 0.015
4 Concrete Block 0.2 0.768 0.260
5 Cement Plaster 0.015 0.970 0.015
6 Emulsion Paint - - Neglect
7 Inside surface - - 0.120

d/ 0.53
U (W / m2K) 1.887
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 16 of 53

4.3.2 Reinforced Concrete Wall

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Inside surface - - 0.120


P2
2 Emulsion Paint - - Neglect
3 Reinforced Concrete 0.2 1.450 0.138
4 Emulsion Paint - - Neglect
5 Inside surface - - 0.120

d/ 0.378
2
U (W / m K) 2.645
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 17 of 53

4.4. FLOOR

4.4.1 Concrete Slab Floor (With Ceiling)

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Inside surface - - 0.160


F1
2 Epoxy Resin Coating - - Neglect
3 Concrete Slab 0.15 1.450 0.104
4 Emulsion Paint - - Neglect
5 Air space - - 0.170
6 Acoustic Ceiling 0.019 0.060 0.317
7 Inside surface - 0.160

d/ 0.911
U (W / m2K) 1.098
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 18 of 53

4.4.2 Concrete Slab Floor (Without Ceiling)

Heat
Thickness Resistance
Conductivity
Part No. Material (d) d/ Remarks
()
(m) (m2K /W)
(W/mK)

1 Inside surface - - 0.160


F2
2 Epoxy Resin Coating - - Neglect
3 Concrete Slab 0.15 1.450 0.104
4 Emulsion Paint - - Neglect
5 Inside surface - 0.160

d/ 0.424
2
U (W / m K) 2.358
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 19 of 53

5. AIR BALANCE SUMMARY

5.1. TECHNICAL AREA (R0TBA-JA001A/B/C/D)

Room Description Transfer Transfer Pressuri


Supply Exhaust Return
air(IN) air(OUT) -zation Remarks
Rm. Room Occu- air(L/s) air(L/s) air(L/s)
(L/s) (L/s) (L/s)
No. Name pants
B01 Cable Room - - 1740 - - 1740 -
Electrical
G01 - 7469 - 1740 450 - 5279
Room
Electrical
F01 - 1318 - 1068 250 - -
Room 1

F02 Rack Room - 1838 - - 170 - 1668


Engineering
F03 4 967 - - 10 - 957
Room
Manager
F04 2 135 - - - - 135
Room
Control
F05 10 1801 - - 280 - 1521 1
Room
Telecom
F06 - 162 - - 60 - 102
Room
Battery
F11 - 1072 1068 - - 2140 - 1
Room

Total 16 14762 2808 2808 1220 3880 9662

Notes: 1. Total Fresh air volume shall be larger than the fresh air volume according
to occupant. (QF > QFO ) : 4370 LPS > 160 LPS
- Centrial System Total Fresh air volume (QF)
QF = Exhaust Air + Pressurization Air = 3140 + 1230 = 4370 LPS
- Requirement Minimum Fresh air volume according to occupant (QFO)
QFO = A x 10 LPS/Person = 16 x 10 LPS/Person = 160 LPS
- A : Total occupant
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 20 of 53

5.2. NON-TECHNICAL AREA (R0TBA-JA002A/B)

Room Description Transfer Transfer Pressuri


Supply Exhaust Return
air(IN) air(OUT) -zation Remarks
Rm. Room Occu- air(L/s) air(L/s) air(L/s)
(L/s) (L/s) (L/s)
No. Name pants
HVAC
G02 - 871 - - - - 871 -
Room

G03 FF Room - 25 - - - - 25 -

G04 Corridor - 108 - 74 - - 34 -


Prayer
G05 6 162 - - - - 162 -
Room
Kitchen
G06 - 73 - - - 73 - -
Area

G07 First Aid 2 125 - - - - 125 -

G08 Air Lock - 13 - - 13 - - -


Shower
G10 - - 110 - - 110 - -
Room (M)
Locker
G11 - 36 74 110 - - - -
Room (M)
Meeting
F07 5 228 - - - - 228
Room
F08 Corridor/
/F10 - 100 - 100 - - -
Stair-1

F09 Toilet (M) - - 100 - - 100 -

Total 13 1741 284 284 13 283 1445

Notes: 1. Total Fresh air volume shall be larger than the fresh air volume according
to occupant. (QF > QFO ) : 296 LPS > 130 LPS
- Centrial System Total Fresh air volume (QF)
QF = Exhaust Air + Pressurization Air = 283 + 13 = 296 LPS
- Requirement Minimum Fresh air volume according to occupant (QFO)
QFO = A x 10 LPS/Person = 13 x 10 LPS/Person = 130 LPS
- A : Total occupant
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 21 of 53

6. HVAC EQUIPMENT SELECTIONS

6.1. AIR HANDLING UNIT

6.1.1 Technical Area (R0TBA-JA001A/B/C/D)

1) Static Pressure Calculation for Supply Fan of Air Handling Unit

Air Static Pressure Remarks


Volume Unit Press. Pressure
(L/s) Part Name Qty
Drop(Pa) Drop(Pa)
14762 Internal Mixing Box 50 1 50 Pressure 1
Pre Filter 100 1 100 drop of fittings
Static are estimated
Pressure Final Filter 250 1 250
75% of total
Cooling Coil (DX Type) 100 1 100 duct pressure
Supply plenum 50 1 50 drop.
Sub Total 550
Safety Factor 55
Safety Factor
: 10 %
Total(a) 605
External Dampers 20 12 240 Internal static 1

Static Sound Attenuator 80 1 80 pressure may


Elec. Duct heating 60 1 60 be changeable
Pressure by vendor data
Humidifier 0 1 0 1

Air Outlet 30 1 30
Blast Protection Damper 100 1 100
Air Intake Stack 30 1 30
Sand Trap Louver 100 1 100
Filter Box 100 1 100
Supply duct (m) 0.6 70 42
Supply duct fitting - - 32
Fresh air duct (m) 1.0 25 25
Fresh air duct fitting - - 19
Sub Total 858
Safety Factor 86 1

Total(b) 944
Total (a)+(b) 1549 1600
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 22 of 53

2) Cooling Load Calculation

Item Calculation Basis Remarks

Refer to Appendix 1
Cooling capacity Sensible capacity : 345.4 kW
Air System Size 1
(qCA) Total Capacity : 475.0 kW
Summary

3) Air Handling Unit Specification

Item Calculation Basis Remarks

Equipment No. R0TBA-JA001A/B/C/D

Quantity 4 Sets (50% x 4 Sets, Two Stand-by)

Location G02-HVAC Room

Cooling Medium R-407C 1

Type Horizontal, Draw-through

Supply Fan 7381 L/s x 1600 Pa x 22.0 kW

Cooling Coil
Type : Direct expansion 1
(qCA)
Sensible capacity : 172.7 kW
Total Capacity : 237.5 kW
Entering Air Temperature : 30.4 DB, 20.8 WB
Leaving Air Temperature : 12.0 DB, 11.7 WB

Electric Source 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 23 of 53

4) Air Cooled Condensing Unit Specification

Item Specification Remarks

Equipment No. R0TBA-JB001A/B/C/D Air-cooled


condensing unit
shall be operable
Type Air cooled, DX Type
at 106 F (41 C)
DB external
Quantity 4 Sets (50% x 4 Sets, Two Stand-by) temperature.

Cooling Capacity 237.5 kW


1
Total Input
112.0 kW
Power for unit

Electric Source 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 24 of 53

6.1.2 Non-Technical Area (R0TBA-JA002A/B)

1) Static Pressure Calculation for Supply Fan of Air Handling Unit

Static Pressure
Air
Volume Unit Remarks
Pressure
(L/s) Part Name Pressure Qty
Drop(Pa)
Drop(Pa)
1741 Internal Mixing Box 50 1 50 Pressure
Pre Filter 100 1 100 drop of fittings
Static are estimated
Pressure Final Filter 250 1 250
75% of total
Cooling Coil (DX Type) 100 1 100 duct pressure
Supply plenum 50 1 50 drop.
Sub Total 550
Safety Factor
Safety Factor 55
: 10 %
Total(a) 605
External Dampers 20 7 140 Internal static 1

Static Sound Attenuator 80 1 80 pressure may


Elec. Duct heating 60 1 60 be changeable
Pressure by vendor data
Humidifier 0 1 0 1

Air Outlet 30 1 30
Blast Protection Damper 100 1 100
Air Intake Stack 30 1 30
Sand Trap Louver 100 1 100
Filter Box 100 1 100
Supply duct (m) 0.6 45 27
Supply duct fitting - - 21
Fresh air duct (m) 1.0 54 54
Fresh air duct fitting - - 41
Sub Total 783
Safety Factor 78 1

Total(b) 861
Total (a)+(b) 1466 1500
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 25 of 53

2) Cooling Load Calculation

Item Calculation Basis Remarks

Refer to Appendix 1
Cooling capacity Sensible capacity : 35.3 kW
Air System Size
(qCA) Total Capacity : 48.3 kW
Summary

3) Air Handling Unit Specification

Item Calculation Basis Remarks

Equipment No. R0TBA-JA002A/B

Quantity 2 Sets (100% x 2 Sets, One Stand-by)

Location G02-HVAC Room

Cooling Medium R-407C 1

Type Horizontal, Draw-through

Supply Fan 1741 L/s x 1500 Pa x 5.5 kW 1

Cooling Coil
Type : Direct expansion
(qCA)
Sensible capacity : 35.3 kW
Total Capacity : 48.3 kW
Entering Air Temperature : 28.0 DB, 19.2 WB
Leaving Air Temperature : 11.5 DB, 11.0 WB

Electric Source 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 26 of 53

4) Air Cooled Condensing Unit Specification

Item Specification Remarks

Equipment No. R0TBA-JB002A/B Air-cooled


condensing unit
shall be operable
Type Air cooled, DX Type
at 106 F (41 C)
DB external
Quantity 2 Sets (100% x 2 Sets, One Stand-by) temperature.

Cooling Capacity 48.3 kW

Total Input
25.2 kW 1
Power for unit

Electric Source 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 27 of 53

6.2. ELECTRIC DUCT HEATER

6.2.1 Technical Area - Electrical Zone (R0TBA-JH001)

Item Calculation Basis Remarks


Refer to Appendix 1
Heat Loss
qHL = 16759 W Space Design load
(qHL)
Summary
Supply Air Refer to Para.5.1
QS = 8787 L/s 1
Volume (QS) Air Balance Summary
Return Air QR1 TR1 + QR2 TR2 TR1 : Control & Rack
Temp.(TR) TR = ----------------------------------------- Room Zone
QR temp.= 22.0
4383 22.0 + 5279 x 19.0
TR2 : Electrical Zone
= -----------------------------------------
temp.= 19.0
9662
= 20.3 DB
QR1 : Control & Rack Zone Return Air Volume
= 4383 L/s
QR2 : Electrical Zone Return Air Volume
= 5279 L/s
QR : Total Return Air Volume
= 9662 L/s
Mixed Air QO TO + QR TR To : Ambient design
Temp. (TM) TM = --------------------------------------- temp.= 8.0
QTS TR : Return Air Temp.
5100 8.0 + 9662 20.3 = 20.3
= --------------------------------------- QO : Outside Air
14762 Volume
= 16.1 DB = 5100 L/s
QTS : Total Supply
Air Volume
= 14762 L/s
qHL
Discharged 1.23 : Constant value
TD = TR + --------------------------
Air Temp.(TD)
1.23 QS (kJ/ m3)
16759 TR: Room design temp.
= 19.0 + ----------------------- = 19.0
1.23 8787
= 20.6 DB
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 28 of 53

qH = 1.23 t QS TM = Mixed Air Temp.


Heating
Capacity (qH) = 16.1 ()
= 1.23 4.5 x 8787 1
t: Differential Temp.
= 48636 W 48.6 kW TD TM
= 20.6 16.1 = 4.5 ()

Electric Duct Equip. No. : R0TBA-JH001


Heater Quantity : 1 Set
Specification
Air Volume : 8787 L/s
Service Area : Electrical Zone
Type : Electric, duct mounted
Capacity : 48.6 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 29 of 53

6.2.2 Technical Area - Control Zone (R0TBA-JH002)

Item Calculation Basis Remarks


Refer to Appendix 1
Heat Loss
qHL = 4473 W Space Design load
(qHL)
Summary
Supply Air Refer to Para.5.1
QS = 3065 L/s
Volume (QS) Air Balance Summary
Return Air QR1 TR1 + QR2 TR2 TR1 : Control & Rack
Temp.(TR) TR = ----------------------------------------- Room Zone 1
QR temp.= 22.0
4383 22.0 + 5279 x 19.0
TR2 : Electrical Zone
= -----------------------------------------
temp.= 19.0
9662
= 20.3 DB
QR1 : Control & Rack Zone Return Air Volume
= 4383 L/s
QR2 : Electrical Zone Return Air Volume
= 5279 L/s
QR : Total Return Air Volume
= 9662 L/s
Mixed Air QO TO + QR TR To : Ambient design
Temp. (TM) TM = --------------------------------------- temp.= 8.0
QTS TR : Return Air Temp.
5100 8.0 + 9662 20.3 = 20.3
= --------------------------------------- QO : Outside Air
14762 Volume
= 16.1 DB = 5100 L/s
QTS : Total Supply
Air Volume
= 14762 L/s
qHL
Discharged 1.23 : Constant value
TD = TR + --------------------------
Air Temp.(TD)
1.23 QS (kJ/ m3)
4473 TR: Room design temp.
= 22.0 + ----------------------- = 22.0
1.23 3065
= 23.2 DB
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 30 of 53

qH = 1.23 t QS TM = Mixed Air Temp.


Heating
Capacity (qH) = 16.1 ()
= 1.23 7.1 x 3065
t: Differential Temp.
= 26766 W 26.8 kW TD TM 1
= 23.2 16.1 = 7.1 ()

Electric Duct Equip. No. : R0TBA-JH002


Heater Quantity : 1 Set
Specification
Air Volume : 3065 L/s
Service Area : Control Zone
Type : Electric, duct mounted
Capacity : 26.8 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 31 of 53

6.2.3 Technical Area - Rack Room (R0TBA-JH003)

Item Calculation Basis Remarks


Refer to Appendix 1
Heat Loss
qHL = 2634 W Space Design load
(qHL)
Summary
Supply Air Refer to Para.5.1
QS = 1838 L/s
Volume (QS) Air Balance Summary
Return Air QR1 TR1 + QR2 TR2 TR1 : Control & Rack
Temp.(TR) TR = ----------------------------------------- Room Zone 1
QR temp.= 22.0
4383 22.0 + 5279 x 19.0
TR2 : Electrical Zone
= -----------------------------------------
temp.= 19.0
9662
= 20.3 DB
QR1 : Control & Rack Zone Return Air Volume
= 4383 L/s
QR2 : Electrical Zone Return Air Volume
= 5279 L/s
QR : Total Return Air Volume
= 9662 L/s
Mixed Air QO TO + QR TR To : Ambient design
Temp. (TM) TM = --------------------------------------- temp.= 8.0
QTS TR : Return Air Temp.
5100 8.0 + 9662 20.3 = 20.3
= --------------------------------------- QO : Outside Air
14762 Volume
= 16.1 DB = 5100 L/s
QTS : Total Supply
Air Volume
= 14762 L/s
qHL
Discharged 1.23 : Constant value
TD = TR + --------------------------
Air Temp.(TD)
1.23 QS (kJ/ m3)
2634 TR: Room design temp.
= 22.0 + ----------------------- = 22.0
1.23 1838
= 25.6 DB
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 32 of 53

qH = 1.23 t QS TM = Mixed Air Temp.


Heating
Capacity (qH) = 16.1 ()
= 1.23 9.5 x 1838
t: Differential Temp. 1
= 21477 W 21.5 kW TD TM
= 25.6 16.1 = 9.5 ()

Electric Duct Equip. No. : R0TBA-JH003


Heater Quantity : 1 Set
Specification
Air Volume : 1838 L/s
Service Area : Rack Room
Type : Electric, duct mounted
Capacity : 21.5 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 33 of 53

6.2.4 Technical Area - Battery Room (R0TBA-JH004)

Item Calculation Basis Remarks


Refer to Appendix 1
Heat Loss
qHL = 2727 W Space Design load
(qHL)
Summary
Supply Air Refer to Para.5.1
QS = 1072 L/s
Volume (QS) Air Balance Summary
Return Air QR1 TR1 + QR2 TR2 TR1 : Control & Rack
Temp.(TR) TR = ----------------------------------------- Room Zone 1
QR temp.= 22.0
4383 22.0 + 5279 x 19.0
TR2 : Electrical Zone
= -----------------------------------------
temp.= 19.0
9662
= 20.3 DB
QR1 : Control & Rack Zone Return Air Volume
= 4383 L/s
QR2 : Electrical Zone Return Air Volume
= 5279 L/s
QR : Total Return Air Volume
= 9662 L/s
Mixed Air QO TO + QR TR To : Ambient design
Temp. (TM) TM = --------------------------------------- temp.= 8.0
QTS TR : Return Air Temp.
5100 8.0 + 9662 20.3 = 20.3
= --------------------------------------- QO : Outside Air
14762 Volume
= 16.1 DB = 5100 L/s
QTS : Total Supply
Air Volume
= 14762 L/s
qHL
Discharged 1.23 : Constant value
TD = TR + --------------------------
Air Temp.(TD)
1.23 QS (kJ/ m3)
2727 TR: Room design temp.
= 22.5 + ----------------------- = 22.5
1.23 1072
= 24.6 DB
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 34 of 53

qH = 1.23 t QS TM = Mixed Air Temp.


Heating
Capacity (qH) = 16.1 ()
= 1.23 8.5 x 1072 1
t: Differential Temp.
= 11207 W 11.2 kW TD TM
= 24.6 16.1 = 8.5 ()

Electric Duct Equip. No. : R0TBA-JH004


Heater Quantity : 1 Set
Specification
Air Volume : 1072 L/s
Service Area : Battery Room
Type : Electric, duct mounted
Capacity : 11.2 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 35 of 53

6.2.5 Non-Technical Area - Office Zone (R0TBA-JH005)

Item Calculation Basis Remarks


Refer to Appendix 1
Heat Loss
qHL = 2527 W Space Design load
(qHL)
Summary
Supply Air Refer to Para.5.2
QS = 615 L/s
Volume (QS) Air Balance Summary
Return Air QR1 TR1 + QR2 TR2 TR1 : Office Zone temp.
Temp.(TR) TR = ----------------------------------------- = 22.0
QR
TR2 : Service Zone temp.
515 22.0 + 930 x 19.0
= 19.0
= -----------------------------------------
1445
= 20.1 DB
QR1 : Office Zone Return Air Volume
= 515 L/s
QR2 : Service Zone Return Air Volume
= 930 L/s
QR : Total Return Air Volume
= 1445 L/s
Mixed Air QO TO + QR TR To : Ambient design
Temp. (TM) TM = --------------------------------------- temp.= 8.0
QTS TR : Return Air Temp.
296 8.0 + 1445 20.1 = 20.1
= --------------------------------------- QO : Outside Air
1741 Volume
= 18.1 DB = 296 L/s
QTS : Total Supply
Air Volume
= 1741 L/s
qHL
Discharged 1.23 : Constant value
TD = TR + --------------------------
Air Temp.(TD)
1.23 QS (kJ/ m3)
2527 TR: Room design temp.
= 22.0 + ------------------------ = 22.0
1.23 615
= 25.4 DB
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 36 of 53

qH = 1.23 t QS TM = Mixed Air Temp.


Heating
Capacity (qH) = 18.1 ()
= 1.23 7.3 x 615
t: Differential Temp.
= 5522 W 5.6 kW TD TM
= 25.4 18.1 = 7.3 ()

Electric Duct Equip. No. : R0TBA-JH005


Heater Quantity : 1 Set
Specification
Air Volume : 615 L/s
Service Area : Office Zone
Type : Electric, duct mounted
Capacity : 5.6 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 37 of 53

6.2.6 Non-Technical Area - Service Zone (R0TBA-JH006)

Item Calculation Basis Remarks


Refer to Appendix 1
Heat Loss
qHL = 6538 W Space Design load
(qHL)
Summary
Supply Air Refer to Para.5.2
QS = 1126 L/s
Volume (QS) Air Balance Summary
Return Air QR1 TR1 + QR2 TR2 TR1 : Office Zone temp.
Temp.(TR) TR = ----------------------------------------- = 22.0
QR
TR2 : Service Zone temp.
515 22.0 + 930 x 19.0
= 19.0
= -----------------------------------------
1445
= 20.1 DB
QR1 : Office Zone Return Air Volume
= 515 L/s
QR2 : Service Zone Return Air Volume
= 930 L/s
QR : Total Return Air Volume
= 1445 L/s
Mixed Air QO TO + QR TR To : Ambient design
Temp. (TM) TM = --------------------------------------- temp.= 8.0
QTS TR : Return Air Temp.
296 8.0 + 1445 20.1 = 20.1
= --------------------------------------- QO : Outside Air
1741 Volume
= 18.1 DB = 296 L/s
QTS : Total Supply
Air Volume
= 1741 L/s
qHL
Discharged 1.23 : Constant value
TD = TR + --------------------------
Air Temp.(TD)
1.23 QS (kJ/ m3)
6538 TR: Room design temp.
= 19.0 + ------------------------ = 19.0
1.23 1126
= 23.8 DB
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 38 of 53

qH = 1.23 t QS TM = Mixed Air Temp.


Heating
Capacity (qH) = 18.1 ()
= 1.23 5.7 x 1126
t: Differential Temp.
= 7895 W 7.9 kW TD TM
= 23.8 18.1 = 5.7 ()

Electric Duct Equip. No. : R0TBA-JH006


Heater Quantity : 1 Set
Specification
Air Volume : 1126 L/s
Service Area : Service Zone
Type : Electric, duct mounted
Capacity : 7.9 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 39 of 53

6.3. ELECTRIC HUMIDIFIER

6.3.1 Technical Area (R0TBA-JG001)


Remarks
Item Calculation Basis
Supply Air Refer to Para. 5.1
Volume (QS) QS = 14762 L/S
Air Balance Summary
Mixed Air QO HO + QR HR Ho: Absolute 1
Humidity.( HM) HM = --------------------------------------- humidity Outdoor
QS = 0.00298 kg/kg'
5100 0.00298 + 9662 0.00819 HR : Return Air Humidity
= --------------------------------------------------- = 0.00819 kg/kg'
14762 QO : Outside Air Volume
= 5100 L/S
= 0.00639 kg/kg'
QR : Return Air Volume
= 9662 L/S
QS : Supply Air Volume
= 14762 L/s
QHU = x QS x dH (Absolute humidity difference) Inside absolute
Humidity Load
= 1.2x14762x3.6x(0.00819-0.00639) Humidity : 0.00819 kg/kg'
= 114.8 kg/hr x 1.1 (S.F) 1.2: Air density (kg/ m3)
= 126.3 kg/hr Safety Factor: 10 %
Humidifier Cap. : 126.3 kg/hr
Water Boiling Heat 5 to 100: 95 kcal/kg
Latent heat (100 water to 100 steam):540 kcal/kg
= 126.3 x (95+540)/860 = 93.3 kW
Electric Equip. No. : R0TBA-JG001
Humidifier
Specification Quantity : 1 Set
Service Area : Technical Area
Type : Electrode
Capacity : 126.3 kg/hr 1
Electric power : 93.3 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 40 of 53

6.3.2 Non-Technical Area (R0TBA-JG002)

Item Calculation Basis Remarks


Supply Air Refer to Para. 5.2
Volume (QS) QS = 1741 L/S
Air Balance Summary
Mixed Air QO HO + QR HR Ho: Absolute
Humidity.( HM) HM = --------------------------------------- humidity Outdoor
QS = 0.00298 kg/kg'
296 0.00298 + 1445 0.00819 HR : Return Air Humidity
= ------------------------------------------------ = 0.00819 kg/kg'
1741 QO : Outside Air Volume
= 296 L/S
= 0.00731 kg/kg'
QR : Return Air Volume
= 1445 L/S
QS : Supply Air Volume
= 1741 L/s
QHU = x QS x dH (Absolute humidity difference) Inside absolute
Humidity Load
= 1.2x1741x3.6x(0.00819-0.00731) Humidity : 0.00819 kg/kg'
= 6.62 kg/hr x 1.1 (S.F) 1.2: Air density (kg/ m3)
= 7.3 kg/hr Safety Factor: 10 %
Humidifier Cap. : 7.3 kg/hr
Water Boiling Heat 5 to 100: 95 kcal/kg
Latent heat (100 water to 100 steam):540 kcal/kg
= 7.3 x (95+540)/860 = 5.4 kW
Electric Equip. No. : R0TBA-JG002
Humidifier
Specification Quantity : 1 Set
Service Area : Non-Technical Area
Type : Electrode
Capacity : 7.3 kg/hr
Electric power : 5.4 kW
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 41 of 53

6.4. VENTILATION FAN

6.4.1 F11-Battery Room (R0TBA-JF001A/B)

Item Description Remarks


Sensible
Ventilation Rm. Room Air Refer to Para.5.1
heat Selected
Airflow No. Name Change(QE) Air Balance Summary
load(QS)
Rate (Q)
F11 Battery Room 2140 1072 2140 V : Volume of the
related room,
Selected Airflow Rate 2140 L/s [Unit : m3]
1) QE = V ACH / 3.6
ACH: Air Change Rate 1
QE1 = 770 10 / 3.6 = 2139 L/s 2140 L/s per hour
2) Supply air volume by room sensible heat load (QS)
Supply air volume for this room by sensible heat load 3.6 : Conversion
factor(m/hr L/s)
QS1 = 1072 L/s
3) Therefore, ventilation airflow rate shall be selected Safety Factor: 10 %
to larger value.= 2140 L/s
Pressure drop of fittings
Pressure
Static Part Pressure Drop are estimated 75% of
Part Name Drop
Pressure Qty (Pa) total duct pressure drop.
(Pa/Part)
(SP)
Air device 30 1 30 BPD : Blast Protection
Damper 30 2 60 Damper
1
BPD 120 1 120
Duct 1.0 20 20
Fitting - - 15
Sub-Total (1) 245
1
Safety Factor (2) 25
Total (1)+(2) 270 300
Fan Equip. No.
Specificatio : R0TBA-JF001A/B
ns Quantity : 2 Sets (100% x 2 Sets, One Stand-by)
Location : F11-Battery Room
Type : Centrifugal, Duct In-Line,
Explosion Proof Type
Capacity : 2140 L/s 300 Pa x 2.20 kW
1
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 42 of 53

6.4.2 Kitchen & Shower (M) (R0TBA-JF002)

Item Description Remarks


Sensible
Ventilation Rm. Room Air Refer to Para.5.2
heat Selected
Airflow No. Name Change(QE) Air Balance Summary
load(QS)
Rate (Q)
G06 Kitchen Area 50 73 73 A : Area of the
related room,
G10 Shower Rm. 110 - 110 [Unit : m2]
Total 183 L/s N : Water closet,
1) QE = A 3.5 L/s/ Urinal, Shower
Total Quantity
QE1 = 13.2 3.5 = 46.2 L/s 50 L/s
2) QE = (N 24 L/s(Shower Head)) Safety Factor: 10 %
+ (N 36 L/s(Water closet, Urinal))
QE2 = (3 24)+(1 x 36) = 108 L/s 110 L/s Pressure drop of fittings
3) Supply air volume by room sensible heat load (QS) are estimated 75% of
Supply air volume for this room by sensible heat load total duct pressure drop.
QS1 = 73 L/s QE1,QS1
4) Therefore, ventilation airflow rate shall be selected
: G06-Kitchen Area
to larger value.= 183 L/s
Pressure QE2
Static Part Pressure Drop
Part Name Drop : G10-Shower Room
Pressure Qty (Pa)
(Pa/Part)
(SP)
Air device 30 1 30 BPD : Blast Protection
Damper
Damper 30 2 60
BPD 100 1 100
Duct 1.0 15 15
Fitting - - 11
Sub-Total (1) 216
Safety Factor (2) 22
Total (1)+(2) 238 250
Fan Equip. No.
Specificatio : R0TBA-JF002
ns Quantity : 1 Set
Location : G06-Kitchen Area
Type : Centrifugal, Duct In-Line
Capacity : 183 L/s 250 Pa x 0.37 kW 1

Electric Source : 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 43 of 53

6.4.3 1st FL. F09-Toilet (M) (R0TBA-JF003)

Item Description Remarks

Ventilation 1) QE = N 36 L/s/(Water closet, Urinal) Refer to Para.5.2


Airflow QE1 = 2 36 = 72 L/s 100 L/s Air Balance Summary
Rate (Q)
N : Water closet,
Urinal, Shower
Total Quantity
A : Area of the
related room,
Pressure [Unit : m2]
Static Part Pressure Drop
Part Name Drop
Pressure Qty (Pa) Safety Factor: 10 %
(Pa/Part)
(SP)
Air device 30 1 30
Pressure drop of fittings
Damper 30 1 30 are estimated 75% of
total duct pressure drop.
BPD 100 1 100
QE1 : F09-Toilet (M)
Duct 1.0 15 15
BPD : Blast Protection
Fitting - - 12
Damper

Sub-Total (1) 187


Safety Factor (2) 19
Total (1)+(2) 206 250
Fan
Specificatio Equip. No. : R0TBA-JF003
ns Quantity : 1 Set
Location : F09-Toilet (M)
Type : Centrifugal, Duct In-Line
Capacity : 100 L/s 250 Pa x 0.37 kW 1

Electric Source : 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 44 of 53

6.4.4 B01-Cable Room Supply Air (R0TBA-JE001)

Item Description Remarks

Ventilation 1) Ventilation Fan volume by room sensible heat load (QS) A : Area of the
Airflow Ventilation Fan volume for this room by sensible related room,
Rate (Q) heat load [Unit : m2]
a) Heat emission (qs)
Safety Factor: 10 %
- Electrical Heat emission (qe) : 24000 W(24.0 kW)
- Fabric and Solar (qf) : 9091 W (9.1 kW) Specific heat (Cp)
: 1005 J/kg.C
- Total : qs = qe+qf
= 24.0 + 9.1 = 33.1 kW Air density (p)
: 0.0011 kg/liter
b) Outside Air Temperature (To) : 41.0 CDB (Density of air at 41 C)
c) Room Temperature (Tr1) : 46.0 CDB
qe : Refer to 3.3
d) Electrical Room Temperature (Tr2) : 27.0 CDB Heat Dissipation
e) Temperature difference (dT= Tr1 - Tr2) : 19.0 CDB from Control &
Q s = qs/(Cp x x dT) x S.F Electrical Panel and
Equipments
= 33.1 x 1000 / ( 1005 x 0.0011 x 19.0 ) x 1.1
qf : Refer to
= 1733 L/s 1740 L/s
APPENDIX 2.
2) Therefore, ventilation airflow rate (Q) : 1740 L/s Space Design Load
Pressure Drop Part Pressure Drop Summary
Static Part Name
(Pa/Part) Qty (Pa)
Pressure BPD : Blast Protection
(SP) Air device 30 2 60 Damper
Damper 30 2 60
Duct 1.0 35 35
Fitting - - 26

Sub-Total (1) 181


Safety Factor (2) 18
Total (1)+(2) 199 200
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 45 of 53

Fan
Specificatio Equip. No. : R0TBA-JE001
ns Quantity : 1 Set
Location : B01-Cable Room
Type : Centrifugal, Duct In-Line
Capacity : 1740 L/s 200 Pa x 1.50 kW
1

Electric Source : 460V / 3Ph / 60Hz

6.4.5 B01-Cable Room Exhaust Air (R0TBA-JF004)

Item Description Remarks

Ventilation 1) Q = 100% of Supply Air Volume


Safety Factor: 10 %
Airflow = 1740 L/s
Rate (Q)
Supply Air Volume
Refer to Para 6.4.4
Pressure
Static Part Pressure Drop BPD : Blast Protection
Part Name Drop
Pressure Qty (Pa) Damper
(Pa/Part)
(SP)
Air device 30 1 30
Damper 30 2 60
BPD 100 1 100
Duct 1.0 35 35
Fitting - - 26
Sub-Total (1) 251
Safety Factor (2) 25
Total (1)+(2) 276 300
Fan
Specificatio Equip. No. : R0TBA-JF004
ns Quantity : 1 Set
Location : B01-Cable Room
Type : Centrifugal, Duct In-Line
Capacity : 1740 L/s 300 Pa x 1.50 kW

Electric Source : 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 46 of 53

6.5. SMOKE EXTRACTION FAN

6.5.1 G01-Electrical Room (R0TBA-JF005)

Item Description Remarks

Ventilation 1) QE = V ACH / 3.6 V : Volume of the


Airflow = 2304 x 6 / 3.6 = 3840 L/s related room,
Rate (Q) Minimum Air Change Rate : 6 ACH [Unit : m3]
Pressure
Static Part Pressure Drop ACH: Air Change Rate
Part Name Drop per hour
Pressure Qty (Pa)
(Pa/Part)
(SP)
Air device 30 1 30 3.6 : Conversion
factor(m/hr L/s)
Damper 30 1 30
BPD 150 1 150 Safety Factor: 10 %
1

Duct 1.0 30 30 Pressure drop of fittings


Fitting - - 22 are estimated 75% of
total duct pressure drop.

BPD : Blast Protection


Damper
Sub-Total (1) 262
Safety Factor (2) 26 1

Total (1)+(2) 288 300


Fan
Specificatio Equip. No. : R0TBA-JF005
ns Quantity : 1 Set
Location : G01-Electrical Room
Type : Centrifugal, Duct In-Line
Capacity : 3840 L/s 300 Pa x 3.70 kW 1

Electric Source : 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 47 of 53

6.5.2 F01-Electrical Room (R0TBA-JF006)

Item Description Remarks

Ventilation 1) QE = V ACH / 3.6 V : Volume of the


Airflow = 1050 x 6 / 3.6 = 1750 L/s 1750 L/s related room, 1
Rate (Q) Minimum Air Change Rate : 6 ACH [Unit : m3]
Pressure
Static Part Pressure Drop ACH: Air Change Rate
Part Name Drop per hour
Pressure Qty (Pa)
(Pa/Part)
(SP)
Air device 30 1 30 3.6 : Conversion
factor(m/hr L/s)
Damper 30 1 30
BPD 100 1 100 Safety Factor: 10 %

Duct 1.0 20 20 Pressure drop of fittings


Fitting - - 15 are estimated 75% of
total duct pressure drop.

BPD : Blast Protection


Damper
Sub-Total (1) 195
Safety Factor (2) 20
Total (1)+(2) 215 250
Fan
Specificatio Equip. No. : R0TBA-JF006
ns Quantity : 1 Set
Location : F01-Electrical Room
Type : Centrifugal, Duct In-Line
1
Capacity : 1750 L/s 250 Pa x 1.50 kW

Electric Source : 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 48 of 53

6.5.3 F05-Central Control Room (R0TBA-JF007)

Item Description Remarks

Ventilation 1) QE = V ACH / 3.6 V : Volume of the


Airflow = 630 x 6 / 3.6 = 1050 L/s related room,
Rate (Q) Minimum Air Change Rate : 6 ACH [Unit : m3]
Pressure
Static Part Pressure Drop ACH: Air Change Rate
Part Name Drop per hour
Pressure Qty (Pa)
(Pa/Part)
(SP)
Air device 30 1 30 3.6 : Conversion
factor(m/hr L/s)
Damper 30 1 30
BPD 200 1 200 Safety Factor: 10 % 1

Duct 1.0 20 20 Pressure drop of fittings


Fitting - - 15 are estimated 75% of
total duct pressure drop.

BPD : Blast Protection


Damper
Sub-Total (1) 295
1
Safety Factor (2) 30
Total (1)+(2) 325 350
Fan
Specificatio Equip. No. : R0TBA-JF007
ns Quantity : 1 Set
Location : F05-Central Control Room
Type : Centrifugal, Duct In-Line
Capacity : 1050 L/s 350 Pa x 1.00 kW 1

Electric Source : 460V / 3Ph / 60Hz


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 49 of 53

7. PLUMBING SYSTEM CALCULATION

7.1. POTABLE WATER DEMAND CALCULATION

7.1.1 CONTROL BUILDING

Item Description Remarks


Piping
Poly Propylene Pipe Based on 2012
Material
Uniform
Velocity It shall not exceed 2.0 m/s Plumbing,
Chapter 6,
Flow Fixture Sub-Total Table 610.3 &
Plumbing Fixture Qty
Demand Unit Fixture Unit Appendix A,
Water Closet Table A.2.1
2.5 2 5.0
(Western Low Tank)
Water Closet
2.5 - -
(Asian High Tank)
Urinal 4.0 1 4.0

Lavatory 1.0 3 3.0

Kitchen Sink 1.5 1 1.5

Shower 2.0 3 6.0


Faucet
2.5 4 10.0
(Hose Bibb)
Service Sink 1.5 1 1.5

Humidifier 2.5 2 5.0

Drinking Fountain 0.5 - -


Emergency
1.0 1 1.0
Eye Washer
Total Fixture Unit 37

Total Flow Rate (L/s) 1.38 (L/s)


Main Pipe
50 mm (2 inch)
Size
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 50 of 53


Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 51 of 53

7.2. ELECTRIC WATER HEATER CALCULATION

7.2.1 G06-Kitchen, G10-Shower Room (M) (R0TBA-JJ001)

Item Description Remarks


Energy
Electric Based on 2011 ASHRAE
Source
Applications Handbook
Warm Water
Required Hot Plumbing Sub-Total Chapter 50.20 Table. 10
Demand Per Qty
Water (QT) Fixture (L/h) - Applied:
Fixture (L/h)
Office building
Lavatory 22 1 22

Shower 110 3 330

Kitchen Sink 75 1 75

Faucet 22 - -

Total 427

Heating Hot Water Demand Qh = Flow rate (L/h)


Capacity (qh)
Qh = QT x = Demand
factor ; 0.3
Qh = 427 x 0.3 = 128.1 L/h 130 L/h
Cp = Specific heat of water
Heating Capacity = 1.0 kcal/kg.C
qh = Qh x Cp x x t
= Density of water
= 130 x 1 x 1 x (55 - 5) x 1.1(S.F) = 1.0 kg/L
= 7150 kcal/hr 8.4 kW t = Temperature rise,
Storage Tank Storage tank Capacity (QS) Qh = Flow rate (L/h)
Capacity (QS)
QS = Qh x = Storage Capacity
factor ; 2.0
= 130 x 2.0 = 260 Liter 300 Liter
Electric Equip No. : R0TBA-JJ001
Water Heater
Specification Quantity : 1 Set
Location : G02-HVAC Room
Type : Storage, Floor Mounted
Heating Cap. : 8.4 kW
Storage Cap. : 300 Liter
Elec. Power : 8.4 kW 1
Electric Source : 460V / 3Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 52 of 53

7.2.2 F09-Toilet (M) (R0TBA-JJ002)

Item Description Remarks


Energy
Electric Based on 2011 ASHRAE
Source
Applications Handbook
Warm Water
Required Hot Plumbing Sub-Total Chapter 50.20 Table. 10
Demand Per Qty
Water (QT) Fixture (L/h) - Applied:
Fixture (L/h)
Office building
Lavatory 22 2 44

Shower 110 - -

Kitchen Sink 75 - -

Faucet 22 - -

Total 44

Heating Hot Water Demand Qh = Flow rate (L/h)


Capacity (qh)
Qh = QT x = Demand
factor ; 0.3
Qh = 44 x 0.3 = 13.2 L/h 15 L/h
Cp = Specific heat of water
Heating Capacity = 1.0 kcal/kg.C
qh = Qh x Cp x x t
= Density of water
= 15 x 1 x 1 x (55 - 5) x 1.1(S.F) = 1.0 kg/L
= 825 kcal/hr 1.0 kW t = Temperature rise,
Storage Tank Storage tank Capacity (QS) Qh = Flow rate (L/h)
Capacity (QS)
QS = Qh x = Storage Capacity
factor ; 2.0
= 15 x 2.0 = 30 Liter 30 Liter
Electric Equip No. : R0TBA-JJ002
Water Heater
Specification Quantity : 1 Set
Location : F09-Toilet (M)
Type : Storage, Wall Mounted
Heating Cap. : 1.0 kW
Storage Cap. : 30 Liter
Elec. Power : 1.0 kW
Electric Source : 230V / 1Ph / 60Hz
Document No.
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS SECL-R0-HV-CA-
TBA-0001
ISSUE DATE HVAC & PLUMBING CALCULATION REV 1

23-FEB-2015 FOR CONTROL BUILDING PAGE 53 of 53

8. APPENDICES

Appendix 1 HVAC Load Calculation Output data (E20-II)

Appendix 2 Pressurization Air Volume Calculation

Appendix 3 Psychrometric Chart


SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

APPENDIX 1
HVAC LOAD CALCULATION OUTPUT DATA (E20-II)
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

TECHNICAL AREA
(R0TBA-JA001A/B/C/D)
Air System Sizing Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Air System Information


Air System Name ...................... CCB-TECHNICAL AREA Number of zones .............................................................. 3
Equipment Class .............................................. SPLT AHU Floor Area................................................................ 1288.8 m
Air System Type ....................................................... 2DMZ Location .................................. Ras Tanura, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s ................................Sum of space airflow rates Calculation Months ........................................... Jan to Dec
Space L/s ............................Individual peak space loads Sizing Data ....................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ............................................................ 475.0 kW Load occurs at ...................................................... Jul 1500
Sensible coil load ...................................................... 345.4 kW OA DB / WB ...................................................... 41.0 / 27.0 C
Coil L/s at Jul 1500 ................................................... 14122 L/s Entering DB / WB .............................................. 30.4 / 20.8 C
Max block L/s ........................................................... 14761 L/s Leaving DB / WB ............................................... 12.0 / 11.7 C
Sum of peak zone L/s .............................................. 14761 L/s Coil ADP ...................................................................... 10.1 C
Sensible heat ratio .................................................... 0.727 Bypass Factor ........................................................... 0.100
m/kW ............................................................................ 2.7 Resulting RH .................................................................. 45 %
W/m .......................................................................... 368.5 Design supply temp. .................................................... 12.0 C
Water flow @ 5.6 K rise .............................................. N/A Zone T-stat Check ..................................................... 3 of 3 OK
Max zone temperature deviation ................................... 0.0 K

Central Heating Coil Sizing Data

Max coil load ............................................................... 67.9 kW Load occurs at ...................................................... Des Htg
Coil L/s at Des Htg ..................................................... 6752 L/s W/m ............................................................................ 52.7
Max coil L/s ................................................................ 6752 L/s Ent. DB / Lvg DB ............................................... 17.3 / 25.6 C
Water flow @ 11.1 K drop........................................... N/A

Supply Fan Sizing Data

Actual max L/s .......................................................... 14762 L/s Fan motor BHP.......................................................... 39.59 BHP
Standard L/s ............................................................. 14732 L/s Fan motor kW .............................................................. 22.0 kW
Actual max L/(s-m) ................................................... 11.45 L/(s-m) Fan static .................................................................... 1600 Pa

Outdoor Ventilation Air Data


Design airflow L/s ....................................................... 5100 L/s L/s/person................................................................ 318.75 L/s/person
L/(s-m) ........................................................................ 3.96 L/(s-m)

Hourly Analysis Program v.4.4 Page 1 of 1


Zone Sizing Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Air System Information


Air System Name ...................... CCB-TECHNICAL AREA Number of zones .............................................................. 3
Equipment Class .............................................. SPLT AHU Floor Area................................................................ 1288.8 m
Air System Type ....................................................... 2DMZ Location .................................. Ras Tanura, Saudi Arabia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ................................Sum of space airflow rates Calculation Months ........................................... Jan to Dec
Space L/s ............................Individual peak space loads Sizing Data ....................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m) L/(s-m)
Zone 1 158.7 8787 8787 Jul 1600 16.8 690.0 12.73
Zone 2 59.0 4902 4902 Jul 1600 7.1 463.8 10.57
Zone 3 8.1 1072 1072 Jul 1900 2.7 135.0 7.94

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m) L/(s-m)
Zone 1
CCB-F01-ELECTRICAL ROOM 1 23.8 Jul 1900 1318 1.4 210.0 6.28
CCB-G01-ELECTRICAL ROOM 1 135.0 Jul 1600 7469 15.4 480.0 15.56
Zone 2
CCB-F02-RACK ROOM 1 22.1 Jul 1800 1838 2.6 180.0 10.21
CCB-F05-CONTROL ROOM 1 21.7 Jul 1600 1801 3.1 210.0 8.57
CCB-F03-ENGINEERING ROOM 1 11.6 Jul 1600 967 0.4 44.0 21.97
CCB-F06-TELECOM ROOM 1 1.9 Aug 1700 162 0.5 13.8 11.70
CCB-F04-MANAGER ROOM 1 1.6 Jul 1500 135 0.4 16.0 8.46
Zone 3
CCB-F11-BATTERY ROOM 1 8.1 Jul 1900 1072 2.7 135.0 7.94

Hourly Analysis Program v.4.4 Page 1 of 1


Ventilation Sizing Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

1. Summary
Ventilation Sizing Method ........................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ....................................................................... 5100 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m) Occupants (L/s) (L/s/person) (L/(s-m)) (L/s) (% of supply) (L/s)
Zone 1
CCB-F01-ELECTRICAL ROOM 1 210.0 0.0 1318.0 0.00 0.00 1318.0 0.0 1318.0
CCB-G01-ELECTRICAL ROOM 1 480.0 0.0 7469.1 0.00 0.00 2190.0 0.0 2190.0
Zone 2
CCB-F02-RACK ROOM 1 180.0 0.0 1838.1 0.00 0.00 170.0 0.0 170.0
CCB-F05-CONTROL ROOM 1 210.0 10.0 1800.5 0.00 0.00 280.0 0.0 280.0
CCB-F03-ENGINEERING ROOM 1 44.0 4.0 966.6 0.00 0.00 10.0 0.0 10.0
CCB-F06-TELECOM ROOM 1 13.8 0.0 161.5 0.00 0.00 60.0 0.0 60.0
CCB-F04-MANAGER ROOM 1 16.0 2.0 135.3 0.00 0.00 0.0 0.0 0.0
Zone 3
CCB-F11-BATTERY ROOM 1 135.0 0.0 1072.0 0.00 0.00 1072.0 0.0 1072.0
Totals (incl. Space Multipliers) 14761.3 5100.0

Hourly Analysis Program v.4.4 Page 1 of 1


Air System Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 850 m 6646 - 850 m 4567 -
Roof Transmission 809 m 4445 - 809 m 2439 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 18 m 436 - 18 m 358 -
Floor Transmission 1099 m 20606 - 1099 m 15380 -
Partitions 316 m 2486 - 316 m 1227 -
Ceiling 12 m 173 - 12 m 46 -
Overhead Lighting 21927 W 21926 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 146830 W 146823 - 0 0 -
People 16 1120 720 0 0 0
Infiltration - 171 218 - 152 6
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 20483 94 10% 2417 1
>> Total Zone Loads - 225316 1032 - 26586 7
Zone Conditioning - 222372 1032 - 25820 7
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 14761 L/s 0 - 14761 L/s 0 -
Ventilation Load 5100 L/s 93512 128378 5100 L/s 71647 0
Supply Fan Load 14761 L/s 29524 - 14761 L/s -29524 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 345407 129410 - 67943 7
Central Cooling Coil - 345407 129547 - 0 0
Central Heating Coil - 0 - - 67943 -
>> Total Conditioning - 345407 129547 - 67943 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.4 Page 1 of 1


Zone Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 365 m 2467 - 365 m 1766 -
Roof Transmission 210 m 1107 - 210 m 593 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 12 m 255 - 12 m 225 -
Floor Transmission 508 m 14223 - 508 m 12450 -
Partitions 124 m 715 - 124 m 201 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 11923 W 11923 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 113567 W 113562 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 14425 0 10% 1524 0
>> Total Zone Loads - 158678 0 - 16760 0

Zone 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 348 m 3271 - 348 m 1989 -
Roof Transmission 464 m 2604 - 464 m 1377 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 179 - 6 m 133 -
Floor Transmission 456 m 4964 - 456 m 2134 -
Partitions 106 m 1091 - 106 m 622 -
Ceiling 12 m 173 - 12 m 46 -
Overhead Lighting 7671 W 7671 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 32398 W 32397 - 0 0 -
People 16 1120 720 0 0 0
Infiltration - 169 218 - 152 6
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5364 94 10% 645 1
>> Total Zone Loads - 59000 1032 - 7099 7

Hourly Analysis Program v.4.4 Page 1 of 2


Zone Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Zone 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.3 C / 26.4 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.5 C OCCUPIED T-STAT 21.5 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 137 m 1377 - 137 m 811 -
Roof Transmission 135 m 956 - 135 m 468 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 135 m 1201 - 135 m 796 -
Partitions 86 m 609 - 86 m 403 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 2333 W 2333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 865 W 865 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 734 0 10% 248 0
>> Total Zone Loads - 8075 0 - 2727 0

Hourly Analysis Program v.4.4 Page 2 of 2


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CCB-F01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.3 C / 26.4 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 74 m 587 - 74 m 357 -
Roof Transmission 210 m 1245 - 210 m 593 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 112 - 6 m 112 -
Floor Transmission 28 m 62 - 28 m 0 -
Partitions 86 m 438 - 86 m 201 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3629 W 3629 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 15580 W 15579 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2165 0 10% 126 0
>> Total Zone Loads - 23818 0 - 1390 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CCB-F01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 74 0.439 - 587 - 357
DOOR 6 1.703 - 112 - 112
H EXPOSURE
ROOF 210 0.257 - 1245 - 593

Hourly Analysis Program v.4.4 Page 1 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' CCB-G01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 292 m 1980 - 292 m 1409 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 128 - 6 m 112 -
Floor Transmission 480 m 14145 - 480 m 12450 -
Partitions 38 m 181 - 38 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 8294 W 8294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 97987 W 97983 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 12271 0 10% 1397 0
>> Total Zone Loads - 134982 0 - 15369 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' CCB-G01-ELECTRICAL ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 144 0.439 - 936 - 696
NE EXPOSURE
WALL 77 0.439 - 577 - 371
SW EXPOSURE
WALL 71 0.439 - 467 - 342
DOOR 6 1.703 - 128 - 112

Hourly Analysis Program v.4.4 Page 2 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' CCB-F02-RACK ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 148 m 1453 - 148 m 845 -
Roof Transmission 180 m 1039 - 180 m 534 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 6 m 170 - 6 m 133 -
Floor Transmission 180 m 1882 - 180 m 849 -
Partitions 36 m 101 - 36 m 34 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3110 W 3110 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 12378 W 12377 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2013 0 10% 239 0
>> Total Zone Loads - 22146 0 - 2634 0

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' CCB-F02-RACK ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 86 0.439 - 843 - 488
NE EXPOSURE
WALL 62 0.439 - 610 - 356
DOOR 6 1.703 - 170 - 133
H EXPOSURE
ROOF 180 0.228 - 1039 - 534

Hourly Analysis Program v.4.4 Page 3 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' CCB-F05-CONTROL ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 138 m 1327 - 138 m 786 -
Roof Transmission 210 m 1179 - 210 m 623 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 210 m 2296 - 210 m 990 -
Partitions 49 m 730 - 49 m 439 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 3402 W 3402 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 10088 W 10088 - 0 0 -
People 10 700 450 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1972 45 10% 284 0
>> Total Zone Loads - 21693 495 - 3122 0

TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' CCB-F05-CONTROL ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 80 0.439 - 775 - 456
SE EXPOSURE
WALL 15 0.439 - 143 - 86
SE EXPOSURE
WALL 43 0.439 - 409 - 244
H EXPOSURE
ROOF 210 0.228 - 1179 - 623

Hourly Analysis Program v.4.4 Page 4 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.3.A. COMPONENT LOADS FOR SPACE '' CCB-F03-ENGINEERING ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 44 m 247 - 44 m 131 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 44 m 481 - 44 m 208 -
Partitions 12 m 105 - 12 m 45 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 713 W 713 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8762 W 8762 - 0 0 -
People 4 280 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1059 18 10% 38 0
>> Total Zone Loads - 11646 198 - 422 0

TABLE 2.3.B. ENVELOPE LOADS FOR SPACE '' CCB-F03-ENGINEERING ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
H EXPOSURE
ROOF 44 0.228 - 247 - 131

Hourly Analysis Program v.4.4 Page 5 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.4.A. COMPONENT LOADS FOR SPACE '' CCB-F06-TELECOM ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 40 m 400 - 40 m 228 -
Roof Transmission 14 m 76 - 14 m 41 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 6 m 45 - 6 m 12 -
Partitions 9 m 149 - 9 m 104 -
Ceiling 12 m 170 - 12 m 46 -
Overhead Lighting 238 W 238 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 690 W 690 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 177 0 10% 43 0
>> Total Zone Loads - 1946 0 - 475 0

TABLE 2.4.B. ENVELOPE LOADS FOR SPACE '' CCB-F06-TELECOM ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 13 0.439 - 123 - 71
SE EXPOSURE
WALL 28 0.439 - 277 - 157
H EXPOSURE
ROOF 14 0.228 - 76 - 41

Hourly Analysis Program v.4.4 Page 6 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.5.A. COMPONENT LOADS FOR SPACE '' CCB-F04-MANAGER ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 23 m 220 - 23 m 130 -
Roof Transmission 16 m 89 - 16 m 47 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 16 m 176 - 16 m 75 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 207 W 207 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 480 W 480 - 0 0 -
People 2 140 90 0 0 0
Infiltration - 171 218 - 152 6
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 148 31 10% 41 1
>> Total Zone Loads - 1631 339 - 446 7

TABLE 2.5.B. ENVELOPE LOADS FOR SPACE '' CCB-F04-MANAGER ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 23 0.439 - 220 - 130
H EXPOSURE
ROOF 16 0.228 - 89 - 47

Hourly Analysis Program v.4.4 Page 7 of 8


Space Design Load Summary for CCB-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' CCB-F11-BATTERY ROOM '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.3 C / 26.4 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.5 C OCCUPIED T-STAT 21.5 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 137 m 1377 - 137 m 811 -
Roof Transmission 135 m 956 - 135 m 468 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 135 m 1201 - 135 m 796 -
Partitions 86 m 609 - 86 m 403 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 2333 W 2333 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 865 W 865 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 734 0 10% 248 0
>> Total Zone Loads - 8075 0 - 2727 0

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' CCB-F11-BATTERY ROOM '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 86 0.439 - 867 - 507
SW EXPOSURE
WALL 51 0.439 - 510 - 304
H EXPOSURE
ROOF 135 0.257 - 956 - 468

Hourly Analysis Program v.4.4 Page 8 of 8


SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

NON-TECHNICAL AREA
(R0TBA-JA002A/B)
Air System Sizing Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Air System Information


Air System Name ............. CCB-NON-TECHNICAL AREA Number of zones .............................................................. 3
Equipment Class .............................................. SPLT AHU Floor Area.................................................................. 478.7 m
Air System Type ....................................................... 2DMZ Location .................................. Ras Tanura, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s ................................Sum of space airflow rates Calculation Months ........................................... Jan to Dec
Space L/s ............................Individual peak space loads Sizing Data ....................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .............................................................. 48.3 kW Load occurs at .................................................... Aug 1500
Sensible coil load ........................................................ 35.3 kW OA DB / WB ...................................................... 41.0 / 27.0 C
Coil L/s at Aug 1500 ................................................... 1615 L/s Entering DB / WB .............................................. 28.0 / 19.2 C
Max block L/s ............................................................. 1741 L/s Leaving DB / WB ............................................... 11.5 / 11.0 C
Sum of peak zone L/s ................................................ 1741 L/s Coil ADP ...................................................................... 10.6 C
Sensible heat ratio .................................................... 0.731 Bypass Factor ........................................................... 0.100
m/kW ............................................................................ 9.9 Resulting RH .................................................................. 45 %
W/m .......................................................................... 100.8 Design supply temp. .................................................... 12.0 C
Water flow @ 5.6 K rise .............................................. N/A Zone T-stat Check ..................................................... 3 of 3 OK
Max zone temperature deviation ................................... 0.0 K

Central Heating Coil Sizing Data

Max coil load ................................................................. 9.1 kW Load occurs at ...................................................... Des Htg
Coil L/s at Des Htg ....................................................... 927 L/s W/m ............................................................................ 19.0
Max coil L/s .................................................................. 927 L/s Ent. DB / Lvg DB ............................................... 18.9 / 27.1 C
Water flow @ 11.1 K drop........................................... N/A

Supply Fan Sizing Data

Actual max L/s ............................................................ 1741 L/s Fan motor BHP............................................................ 4.67 BHP
Standard L/s ............................................................... 1737 L/s Fan motor kW .............................................................. 5.5 kW
Actual max L/(s-m) ..................................................... 3.64 L/(s-m) Fan static .................................................................... 1500 Pa

Outdoor Ventilation Air Data


Design airflow L/s ......................................................... 296 L/s L/s/person.................................................................. 17.42 L/s/person
L/(s-m) ........................................................................ 0.62 L/(s-m)

Hourly Analysis Program v.4.4 Page 1 of 1


Zone Sizing Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Air System Information


Air System Name ......... CCB-NON-TECHNICAL AREA Number of zones .......................................................... 3
Equipment Class .......................................... SPLT AHU Floor Area .............................................................. 478.7 m
Air System Type .................................................... 2DMZ Location ............................... Ras Tanura, Saudi Arabia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone L/s ............................ Sum of space airflow rates Calculation Months ....................................... Jan to Dec
Space L/s ........................ Individual peak space loads Sizing Data ................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (kW) (L/s) (L/s) Load (kW) (m) L/(s-m)
Zone 1 6.2 515 515 Aug 1600 1.7 59.0 8.73
Zone 2 17.5 980 980 Aug 1500 5.8 299.3 3.27
Zone 3 4.1 246 246 Aug 1500 1.5 120.4 2.04

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m) L/(s-m)
Zone 1
CCB-G07-FIRST AID 1 1.5 Aug 1800 125 0.5 14.9 8.38
CCB-F07-MEETING ROOM 1 2.7 Aug 1500 228 0.8 25.9 8.80
CCB-G05-PRAYER ROOM 1 2.0 Aug 1700 162 0.5 18.2 8.91
Zone 2
CCB-G02-HVAC ROOM 1 15.7 Aug 1500 871 5.2 272.5 3.20
CCB-G06-KITCHEN AREA 1 1.3 Aug 1700 73 0.3 13.2 5.54
CCB-G11-LOCKER ROOM(M) 1 0.5 Jul 1500 36 0.2 13.6 2.65
Zone 3
CCB-G03-FF ROOM 1 0.5 Jul 1500 25 0.3 14.5 1.71
CCB-G04-Corridor 1 2.3 Aug 1500 108 0.4 51.0 2.11
CCB-F08,F10-Corri,Stair1 1 1.0 Aug 1500 100 0.8 49.4 2.02
CCB-G08-Air Lock 1 0.2 Aug 1600 13 0.1 5.5 2.36

Hourly Analysis Program v.4.4 Page 1 of 1


Ventilation Sizing Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

1. Summary
Ventilation Sizing Method ....................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ...................................................................... 296 L/s

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (m) Occupants (L/s) (L/s/person) (L/(s-m)) (L/s) (% of supply) (L/s)
Zone 1
CCB-G07-FIRST AID 1 14.9 2.0 124.9 0.00 0.00 0.0 0.0 0.0
CCB-F07-MEETING ROOM 1 25.9 5.0 227.8 0.00 0.00 0.0 0.0 0.0
CCB-G05-PRAYER ROOM 1 18.2 6.0 162.2 0.00 0.00 0.0 0.0 0.0
Zone 2
CCB-G02-HVAC ROOM 1 272.5 0.0 871.1 0.00 0.00 0.0 0.0 0.0
CCB-G06-KITCHEN AREA 1 13.2 4.0 73.1 0.00 0.00 0.0 100.0 73.1
CCB-G11-LOCKER ROOM(M) 1 13.6 0.0 36.0 0.00 0.00 36.0 0.0 36.0
Zone 3
CCB-G03-FF ROOM 1 14.5 0.0 24.9 0.00 0.00 0.0 0.0 0.0
CCB-G04-Corridor 1 51.0 0.0 107.7 0.00 0.00 74.0 0.0 74.0
CCB-F08,F10-Corri,Stair1 1 49.4 0.0 100.0 0.00 0.00 100.0 0.0 100.0
CCB-G08-Air Lock 1 5.5 0.0 13.0 0.00 0.00 13.0 0.0 13.0
Totals (incl. Space Multipliers) 1740.7 296.1

Hourly Analysis Program v.4.4 Page 1 of 1


Air System Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 291 m 2246 - 291 m 1490 -
Roof Transmission 75 m 315 - 75 m 201 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 15 m 296 - 15 m 279 -
Floor Transmission 26 m 284 - 26 m 122 -
Partitions 276 m 2546 - 276 m 1282 -
Ceiling 13 m 89 - 13 m 80 -
Overhead Lighting 6728 W 6728 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6981 W 6981 - 0 0 -
People 17 1190 765 0 0 0
Infiltration - 4607 5037 - 4761 -80
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2528 580 10% 821 -8
>> Total Zone Loads - 27810 6383 - 9036 -89
Zone Conditioning - 26688 6383 - 8563 -89
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1741 L/s 0 - 1741 L/s 0 -
Ventilation Load 296 L/s 5101 6045 296 L/s 3992 0
Supply Fan Load 1741 L/s 3482 - 1741 L/s -3482 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 35271 12428 - 9073 -89
Central Cooling Coil - 35271 12986 - 0 0
Central Heating Coil - 0 - - 9073 -
>> Total Conditioning - 35271 12986 - 9073 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.4 Page 1 of 1


Zone Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 97 m 931 - 97 m 553 -
Roof Transmission 26 m 141 - 26 m 77 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 26 m 283 - 26 m 122 -
Partitions 81 m 1006 - 81 m 307 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 908 W 907 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 885 W 885 - 0 0 -
People 13 910 585 0 0 0
Infiltration - 560 658 - 506 27
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 562 124 10% 157 3
>> Total Zone Loads - 6187 1367 - 1722 30

Zone 2 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 132 m 957 - 132 m 638 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 11 m 225 - 11 m 197 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 162 m 1256 - 162 m 636 -
Ceiling 13 m 89 - 13 m 80 -
Overhead Lighting 4998 W 4998 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4484 W 4483 - 0 0 -
People 4 280 180 0 0 0
Infiltration - 3622 3973 - 3710 -94
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1591 415 10% 526 -9
>> Total Zone Loads - 17501 4568 - 5786 -103

Hourly Analysis Program v.4.4 Page 1 of 2


Zone Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

Zone 3 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 62 m 390 - 62 m 298 -
Roof Transmission 49 m 176 - 49 m 124 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 4 m 72 - 4 m 82 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 33 m 280 - 33 m 339 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 822 W 822 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1613 W 1612 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 418 407 - 545 -14
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 377 41 10% 139 -1
>> Total Zone Loads - 4148 448 - 1529 -16

Hourly Analysis Program v.4.4 Page 2 of 2


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CCB-G07-FIRST AID '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 43 m 440 - 43 m 246 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 21 m 241 - 21 m 80 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 193 W 193 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 224 W 223 - 0 0 -
People 2 140 90 0 0 0
Infiltration - 131 165 - 128 7
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 137 26 10% 45 1
>> Total Zone Loads - 1505 281 - 498 8

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CCB-G07-FIRST AID '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 18 0.439 - 183 - 104
SW EXPOSURE
WALL 25 0.439 - 257 - 142

Hourly Analysis Program v.4.4 Page 1 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' CCB-F07-MEETING ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 28 m 275 - 28 m 157 -
Roof Transmission 26 m 139 - 26 m 77 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 26 m 284 - 26 m 122 -
Partitions 28 m 390 - 28 m 104 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 420 W 420 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 389 W 388 - 0 0 -
People 5 350 225 0 0 0
Infiltration - 249 289 - 222 12
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 250 51 10% 68 1
>> Total Zone Loads - 2745 565 - 750 13

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' CCB-F07-MEETING ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 28 0.439 - 275 - 157
H EXPOSURE
ROOF 26 0.228 - 139 - 77

Hourly Analysis Program v.4.4 Page 2 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' CCB-G05-PRAYER ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 22.0 C OCCUPIED T-STAT 21.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 26 m 260 - 26 m 151 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 33 m 361 - 33 m 123 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 295 W 295 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 273 W 273 - 0 0 -
People 6 420 270 0 0 0
Infiltration - 168 203 - 156 8
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 178 47 10% 43 1
>> Total Zone Loads - 1954 520 - 473 9

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' CCB-G05-PRAYER ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 26 0.439 - 260 - 151

Hourly Analysis Program v.4.4 Page 3 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' CCB-G02-HVAC ROOM '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 111 m 821 - 111 m 536 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 11 m 225 - 11 m 197 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 132 m 1037 - 132 m 524 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 4709 W 4709 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4088 W 4087 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 3432 3765 - 3515 -89
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1431 376 10% 477 -9
>> Total Zone Loads - 15742 4141 - 5249 -98

TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' CCB-G02-HVAC ROOM '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 45 0.439 - 305 - 216
DOOR 11 1.703 - 225 - 197
SE EXPOSURE
WALL 66 0.439 - 517 - 320

Hourly Analysis Program v.4.4 Page 4 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' CCB-G06-KITCHEN AREA '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.2 C / 26.8 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 21 m 160 - 21 m 101 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 11 m 49 - 11 m 0 -
Ceiling 13 m 85 - 13 m 80 -
Overhead Lighting 143 W 143 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 396 W 396 - 0 0 -
People 4 280 180 0 0 0
Infiltration - 88 103 - 96 -2
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 120 28 10% 28 0
>> Total Zone Loads - 1321 311 - 305 -3

TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' CCB-G06-KITCHEN AREA '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 21 0.439 - 160 - 101

Hourly Analysis Program v.4.4 Page 5 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 2.3.A. COMPONENT LOADS FOR SPACE '' CCB-G11-LOCKER ROOM(M) '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 27.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 20 m 168 - 20 m 112 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 147 W 147 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 96 106 - 99 -2
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 41 11 10% 21 0
>> Total Zone Loads - 453 116 - 232 -3

TABLE 2.3.B. ENVELOPE LOADS FOR SPACE '' CCB-G11-LOCKER ROOM(M) '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)

Hourly Analysis Program v.4.4 Page 6 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' CCB-G03-FF ROOM '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 10 m 60 - 10 m 47 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 2 m 36 - 2 m 41 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 251 W 251 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 143 139 - 187 -5
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 49 14 10% 28 0
>> Total Zone Loads - 539 153 - 303 -5

TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' CCB-G03-FF ROOM '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 10 0.439 - 60 - 47
DOOR 2 1.703 - 36 - 41

Hourly Analysis Program v.4.4 Page 7 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 3.2.A. COMPONENT LOADS FOR SPACE '' CCB-G04-Corridor '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 22 m 142 - 22 m 106 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 21 m 176 - 21 m 213 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 275 W 275 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1530 W 1530 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 212 0 10% 32 0
>> Total Zone Loads - 2336 0 - 351 0

TABLE 3.2.B. ENVELOPE LOADS FOR SPACE '' CCB-G04-Corridor '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 22 0.439 - 142 - 106

Hourly Analysis Program v.4.4 Page 8 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 3.3.A. COMPONENT LOADS FOR SPACE '' CCB-F08,F10-Corri,Stair1 '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 41.0 C / 27.0 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 20 m 129 - 20 m 97 -
Roof Transmission 49 m 176 - 49 m 124 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 12 m 105 - 12 m 127 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 267 W 267 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 275 267 - 358 -9
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 95 27 10% 71 -1
>> Total Zone Loads - 1047 294 - 776 -10

TABLE 3.3.B. ENVELOPE LOADS FOR SPACE '' CCB-F08,F10-Corri,Stair1 '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 20 0.439 - 129 - 97
H EXPOSURE
ROOF 49 0.228 - 176 - 124

Hourly Analysis Program v.4.4 Page 9 of 10


Space Design Load Summary for CCB-NON-TECHNICAL AREA
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 3.4.A. COMPONENT LOADS FOR SPACE '' CCB-G08-Air Lock '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.8 C / 26.9 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 30.0 C OCCUPIED T-STAT 19.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 10 m 65 - 10 m 48 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 2 m 36 - 2 m 41 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 30 W 30 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 83 W 82 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 21 0 10% 9 0
>> Total Zone Loads - 234 0 - 98 0

TABLE 3.4.B. ENVELOPE LOADS FOR SPACE '' CCB-G08-Air Lock '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 10 0.439 - 65 - 48
DOOR 2 1.703 - 36 - 41

Hourly Analysis Program v.4.4 Page 10 of 10


SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

B01-CABLE ROOM
(Space Design Load Summary)
Space Design Load Summary for CCB-Cable Room
SAUDI ARAMCO THIRD PARTY COGENERATION PROJECT
CONTROL BUILDING

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' CCB-B01-CABLE ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.3 C / 26.6 C HEATING OA DB / WB 8.0 C / 3.4 C
OCCUPIED T-STAT 48.5 C OCCUPIED T-STAT 6.0 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 48 m -30 - 48 m 0 -
Roof Transmission 0 m 0 - 0 m 0 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 8294 W 8294 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 826 0 10% 0 0
>> Total Zone Loads - 9091 0 - 0 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' CCB-B01-CABLE ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 27 0.414 - -50 - 0
SW EXPOSURE
WALL 21 0.414 - 21 - 0

Hourly Analysis Program v.4.4 Page 1 of 1


SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

APPENDIX 2
PRESSURIZATION AIR VOLUME CALCULATION
CALCULATION EXAMPLE OF FLOW RATE OF SUPPLY AIR FOR PRESSURIZATION
(Based on ASHRAE Application, Chapter 53, Equation 8 & 9, edition on 2011)
The air flow rate, through a construction crack, door gap, or other flow path is proportional to the pressure
difference across that path raised to the power n.
For a flow path of fixed geometry, n is theoretically in the range of 0.5 to 1.
However, for all flow paths, except extremely narrow cracks, n = 0.5, and the flow can be expressed as ;

Q = CA(2p/)
where,
Q = volumetric air flow rate
C = flow coefficient
A = flow area (called leakage area)
p = pressure difference across the flow path
= density of air entering the flow path

The flow coefficient depends on the geometry of the flow path, as well as on turbulence and friction.
In the present context, the flow coefficient is generally in the range of 0.6 to 0.7.
For = 1.2 kg/, and C = 0.65, the flow equation above can be expressed as ;

Q = 0.8392 Ap

where,
Q = volumetric air flow rate (/s)
A = flow area (called leakage area) ()
p = pressure difference across the flow path (Pa)

Total leakage area should be summed with data of each architectural component as below ;
Room name : G01-ELECTRICAL ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 135.0 25.7
Cast-in-place concrete cm2/m2 0.50 297.6 148.8
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40 480 192.0
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 366.5
Leakage air volume to be maintain 62Pa (m /hr) 1,040.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1

2. Calculation of Leakage air flows thru Door


- The air leakage will be computed by The following formula.
V = 3600 x a x A x (2 x P/d)
where ; V : Leakage air flow
a : Flow coefficient, 0.7 will be applied
A : Actual area of the threshold gap (m )
P : Room pressure differnce (Pa)
d : Density of standard air at 20 deg. C (1.2 kg/m )
- Actual area of the threhold Gap of 2mm
For Double door 2.0m width A = 2.0 x 2.0 x 0.002 = 0.0080
For Single door 1.0m width A = 1.0 x 2.0 x 0.002 = 0.0040

- Calculation of leakage air flow

a) Through Double Door at P=62Pa Q'ty Volume


V = 3600 x 0.7 x 0.008 (2 x 62/1.2) = 200 (m /hr) 1 200

b) Through Single Door at P=62Pa


V = 3600 x 0.7 x 0.004 (2 x 62/1.2) = 100 (m /hr) 1 100

3. Required leakage air flows for pressurizing


a) leakage air flows through structure : 1,040 (m /hr)
b) leakage air flows through door : 300 (m /hr)
c) total leakage air flows for pressurizing(20% S.F) : 1,600 (m /hr) 450 (L/S)
Room name : F01-ELECTRICAL ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 210.0 39.9
Cast-in-place concrete cm2/m2 0.50 79.8 39.9
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40 105 42.0
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 121.8
Leakage air volume to be maintain 62Pa (m /hr) 340.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1

2. Calculation of Leakage air flows thru Door


- The air leakage will be computed by The following formula.
V = 3600 x a x A x (2 x P/d)
where ; V : Leakage air flow
a : Flow coefficient, 0.7 will be applied
A : Actual area of the threshold gap (m )
P : Room pressure differnce (Pa)
d : Density of standard air at 20 deg. C (1.2 kg/m )
- Actual area of the threhold Gap of 2mm
For Double door 2.0m width A = 2.0 x 2.0 x 0.002 = 0.0080
For Single door 1.0m width A = 1.0 x 2.0 x 0.002 = 0.0040

- Calculation of leakage air flow

a) Through Double Door at P=62Pa Q'ty Volume


V = 3600 x 0.7 x 0.008 (2 x 62/1.2) = 200 (m /hr) 1 200

b) Through Single Door at P=62Pa


V = 3600 x 0.7 x 0.004 (2 x 62/1.2) = 100 (m /hr) 2 200

3. Required leakage air flows for pressurizing


a) leakage air flows through structure : 340 (m /hr)
b) leakage air flows through door : 400 (m /hr)
c) total leakage air flows for pressurizing(20% S.F) : 880 (m /hr) 250 (L/S)
Room name : F02-RACK ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 180.0 34.2
Cast-in-place concrete cm2/m2 0.50 153.9 77.0
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 111.2
Leakage air volume to be maintain 62Pa (m /hr) 310.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1

2. Calculation of Leakage air flows thru Door


- The air leakage will be computed by The following formula.
V = 3600 x a x A x (2 x P/d)
where ; V : Leakage air flow
a : Flow coefficient, 0.7 will be applied
A : Actual area of the threshold gap (m )
P : Room pressure differnce (Pa)
d : Density of standard air at 20 deg. C (1.2 kg/m )
- Actual area of the threhold Gap of 2mm
For Double door 2.0m width A = 2.0 x 2.0 x 0.002 = 0.0080
For Single door 1.0m width A = 1.0 x 2.0 x 0.002 = 0.0040

- Calculation of leakage air flow

a) Through Double Door at P=62Pa Q'ty Volume


V = 3600 x 0.7 x 0.008 (2 x 62/1.2) = 200 (m /hr) 1 200

b) Through Single Door at P=62Pa


V = 3600 x 0.7 x 0.004 (2 x 62/1.2) = 100 (m /hr) -

3. Required leakage air flows for pressurizing


a) leakage air flows through structure : 310 (m /hr)
b) leakage air flows through door : 200 (m /hr)
c) total leakage air flows for pressurizing(20% S.F) : 610 (m /hr) 170 (L/S)
Room name : F03-ENGINEERING ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 44.0 8.4
Cast-in-place concrete cm2/m2 0.50
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 8.4
Leakage air volume to be maintain 62Pa (m /hr) 20.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1

2. Calculation of Leakage air flows thru Door


- The air leakage will be computed by The following formula.
V = 3600 x a x A x (2 x P/d)
where ; V : Leakage air flow
a : Flow coefficient, 0.7 will be applied
A : Actual area of the threshold gap (m )
P : Room pressure differnce (Pa)
d : Density of standard air at 20 deg. C (1.2 kg/m )
- Actual area of the threhold Gap of 2mm
For Double door 2.0m width A = 2.0 x 2.0 x 0.002 = 0.0080
For Single door 1.0m width A = 1.0 x 2.0 x 0.002 = 0.0040

- Calculation of leakage air flow

a) Through Double Door at P=62Pa Q'ty Volume


V = 3600 x 0.7 x 0.008 (2 x 62/1.2) = 200 (m /hr) -

b) Through Single Door at P=62Pa


V = 3600 x 0.7 x 0.004 (2 x 62/1.2) = 100 (m /hr) -

3. Required leakage air flows for pressurizing


a) leakage air flows through structure : 20 (m /hr)
b) leakage air flows through door : - (m /hr)
c) total leakage air flows for pressurizing(20% S.F) : 20 (m /hr) 10 (L/S)
Room name : F05-CONTROL ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 210 39.9
Cast-in-place concrete cm2/m2 0.50 122.6 61.3
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40 210 84.0
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 185.2
Leakage air volume to be maintain 62Pa (m /hr) 520.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1

2. Calculation of Leakage air flows thru Door


- The air leakage will be computed by The following formula.
V = 3600 x a x A x (2 x P/d)
where ; V : Leakage air flow
a : Flow coefficient, 0.7 will be applied
A : Actual area of the threshold gap (m )
P : Room pressure differnce (Pa)
d : Density of standard air at 20 deg. C (1.2 kg/m )
- Actual area of the threhold Gap of 2mm
For Double door 2.0m width A = 2.0 x 2.0 x 0.002 = 0.0080
For Single door 1.0m width A = 1.0 x 2.0 x 0.002 = 0.0040

- Calculation of leakage air flow

a) Through Double Door at P=62Pa Q'ty Volume


V = 3600 x 0.7 x 0.008 (2 x 62/1.2) = 200 (m /hr) -

b) Through Single Door at P=62Pa


V = 3600 x 0.7 x 0.004 (2 x 62/1.2) = 100 (m /hr) 3 300

3. Required leakage air flows for pressurizing


a) leakage air flows through structure : 520 (m /hr)
b) leakage air flows through door : 300 (m /hr)
c) total leakage air flows for pressurizing(20% S.F) : 980 (m /hr) 280 (L/S)
Room name : F06-TELECOM ROOM (CONTROL & ADMIN_RTR) Room pressure (Pa) : 62
1. Calculation leakage air flows thru structure
Best Leak area
Component Units Quantity
estimate (cm2)
General cm2/m2 1.80
Ceiling
Drop cm2/m2 0.19 13.8 2.6
Cast-in-place concrete cm2/m2 0.50 40.0 20.0
Clay brick cavity wall, finished cm2/m2 0.68
Walls (exterior) Pre-cast concrete panel cm2/m2 1.20
Low-density concrete block, unfinished cm2/m2 3.50
Low-density concrete block,painted or stucco cm2/m2 1.10
Floor Concrete slab cm2/m2 0.40 13.8 5.5
Masonry, not caulked cm2/m2 6.50
Masonry, caulked cm2/m2 1.30
Window frame
Wood, not caulked cm2/m2 1.70
Wood, caulked cm2/m2 0.30
Double horizontal slider, not weatherstripped cm2/lmc 1.10
Double horizontal slider, wood weatherstripped cm2/lmc 0.55
Double horizontal slider, aluminum weather stripped cm2/lmc 0.72
Double hung, not weatherstripped cm2/lmc 2.50
Double hung, weatherstripped cm2/lmc 0.65
Windows
Single horizontal slider, weatherstripped cm2/lmc 0.67
Single horizontal slider, aluminum cm2/lmc 0.80
Single horizontal slider, wood cm2/lmc 0.44
Single horizontal slider, wood clad cm2/lmc 0.64
Single-hung, weatherstripped cm2/lmc 0.87
Total Area 28.1
Leakage air volume to be maintain 62Pa (m /hr) 80.0
Abbreviations
= gross area in square meters, ea = each, lmc = linear meter of crack, lms = linear meter of sash
The data of other component not defined above will be referred in ASHRAE Fundamentals 2001, chapter 26, table 1

2. Calculation of Leakage air flows thru Door


- The air leakage will be computed by The following formula.
V = 3600 x a x A x (2 x P/d)
where ; V : Leakage air flow
a : Flow coefficient, 0.7 will be applied
A : Actual area of the threshold gap (m )
P : Room pressure differnce (Pa)
d : Density of standard air at 20 deg. C (1.2 kg/m )
- Actual area of the threhold Gap of 2mm
For Double door 2.0m width A = 2.0 x 2.0 x 0.002 = 0.0080
For Single door 1.0m width A = 1.0 x 2.0 x 0.002 = 0.0040

- Calculation of leakage air flow

a) Through Double Door at P=62Pa Q'ty Volume


V = 3600 x 0.7 x 0.008 (2 x 62/1.2) = 200 (m /hr) -

b) Through Single Door at P=62Pa


V = 3600 x 0.7 x 0.004 (2 x 62/1.2) = 100 (m /hr) 1 100

3. Required leakage air flows for pressurizing


a) leakage air flows through structure : 80 (m /hr)
b) leakage air flows through door : 100 (m /hr)
c) total leakage air flows for pressurizing(20% S.F) : 210 (m /hr) 60 (L/S)
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

APPENDIX 3
PSYCHROMETRIC CHART
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

TECHNICAL AREA
(R0TBA-JA001A/B/C/D)
SAUDI ARAMCO THIRD PARTY
COGENERATION PROJECTS

CONTROL BUILDING

NON-TECHNICAL AREA
(R0TBA-JA002A/B)