Type

AGS0330D DIESEL GENERATOR SET


M

315/350 kVA
ac
hi
en
Se
t
Diesel Generating Set
Type AGS0330D
315/350 kVA

Torsion-free base frame made of laser-cut, welded tilted steelprofiles; machine group is mounted on base frame with rubber buffers which allow the ma-
chine group to vibrate; however, there is no transfer of vibration to frame; base frame with pallet feet can be carried with pallet truck or fork lift; engine and
alternator are connected with steel flange coupling;

Genset Data Fuel System4

Variable continuous power (PRP)1 315 kVA Fuel consumption at


Emergency power (LTP) 2
350 kVA 100 % load 77.7 l/h
75 % load 57.2 l/h
Power factor (cos phi) 0.8 50 % load 37.9 l/h
Nominal voltage 400 V / 230 V 25 % load 20.2 l/h
Nominal current 471 A Specific fuel consumption at
Frequenzy 50 Hz 100 % load 206 g/kWh
-1 75 % load 202 g/kWh
Speed 1 500 min
50 % load 201 g/kWh
Load acceptance3 60 % 25 % load 214 g/kWh
Fuel tank capacity (Open Set) 400 l
Fuel tank capacity (Sound Proof) 900 l
Autonomy at full load (Open Set) 5.1 h
Autonomy at full load (Sound Proof) 11.6 h

Dimensions and Weights Noise Emission5

Open Set Sound pressure LPA @ 1m (Open Set) 101 dB(A)


Length 2 800 mm Sound pressure LPA @ 7m (Sound Proof) approx. 70 dB(A)
Width 1 147 mm
Height 2 097 mm
Weight 2 500 kg
Sound Proof
Length 4 180 mm
Width 1 580 mm
Height 2 470 mm
Weight 4 000 kg
Engine Data Alternator Data

Manufacturer Deutz Manufacturer Aggretech


Type BF6M 1015 C Type ACG0315-4-400
Configuration 4 cycle; V; 6 cylinder Mechanical protection (IP class) IP 23
Diesel Insulation class H
Aspiration turbo charged with Excitation brushless, self-exciting
charge air cooler synchronous alternator
Displacement 11.9 l Voltage control electronic, self-regulating
Gross output - Prime power (PRP) 285.0 kW +/- 1 %
Gross output - Emergency power (LTP) 314.0 kW Short circuit capability 3x nominal current
Compression ratio 16.5:1 AC wavefactor total harmonic distorsion <2%
Govenor type electronic Radio interference EN 55011 Class B, Group 1
Governing standards G2 Efficiency (cos phi 0,8 / 400V) at
Oil capacity (sump) 34 l 100 % load 93.4 %
75 % load 93.2 %
Oil consumption 0.3 % of fuel consumption
50 % load 92.2 %
Starting voltage 12 V
Cooling air volume 2 322 m3/h
Exhaust emission standard TA Luft 2000

Combustion Air Cooling System

Combustion air volume 1 432 m3/h Standard of cooling system water cooled
Air cleaner type dry; replaceable element Fan power consumption 13.8 kW
with safety cartridge Cooling air flow 24 120 m3/h
Air pressure loss 1.5 mbar

Exhaust System Powered by

Max. exhaust gas temperature 520 C


Max. exhaust back pressure 50 mbar
Exhaust gas flow 3 915 m3/h

Legend: Quality standards:


1
PRP (Prime Power) is available at a variable load for unlimited hours. VDE 0530, DIN 6280, ISO 8528, IEC 34, BS 4999, BS 5000, BS 5514;
Adjustable permanent output 100 %, no time restrictions. Prime Power is in accordance with We are certified specialist according to 19 I WHG.
ISO 8528. A 10 % overload capacity is available for limited time in accordance with All performance figures are to be understood for ambient conditions as follows:
ISO 3046, AS 2789, DIN 6271 and BS 5514. ambient temperature 25 C, 100 m above sea level, rel. humidity 30 %.
2
LTP (Limited Time Power)) is applicable for supploying power to a constant electrical load We reserve the right to change specifications without notice.
for limited hours in the event of a main power network failure. No overload is permitted. LTP
is in accordance with ISO 8528.
3
max. additional output in kVA (PRP).
4
Fuel consumption according to Deutz datasheet as shown on www.deutz.com
5
at 75 % load, according to EU directive 2000/14/EGthe PRP and LTP power ratings
Diesel Generating Set
Type AGS0330D
315/350 kVA

4 180 1 580

2 470

Your authorised dealer Drawings are not true to scale.

Weights refer to the dry weights and represent a set with standard features. Accesso-
ries and loose parts are not accounted. Drawings are for illustrative purposes only and
might include special accessories.
We reserve the right to change specifications without notice.

A 2 / AGS0330D 08/11/2010 E

AGGRETECH AG

Geschftsbereich Stromaggregatebau
Division Generator Sets
Rotthofer Str. 8, 94099 Ruhstorf
Germany
Telefon/Phone +49 (0) 8531 9782-0
Telefax/Fax +49 (0) 8531 9782-1510
gensets@aggretech.de