www.tyco-fire.com
Contacts

Style 60
Two-Piece Flush Escutcheon
3/4 Inch NPT
General Technical
Description Data
The TYCO Style 60 Two-Piece Flush Approvals
Escutcheon illustrated in Figure 1 is UL Listed and FM Approved for use
designed for use with TYCO Series with Series EC-11 and EC-14 Pendent
EC-11 and EC-14 Pendent Sprinklers Sprinklers.
(described in Technical Data Sheet Finishes
TFP220) where the piping is installed Chrome, Signal White, or Brass
above a ceiling. They are used to im-
prove the overall appearance of the in- Material STYLE 60
Carbon Steel TWO-PIECE ESCUTCHEON
stallation by concealing the clearance
holes required for the connecting pip-
ing and fittings to the sprinkler. Installation Step 5. After suspended ceiling pan-
el has been installed or finish coat has
The separable two-piece design of The TYCO Style 60 Two-Piece Flush been applied to fixed ceiling, slide es-
the Style 60 allows installation of the Escutcheon must be installed in ac- cutcheon closure over sprinkler and
sprinklers and pressure testing of the cordance with this section. mounting plate, pushing until flush
fire protection system/evaluation of
General Instructions against mounting surface. If installed
leak tightness, prior to installation of
A leak tight 3/4 inch NPT sprinkler joint beneath suspended ceiling do not
a suspended ceiling or application of
should be obtained with a torque of push escutcheon closure beyond point
the finish coating to a fixed ceiling. It
10 to 20 ft.-lbs. Higher levels of torque of contact with mounting surface and
also permits the removal of suspended
may distort the sprinkler orifice seat lift ceiling panel above normal position.
ceiling panels, for access to building
service equipment, without having to with consequent leakage.
first shut down the fire protection sys-
tem and remove sprinklers.
The face of the sprinkler fitting must
be positioned from 3/8 inch (9,5 mm)
Care and
NOTICE
above to 1/8 inch (3,2 mm) below the
level of the finished ceiling mounting
Maintenance
surface. This will ensure that when in- The following inspection procedure
The Style 60 Escutcheon described must be performed as indicated, in ad-
herein must be installed and main- stalled the sprinkler escutcheon plate
seating surface is located within the dition to any specific requirements of
tained in compliance with this docu- the NFPA. Any impairments must be
ment, as well as with the applicable nominal range to allow proper installa-
tion of the escutcheon closure. immediately corrected.
standards of the National Fire Pro-
tection Association, in addition to the Do not attempt to correct for insuffi- The owner is responsible for the in-
standards of any other authorities cient installation and adjustment of the spection, testing, and maintenance of
having jurisdiction. Failure to do so escutcheon closure by under- or over- their fire protection system and devic-
may impair the performance of these tightening the sprinkler. Readjust the es in compliance with this document,
devices. position of the sprinkler fitting to suit. as well as with the applicable stan-
dards of the National Fire Protection
The owner is responsible for maintain- Step 1. Orient flat face of escutcheon Association (e.g., NFPA 25), in addition
ing their fire protection system and de- mounting plate parallel with open end to the standards of any authority hav-
vices in proper operating condition. of sprinkler threads. ing jurisdiction. The installing contrac-
The installing contractor or sprinkler tor or product manufacturer should be
manufacturer should be contacted Step 2. Engage sprinkler threads with
mounting plate threads and rotate un- contacted relative to any questions.
with any questions.
til mounting plate is flush with sprinkler It is recommended that automatic sprin-
frame arms. kler systems be inspected, tested, and
Step 3. With thread sealant applied maintained by a qualified Inspection
to sprinkler pipe threads, hand tighten Service in accordance with local re-
sprinkler into sprinkler fitting. quirements and/or national codes.
Step 4. Using appropriate sprinkler After placing a fire protection system
wrench, apply wrench to designated in service, notify the proper authori-
sprinkler wrenching area and tighten ties and advise those responsible for
sprinkler into sprinkler fitting. (Refer to monitoring proprietary and/or central
Technical Data Sheet TFP220). station alarms.

Page 1 of 2 MAY 2014 TFP778


TFP778
Page 2 of 2

2-7/8" DIA.
(73,0 mm)

2-1/4" DIA.
(57,2 mm)

INTERNAL
DIMENSIONS OF
STYLE 60 ESCUTCHEON
ACCOMMODATE
CLASS 150 MALLEABLE
IRON REDUCING
SPRINKLER FITTING

MOUNTING
SURFACE

1/8"
(3,2 mm)

FACE OF
SPRINKLER FITTING:
3/8" (9,5 mm) ABOVE
TO 1/8" (3,2 mm) BELOW CLOSURE
MOUNTING SURFACE
3/4" NPT
MOUNTING
ESCUTCHEON PLATE
PLATE
SEATING SURFACE:
1/4" (6,4 mm) ABOVE 2-5/16" (58,7 mm)
TO 1/2" (12,7 mm) BELOW
MOUNTING SURFACE; 1-13/16" (46,0 mm)
3/4" (19,1 mm) TOTAL
ADJUSTMENT

FIGURE 1
SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY WITH
3/4 INCH TOTAL ADJUSTMENT STYLE 60 TWO-PIECE FLUSH ESCUTCHEON

Limited Ordering
Warranty Procedure
For warranty terms and conditions, Contact your local distributor for avail-
visit www.tyco-fire.com. ability. When placing an order, indicate
the full product name and Part Num-
ber (P/N).
Style 60 Two-Piece Flush
Escutcheon:
Specify: Style 60 Two-Piece Flush Es-
cutcheon with 3/4 NPT, (specify) Fin-
ish, P/N (specify):
Chrome. . . . . . . . . . . . . . . . . . . . . . . . . P/N 208102
Signal White (RAL9003) P/N 208104
Brass. . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 208107

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

Copyright 2014 Tyco Fire Products, LP. All rights reserved.


TEFLON is trademark of The DuPont Corporation