Você está na página 1de 1

Eurovent Energy Efficiency Class Calculator 2013

Project 1530 DV
Project number Dummy
Location The Netherlands
Date 2013-02-19

Basic requirements selected class Final evaluation of aimed class

Aimed Eurovent label C fs [-] 0.88


velocity [m/s] 2.2 result OK
f-ref 1
efficieny [%] 57
pressure drop [Pa] 170 RESULTING CLASS C

Input data AHU Details of correction


Unit type designation Subgroup 1, 2 or 3
1: Connected to outdoor air 9C

SUPPLY part SUPPLY


air flow [m3/s] 4.3056 velocity [Pa] 106
internal static pressure [Pa] 780 HRS pressure drop [Pa] 40
total static pressure = internal+external [Pa] 1280 HRS efficieny SUP [Pa] -94
power input real [kW] 8.2
velocity real [m/s] 2.55 Pref-class [kW] 10.305
efficiency HRS mass flow balanced [%] 68
pressure drop HR real [Pa] 210
mixing ratio = recirculated air / supply air [%] 0.0
design outdoor temperature [C] -10
electric re-heater - Yes

EXTRACT part EXTRACT


air flow [m3/s] 4.3056 velocity [Pa] 33
internal static pressure [Pa] 389 HRS pressure drop [Pa] 40
total static pressure = internal+external [Pa] 639 HRS efficieny EXT [Pa] -94
power input real [kW] 5.9
velocity real [m/s] 2.55 Pref-class [kW] 5.800
efficiency HRS mass flow balanced [%] 68
pressure drop HR real [Pa] 210

Comments

= 0; If no supply fan(s) Version: 2013-02-15


= 0; If no extract fan(s)