UPS Failure Reaction P

O/M Technician
Start

Verify the alarm of UPS.

Log all UPS alarms

Verify UPS Status

Check Bypass breaker it must in ON position and


Normal voltage output is present..

Verify the status of Connected load

Is the connected load shutdown?

(YES) Inform shift leader & Power-ON all Affected CPS


(Conditioner Power Supply) transformer.

Inform Equipment/Manufacturing to start affected testers

(No) Inform Shift leader and Transfer the UPS to


Maintenance Bypass Mode ( following MBB procedures)

Reset UPS alarm

Is the alarm reset?

(YES) Re-start the UPS following the start-up


procedure two(2) man verification checklist.

Is the UPS start -up successful?

(YES) Simulate from bypass to UPS mode and from


UPS to Bypas mode (2)times.

Transfer UPS to STATIC bypass mode

(NO), Shift leader to Escalate to SME the status of UPS


for repair.
Performed UPS Repair.

Repair completed

Re-start UPS

Simulate from Bypass to UPS mode and vise versa


( 2 times)

Transfer UPS to STATIC bypass mode

Inform manufacturing, Then shift the unit on UPS MODE.

END

DOCUMENT REVISION HISTORY

Revision No. Revision Date

B 6-Feb-12

A 1/27/2011
ailure Reaction Plan
Shift Leader SME Remarks
If the Repair was completed endorse to
Facilities O/M shift leader the Status of
UPS to shift the unit to UPS mode.

HISTORY
Document Review
Nature of Revision
Participants
Review reaction plan,
Karno/Edward
No changes
Follow proper naming
Karno Austria
convention
UPS ALARM Reaction Pla
O/M Technician Shift Leader
Start
1

Verify UPS alarm status .


2

Log all alarms


3

Is the alarm critical


4
(YES) Inform shift leader and shift to bypass
mode the UPS if ff. alarm is eminent on the
5 Remarks portion:
Inform Manufacturing about the status of UPS
6 on Bypass mode.

Escalate to SME the status of UPS for repair.


7

SME to performed UPS Repair.


8

Repair completed
9
Inform manufacturing, Then shift the unit on
10 UPS MODE.

Verify the status of Connected load status


11

Load on UPS mode


12

(NO) Reset the UPS minor alarm


13

14 End

DOCUMENT REVISION HISTORY

Revision No. Revision Date Nature of Revision


Follow proper naming
A 1/27/2011
convention
eaction Plan
SME Remarks

Critical alarm: UPS Overtemp./ Battery


discharging/Overload

If the Repair is completed endorse to


Facilities O/M shift leader the Status of
UPS to shift the unit to UPS mode.

Minor alarm : OF/UF, OV/UV, static switch


unable.

Document Review
Participants
Karno Austria
DOCUMENT REVISION HISTORY
Revision
Revision Date Nature of Revision
No.
Review documents and Follow proper
B 1/27/2012
naming convention
A 2/20/2011 Original Documents generated
N HISTORY
Document Review
Participants
Karno Austria/Edward Eslava

Karno Austria
UPS SINGLE LINE
LIEBERT SERIES 600

Input
BYPASS BREAKER

MBB

BIB

INPUT
BREAKER
RECTIFIER

BATTERY
BREAKER

BATTERY
PS SINGLE LINE
BERT SERIES 600

CRITICAL
LOAD

BYPASS MIB
BREAKER

4-7ms

STATIC
SWITCH

OUTPUT
BREAKER
INVERTER

BATTERY
BREAKER