Você está na página 1de 2

50Hz Copeland CR compressor - R22

Aftermarket cross-reference guide

Superior efficiency Best for Better liquid UL and CB certified


high ambient handling

BRISTOL EMERSON
Run Mounting
Bristol model Capacity* EER Voltage Copeland Model Capacity* EER Voltage capacitor feet
details dimension
H2EB24SABKA 20,200 9.5 220-240 CR24K6M-PFZ-141 19,800 10.2 220-240 36 @ 370 7.5x7.5
H2EB24SABKB 20,200 9.5 220-240 CR24K6M-PFZ-341 19,800 10.2 220-240 36 @ 370 4.8x8.0
H2EB243ABKA CR24K6M-PFZ- 141 19,800 10.2 220-240 36 @ 370 7.5x7.5
H2EB243ABKB 20,600 9.3 220-240 CR24K6M-PFZ- 341 19,800 10.2 220-240 36 @ 370 4.8x8.0
H2EB243ABKC CR24K6M-PFZ- 441 19,800 10.2 220-240 36 @ 370 8.44x9.75
H2EB29SABKA 24,500 9.2 220-240 CR30K6M-PF1-101/102 24,250 10.3 230 45 @ 440 7.5x7.5
H2EB32SABKA 26,000 9.0 220-240 CR32K6M-PFZ-141 27,200 10.0 220-240 45 @ 370 7.5x7.5
Single H2EB32SABKB 26,000 9.0 220-240 CR32K6M-PFZ-341 27,200 10.0 220-240 45 @ 370 4.8x8.0
Phase H2EB323ABKA CR32K6M-PFZ-141 27,200 10.0 220-240 45 @ 370 7.5x7.5
H2EB323ABKB 26,600 9.2 220-240 CR32K6M-PFZ-341 27,200 10.0 220-240 45 @ 370 4.8x8.0
H2EB323ABKC CR32K6M-PFZ-441 27,200 10.0 220-240 45 @ 370 8.44x9.75
H29B35UABHA 30,000 10.6 220-240 CR36K6M-PFZ-101/102 29,300 10.8 220-240 45 @ 370 7.5x7.5
H29B35UABHABN 30,000 10.6 220-240 CR37K6M-PFZ-101 30,600 10.0 220-240 50 @ 440 7.5x7.5
H23A383ABKA 32,400 10.1 220-240 CR42K6M-PFZ-101 35,200 10.9 220-240 60 @ 370 7.5x7.5
H23A423ABKA 35,000 10.2 220-240 CR42K6M-PFZ-101 35,200 10.9 220-240 60 @ 370 7.5x7.5
H23A463ABKA 39,200 10.4 220-240 CR47KQM-PFZ-101/102 40,700 10.3 220-240 60 @ 440 7.5x7.5

H23A383DBEA 31,400 10.3 380-415 CR37K6M-TFD-101/102/103 31,200 10.4 380-420 - 7.5x7.5


H23A463DBEA 38,800 10.1 380-415 CR47KQM-TFD-233 39,700 10.4 380-420 - 7.5x7.5
H23A543DBEA 46,000 10.3 380-415 CR53KQM-TFD-233 44,700 10.3 380-420 - 7.5x7.5
Three
H23A563DBEA 47,500 10.4 380-415 CR57KQM-TFD-233 47,800 10.3 380-420 - 7.5x7.5
Phase
H23A623DBEA 51,800 10.3 380-415 CR62KQM-TFD-233 51,500 10.1 380-420 - 7.5x7.5
H29A723DBVA 61,700 11.1 380-415 CR72KQM-TFM-233 60,000 9.8 380-420 - 7.5x7.5
H29A723DBEA 61,700 11.1 380-415 CR72KQM-TFM-233 60,000 9.8 380-420 - 7.5x7.5
Note: * ARI rating conditions - Evaporating temp 7.2C (45F), Condensing temp. 54.4C (130F), Ambient temp. 35C (95F), Liquid temp. 46C (115F), Return gas temp. 18.3C (65F).
Nomenclature
Compressor family series Capacity Motor protection type
C Hermetic reciprocating XX First two digits of nominal F Internal Protection use
Refrigerant capacity Btu/h @ 60 Hz with Single or Three Bill of material (BOM)
R R22,R134a,R407C K x 1,000 multiplier phase contactor suffix

C R 2 4 K 6 M E - P F Z - 1 0 1
Product family variations
6,7,8 CR
Q CR large Electrical codes
Code 50 Hz 60 Hz
Identifier V 208-230 V
M Optimized design Z 220-240 V
D 380-420 V 380-460 V
Oil type M 380-420 V
Blank Mineral oil 5 200-230 V
E POE oil 1 230 V
Motor type
P Single phase
Permanent split capacitor
T Three Phase
Tube orientation
Mounting Mounting kit Terminal fence Suction Discharge Process
1 Long leg Standard Standard 0 Upward Tube Upward
2 Long leg Standard Rectangular 1 Angular Tube Upward
3 Short leg Standard Standard 2 Angular Tube Other Crank case Heater
4 3 leg Standard Standard 3 Spud Spud Upward 1 No heater
5 Short leg Other Standard 4 Upward Tube Inclined outwards 2 1 Phase heater
6 3 leg modified Other Standard 5 Angular Tube Inclined outwards 3 3 Phase heater
Side View
Compressor BOM
"A" "B" Suction "C" "D"
Discharge
"Mounting Side view
Total Suction Tube Tube Process Tube Discharge Type"
Model code Tube ID
Height Height ID Height Tube Height Refer View Suction Tube

141 13.35 12.92 0.51 9.49 2.28 0.38 P Process Tube


CR24K6M-PFZ 341 13.35 12.92 0.51 9.49 2.28 0.38 Q
441 13.35 12.92 0.51 9.49 2.28 0.38 R
101 14.11 13.66 0.63 9.71 2.28 0.38 P Crank Case Heater
CR30K6M-PF1
102 14.11 13.66 0.63 9.71 2.28 0.38 P A B C
141 14.11 13.63 0.63 9.49 2.28 0.38 P Discharge Tube
CR32K6M-PFZ 341 14.11 13.69 0.63 9.49 2.28 0.38 Q
441 14.11 13.66 0.63 9.49 2.28 0.38 R
101 13.76 13.40 0.76 10.53 5.74 0.38 P D
CR36K6M-PFZ
102 13.76 13.40 0.76 10.53 5.74 0.38 P
CR37K6M-PFZ 101 14.11 13.73 0.76 9.72 2.28 0.38 P
7.50
101 14.00 13.79 0.75 9.61 2.28 0.38 P 7.50
Top
Top
Top
Views Views8.00
Views 8.00

CR37K6M-TFD 102 14.00 13.79 0.75 9.61 2.28 0.38 P


103 14.00 13.79 0.75 9.61 2.28 0.38 P
Top views
CR42K6M-PFZ 101 14.26 13.90 0.76 12.87 5.74 0.38 P
7.50
7.50
7.50 8.00
8.00
8.00
101 14.26 14.15 0.88 12.87 5.74 0.51 P 7.50 7.50 4.81 4.81 8.44
CR47KQM-PFZ
102 14.26 14.15 0.88 12.87 5.74 0.51 P
CR47KQM-TFD 233 14.26 12.87 1.25 (Spud) 12.40 4.24 1.25 (Spud) P 7.50
7.50
7.50 4.81 4.81
4.81 8.44 8.44
8.44
CR53KQM-TFD 233 14.26 12.87 1.25 (Spud) 12.40 4.24 1.25 (Spud) P
CR57KQM-TFD 233 14.26 12.87 1.25 (Spud) 12.40 4.24 1.25 (Spud) P 9.75 9.75
CR62KQM-TFD 233 14.26 12.87 1.25 (Spud) 12.40 4.24 1.25 (Spud) P 9.75 9.75
9.75
CR72KQM-TFM 233 14.26 12.87 1.25 (Spud) 12.40 4.24 1.25 (Spud) P
View P View P ViewViewView
P
View
PP
View Q
P View Q
View
View
Q
View
QQ
View
View
View
R
R
View
RR
View R
Note: All dimensions are in inches. For detailed drawings, please contact local Emerson representative.

Follow these field replacement best practices 2 2 2

Ensure the air conditioning system is clean and free from contaminants Replace the liquid line filter drier.
before replacing the compressor. Use proper vacuum pump and micron gauge during evacuation.
Use suction line filter with acid removal core during replacement, if the Use correct amount of refrigerant charge by weight.
previous compressor failure was due to motor burn out. Monitor the system to ensure proper operation.
Inspect all system controls like expansion valve, solenoid valves,
accumulators, contactors etc. and clean/replace if necessary.
2017/MEA/46

For complete product details and additional information, visit

Emerson, Copeland Scroll and CoreSense are trademarks of Emerson Electric Co. or one of its affiliated companies.
2017 Emerson Climate Technologies, Inc. All rights reserved.