9.CONTOHSOALDANPENYELESAIAN
1.
Jawab :
Diasumsikan mesin sinkron menggunakan rotor silinder, sehingga reluktansi kopel
diabaikan. Rangkaian ekivalen mesin (motor) sinkron sperti terlihat pada gambar berikut.
Daya mesin (motor) sinkron 3 fasa : P = 2000 HP x 0.746 kW = 1.492 kW = 1.492 kVA .
Daya masing-masing fasa : P = 1.497 kW/3 = 497 kVA. cos = pf = 1. 1 HP = 0.746 kW.
Tegangan fasa nominal (terminal) Vt = 2300/3 = 1330 Volt. Arus nominal/fasa = Ia =
497.000/1330 = 374 A/fasa. Ia.Xsm = 374 A/fasa x 1.95 Ohm = 730 V/fasa.
Dari diagram vektor, untuk cos = pf = 1,
Gambar e
Sehingga
2.
JAWAB :
3.
JAWAB :
4.
JAWAB :
5.
JAWAB :
6.
JAWAB :
7.
SOLUTION :
C.
8. 1
2. 1
SOLUTION :
Note that because of the motor action the motor action, the power angel is negative.
The Phasor diagram is shown in the above figures Ft and can alaso be
calculated by the phasor diagram.
9.
SOLUTION :
a. For rated conditions, see item c in teh figure below
Let
(b)
(c)
below
10.
SOLUTION :