SVEL Group

dry-type transformers

www.svel.ru
2

History
Start-up of SVEL RsEnergrns plant 1st plant of SVEL Group, spe-
2003
cialized in manufacturing of the cast resin dry-type transformers, voltage
classes are 6-10 kV, rated power is from 25 t 2500 kV.

Start-up production of dry-type current limiting reactors, 4000 , voltage


2004
classes are up to 20 kV, inductive resistance is up to 2,0 ohm;
Realization of the first project n design and construction of unitized
transformer substation.

Designed and manufactured dry-type converter transformers


2005
-3200/6 for zones with moderate cold climate outdoor installation
(possibility of exploitation at the ambient temperature up t minus 60);
Obtained patent on dry-type current limiting reactors;
Obtained certificates of compliance of SVEL power equipment to Federal
norms of industrial safety and working conditions for objects of JSC Gaz-
prom and JSC rnsnft.

Obtained certificate of compliance of the quality management system to


2007
IS0 9001:2000;
Start-up of the project n the onstruction of a new plant SVEL Power
Transformers, manufacturing oil-immersed transformers, voltage classes
are from 10 t 220 kV, rated power is from 2 500 t 250 000 kV.

Branch Offices were opened in the following cities: scow, St-Peters-


2008
burg, Krasnoyarsk, Krasnodar and Kiv.

Start-up of manufacturing of the unitized transformer substations and


2009
factory-assembled switchgears SVEL switchgears.

Start-up of manufacturing of SVEL Instrument transformers;


2010
Branch Offices were opened in Astana, Kazan and Novosibirsk;
Plant of metal structures was integrated into SVEL Group.

Designed and manufactured 250 000/220- the most powerful


oil-immersed transformer manufactured by SVEL Group before 2011. 2011

Branch Office was opened in Khabarovsk


3

BUSINESS CTIVITY
SVEL Group is a leader among national manufac-
turers of the electrotechnical equipment. It is a pro-
ducer of power dry-type and oil-immersed trans-
formers, provider of solutions in electric power
quality improvement and electric network protection.
SVEL Group is also taking advantage of its cutting
edge technologies to be a reliable provider in such
products as switchgears, packaged transformer sub-
stations, instrument transformers, circuit breakers and
disconnectors.

SVEL specialists solutions allow to produce the


equipment that assists enterprises in the reduction of
energy consumption up to 45%. Going forward, SVEL
Group will continue to make big steps in other MV, HV
and UHV equipment.

Manufacture of dry-type
transformers and current-
limiting reactors;

Manufacture of power oil


immersed transformers;

Manufacture of
Integrated switchgears,
transformer substations,
complete block
transformer substations;

Manufacture of current
and voltage transformers;

Manufacture
of transmission angle
and pipe towers, special
distribution steel towers;

Design and installation;

Manufacture
of circiut breakers and
disconnectors.
4

COMPANY PROFILE
Rosenergotrans is a first plant of SVEL Group in Rus-
sia, established in 2003. Plant develops and manufac-
tures such products as:
ast resin dry-type transformers rated from 25 t
16 000 kV, voltage classes are up t 35 kV;
Dry-type current limiting reactors, rated up t 8
000 , voltage classes are up t 230 kV with induc-
tive reactance from 0,1 t 2,5 hm.
ast resin dry-type transformers of and
series manufactured by SVEL Group may replace earlier
installed ones without any additional expenditures:
Oil-immersed transformers;
Sovtol transformers;
Dry-type transformers: , , ,
GDNN, GEAFOL, SGB, RESIBLOC, TRIHAL, TTA-RES
and others.
SVEL Group upon individual orders can make dry-
type transformers with air-barrier insulation rated up
t 12 500 kV, voltage classes are up t 35 kV and
transformers with amorphous metal cores from 25 to
2500 kVA, voltage classes are up to 35kV.
Experience, constant dialogue with customers, sup-
pliers and innovations applied by SVEL Group, allow to
offer a reliable and qualitative product.
All products rrespond to GOST, IEC and EN.
5

QUALITY POLITICS
Company mission
We transform energy into life, creating unique solutions in the field of
electric power equipment in all the chain: from generation to consump-
tion.
Principles that we follow to realize our company mission:
1. Customer requests and expectations a subject of our research
and embodiment.
Our aim - loyal customers, appreciating mutual relations with us.
2. Company personnel value 1.
We strive to create necessary conditions for the enjoyment from
work and full realization of each worker potential.
3. We eliminate the reasons of mistakes, not only their consequences.
We admit our mistakes, analyze and eliminate the reasons of their
occurrence.
4. Every step should be efficient.
We make decisions on the base of combination of the theoretical
knowledge, professional experience and objective data.
5. Our suppliers basis of our production quality.
Only companies, corresponding to our requirements concerning
the quality of production, terms of delivery and prices, can become
our suppliers.
6. There is no limit to perfection any work is carried out much better.

Constant improvement of carried out activity by means of training and


perfection of employees the guarantee of our success.
Top management undertakes the obligation to control the quality man-
agement system of the company and to improve constantly its effective-
ness on the basis of the given principles, and also to control the compli-
ance with legislation of the Russian Federation and other normative acts.
6

Benefits of SVEL dry-type transformers

Reduced on-load and no-load losses;


Reduced noise level;
Possibility of operation at the temperature range
up t 60;
Qualitative materials and components:
- electrotechnical steel with low specific losses;
- foil for windings is bought from the best manufac-
turers of Germany and Norway.

Advantages of Svel Group

Skilled staff;
Modern equipment with software and automated
technologies allow to carry out the complete cycle
of manufacture, reducing the human factor;
Flexibility of manufacturing process according to
the customers requirements;
Effective Quality System Management
QS (ISO 9001);
High production standards;
Warehouse of finished products with wide assort-
ment of items;
Favorable geographical position;
High level of maintenance and warranty service.
7

AST-RESIN DRY-TYPE TRANSFORMERS


SVEL Group offers transformers for different appli-
cations:
Power distribution general-purpose transformers;
Service transformers for electric power stations
and other objects;
Converter transformers for direct-current drive in
metallurgical, drill, gas-and-oil producing and oth-
ers branches of industry;
ransformers for converter installations of the
urban transport (subway, tramway, trolleybus);
ransformers for converters of the excitation sys-
tem of turbo- and hydrogenerators.

Depending on the customer requirements, transformers can be of the following design versions:
Lft: HV winding inputs are on the left regarding the front (side of the rating plate);
Right: HV winding inputs are on the right regarding the front (side of the rating plate);
Up: inputs of the LV and HV windings are on the transformer upper cover;
Other design versions are up to the customer request.

Structure of the transformer designation:


- /
Placement category according to GS 15150;
Climatic modification according to GS 15150;
Voltage of the HV winding, kV;
Rated pwer, kV;
Scope f application:
- service transformer;
- converter transformer;
Absence of letter - pwer distribution transformer;
Voltage regulation system:
presence of the OLTC;
Absence of letter - absence of the OLTC;
Type of cooling system:
= AN (Air Norm);
3 = ANAN (Air Norm/Air Norm);
= ANAF (Air Norm/ Air Force);
= Air Force at the enclosed design;
Type of the LV winding:
- split LV winding;
Absence of letter - nonsplit LV winding;
Number of transformer phases:
three phase transformer;
0 single phase transformer.
8

Classification of the climatic modifications:


zones with moderate climate (up t -40);
zones with moderate cold climate (up t -60);
zones with tropical climate.
Classification of the placement categories at the operation:
1 outdoor installation;
2 - installation under shed or in a room with the outside air inlet;
3 - installation in a closed room with air norm;
4 - installation in a closed room with a non natural regulation of the climatic conditions;
5 - installation in a closed room with high humidity.
Example of the transformer designation:
- 1600/10
Three phase dry-type transformer with air forced cooling of the protected design version, 1600 kV, with the HV
winding voltage of 10 kV, of climatic modification and the placement category is according to GS 15150-69.

hnical prmters of the cast-resin dry-type transformers


ransformer type ,
ypical power, kVA 10-6300*
Primary voltage *
6 6,3 10 10,5
(rated voltage of HV winding), kV
High voltage regulation (changing type, number of steps
Off-load tap changer 2 2,5%
and range of regulation)
Secondary voltage
0,23 0,4 0,69
(rated voltage of LV winding ), kV
Frequency, Hz 50; 60
Winding connection group D/Y -11 Y/Y - 0
Heat-resistance class (according to GS 52719-2007) F
Climatic modification (according to GS 15150-69) any
Degree of protection (according to GS 14254-96) IP00-IP54
The sound pressure level 63 dB
Seismicity of the installation zone according to MSK-64
up t 9 pints
scale
Guaranteed period of operation from 3 years
Service life not less than 30 years
Note: the main characteristics of transformers of 15-35 kV voltage class and power over 6300 kV are to be ap-
proved upon the individual customer request.
9
9

TH MAIN DVANTAGES OF AST-RESIN DRY-TYPE TRANSFORMERS

A high level of fire safety, therefore, transformer


stations may be placed close to energy sinks, that
significantly reduces losses at transferring the elec-
tric power in low voltage power supply networks.
Environmentally friendly. Oil absence in the trans-
former eliminates the risk of the environment pol-
lution at oil leakage.
Safety operation. Windings are non-inflammable,
so they cant cause the fire.
Easy installation, because it doesnt require any ex-
tra measures of fire safety at site.
Minimal running costs, as there is no need in con-
trolling or substituting the dielectric liquid.
Small dimensions give an opportunity to install trans-
former of bigger power in the existing transformer
chamber while reconstructing the substation.
High dynamic strength at short circuit currents.
Windings are not exposed to humidifying and con-
tamination.
Enhanced reliability. High level of the impulse
strength of dry-type transformers allows not to in-
stall the overvoltage limiter.
10

BASIC PARTS OF THE TRANSFORMER DESIGN

The mgnetic core


is made of cold-rolled electrotechnical sheet steel
with a heat-proof coating. Stacking tchnology and
step-lap cutting provide low level of no-load losses.
Cutting of electrotechnical steel is carried out on the
automatic cutting line with the high cut accuracy.
High voltage windings
are made in section-layer form with the series con-
nection of sections. HV winding is made of insulated
wire or foil on high accuracy coil-processing machines.
Vacuum resin filling of windings is carried out during a
completely automated process. Epoxy compound in-
cludes a number of components providing a good heat
emission, and also a high thermostability.
Low voltage windings
are made of foil on automatic winding machine
with simultaneous winding of interlaminar and frontal
insulation. Number of cooling ducts in the winding de-
pends on the transformer power. Ducts are provided
with fiberglass profiles of a high heat resistance class.
Windings are covered with insulating enamels and
heat treated.
Transformer housing
provides necessary protection degree of the ac-
tive part. It is made of steel construction with walls,
a bottom and a roof. The walls and the bottom have
vent holes, providing a normalized cooling level of the
transformer. Wide walls have access panels for access
to adjusting taps. All walls are detachable, that assures
visual inspection and maintenance service on a sched-
ule date.
Transformers can be manufactured of the following
design versions:
Lft: HV winding inputs are on the left regarding
the front;
Right: HV winding inputs are on the right regarding
the front;
Up: inputs of the LV and HV windings are on the
transformer upper cover.
Other design versions are up to the customer re-
quest.
Transformers can have any protection class up to
IP54 included, n the clients request.
11

HUSING
The protection class of transformer, provided by its
housing, is indicated as IP code. The IP de consists
of two figures: the first indicates the transformer pro-
tection against the external penetration; the second
figure indicates the protection against the water. The
less figures the less requirements to the transformer
protection.

The first figure of code


Value of the equipment The protection value
protection for people
Figure (against penetration (against access
of solid bjects) to the active part)
0 No protection No protection
1 Dimter > 50 mm By back of the hand
2 Dimter > 12,5 mm By finger
3 Dimter > 2,5 mm By tools
4 Dimter > 1 mm By wire
5 Dustproof By wire
6 Dust-tight By wire

The second figure of code


Value of the equipment protection against the
Figure external impact as a result of the water penetration

0 No protection
Vrtical water dropping: water drops dripping vertically
1 net
shouldnt have a harmful effect
Water dropping (nminal angle 15): water drops
dripping vertically shouldnt have a harmful effect,
2
when the housing deviates from the vertical position
to any side for an angle up t 15 included
Sprinkling: wter, sprayed as splashes in any direction
which is together with the vertical line comprise an
3
angle up to 60 included, shouldnt have a harmful
effect
mplete sprinkling: wter, sprayed as splashes on
4 the housing in any direction shouldnt have a harmful
effect
Jet effect: wter, guided to the housing as a jet from
5
any direction, shouldnt have a harmful effect
6 Strong jet effect
7 Short-term immersion
8 Short-term immersion
12

Temperature control device


Temperature control device is designed to control
the temperature mode of dry-type transformers. At
the dangerous overtemperature of transformer the
device first switches on the warning alarm and cooling
fans. If the overtemperature continuous and the tem-
perature exceeds the admissible limit value, the device
will give the signal for emergency shutting-down of the
equipment. The temperature control device has four
channels to measure the temperature and four output
relays. Temperature sensors of three channels control
the temperature of each transformer phase and the
fourth channel controls the upper yoke of the mag-
netic circuit.
The device carries out the following functions:
At the overtemperature of 145 on any sensor the
relay warning acts and a spot indicator is lit on the
front panel warning.
At the overtemperature of 155 on any sensor the
relay overheating acts and the corresponding spot
indicator is lit.
At the overtemperature of 135 on any sensor the
relay coling acts and the fan is switched-on, when
the temperature decreases up t 110 the fan is
switched-off. To show functioning of the fan, the spot
indicator coling is located on the front panel.
Rlay fault sensor indicates the fault temperature
sensor(s) in any channel in case of breakdown or short-
circuit of sensor and also in case of anomalously fast
temperature rise (20/sc. or faster), that also means
a fault temperature sensor. The corresponding indica-
tor is lit on the device front panel if any temperature
sensor is defected.
Reset button serves to switch off the relay overheat-
ing. 5 before the temperature of emergency shut-
ting-down the alarm switches on again. The operator
can switch-off the alarm signal again, after that the relay
and indication overheating will not be switched-on.

Overall and mounting dimensions of the device


Cutout in the panel
13

Indoor installation of the transformer


To provide a good functioning of the transformer at
its indoor installation respect the following conditions:
Distance from the transformer conducting parts t
the wall shall be chosen according to the Operat-
ing rules of electrical installations;
Available access for inspection and maintenance of
transformer (including access to the NLTC taps);
The ventilation system of a room shall be of the
required power which provides the extraction of
the transformer heat.
Transformer shall be protected against atmospheric
precipitations, condensate, foreign particles and
objects.

Vntilation
Clculation of the ventilation system includes the Initial data for the calculation:
calculation of the air inlet and outlet holes and, if nec- sh.c. short-circuit losses of transformer, kWt at
essary, the power calculation for the forced cooling of 115;
room. nl no-load losses, kWt
the height difference of the air inlet and outlet
holes, m;
k cfficient, taking into account the protection
class of transformer
Protection class IP00: k=1;
Protection class IP21, IP31: k=0,5.
Surface area of a hole, S, m2 (without surface area
of grids) for the air inlet is calculated according to the
following formula:
sh.c. nl
sh.c. nl

Surface area of a hole S1, m2 (without surface area


of grids) for the air inlet is calculated according to the
following formula:
sh.c. nl

Dimensions of holes, clculated according to the


formulas, will be correct at the average air tempera-
ture 20 and height above the
sh.c.seanllevel up to 1000 m.
sh.c. nl
If its impossible t provide a required sur-
face area of holes for the ventilation, its neces-
sary to foresee the forced ventilation of the room.
Capacity of the ventilation system, m3/min:
sh.c. nl
14

Cmpleteness

STANDARD CMPLETENESS:
Together with the transformer the scope of supply
includes:
temperature control device;
4 temperature sensors;
4 pivotal rolls;
the transformer passport, its installation, operation
and maintenance manuals;
the original pckage;
a set of quick-break fuses.

ADDITIONAL CMPLETENESS:
a protective housing;
a set of forced ventilation fans with automatic
devices;
a set of vibration dampers;
a set of current transformers;
15

TESTS

Carried out according to IEC 60076-11 and GS


52719-2007 control, type and special tests confirm
that dry-type transformers correspond to all specified
requirements.
The manufacturing plant can carry out a number
of type and special tests upon additional request. This
opportunity allows to confirm the declared technical
characteristics of the manufactured transformers.
SVEL dry-type transformers correspond to electro-
magnetic emission norms:
SnPiN 2.1.2.265-10 (sanitary - epidemiological require-
ments to the living conditions in residential buildings and
premises), SnPiN 2.2.2.1191-03 (Electromagnetic fields
in production conditions); nd also noise and vibration
norms: SN 2.2.4/2.1.8562-96 (noise at the workplaces, in
residential and public buildings and residential areas), SN
2.2.4/2.1.8.566-96 (Industrial vibration, and vibration in
residential and public buildings).
16

SERVICE PCKAGE

Installation supervision (technical manual and


engineering supervision);
After-sales service of the installed transformers
and reactors;
Recommendations on installation;
Service and warranty maintenance, including
warranty repair .

WRRNTY

SVEL Group provides the full quality warranty on All equipment supplied by SVEL Group undergoes
the manufactured equipment: the presale preparation. Technical specialists give
3 years warranty on dry-type transformers from the recommendations on installation and settings of the
commissioning date; equipment and also consult the clients operating per-
sonnel about possible faults reasons and troubleshoot-
Service life 30 years.
ing in the case of occurrence. Transformers are sent to
the customer packed in wooden boxes. he packing
STORAGE type is chosen depending on the protection require-
Before placing the transformer for storage it is nec- ments against climatic factors , way of transportation
essary to inspect the unharmed package and trans- and design features of the transformer.
former itself and also to check the completeness of The nameplate, the input contact surfaces and
the supply and to restore the damaged package. earthing clamps shall undergo the conservation (cov-
The transformer is to be kept in the package of the ered with preservation grease).
manufacturing plant in closed, dry, clean, ventilated
room. The storage conditions are according to GOST The set of spare parts correspond to the list of SPTA
15150-69. and is packed together with the transformer.

At the transformer storage it is necessary to take The exploitative documents supplied with the
measures, excluding the possibility of its mechanical product are in a hermetic bag inside the package.
damage and contamination.
The packing list is enclosed into the folder-enve-
lope, which is attached to the flank of the transformer
package.
17

RNSPORTION
Transformers are delivered to the Customer by railroad or by
motor transport. It is admitted to transport the transformers by air,
by river boat or sea craft.
Usually transformers are delivered to the Customer being com-
pletely assembled or partly dismantled depending on the mass and
overall dimensions.
Right after arrival to the point of destination before the trans-
former unloading together with the representative of the forward-
er it is necessary to inspect the package to be sure in absence of the
mechanical damage.
In case of revealing of any mechanical damage of the transform-
er it is necessary to draw up a statement of the inspection results
and to address to the manufacturing plant.

Lading-unloading works
Unloading of the transformer shall be carried out with facilities
which loading capacity corresponds to the transformer mass. The
arrangement of strapping is indicated on the transformer package.
To move the transformer without its package its necessary to
use all the lifting lugs at the same time. The arrangement of strap-
ping is indicated on the dimensional drawing.
Transformers despite their solid design can not withstand strong
impacts or jerking via the lifting lugs. When unloading it is recom-
mended to use the appropriate rope, according to the attached
drawing, where level B shall be higher than level A

Transformers are equipped with ground wheels pivotal in two


directions. For dragging, you can use the special lifting lugs which
are near the wheels. If the transformer is not equipped with a pal-
let, lifting to the electric car can be carried out only in the longitu-
dinal direction.
18

Operation capabilities at the overloads


Life cycle of dry-type transformers is several
decades, but the exact lifetime is rather hard to be
defined as it depends on the operation conditions. h

Service life depends n overloads, which the dry-


type transformer undergoes during its service life. As
a rule the overloads produce heating of windings, that
has negative thermal effect on the insulation and leads
to its thermal wear.
Transformer can work with the presence of some
overloads which dont influence its service life. Its
possible when normal load is less than rated load.
Admissible loads (2) are limited by time (tp) acording
to the previous functional indicator (cefficient of the
previous load, 1) and depend n the average environ-
mental indicator 0. h

Transformer is designed taking into account its


operation under the rated power and at the normal
ambient temperature according to IEC 60726:
ximum temperature 40
Daily average temperature 30
Average annual temperature 20
If not specified otherwise, initial temperature is
considered to be the average annual temperature of
20.
Transformer, designed for operation at the average h
annual temperature of 20, can be also used at higher
or lower temperatures, with increasing or decreasing
of power according to the following parameters:

Average annual Pwer


temperature: (% to nom)

-10C 116 %
0C 110 %
10C 104 %
20C 100 % ambient temperature;
25C 97 %
initial load;
30C 94 % nominal

35C 90 % load duration, tp, h;


nominal
load current;
the maximum time specified load current K2, h.
19

The main characteristics of transformer


On-load losses, Wt
No-load losses,
Pwer, kV 115C 75C Wt

25 530 550 470 490 180
40 730 760 650 680 220
63 1160 1200 1020 1060 275
100 1400 1450 1230 1280 390
160 2410 2500 2130 2210 550
250 3080 3200 2720 2830 700
400 4330 4500 3830 3980 1000
630 7200 7700 6380 6800 1150
1000 9700 10200 8590 9000 1550
1250 11000 11700 9750 10350 2300
1600 13100 13900 11600 12300 2500
2000 15400 16300 13600 14400 2850
2500 19500 20900 17200 18500 3200
3200 24800 26300 21950 23300 5200
4000 26000 27500 24350 24350 5900

Notes:
1) for transformers of the power over 4000 kV th main characteristics are to be agreed upon additionally;
2) th main characteristics of transformers of voltage classes 15-35 kV are to be agreed upon the clients individual request.
20

The main characteristics of series transformers


1 1
2 23 3

5
Pwer, Dimensions, mm Mass not
kV L B H 2 3 5 1 2 3 Z1 x Z2 more, kg
25 880 520 805 290 520 740 75 205 155 220 420 420 380
40 940 520 835 305 535 770 75 210 155 225 420 420 440
63 950 520 925 310 625 845 75 205 155 225 420 420 500
100 1050 620 1025 350 705 1020 75 215 160 255 520 520 690
160 1060 620 1145 365 755 1070 75 225 170 285 720 520 790
250 1135 620 1215 385 815 1120 75 240 185 270 720 520 930
400 1280 770 1350 435 925 1245 75 255 200 295 840 670 1500
630 1450 770 1445 490 970 1345 75 275 220 345 840 670 1950
1000 1570 970 1640 530 1125 1530 75 300 240 385 1070 820 2700
1250 1660 970 1760 565 1240 1640 75 295 235 380 1070 820 3180
1600 1730 1100 1855 580 1305 1730 75 310 250 390 1070 820 3790
2000 1825 1270 2025 620 1455 1895 90 320 260 410 1070 1070 4470
2500 2000 1270 2160 650 1600 2010 90 350 285 400 1070 1070 5270
3200 2285 1500 2450 770 1780 2300 90 395 300 480 1300 1300 7950
For transformers of the power over 3200 kV the overall dimensions are to be agreed upon additionally.
21

Overall installation dimensions of series transformers with


the side lcation of inputs (left and right design version)
example of left design version

Z1 x Z2

Dimensions, mm Mass
Pwer, kV
L B H Z1 x Z2 not more, kg
100 1560 820 1340 520 520 780
160 1720 880 1385 720 520 930
250 1720 880 1410 720 520 1100
400 1905 980 1650 840 670 1730
630 1995 980 1900 840 670 2200
1000 2145 1055 1985 1070 820 2890
1250 2390 1080 2100 1070 820 3365
1600 2465 1180 2115 1070 820 3830
2000 2665 1270 2350 1070 1070 4600
2500 2825 1270 2655 1070 1070 5700
3200 3255 1580 2890 1300 1300 8780
For transformers of the power over 3200 kV the overall dimensions are to be agreed upon additionally.
22

Overall installation dimensions of series transformers with


location of the HV and LV windings inputs on the upper cover

Z1 x Z2

Dimensions, mm Mass
Pwer, kV
L B H Z1 x Z2 not more, kg
160 1420 880 1565 720 520 930
250 1420 880 1565 720 520 1100
400 1520 980 1795 840 670 1700
630 1630 980 2015 840 670 2080
1000 1780 1050 2160 1070 820 2860
1250 2040 1180 2245 1070 820 3440
1600 2040 1180 2245 1070 820 3650
2000 2250 1270 2470 1070 1070 4660
2500 2400 1270 2770 1070 1070 5780
3200 2870 1580 3010 1300 1300 8850
For transformers of the power over 3200 V the overall dimensions are to be agreed upon additionally.
23

Overall installation dimensions of series transformers


rated 25-250 KV (dsign version: LV and V windings inputs - down)

Dimensions, mm Mass
Pwer, kV
L B H Z1 x Z2 not more, kg
25 1120 830 1020 420 420 410
40 1120 830 1020 420 420 490
63 1120 830 1020 420 420 580
100 1260 820 1340 520 520 780
160 1420 880 1390 720 520 910
250 1420 880 1410 720 520 1100
For transformers of the power over 250 V the overall dimensions are to be agreed upon additionally.
24

NOTE:
25

Questionnaire
Cmpany: _______________________________________________ p/b 242, Pervoi Pjatiletki sq.,
_______________________________________________________ Yekaterinburg 620012, Russia
l:____________________________________________________ l: +7 (343) 253-50-21
Fx: +7 (343) 253-50-12
Fax:____________________________________________________
E-mail: sale@svel.ru
E-mail:__________________________________________________ www.svel.ru

CAST RESIN DRY-TYPE CONVERTER RANSFORMER


chnical data of transformer (type):
Purpose:
Rated pwer:
25 40 63 100 160 250 400 630 1000 1250 1600 2000 2500 3200 4000 6300 10000

MV winding (kV): HV winding (kV0: Winding connecon group: Short-circuit voltage,%:


6 0,4 /-11 4
10 0,69 /-0 6
35 8

Off-load tap changer,%: The installaon height Cmposion


above the sea level, m: of the highest harmonics:
22,5 <1000

Recfied vltag Ud, B: Recfied current ld, A: Overcurrent class according to GOST 16772:

Climac modifiicaon and placement category: Protecon class IP:


moderate climate 1 IP00
moderate cold climate 2 IP21
tropical climate 3 IP33
Front side
(Rang plate side)
Version of inputs:
l right
MV, HV windings - up right mirrr Front side
without busbars (for IP00) (Rang plate side)
Addional requirements to the operaon condion and completness:

Number:
Delivery date:

The questionnaire is to be sent by fax: +7 (343) 253-50-12


26

Questionnaire
Cmpany: _______________________________________________ p/b 242, Pervoi Pjatiletki sq.,
_______________________________________________________ Yekaterinburg 620012, Russia
l:____________________________________________________ l: +7 (343) 253-50-21
Fx: +7 (343) 253-50-12
Fax:____________________________________________________
E-mail: sale@svel.ru
E-mail:__________________________________________________ www.svel.ru

CAST RESIN DRY-TYPE POWER RANSFORMER


chnical data of transformer (type):
Rated pwer (kV):

25 40 63 100 160 250 400 630 1000 1250 1600 2000 2500 3200 4000 6300 10000

HV winding (kV): LV winding (kV): Winding connecon group:


6 0,4 /n-11
10 0,69 /n-0
35

Short-circuit voltage, %: Off-load tap changer, %: The installaon height (above the sea level), m:
4 22,5 <1000
6
8

Climac modifiicaon and placement category: Protecon class IP:


moderate climate 1 IP00
moderate cold climate 2 IP21
tropical climate 3 IP33
Front side
(Rang plate side)

Version of inputs:
l
MV, HV windings - up Front side
without busbars (for IP00) (Rang plate side)

Addional requirements to the operaon condion and completness:

Number:
Delivery date:

The questionnaire is to be sent by fax: +7 (343) 253-50-12


27

High energy efficiency

Higher cost effectiveness

Environmental care

Wrranty srvice

Increased service life

Team of professionals
Headquarters
61, Chernyakhovsky st., Yekaterinburg 620010, Russia
l.: +7 (343) 253-50-13
Fx: +7 (343) 253-50-18
www.svel.ru
sale@svel.ru

Branch Offices
scow
office 114, sector 2, building , 11a Derbenevskaya quay,
scow 115114, Russia
l./fx: +7 (495) 913-89-00, 913-89-11
msk@svel.ru

iv
705, 11, Ruskovoy st., iv 02660, Ukraine
l.: +38 (044) 581-57-50
kiev@svel.ru

stn
office 804, 33 D.nv st., Esil district,
Astana 010000, Kazakhstan
l.: +7 (7172) 73-81-24, 73-81-25.
Fx: +7 (7172) 73-81-26
kz@svel.ru

Remark:
In connection with a constant improvement we retain the
right to make changes and technical corrections of the given
document without previous notice
For detailed information please contact our experts.