Operating Instructions
2. Scope of application
This type of humidifier is specially applicable to the central air-conditioning systems in war industry,
laboratory, hospital, medical appliances, electronic workshops, offices, working places and private apartments,
refrigerating devices, purifying rooms, production buildings and computer rooms and other aseptic locations.
3. Model
Improved SN
S R A X X K Capable of receiving signal
STAND Company of 0-10 V or 4-20 mA
Electric Humidifier N: Capable of receiving signal of ON/OFF
A: indicate concealed type Electric Humidifier
B: indicate surface mounted type Electric Humidifier Maximum Humidifying Capacity
Voltage Type
1 Represent 220 V &
3 Represent 380 V
Notes: The standard factory setting of Type K product is to receive the control signal of 0-10 V. If the user
supplies the control signal of 4-20 mA, please specify when ordering.
4. Operational features
Strong applicability can be applied to any water quality, particularly the pure water; under the
conditions of pure water applied, the scale will not form in the humidifier in case of
long period of operation and no maintenance is required.
Safe and reliable in case of water shortage of heating cabinet of the steam humidifier, no dry burning
will occur, avoiding the risks of fire and leakage of electricity to achieve absolute
safe and reliable.
Automatic control automatic control of water feed, and only the water in the box covers over the heating
elements to specific height, the electric heating elements start heating
Clean and aseptic steam humidifying, in compliance with the requirements of sanitary and clean,
particularly suitable for the locations with aseptic operations required
5. Technical data
Two control modes (N: ON/OFF; K: 0~10V regulating mode; in case of control of 4-20 mA required,
please specify in advance when ordering.
2
Humidifying
Model Current (A) Power Supply Power (KW)
Capacity (Kg/h)
SRA (II) 1--04 N (K) 5 13.6 AC 220V/50Hz 3.0
SRA (II) 3--10 N (K) 10 11.4 7.5
SRA (II) 3--20 N (K) 22 22.8 15
SRA (II) 3--30 N (K) 30 34.2 22.5
SRA (II) 3--40 N (K) 40 45.6 30
AC 380V/50Hz
SRA (II) 3--60 N (K) 60 68.4 45
SRA (II) 3--80 N (K) 80 91.2 60
SRA (II) 3--100 N (K) 100 114 75
SRA (II) 3--120 N (K) 120 136.8 90
6. Operating conditions
Ambient temperature 1~ 40
Ambient humidity 0~80% RH
Water supply pressure 1~5 Bar
Water quality clean tap water or softened water, pure water or deionized water is better
Pressure in air duct Series SRA 200mmH2O
7. Outline dimensions
7.1 Outline dimensions of main engine of Series SRA humidifier
Model SRA
3
1.2 Relevant sizes table
Size
A B C D F G L H
Model
SRA (II) 1--04 N (K) 450 230 272 462 190 210 380 370
SRA (II) 3--10 N (K) 570 302 344 576 262 330 500 385
SRA (II) 3--20 N (K) 570 302 344 576 262 330 500 435
SRA (II) 3--30 N (K) 570 410 452 612 370 330 500 435
SRA (II) 3--40 N (K) 570 410 452 612 370 330 500 475
SRA (II) 3--60 N (K) 570 518 560 612 478 330 500 475
SRA (II) 3--80 N (K) 570 410 452 612 370 330 500 585
SRA (II) 3--100 N (K) 570 490 530 612 450 330 500 640
SRA (II) 3--120 N (K) 570 526 568 612 486 330 500 675
Type of electric cabinet: DRK (electrically heated cabinet) 1/3 (single phase or three-phase) K/N
The Arabic figures such as 1, 2 or 3 following N/K represent the improved SN.
4
-N -K - N -K - N -K -N/K -N/K -N/K -N/K -N/K -N/K
DRK
-04 -04 -10 -10 -20 -20 -30 -40 -60 -80 -100 -120
A (mm) 500 500 500 600 500 600 600 600 950 950 1000 1000
B (mm) 400 400 400 500 400 500 500 500 550 550 600 600
C (mm) 180 180 180 200 180 200 200 200 220 220 250 250
D(mm) 350 350 350 350 350 450 450 450 500 500 550 550
E (mm) 450 450 450 450 450 550 550 550 900 900 950 950
6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 10 10 10 10
(mm)
Steam outlet
Tank cover
Steam generator
Temperature
protection switch 1
Electric-thermal
tube wiring terminal Electric-thermal
tube
Electric
protecting cover
5
10. Installing the humidifier
10.1 Sketch of Installing Series SRA Humidifier
CAUTION: when installing Series SRA humidifiers, install the main engine in the air conditioning box while
the electric cabinet outside the air conditioning box.
10.1.1 Installing horizontal air conditioning box at the humidifying section
Heat exchange
Humidifier
Electric cabinet
Main engine of
humidifier
Surface cooler
6
down with a cooling water tank or cooling pipeline (metallic) to below 50 before introducing to
common PVC or plastic pipes.
b) STAND Electric cooling water tank is considered as options and subject to the users selection when
ordering.
c) The drain line is provided with manual ball valve. The user shall drainage the dirt in the tank on a
timing basis.
The user shall make the preparations as below:
1. Water feed: prepare G1/2 water source interface in the air conditioning engine room; the water source
line shall be provided with additional ball valve.
2. Water drain: prepare G3/4 metallic water drain line in the air conditioning engine room.
3. Prepare corresponding pipe fittings joints, reducer unions, and unions.
Model
1-04 3-10 3-16 3-22 3-30 3-40 3-60 3-80 3-100 3-120
SRA/B (II)
Cable
Cross-section 4 2.5 4 6 10 10 16 25 35 50
(mm2)
a) Select the diameter of conductors connecting the heating elements and the wiring terminals of electric
cabinet as per the value listed in the above table. Separately connect three live wires and one zero line
and one ground wire as well as two lead-out wires of safety and protection to corresponding terminals
7
inside the electric cabinet as per the wiring diagram, and then pack them firmly.
b) Properly connect the wires as per the terminals wiring diagram inside the electric cabinet.
8
Green
TC
Green
Blower Over-
Low level temperature
locking float switch
Brown
FU 2A
Brown
Yellow
ON/OFF
ON/OFF
LOCK
LOCK
OVER.T
OVER.T
+24V
GND
Red
SA
To upper- Lock Over-
humidity sensor temperature
L
1KM
J3
J2 2KM
J1
Power L
Intervel (h) supply N
21
Drain pump
12 30
OF Drain
F 36
valve
N
ALARM
Drain.Time(s) Alarm
ALARM
20
15
Working state STATE
10 25 STATE
Control signal input
30
ON/OFF
4~20mA
5
0~10V
+24V
GND
9
1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1R 1S 1T N1 2R 2S 2T N1 6 2 6 7 8 9 19 20 21 22 23 10 11 12 13 15 16 17 18
Electric-thermal Electric-thermal Abnormal Working
Drain Blower Over- Control signals Upper-
outgoings outgoings temperature feedback feedback
pump locking temperature
sensor
Notes: above circuits are of standard circuit. If the silicon-controlled analogue electric cabinet is
applied, you may consult with our technical department in respect of technological matters. For
humidifying capacity below (including) 20 Kg/h, the humidifier is subject to control of controlled silicon.
10
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1R 1S 1T 1N 21 23 23 24
11 12 25 27 47 48 49 50 71 70
Load outgoings
Blower Over- Fault Working Control Upper humidity
locking temperature feedback feedback signals controller
lowlevel
protection
1N
Power
HW supply
fan
Radiator
fan
SB1 KM
KA2
L11 FU1 11 LS 12 13 15
2A Working
HG
SB2
Automatic KA1
17 Manual-
Automatic
Manual selection
KA2 HY
19 Faults
alarm
TC
21 23
FU2 Over-
2A Over- temperature
temperature Low level switch
25 protection KA2
switch 24
27 Low
level
protection
KA2
Fault
47 48 feedback
KM Fault
feedback
49 50
13.4 Model SRA (II) 1 (3) 04~20K Electric Humidifier Main Loop Principle Diagram
11
B30
PE
12
13.6 Model SRA (II) 1 (3) 04~20N Electric Humidifier Main Loop Principle Diagram
13
13.7 Model DRK- N-04~20 Control Cabinet Terminal Diagram
14
15. Troubleshooting
15.1 Water shortage
After the feed valve is opened for feeding the water for 20 minutes, there is still no humidifying current or
the current is too weak;
Reasons:
1. There is no water in feed pipe or the water pressure is insufficient
2. Feed valve is blocked or damaged
3. Electric heating pipelines are virtually connected, pressure switch are virtually connected or float
switch is virtually connected
4. Feed lines are blocked
Check and handling method
1. Check the feed lines
2. Check the feed valve and the filter
3. Check whether the pipeline between the water tank and the heating water tank is blocked
4. Check the wiring
15
1. The wiring inside the electric cabinet is made improperly
2. The transformer has no output voltage
3. The circuit of power supply switch on the panel is broken
4. The fuse is burned out
Check and handling method
1. Check the correctness of the wiring
2. Check the secondary output of the transformer
3. Close the power supply switch on the panel
4. Check the fuse of original secondary
16
cabinet contains foreign substances and ensure the pin slide freely
17.7 Frequent check shall be made on the water tank in respect of the scale and if yes, clean the tank. The
power supply must be switched off during cleaning
17.8 In case of long period of out-of-operation, the power supply and the water source shall be closed and
completely empty the remaining water in the tank.