Model SRA (II) Electric Humidifier

Operating Instructions

BEIJING STAND ELECTRONIC TECHNOLOGY COMPANY


1. Working principle of STAND electric humidifier
STAND Electric humidifier operates on the Joule Effect, i.e. have the electric heating elements immersed
into the water and make them energized, then they will generate the heat; such heat will warm up the water to
the boiling point to generate the vapour, thus make the water content evaporate.

2. Scope of application
This type of humidifier is specially applicable to the central air-conditioning systems in war industry,
laboratory, hospital, medical appliances, electronic workshops, offices, working places and private apartments,
refrigerating devices, purifying rooms, production buildings and computer rooms and other aseptic locations.

3. Model

Improved SN
S R A X X K Capable of receiving signal
STAND Company of 0-10 V or 4-20 mA
Electric Humidifier N: Capable of receiving signal of ON/OFF
A: indicate concealed type Electric Humidifier
B: indicate surface mounted type Electric Humidifier Maximum Humidifying Capacity
Voltage Type
1 Represent 220 V &
3 Represent 380 V

Notes: The standard factory setting of Type K product is to receive the control signal of 0-10 V. If the user
supplies the control signal of 4-20 mA, please specify when ordering.

4. Operational features
Strong applicability can be applied to any water quality, particularly the pure water; under the
conditions of pure water applied, the scale will not form in the humidifier in case of
long period of operation and no maintenance is required.
Safe and reliable in case of water shortage of heating cabinet of the steam humidifier, no dry burning
will occur, avoiding the risks of fire and leakage of electricity to achieve absolute
safe and reliable.
Automatic control automatic control of water feed, and only the water in the box covers over the heating
elements to specific height, the electric heating elements start heating
Clean and aseptic steam humidifying, in compliance with the requirements of sanitary and clean,
particularly suitable for the locations with aseptic operations required

5. Technical data
Two control modes (N: ON/OFF; K: 0~10V regulating mode; in case of control of 4-20 mA required,
please specify in advance when ordering.

2
Humidifying
Model Current (A) Power Supply Power (KW)
Capacity (Kg/h)
SRA (II) 1--04 N (K) 5 13.6 AC 220V/50Hz 3.0
SRA (II) 3--10 N (K) 10 11.4 7.5
SRA (II) 3--20 N (K) 22 22.8 15
SRA (II) 3--30 N (K) 30 34.2 22.5
SRA (II) 3--40 N (K) 40 45.6 30
AC 380V/50Hz
SRA (II) 3--60 N (K) 60 68.4 45
SRA (II) 3--80 N (K) 80 91.2 60
SRA (II) 3--100 N (K) 100 114 75
SRA (II) 3--120 N (K) 120 136.8 90

6. Operating conditions
Ambient temperature 1~ 40
Ambient humidity 0~80% RH
Water supply pressure 1~5 Bar
Water quality clean tap water or softened water, pure water or deionized water is better
Pressure in air duct Series SRA 200mmH2O

7. Outline dimensions
7.1 Outline dimensions of main engine of Series SRA humidifier

7.1.1 Sketch of outline dimensions

Model SRA

3
1.2 Relevant sizes table

Size
A B C D F G L H
Model
SRA (II) 1--04 N (K) 450 230 272 462 190 210 380 370
SRA (II) 3--10 N (K) 570 302 344 576 262 330 500 385
SRA (II) 3--20 N (K) 570 302 344 576 262 330 500 435
SRA (II) 3--30 N (K) 570 410 452 612 370 330 500 435
SRA (II) 3--40 N (K) 570 410 452 612 370 330 500 475
SRA (II) 3--60 N (K) 570 518 560 612 478 330 500 475
SRA (II) 3--80 N (K) 570 410 452 612 370 330 500 585
SRA (II) 3--100 N (K) 570 490 530 612 450 330 500 640
SRA (II) 3--120 N (K) 570 526 568 612 486 330 500 675

7.2 Outline dimensions of electric control cabinet of electric humidifier

Type of electric cabinet: DRK (electrically heated cabinet) 1/3 (single phase or three-phase) K/N

(control form) - 04~120 (humidity capacity)

The Arabic figures such as 1, 2 or 3 following N/K represent the improved SN.

Sketch of Mounting Hole

4
-N -K - N -K - N -K -N/K -N/K -N/K -N/K -N/K -N/K
DRK
-04 -04 -10 -10 -20 -20 -30 -40 -60 -80 -100 -120
A (mm) 500 500 500 600 500 600 600 600 950 950 1000 1000
B (mm) 400 400 400 500 400 500 500 500 550 550 600 600
C (mm) 180 180 180 200 180 200 200 200 220 220 250 250
D(mm) 350 350 350 350 350 450 450 450 500 500 550 550
E (mm) 450 450 450 450 450 550 550 550 900 900 950 950

6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 10 10 10 10
(mm)

8. Basic configuration of humidifier system

Humidity signal wire Humidity controller

Control cabinet Humidity control knob

Control signal wire

Power lead Steam outlet

Power line Humidifier

Notes: in the figure, the humidity controller is of options.

9. Basic configuration of main engine of humidifier

Temperature protection switch 2 Water tank attached

Steam outlet
Tank cover
Steam generator

Temperature
protection switch 1

Electric-thermal
tube wiring terminal Electric-thermal
tube
Electric
protecting cover

Wiring Low level


terminals protective switch Float valve Base Water inlet Water drain Water drain ball valve

5
10. Installing the humidifier
10.1 Sketch of Installing Series SRA Humidifier
CAUTION: when installing Series SRA humidifiers, install the main engine in the air conditioning box while
the electric cabinet outside the air conditioning box.
10.1.1 Installing horizontal air conditioning box at the humidifying section

Heat exchange

Main air flow

Humidifier

Water collecting pan


Water
Electric cabinet discharge

10.1.2 Installing vertical air conditioning box at the humidifying section

Electric cabinet
Main engine of
humidifier

Surface cooler

11. Connecting water line


The user shall connect the feed line and drain line to the humidifier in accordance with the following
requirements during installation of the humidifier.
11.1 Feed line
The internal diameter of feed pipe is G1/2. The feed line must be provided with a ball valve with through
diameter of G1/2. The feed pressure varies from 1 to 5bar. The water temperature shall not exceed 40. It is
particularly noted that it is better to apply the softened water and pure water.
11.2 Drain line
a) The water drained from the humidifier is non-toxic and non-corrosive, therefore can be directly drained
into the sewage system; however, the drain temperature of sewage from the electric humidifier is very
high, approaching 100, and common PVC or plastic pipes cant be used as sewage pipe and if the
sewage pipe must be applied with common PVC or plastic pipes, then the temperature must be dropped

6
down with a cooling water tank or cooling pipeline (metallic) to below 50 before introducing to
common PVC or plastic pipes.
b) STAND Electric cooling water tank is considered as options and subject to the users selection when
ordering.
c) The drain line is provided with manual ball valve. The user shall drainage the dirt in the tank on a
timing basis.
The user shall make the preparations as below:
1. Water feed: prepare G1/2 water source interface in the air conditioning engine room; the water source
line shall be provided with additional ball valve.
2. Water drain: prepare G3/4 metallic water drain line in the air conditioning engine room.
3. Prepare corresponding pipe fittings joints, reducer unions, and unions.

12. Electric connections


12.1 Connecting electric cabinet to the grid
a) The humidifier must be connected to the grid. Moreover, this grid must be capable of providing
power for the humidifier (including electric cabinet) via ground wire, phase wire and neutral wire
(single phase voltage) of sufficient capacity. The user is suggested to configure the power leads as

Model
1-04 3-10 3-16 3-22 3-30 3-40 3-60 3-80 3-100 3-120
SRA/B (II)
Cable
Cross-section 4 2.5 4 6 10 10 16 25 35 50
(mm2)

shown in the following table:


b) Precautions:
- Before connecting the circuits, please carefully read the data noted on the nameplate provided to the
main engine of humidifier;
- Check whether the power supply meets the standard voltage of the humidifier;
- Configure the fuses or other protective devices to protect the humidifier;
- The power leads shall not be longer than 50 m generally.
12.2 Connecting main engine of humidifier to electric cabinet
Model
1-4 3-10 3-20 3-30 3-40
SRA (II)
Cable Cross-section Area 2.5x5 2.5x5
4x3 2.5x5 6x3+4x2
mm2x number of strand 6x3+4x2 10x3+6x2
Model
SRA (II) 3-60 3-80 3-100 3-120 -----------

Cable Cross-section Area 6x3+4x2 6x3+4x2 10x3+6x2 10x3+6x2


-----------
mm2x number of strand 10x3+6x2 16x3+10x2 16x3+10x2 25x3+16x2

a) Select the diameter of conductors connecting the heating elements and the wiring terminals of electric
cabinet as per the value listed in the above table. Separately connect three live wires and one zero line
and one ground wire as well as two lead-out wires of safety and protection to corresponding terminals

7
inside the electric cabinet as per the wiring diagram, and then pack them firmly.
b) Properly connect the wires as per the terminals wiring diagram inside the electric cabinet.

CAUTION: Cable diameter corresponding to each group of electric heating elements!!!


12.3 Connecting control signals to electric cabinet
a) Type N Electric cabinet can receive a humidity control signal or a ON/OFF passive relay-type switch
signal from automatic system to control the operation of humidifier.
b) Type K Electric cabinet can receive a 0~10V/4~20mA continuous regulating signal from automatic
system to control the operation of humidifier.
c) Properly connect the wires as per the terminals wiring diagram inside the electric cabinet.
12.4 The electric installation professions must obtain appropriate qualification permit.

13. Electrical principle


13.1 Model DRK-N/K-30~120 control cabinet electric control board, terminal diagram and
humidifier main loop principle diagram

8
Green
TC

Green
Blower Over-
Low level temperature
locking float switch
Brown

FU 2A
Brown

Yellow

ON/OFF
ON/OFF

LOCK
LOCK
OVER.T
OVER.T
+24V
GND
Red

SA
To upper- Lock Over-
humidity sensor temperature
L
1KM
J3
J2 2KM
J1
Power L
Intervel (h) supply N
21
Drain pump
12 30
OF Drain
F 36
valve
N

ALARM
Drain.Time(s) Alarm
ALARM
20
15
Working state STATE
10 25 STATE
Control signal input
30
ON/OFF
4~20mA

5
0~10V

+24V
GND

9
1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1R 1S 1T N1 2R 2S 2T N1 6 2 6 7 8 9 19 20 21 22 23 10 11 12 13 15 16 17 18
Electric-thermal Electric-thermal Abnormal Working
Drain Blower Over- Control signals Upper-
outgoings outgoings temperature feedback feedback
pump locking temperature
sensor

Notes: above circuits are of standard circuit. If the silicon-controlled analogue electric cabinet is
applied, you may consult with our technical department in respect of technological matters. For
humidifying capacity below (including) 20 Kg/h, the humidifier is subject to control of controlled silicon.

13.2 Model DRK- K-04~20 Control Cabinet Terminal Wiring Diagram

10
1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

1R 1S 1T 1N 21 23 23 24
11 12 25 27 47 48 49 50 71 70
Load outgoings
Blower Over- Fault Working Control Upper humidity
locking temperature feedback feedback signals controller
lowlevel
protection

13.3 Model DRK- K-04~20 Control Cabinet Control Principle Diagram

1N

Power
HW supply

fan
Radiator
fan
SB1 KM
KA2
L11 FU1 11 LS 12 13 15
2A Working
HG

SB2
Automatic KA1
17 Manual-
Automatic
Manual selection
KA2 HY
19 Faults
alarm
TC

ZAC10- P High temperature


switch
Transformer

21 23

FU2 Over-
2A Over- temperature
temperature Low level switch
25 protection KA2
switch 24
27 Low
level
protection

KA2
Fault
47 48 feedback

KM Fault
feedback
49 50

13.4 Model SRA (II) 1 (3) 04~20K Electric Humidifier Main Loop Principle Diagram

11
B30

PE

13.5 Model DRK- N-04~20 Control Cabinet Control Principle Diagram

12
13.6 Model SRA (II) 1 (3) 04~20N Electric Humidifier Main Loop Principle Diagram

13
13.7 Model DRK- N-04~20 Control Cabinet Terminal Diagram

14. Operating procedures


14.1 Check

Before switching on the humidifier, the following respects must be checked:


Whether the power leads, working ground wires and protective wires are connected properly and firmly in
accordance with the requirements
Connection of sensors and control signals
The steam outlet must be free of obstruction
Water feed connection of the humidifier
Water drain connection of the humidifier
Whether the electric cabinet matches the humidifier

14.2 Switching on the humidifier


Open the electric cabinet and pull the trigger of air switch to the position of ON;
Press the power switch on the control cabinet. The switch indicator goes on, indicating the power has been
put through
CAUTION: to prevent dry burning of heating elements, please do confirm the water line has been
supplied with water and opened before switching on the power switch.

14.3 Humidity setting


Type N: a passive relay type switch signal ON/OFF is sent to the humidifier from the automatic control
system. The humidifier may work or stop as per the signal;
Type K: a 0~10V/4~20mA continuous regulating signal is sent to the humidifier from the automatic
control system; the humidifier may automatically regulate the steam output (i.e. humidifying
capacity) as per the changes of signal. Attention is required that such signal must be the control
signal from the automatic control system but not the humidity signal from the humidity sensor.
14.4 Indicators
After connecting above parts and feeding the water via feed valve for a period of time, the float switch
controlling the level is connected; at this time you may hear pa sent by the main contactor in the electric
cabinet and the cabinet is put through. The working indicators on the control cabinet go on; the electric heating
elements make the power supply put through, and the humidifier starts heating. In several minutes, you may
find steam ejecting from the steam outlet or the steam distributor.

14
15. Troubleshooting
15.1 Water shortage
After the feed valve is opened for feeding the water for 20 minutes, there is still no humidifying current or
the current is too weak;
Reasons:
1. There is no water in feed pipe or the water pressure is insufficient
2. Feed valve is blocked or damaged
3. Electric heating pipelines are virtually connected, pressure switch are virtually connected or float
switch is virtually connected
4. Feed lines are blocked
Check and handling method
1. Check the feed lines
2. Check the feed valve and the filter
3. Check whether the pipeline between the water tank and the heating water tank is blocked
4. Check the wiring

15.2 Insufficient humidifying current


The water level of the humidifying water tank has approached the highest level, but there is no current
through the heating elements
Reasons:
1. One or multiple heating elements are damaged
2. The main contactor is damaged
3. The float switch is damaged
Check and handling method
1. Check whether all heating elements are current
2. Check the main contactor
3. Change the float switch

15.3 The humidifier does not start


The electric cabinet is not energized and the whole humidifier fails to start
Reasons:
1. The general power supply does not provide the electricity or the power switch on the
electric cabinet is not opened
2. The external signals do not reach the humidifier
3. The external regulator, the humidity switch or sensor is wired improperly
4. The humidity setting point is too low
Check and handling method
1. Check each protection in a direction reverse to power supplying
2. The contact point for connecting the humidity control on the terminal must be closed
3. Check the external wiring
4. Increase the humidity setting point

15.4 No power supply for electric cabinet


Reasons:

15
1. The wiring inside the electric cabinet is made improperly
2. The transformer has no output voltage
3. The circuit of power supply switch on the panel is broken
4. The fuse is burned out
Check and handling method
1. Check the correctness of the wiring
2. Check the secondary output of the transformer
3. Close the power supply switch on the panel
4. Check the fuse of original secondary

15.5 Circuit breaker tripping


Reasons:
1. The drain line has leakage to the ground
2. The steam line has leakage to the ground
Check and handling method
Check that the steam or drain line shall not be made of metallic or conductive rubber.

15.6 External circuit breaker tripping


Reasons:
The capacity of circuit breaker is too small
Check and handling method
Check that the current through the circuit breaker shall be at least one and half of the rated current of
the humidifier

16. Main performance indicators of humidifier


Model SRA/B (II) 1-04 3-10 3-20 3-30 3-40 3-60 3-80 3-100 3-120
Control mode Type N/Type K

Operating environment -10~40 0~60% RH


of electric cabinet
Operating environment 1-40 C 0-80% RH
of main machine
Feed water pressure 1~5 Bar
Pressure in Air Duct Series SRA 200mmH2O

17. Operating, maintenance and precautions


17.1 Working voltage: not greater than 1.1 times of rated value, the enclosure shall be earthed effectively
17.2 Water supply: clean water unlikely forming scale, free of corrosion and impurities
17.3 The humidifier shall be installed horizontally and shall not be inclined. During connecting the external
water pipes, attention shall be given that the valve port direction of feed valve shall not rotate.
17.4 During the operation of the humidifier, the steam outlet shall not be covered to prevent the steam drain
from being affected
17.5 Do not regulate and remove the float valve and the control switch to avoid damage.
17.6 Frequent check shall be made to confirm whether the travel switch knockout-pin inside the control

16
cabinet contains foreign substances and ensure the pin slide freely
17.7 Frequent check shall be made on the water tank in respect of the scale and if yes, clean the tank. The
power supply must be switched off during cleaning
17.8 In case of long period of out-of-operation, the power supply and the water source shall be closed and
completely empty the remaining water in the tank.

This Operating Instructions is Subject to Changes without Further Notice

17
STAND Humidifier After-sale Service Centre
No.1 Shangdisijie, Haidian District, Beijing Postal Code: 100085
Tel: 01062968335 (36/37/38) Fax: 010--62984488