M.Tech - I Semester Regular & Supplementary Examinations, April/May 2013
AIR-CONDITIONING - I
(Refrigeration & Air Conditioning)
L D
The room sensible and latent heat loads for an air conditioned space are 25 KW and 5
KW respectively. The room condition is 250C dry bulb temperature and 50% relative
O R
humidity. The outdoor condition is 400C dry bulb temperature and 50% relative humidity.
The ventilation requirement is such that on mass flow rate basis 20% of fresh air is
introduced and 80% of supply air is re-circulated. The by-pass factor of the cooling coil is
0.15. Determine
(a)
(b)
(c)
Supply air-flow rate.
Outside air sensible heat.
Outside air latent heat.
U W
T
(d) Grand total heat and
(e) Effective room sensible heat factor.
4 (a)
J N
Explain with a neat schematic diagram the working principle of year-round air
conditioning system and describe the functions of different components in the circuit.
6 Explain briefly different types of ventilation systems used in air conditioning systems.
7 Explain briefly the different types of humidity control systems used in air-conditioning
systems.