Relays used
50BF Circuit Breaker Failure I
87G Differential Protection
64R Rotor Earth fault
37 Low Forward Power
59N Stator Earth fault 90%/95%
32R Reverse Power(high/low)
21 Min. Impedance
60FL Fuse Failure
Trip
Trip ok
Alarm/Trip/fault ok
ok
64S1-90%& 64S2 100% Alarm/Trip/fault ok
Trip ok
Trip ok
Unbalance Voltage Alarm
can be superceed in
the configration
GEN,GCB & T/f as
taken care by 64
earth fault protection ok
open1,cbclose2)
50BF Circuit Breaker Failure II Trip
87G Differential Protection Trip
64R Rotor Earth fault+Sensitive Rotor E/F Alarm/Trip/fault
Low Forward Power
64G Stator Earth fault 100% Alarm/Trip/fault
32R Reverse Power Trip
21 Impedance Trip
60FL Fuse Failure Alarm
voltage restrained
overcurrent
51V Over current protection Trip
59 Over Voltage Trip
81 Frequency Stage 1 Trip
81 Frequency Stage 2 Trip
50/27 Inadvertand energization Trip
46 Unbalanced Load alarm/trip
BAT
870A Differential Trip 870A Differential
50/51 Overcurrent 1 phase breaker failure 50/51 Overcurrent 1 phase
50/51N Over current 1 Ie>Ie>> Trip 50/51N Over current 1 Ie>Ie>>
50/51 Overcurrent 2 phase 50/51 Overcurrent 2 phase
50/51N Over current 2 Ie>Ie>> Trip 50/51N Over current 2 Ie>Ie>>
50/51 Overcurrent 3 phase 50/51 Overcurrent 3 phase
50/51N Over current 3 Ie>Ie>> Trip 50/51N Over current 3 Ie>Ie>>
27 under voltage 87N Restricted E/F 1
59 Over Voltage
59N Bus Earth Fault-Over Voltage Alarm 59N Bus Earth Fault
24/(59/81) Over Excitation U/F-Over flux Alarm/Trip 24 Over Excitation U/F
Buchholz Relay Trip
Pressure Relief Device Trip
Trip
22O KV Substation Protection chan1 Trip
Fire Protection Trip
From Generator Protection chan 1 Trip
Winding Temp. Trip
Trip
Trip
Buchholz Relay Trip
Pressure Relief Device Trip
Fire Protection Trip
Winding Temp. Trip
Trip
Differential Trip
Overcurrent 1 phase Trip
Over current 1 Ie>Ie>>
Overcurrent 2 phase
Over current 2 Ie>Ie>>
Overcurrent 3 phase
Over current 3 Ie>Ie>>
Restricted E/F 1 Trip