Você está na página 1de 26

Copyright 2013 AIA MasterSpec Premium 12/13

PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING


DEVICES - KELLEMS.

Copyright 2013 by The American Institute of Architects (AIA)

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

This Product MasterSpec Section is licensed by ARCOM to Hubbell Incorporated Wiring Devices -
Kellems ("Licensee").

This Product MasterSpec Section modifies the original MasterSpec text.

Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by,
or representative of the opinions of, ARCOM or The American Institute of Architects (AIA). Neither AIA
nor ARCOM are liable in any way for such revisions or for the use of this Product MasterSpec Section by
any end user. A qualified design professional should review and edit the document to suit project
requirements.

For more information, contact Hubbell Incorporated Wiring Devices - Kellems, 40 Waterview Dr.,
Shelton, CT 06484; Phone: (800) 288-6000; Fax: (800) 255-1031; Website: www.hubbell-wiring.com;
Email: jcarrol@hubbell.com.

For information about MasterSpec contact ARCOM at (800) 424-5080 or visit www.MasterSpec.com.

SECTION 262726 - WIRING DEVICES

TIPS:

To view non-printing Editor's Notes that provide guidance for editing, click on Masterworks/Single-File
Formatting/Toggle/Editor's Notes.

To read detailed research, technical information about products and materials, and coordination
checklists, click on Masterworks/Supporting Information.

Revise this Section by deleting and inserting text to meet Project-specific requirements.

This Section uses the term "Architect." Change this term to match that used to identify the design
professional as defined in the General and Supplementary Conditions.

Verify that Section titles referenced in this Section are correct for this Project's Specifications; Section
titles may have changed.

PART 1 - GENERAL

0.1 RELATED DOCUMENTS

Retain or delete this article in all Sections of Project Manual.

A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.

WIRING DEVICES 262726 - 1


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

0.2 SUMMARY

A. Section Includes:

1. Receptacles, receptacles with integral GFCI, and associated device plates.


2. Receptacles with integral USB charger.
3. Receptacles with integral Arc Fault Circuit Interrupter, AFCI.
4. Plugload Control Receptacles.
5. Twist-locking receptacles.
6. Receptacles with integral surge-suppression units.
7. Isolated-ground receptacles.
8. Hospital-grade receptacles.
9. Tamper-resistant receptacles.
10. Weather-resistant receptacles.
11. Snap switches and wall-box dimmers.
12. Solid-state fan speed controls.
13. Wall-switch and exterior occupancy sensors.
14. Communications outlets.
15. Pendant cord-connector devices.
16. Cord and plug sets.
17. Floor service outlets, poke-through assemblies, service poles, and multioutlet assemblies.

0.3 DEFINITIONS

Retain terms that remain after this Section has been edited for a project.

A. AFCI: Arc fault circuit interrupter.

B. EMI: Electromagnetic interference.

C. GFCI: Ground-fault circuit interrupter.

D. Pigtail: Short lead used to connect a device to a branch-circuit conductor.

E. Plugload Control Receptacle: Automatically occupancy switched receptacle.

F. RFI: Radio-frequency interference.

G. TVSS: Transient voltage surge suppressor.

H. UTP: Unshielded twisted pair.

0.4 ADMINISTRATIVE REQUIREMENTS

Retain this article if receptacles for Owner-furnished equipment with plugs have unknown or special
configurations.

A. Coordination:

WIRING DEVICES 262726 - 2


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

1. Receptacles for Owner-Furnished Equipment: Match plug configurations.

Retain "Cord and Plug Sets" Subparagraph below if retaining "Cord and Plug Sets" Article.
2. Cord and Plug Sets: Match equipment requirements.

0.5 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: List of legends and description of materials and process used for premarking
wall plates.

Retain "Samples" Paragraph below if products have critical features needing hands-on appraisal.

C. Samples: One for each type of device and wall plate specified, in each color specified.

0.6 INFORMATIONAL SUBMITTALS

A. Field quality-control reports.

0.7 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For wiring devices to include in all manufacturers' packing-
label warnings and instruction manuals that include labeling conditions.

0.8 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.

1. Service/Power Poles: [One for every 10] <Insert quantities>, but no fewer than [one]
<Insert number>.
2. Floor Service-Outlet Assemblies: [One for every 10] <Insert quantities>, but no fewer
than [one] <Insert number>.
3. Poke-Through, Fire-Rated Closure Plugs: [One for every five] <Insert quantities> floor
service outlets installed, but no fewer than [two] <Insert number>.
4. TVSS Receptacles: [One for every 10] <Insert quantities> of each type installed, but no
fewer than [two of each type] <Insert number>.

PART 2 - PRODUCTS

See Editing Instruction No. 1 in the Evaluations for cautions about named manufacturers and products.
For an explanation of options and Contractor's product selection procedures, see Section 016000 "Product
Requirements."

WIRING DEVICES 262726 - 3


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

0.1 MANUFACTURERS

A. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; Wiring Device-Kellems (Hubbell) or a comparable
product by one of the following:

1. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


2. Leviton Manufacturing Co., Inc.
3. Pass & Seymour/Legrand (Pass & Seymour).
4. <Insert manufacturer's name>

B. Source Limitations: Obtain each type of wiring device and associated wall plate from single
source from single manufacturer.

0.2 GENERAL WIRING-DEVICE REQUIREMENTS

A. Wiring Devices, Components, and Accessories: Listed and labeled as defined in NFPA 70, by a
qualified testing agency, and marked for intended location and application.

B. Comply with NFPA 70.

Not all standard devices are available with a modular plug-in configuration. For example, this Section
does not include specifications for modular devices.

C. Devices that are manufactured for use with modular plug-in connectors may be substituted
under the following conditions:

1. Connectors shall comply with UL 2459 and shall be made with stranding building wire.
2. Devices shall comply with the requirements in this Section.

0.3 STRAIGHT-BLADE RECEPTACLES

For extra heavy duty applications use HBL 5352 duplex convenience receptacle.

A. Convenience Receptacles, Heavy Duty 125 V, 20 A: Comply with NEMA WD 1, NEMA WD 6


Configuration 5-20R, UL 498, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL536151 (single), HBL536252 (duplex), or a
comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 5361 (single),
AH 5362 (duplex).
b. Leviton Manufacturing Co., Inc.; 5361 (single), 5362 (duplex).
c. Pass & Seymour/Legrand (Pass & Seymour); 5361 (single), 5362 (duplex).
d. <Insert manufacturer's name>

WIRING DEVICES 262726 - 4


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

B. USB Charging Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1, NEMA WD


6 Configuration 5-20R, UL 498, UL 1310, and FS W-C-596. Compatible with USB 1.1/2.0/3/0
devices, including Apple products.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; USB 20X2 duplex receptacle with 2 USB
charging Ports or a comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


b. Leviton Manufacturing Co., Inc.
c. Pass & Seymour/Legrand (Pass & Seymour).
d. <Insert manufacturer's name>

C. Arc Fault Convenience Receptacles, 125 V, 15A and 20A: Comply with NEMA WD 1, NEMA
WD 6 Configuration 5-20R, UL 498, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; AFR25TRW, AFR20TRW, or a comparable
product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


b. Leviton Manufacturing Co., Inc.
c. Pass & Seymour/Legrand (Pass & Seymour).
d. <Insert manufacturer's name>

D. Plugload Controlled Convience Receptacles, 125 V, 20 A: Comply with NEMA WD 1, NEMA


WD 6 Configuration 5-20R, UL 498, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; DR 20 LA with Load Logic [wired] [wireless]
transmitter and control units or a comparable product by one of the following:

a. Lutron.
b. <Insert manufacturer's name>

E. Hospital-Grade, Heavy Duty, Duplex Convenience Receptacles, 125 V, 20 A: Comply with


NEMA WD 1, NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL8310 (single), HBL83008300 (duplex), or a
comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 8310 (single),
AH8300 (duplex).
b. Leviton Manufacturing Co., Inc.; 8310 (single), 8300 (duplex).
c. Pass & Seymour/Legrand (Pass & Seymour); 5361 (single), 8300 (duplex).
d. <Insert manufacturer's name>

2. Description: Single-piece, rivetless, nickel-plated, all-brass grounding system. Nickel-


plated, brass mounting strap.

WIRING DEVICES 262726 - 5


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

F. Hospital-Grade, Construction Grade Duplex Convenience Receptacles, 125 V, 20 A. Comply


with NEMA WD 1, NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-
596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL8310 (single), 8300 (duplex), or a
comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 8310 (single),
AH8300 (duplex).
b. Leviton Manufacturing Co., Inc.; 8310 (single), 8300H (duplex).
c. Pass & Seymour/Legrand (Pass & Seymour); 8301 (single), 8300-H (duplex).
d. <Insert manufacturer's name>

2. Description: Single-piece, rivetless, nickel-plated, all-brass grounding system. Nickel-


plated, brass mounting strap.

Isolated-ground receptacles are available in a variety of configurations and ratings including locking-
blade types up to 50 A and 250 V. Revise "Isolated-Ground, Duplex Convenience Receptacles, 125 V,
20 A" Paragraph below to suit Project; indicate different types on Drawings.

G. Isolated-Ground, Duplex Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1,


NEMA WD 6 Configuration 5-20R, UL 498, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; IG535262 or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; IG 5362.


b. Leviton Manufacturing Co., Inc.; 5362IG.
c. Pass & Seymour/Legrand (Pass & Seymour); IG5362.
d. <Insert manufacturer's name>.

2. Description: Straight blade; equipment grounding contacts shall be connected only to the
green grounding screw terminal of the device and with inherent electrical isolation from
mounting strap. Isolation shall be integral to receptacle construction and not dependent
on removable parts.

Receptacles in "Tamper-Resistant Convenience Receptacles, 125 V, 20 A" Paragraph below are for
installation in pediatric-care locations.

H. Tamper-Resistant Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1,


NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Premise Wiring Device - Kellems; BR20TR HBL83008300SGA or a comparable product
by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TRBR20.


b. Leviton Manufacturing Co., Inc.; TBR20.

WIRING DEVICES 262726 - 6


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

c. Pass & Seymour/Legrand (Pass & Seymour); TR63.


d. <Insert manufacture's name>.

2. Description: Labeled shall comply with NFPA 70, "Health Care Facilities" Article,
Tamper-Resistant Convenience Receptacles, 125 V, 20 A. Comply with NEMA WD 1,
NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-596. "Pediatric
Locations" Section.

I. Weather Resistant and Tamper-Resistant Convenience Receptacles, 125 V, 20 A: Comply with


NEMA WD 1, NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Wiring Device - Kellems; BR20 WRTR or a comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TWR20.


b. Leviton Manufacturing Co., Inc.; TWR20.
c. Pass & Seymour/Legrand (Pass & Seymour); NO EQUAL.
d. <Insert manufacture's name>.

2. Description: Labeled shall comply with NFPA 70, "Health Care Facilities" Article,
Tamper-Resistant Convenience Receptacles, 125 V, 20 A. Comply with NEMA WD 1,
NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-596.

0.4 GFCI RECEPTACLES

Non-feed-through-type GFCI unit shall be selected where no protection of downstream receptacles is


required.

A. General Description:

1. Straight blade, [feed] [non-feed]-through type.


2. Comply with NEMA WD 1, NEMA WD 6, UL 498, UL 943 Class A, and FS W-C-596.
3. Include indicator light that shows when the GFCI has malfunctioned and no longer
provides proper GFCI protection.

B. Duplex GFCI Convenience Receptacles, 125 V, 20 A:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; GF20LA GFR5352L or a comparable product by
one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; VGF20.


b. Leviton Manufacturing Co., Inc.; 7899.
c. Pass & Seymour/Legrand (Pass & Seymour); 2099.
d. <Insert manufacturer's name>

C. Tamper-Resistant GFCI Convenience Receptacles, 125 V, 20 A:

WIRING DEVICES 262726 - 7


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; GFTR20 or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TRVGF20.


b. Leviton Manufacturing Co., Inc.; T7899.
c. Pass & Seymour/Legrand (Pass & Seymour); 2095TR.
d. <Insert manufacturer's name>

D. Hospital-Grade, Duplex GFCI Convenience Receptacles, 125 V, 20 A: Comply with


NEMA WD 1, NEMA WD 6 Configuration 5-20R, UL 498 Supplement sd, and FS W-C-596.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; GFR 8300H-LA HFR8300HL or a comparable
product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; VGFFH20.


b. Leviton Manufacturing Co., Inc.; 7899HG.
c. Pass & Seymour/Legrand (Pass & Seymour); 2095HG.
d. <Insert manufacturer's name>

0.5 TVSS RECEPTACLES

See Editing Instruction No. 3 in the Evaluations for information on TVSS ratings.

A. General Description: Comply with NEMA WD 1, NEMA WD 6, UL 498, UL 1449, and FS W-


C-596, with integral TVSS in line to ground, line to neutral, and neutral to ground.

1. TVSS Components: Multiple metal-oxide varistors; with a nominal clamp-level rating of


400 V and minimum single transient pulse energy dissipation of 240 J, according to
IEEE C62.41.2 and IEEE C62.45.
2. Active TVSS Indication: Visual and audible, with light visible in face of device to
indicate device is "active" or "no longer in service."

B. Duplex TVSS Convenience Receptacles:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL5362SA or a comparable product by one of
the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 5362 S.


b. Leviton Manufacturing Co., Inc.; 7380.
c. Pass & Seymour/Legrand (Pass & Seymour); 5362 SP.
d. <Insert manufacturer's name>

2. Description: Straight blade, 125 V, 20 A; NEMA WD 6 Configuration 5-20R.

C. Isolated-Ground, Duplex Convenience Receptacles:

WIRING DEVICES 262726 - 8


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; IG5362SA or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; IG5362.


b. Leviton Manufacturing Co., Inc.; 5380-IG.
c. Pass & Seymour/Legrand (Pass & Seymour); IG5362 SP.
d. <Insert manufacturer's name>

2. Description:

a. Straight blade, 125 V, 20 A; NEMA WD 6 Configuration 5-20R.


b. Equipment grounding contacts shall be connected only to the green grounding
screw terminal of the device and with inherent electrical isolation from mounting
strap. Isolation shall be integral to receptacle construction and not dependent on
removable parts.

D. Hospital-Grade, Duplex SPD Convenience Receptacles: Comply with UL 498 Supplement sd.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL8362SA or a comparable product by one of
the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 8300 S.


b. Leviton Manufacturing Co., Inc.; 8380.
c. Pass & Seymour/Legrand (Pass & Seymour); 8300 SP.
d. <Insert manufacturer's name>

2. Description: Straight blade, 125 V, 20 A; NEMA WD 6 Configuration 5-20R.


3. Electrical Components, Devices, and Accessories: Listed and labeled as defined in
NFPA 70, by a qualified testing agency, and marked for intended location and
application.
4. Comply with NFPA 70.

E. Isolated-Ground, Hospital-Grade, Duplex Convenience Receptacles:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; IG8362SA or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; IG8300 IG.
b. Leviton Manufacturing Co., Inc.; 8300 IG.
c. Pass & Seymour/Legrand (Pass & Seymour); IG8300 SP.
d. <Insert manufacturer's name>

2. Description:

a. Straight blade, 125 V, 20 A; NEMA WD 6 Configuration 5-20R.


b. Comply with UL 498 Supplement sd.

WIRING DEVICES 262726 - 9


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

c. Equipment grounding contacts shall be connected only to the green grounding


screw terminal of the device and with inherent electrical isolation from mounting
strap. Isolation shall be integral to receptacle construction and not dependent on
removable parts.

0.6 HAZARDOUS (CLASSIFIED) LOCATION RECEPTACLES

A. [Available ]Wiring Devices for Hazardous (Classified) Locations: Comply with NEMA FB 11
and UL 1010.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the


following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


b. EGS/Appleton Electric.
c. Killark.
d. <Insert manufacturer's name>

0.7 TWIST-LOCKING RECEPTACLES

A. Single Convenience Receptacles, 125 V, 20 A: Comply with NEMA WD 1, NEMA WD 6


Configuration L5-20R, and UL 498.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL2310 or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.CWL520R.


b. Leviton Manufacturing Co., Inc.; 2310.
c. Pass & Seymour/Legrand (Pass & Seymour); L520-R.
d. <Insert manufacturer's name>

B. Isolated-Ground, Single Convenience Receptacles, 125 V, 20 A:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; IG2310 or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; IGL520R.


b. Leviton Manufacturing Co., Inc.; 2310-IG.
c. Pass & Seymour/Legrand (Pass & Seymour); IGL520R.
d. <Insert manufacturer's name>

2. Description:

a. Comply with NEMA WD 1, NEMA WD 6 Configuration L5-20R, and UL 498.


b. Equipment grounding contacts shall be connected only to the green grounding
screw terminal of the device and with inherent electrical isolation from mounting

WIRING DEVICES 262726 - 10


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

strap. Isolation shall be integral to receptacle construction and not dependent on


removable parts.

0.8 PENDANT CORD-CONNECTOR DEVICES

Revise NEMA configuration in "Description" Paragraph below to suit Project. Delete "External Cable
Grip" Subparagraph if not required.

A. Description:

1. Matching, locking-type plug and receptacle body connector.


2. NEMA WD 6 Configurations L5-20P and L5-20R, heavy-duty grade, and FS W-C-596.
3. Body: Nylon, with screw-open, cable-gripping jaws and provision for attaching external
cable grip.
4. External Cable Grip: Woven wire-mesh type made of high-strength, galvanized-steel wire
strand, matched to cable diameter, and with attachment provision designed for
corresponding connector.

0.9 CORD AND PLUG SETS

Retain this article if cord and plug sets for equipment are furnished by Owner or are specified in other
Sections. Coordinate with other Sections and with Part 3.

A. Description:

1. Match voltage and current ratings and number of conductors to requirements of


equipment being connected.
2. Cord: Rubber-insulated, stranded-copper conductors, with Type SOW-A jacket; with
green-insulated grounding conductor and ampacity of at least 130 percent of the
equipment rating.
3. Plug: Nylon body and integral cable-clamping jaws. Match cord and receptacle type for
connection.

0.10 TOGGLE SWITCHES

A. Comply with NEMA WD 1, UL 20, and FS W-S-896.

B. Switches, 120/277 V, 20 A:

1. Single Pole:

a. Basis-of-Design Product: Subject to compliance with requirements, provide


Hubbell Incorporated; Wiring Device-Kellems; HBL12211221 or a comparable
product by one of the following:

1) Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; AH 1221.


2) Leviton Manufacturing Co., Inc.; 1221-2.

WIRING DEVICES 262726 - 11


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

3) Pass & Seymour/Legrand (Pass & Seymour); PSAC1.


4) <Insert manufacturer's name>

2. Double Pole:

a. Basis-of-Design Product: Subject to compliance with requirements, provide


Hubbell Incorporated; Wiring Device-Kellems; HBL12221222 or a comparable
product by one of the following:

1) Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; AH1222.


2) Leviton Manufacturing Co., Inc.; 1222-2.
3) Pass & Seymour/Legrand (Pass & Seymour); PS20AC2.
4) <Insert manufacturer's name>

3. Three Way:

a. Basis-of-Design Product: Subject to compliance with requirements, provide


Hubbell Incorporated; Wiring Device-Kellems; HBL12231223 or a comparable
product by one of the following:

1) Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; AH1223.


2) Leviton Manufacturing Co., Inc.; 1223-2.
3) Pass & Seynour/Legrand (pPass & Seymore); PS20AC3.
4) <Insert manufacturer's name>

4. Four Way:

a. Basis-of-Design Product: Subject to compliance with requirements, provide


Hubbell Incorporated; Wiring Device-Kellems; HBL12241224 or a comparable
product by one of the following:

1) Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; AH1224.


2) Leviton Manufacturing Co., Inc.; 1224-2.
3) Pass & Seymour/Legrand (Pass & Seymour); PS20AC4.
4) <Insert manufacturer's name>

C. Pilot-Light Switches, 20 A:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; 1221-PL HBL1201PL for 120 and 277 V or a
comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; AH1221-PL


(120 ad 277 V).
b. Leviton Manufacturing Co., Inc.; 1221-PLR (120V) or 1221-7PLR (277V).
c. Pass & Seymour/Legrand (Pass & Seymour); PS20AC1RPL (120V) or
PS20AC1RPL7 (277V).
d. <Insert manufacturer's name>

2. Description: Single pole, with neon-lighted handle, illuminated when switch is "off."

WIRING DEVICES 262726 - 12


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

D. Key-Operated Switches, 120/277 V, 20 A:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL12211221L or a comparable product by one
of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; AH1221L.


b. Leviton Manufacturing Co., Inc.; 1221-2L.
c. Pass & Seymour/Legrand (Pass & Seymour); PS20AC1-L.
d. <Insert manufacturer's name>

2. Description: Single pole, with factory-supplied key in lieu of switch handle.

E. Single-Pole, Double-Throw, Momentary-Contact, Center-off Switches: 120/277 V, 20 A; for use


with mechanically held lighting contactors.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL1557 or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 1995.


b. Leviton Manufacturing Co., Inc.; 1257.
c. Pass & Seymour/Legrand (Pass & Seymour); 1251.
d. <Insert manufacturer's name>

F. Key-Operated, Single-Pole, Double-Throw, Momentary-Contact, Center-off Switches:


120/277 V, 20 A; for use with mechanically held lighting contactors, with factory-supplied key
in lieu of switch handle.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; HBL1557L or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 1995L.


b. Leviton Manufacturing Co., Inc.; 1257L.
c. Pass & Seymour/Legrand (Pass & Seymour); 1251L.
d. <Insert manufacturer's name>

0.11 DECORATOR-STYLE DEVICES

Convenience receptacles in this article are commercial grade, 15 A, duplex.

A. Convenience Receptacles: Square face, 125 V, 15 20 A; comply with NEMA WD 1,


NEMA WD 6 Configuration 5-20R 5-15R, and UL 498.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; DR 20 DR15 or a comparable product by one of
the following:

WIRING DEVICES 262726 - 13


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 6352.


b. Leviton Manufacturing Co., Inc.; 16352.
c. Pass & Seymour/Legrand (Pass & Seymour); 26352.
d. <Insert manufacturer's name>

B. Tamper-Resistant Convenience Receptacles: Square face, 125 V, 15 20 A; comply with


NEMA WD 1, NEMA WD 6 Configuration 5-20R 5-15R, and UL 498.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; DR20TR DR15TR or a comparable product by
one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TR6352.


b. Leviton Manufacturing Co., Inc.; TDR20.
c. Pass & Seymour/Legrand (Pass & Seymour); TR26362.
d. <Insert manufacturer's name>

2. Description: Labeled to comply with NFPA 70, "Receptacles, Cord Connectors, and
Attachment Plugs (Caps)" Article, "Tamper-Resistant Receptacles in Dwelling Units"
Section.

C. Tamper-Resistant and Weather-Resistant Convenience Receptacles: Square face, 125 V, 15 20


A; comply with NEMA WD 1, NEMA WD 6 Configuration 5 20R 5-15R, and UL 498.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; DR20WRTR DR15TR or a comparable product
by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


b. Leviton Manufacturing Co., Inc.
c. Pass & Seymour/Legrand (Pass & Seymour).
d. <Insert manufacturer's name>

2. Description: Labeled to comply with NFPA 70, "Receptacles, Cord Connectors, and
Attachment Plugs (Caps)" Article, "Tamper-Resistant Receptacles in Dwelling Units"
Section, when installed in wet and damp locations.

D. GFCI, [Feed] [Non-Feed]-Through Type, Convenience Receptacles: Square face, 125 V, 15 20


A; comply with NEMA WD 1, NEMA WD 6 Configuration 5-15R, UL 498, and UL 943
Class A.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; GF20 GF15LA or a comparable product by one of
the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; VGF20.


b. Leviton Manufacturing Co., Inc.; 7899.
c. Pass & Seymour/Legrand (Pass & Seymour); 2095.
d. <Insert manufacturer's name>

WIRING DEVICES 262726 - 14


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

E. GFCI, Tamper-Resistant and Weather-Resistant Convenience Receptacles: Square face, 125 V,


15 20 A; comply with NEMA WD 1, NEMA WD 6 Configuration 5-15R, UL 498, and UL 943
Class A.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; GFTR20 GFTR15 or a comparable product by one
of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TWRVGF20.


b. Leviton Manufacturing Co., Inc.; W7899-TR.
c. Pass & Seymour/Legrand (Pass & Seymour); 2095TRWR.
d. <Insert manufacturer's name>

2. Description: Labeled to comply with NFPA 70, "Receptacles, Cord Connectors, and
Attachment Plugs (Caps)" Article, "Tamper-Resistant Receptacles in Dwelling Units"
Section.

F. Toggle Switches, Square Face, 120/277 V, 15 20 A: Comply with NEMA WD 1, UL 20, and
FS W-S-896.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; DS 120 DS115 (single pole), DS 220 (two pole),
DS 320 DS315 (three way) DS 420 (4 way), or a comparable product by one of the
following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 7621 (single
pole), 7622 (two pole), 7623 (three way), 7624 (four way).
b. Leviton Manufacturing Co., Inc.; 5621-2 (single pole), 5622-2 (two pole), 5623-2
(three way), 5624-2 (four way).
c. Pass & Seymour/Legrand (Pass & Seymour); 2621 (single pole), 2622 (two pole),
2623 (three way), 2624 (four way).
d. <Insert manufacturer's name>

G. Lighted Toggle Switches, Square Face, 120 V, 15 20 A: Comply with NEMA WD 1 and UL 20.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; DS120IL (single pole), DS 3201L DS320 (three
way) or a comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; 7631 (single
pole), 7633 (three way).
b. Leviton Manufacturing Co., Inc.; 5631-2 (single pole), 5633-2 (three way).
c. Pass & Seymour/Legrand (Pass & Seymour); 2625 (single pole), 2626 (three way).
d. <Insert manufacturer's name>

2. Description: With neon-lighted handle, illuminated when switch is "off."

WIRING DEVICES 262726 - 15


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

0.12 RESIDENTIAL DEVICES

Receptacles in this article are usually considered residential grade, for installation in dwelling units.

A. Residential-Grade, Tamper-Resistant Convenience Receptacles, 125 V, 15 A: Comply with


NEMA WD 1, NEMA WD 6 Configuration 5-15R 5-20R, and UL 498.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; RR15STR RR155TR or a comparable product by
one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TR270.


b. Leviton Manufacturing Co., Inc; T5320. .
c. Pass & Seymour/Legrand (Pass & Seymour); 3232TR.
d. <Insert manufacturer's name>

2. Description: Labeled to comply with NFPA 70, "Receptacles, Cord Connectors, and
Attachment Plugs (Caps)" Article, "Tamper-Resistant Receptacles in Dwelling Units"
Section.

B. Weather-Resistant and Tamper-Resistant Convenience Receptacles, 125 V, 15 A: Comply with


NEMA WD 1, NEMA WD 6 Configuration 5-15R 5-20R, and UL 498.

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; RR15SWRTR RR155WRTR or a comparable
product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.; TWR 270.
b. Leviton Manufacturing Co., Inc.; W5329TO.
c. Pass & Seymour/Legrand (Pass & Seymour); 3232TRWR.
d. <Insert manufacturer's name>

2. Description: Labeled to comply with NFPA 70, "Receptacles, Cord Connectors, and
Attachment Plugs (Caps)" Article, "Tamper-Resistant Receptacles in Dwelling Units"
Section, when installed in wet and damp locations.

C. Fan Speed Controls:

1. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated, Wiring Device-Kellems; RDVFSQ or a comparable product by one of the
following:

a. Leviton Manufacturing Co., Inc.

b. Pass & Seymour/Legrand (Pass & Seymour).

c. <Insert manufacturer's name>.

2. Modular, 120-V, full-wave, solid-state units with integral, quiet on-off switches and
audible frequency and EMI/RFI filters.

WIRING DEVICES 262726 - 16


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

3. Comply with UL 1917.

The 5-A rating in first subparagraph below allows more than one fan to be controlled by the same device.
4. Continuously adjustable [slider] [toggle switch] [rotary knob], [5 A] [1.5 A].
5. Three-speed adjustable [slider] [rotary knob], 1.5 A.

Coordinate "Telephone Outlet" Paragraph below with Section 271500 "Communications Horizontal
Cabling."

D. Telephone Outlet:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the


following:

2. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Wiring Device Kellems: NSJ5E Jack, NS614 Frame with NP 26 Wall Plate, or
comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


b. Leviton Manufacturing Co., Inc.
c. <Insert manufacturer's name>

In determining cable category in "Description" Subparagraph below, Category 5e and Category 6 are
covered by the referenced TIA/EIA standard. Use of Category 3 cabling may be permitted by authorities
having jurisdiction; however, this category is covered by an obsolete TIA/EIA standard.

3. Description: Single RJ-45 jack for terminating 100-ohm, balanced, four-pair UTP;
TIA/EIA-568-B.1; complying with [Category 5e] <Insert category>. Comply with
UL 1863.

E. Combination TV and Telephone Outlet:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the


following:

2. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Wiring Device Kellems; NSJ5E Jack, SFGRF Connector, NS614 Frame with NP 26 Wall
Plate or comparable product by one of the following:

a. Cooper Wiring Devices, Inc.; Division of Cooper Industries, Inc.


b. Leviton Manufacturing Co., Inc.
c. <Insert manufacturer's name>

3. Description: Single RJ-45 jack for 100-ohm, balanced, four-pair UTP; TIA/EIA-568-B.1;
complying with [Category 5e] <Insert category>. Comply with UL 1863.

WIRING DEVICES 262726 - 17


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

0.13 WALL-BOX DIMMERS

A. Dimmer Switches: Modular, full-wave, solid-state units with integral, quiet on-off switches,
with audible frequency and EMI/RFI suppression filters.

Four-way switching may be added to "Control" Paragraph below after verifying availability with
manufacturers.

B. Control: Continuously adjustable [slider] [toggle switch] [rotary knob]; with single-pole or
three-way switching. Comply with UL 1472.

C. Incandescent Lamp Dimmers: 120 V; control shall follow square-law dimming curve. On-off
switch positions shall bypass dimmer module.

Retain one of two subparagraphs below. UL 1472 covers ratings from 300 to 2000 W in increments of
50 W.

1. 600 W; dimmers shall require no derating when ganged with other devices.[ Illuminated
when "off."]
2. <Insert wattage ratings and descriptions>.

Retain "Fluorescent Lamp Dimmer Switches" Paragraph below with compatible dimming-type ballasts.
Coordinate with Section 265116 "Fluorescent Interior Lighting." Use uniform ballast and lamp types to
obtain consistent dimming characteristics.

D. Fluorescent Lamp Dimmer Switches: Modular; compatible with dimmer ballasts; trim
potentiometer to adjust low-end dimming; dimmer-ballast combination capable of consistent
dimming with low end not greater than 20 percent of full brightness.

0.14 WALL PLATES

A. Single and combination types shall match corresponding wiring devices.

1. Plate-Securing Screws: Metal with head color to match plate finish.

Third option in "Material for Finished Spaces" Subparagraph below is also available in Type 430 but is
susceptible to rust and corrosion even in finished spaces.
2. Material for Finished Spaces: [Steel with white baked enamel, suitable for field
painting] [Smooth, high-impact thermoplastic] [0.035-inch- (1-mm-) thick, satin-
finished, Type 302 stainless steel] [0.04-inch- (1-mm-) thick, brushed brass with
factory polymer finish] [0.05-inch- (1.2-mm-) thick, anodized aluminum] [0.04-inch-
(1-mm-) thick steel with chrome-plated finish].
3. Material for Unfinished Spaces: [Galvanized steel] [Smooth, high-impact
thermoplastic].
4. Material for Damp Locations: [Thermoplastic] [Cast aluminum] with spring-loaded lift
cover, and listed and labeled for use in wet and damp locations.

B. Wet-Location, Weatherproof Cover Plates: NEMA 250, complying with Type 3R, weather-
resistant[, die-cast aluminum] [thermoplastic] with lockable cover.

WIRING DEVICES 262726 - 18


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

0.15 FLOOR SERVICE FITTINGS

Service fittings in "Type" Paragraph below are available for voice and data communication cabling as
well as for power.

A. Type: Modular, [flush-type] [flap-type] [above-floor], dual-service units suitable for wiring
method used.

B. Compartments: Barrier separates power from voice and data communication cabling.

C. Service Plate: [Rectangular] [Round], [die-cast aluminum] [solid brass] with satin finish.

D. Power Receptacle: NEMA WD 6 Configuration 5-20R, gray finish, unless otherwise indicated.

E. Voice and Data Communication Outlet: [Blank cover with bushed cable opening] [Two
modular, keyed, color-coded, RJ-45 jacks for UTP cable complying with requirements in
Section 271500 "Communications Horizontal Cabling."]

0.16 POKE-THROUGH ASSEMBLIES

A. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; products named below <product name or
designation> or a comparable product by one of the following:

1. Pass & Seymour/Legrand (Pass & Seymour).


2. Square D; by Schneider Electric.
3. Thomas & Betts Corporation, A Member of the ABB Group.

4. FSR.
5. Wiremold / Legrand.
6. <Insert manufacturer's name>

B. Activation Type:

1. Recessed Activation.

a. Basis-of-Design Product: Hubbell System One - Recessed Activation.

Retain one of more of the following three subparagraphs per Project requirements.

1) S1R4PT: 4 inch (100 mm) core with two 1/2 inch (13 mm) and one 3/4 inch
(19 mm) feed conduits.

a) Outlets: [S1R4PTQUAD: Power only, with four power outlets]


[S1R4PTS2X2: Two power and two data outlets].

2) S1R6PT: 6 inch (150 mm) with one 3/4 inch (19 mm) and one 2 inch (50
mm) feed conduits.

a) Subplate Configuration for S1R6: [50/50] [60/40].

WIRING DEVICES 262726 - 19


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

3) S1R8PT: 8 inch (200 mm) with bottom feed box.

a) Bottom Feed Configuration Option: [S1R8JNC1; one 1 inch (25


mm), one 1-1/4 inch (32 mm)] [S1R8JNC2; two 1 inch (25 mm)]
[S1R8JNC3; one 2 inch (50 mm)] [S1R8JNC4; three 1 inch (25
mm)] [S1R8JNC5; one 1-1/2 inch (38 mm) and one 1-1/4 inch (32
mm)] [S1R8JNC6; two 1-1/4 inch (32 mm)].

4) Provided with appropriate subplate for device mounting and cover, finish
chosen by Architect.

a) Cover Flange: 0.12 inch (3 mm) thick, ADA compliant.

Furniture feed cover is only available for 6 inch (150 mm) cover.
b) S1R6FFCVR Furniture Feed Cover: with one 3/4 inch (19 mm)
connection for power and one 2 inch (50 mm) connection for low
voltage.
c) Finish: [Brushed aluminum] [Black powder coat] [Gray powder
coat] [Brushed brass plated] [Bronze plated] [Satin nickel plated].

2. Surface Activation.

a. Basis-of-Design Product: Hubbell System One - Surface Activation:

Retain one of more of the following three subparagraphs per Project requirements.

1) S1PTFIT with two 1 inch (25 mm) conduit feeds.


2) S1PTAVFIT with one 1-1/2 inch (38 mm) and one 3/4 inch (19 mm) conduit
feed.
3) S1PT4X4FIT with two 3/4 inch (19 mm) conduits for low voltage, one 3/4
inch (19 mm) for power.
4) Provided with appropriate subplate for device mounting and cover, finish
chosen by Architect.

a) Cover Flange: ADA compliant [carpet cover] [tile over].


b) Furniture Feed Cover: [S1PFFT for tile applications] [S1PFF for
carpet applications] with one 3/4 inch (19 mm) connection for
power and one 1-1/2 inch (38 mm) connection for low voltage.
c) Finish: [Aluminum powder coat] [Black powder coat] [Gray
powder coat] [Brass powder coat].

3. Pedestal Activation.

a. Basis-of-Design Product: [PT7XC] [PT27A] [2 inch (51 mm) poke through


insert] [3 inch (76 mm) poke through insert] with a [FR 80 (single gang)] [FR
280 (two gang)] [FR 480 (four gang)] [FR 680 (6 gang)] pedestal.

C. Description:

WIRING DEVICES 262726 - 20


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

1. Factory-fabricated and -wired assembly of below-floor junction box with multichanneled,


through-floor raceway/firestop unit and detachable matching floor service-outlet
assembly.
2. Comply with UL 514 scrub water exclusion requirements.

Coordinate "Service-Outlet Assembly" Subparagraph below with Section 271500 "Communications


Horizontal Cabling."

Coordinate options in "Service Outlet Assembly" subparagraph below with poke through pedestals
specified. 4 inch (100 mm) = 2 gangs. 6 inch (150 mm) = 3 gangs. 8 inch (200 mm) = 5 gangs.
3. Service-Outlet Assembly: [Pedestal type with services indicated] [Flush type with two
simplex receptacles and space for two RJ-45 jacks] [Flush type with four simplex
receptacles and space for four RJ-45 jacks] [Recessed type with 2 gangs populated
with services indicated] [Recessed type with three gangs populated with services as
indicated] [Recessed type with 5 gangs populated with services indicated] complying
with requirements in Section 271500 "Communications Horizontal Cabling."

Larger-diameter assembly in "Size" Subparagraph below is available for four simplex receptacles and
four voice and data communication outlets in a single, flush-type service outlet.
4. Size: Selected to fit nominal [2-inch (50-mm)] [3-inch (75-mm)] [4-inch (100-mm)] [6-
inch (150-mm)] [8-inch (200-mm)]cored holes in floor and matched to floor thickness.

Revise "Fire Rating" Subparagraph below to coordinate with fire ratings.


5. Fire Rating: Unit is listed and labeled for fire rating of floor-ceiling assembly.
6. Closure Plug: Arranged to close unused [2-inch (50-mm)] [3-inch (75-mm)] [4-inch
(100-mm)] [6-inch (150-mm)] [8-inch (200-mm)] cored openings and reestablish fire
rating of floor.

Coordinate "Wiring Raceways and Compartments" Subparagraph below with Section 271500
"Communications Horizontal Cabling."
7. Wiring Raceways and Compartments: For a minimum of four No. 12 AWG conductors
and a minimum of [two] [four], four-pair cables that comply with requirements in
Section 271500 "Communications Horizontal Cabling."

0.17 PREFABRICATED MULTIOUTLET ASSEMBLIES

A. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell


Incorporated; Wiring Device-Kellems; [Plug Trak HBL20, HBL24 series steel] [HBLALU20,
HBLALU24 Alumium] [Plug Trak PT 20 series PVC] <product name or designation> or a
comparable product by one of the following:

1. Wiremold / Legrand.
2. <Insert manufacturer's name>

If not indicated on Drawings, add mounting heights, raceway sizes, and types and spacing of receptacle
devices to "Description" Paragraph below. Add descriptions of special features in assemblies such as
fused receptacles, special-purpose switches, and channels for communication wiring.

B. Description:

WIRING DEVICES 262726 - 21


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

1. Two-piece surface metal painted steel, brushed aluminum or PVC raceway, with factory-
wired multioutlet harness.
2. Components shall be products from single manufacturer designed for use as a complete,
matching assembly of raceways and receptacles.

Some finish options may be available from manufacturers. Retain "Raceway Material" or "Multioutlet
Harness" paragraphs below and revise to suit Project. Select option in "Raceway Material" paragraph
below to coordinate with model specified in "Basis-of-Desig Product" paragraph above.

C. Raceway Material: [Painted Metal, with manufacturer's standard finish] [Brushed


anodized aluminum] [PVC].

D. Multioutlet Harness:

1. Receptacles: 20 A15-A, 125-V, NEMA WD 6 Configuration 5-20R 5-15R receptacles


complying with NEMA WD 1, UL 498, and FS W-C-596.
2. Receptacle Spacing: [6 inches (150 mm)] [9 inches (230 mm)] [12 inches (300 mm)]
[18 inches (460 mm)].
3. Wiring: No. 12 AWG solid, Type THHN copper, [single circuit] [two circuit,
connecting alternating receptacles].

0.18 SERVICE POLES

A. Basis-of-Design Product: Subject to compliance with requirements, provide Hubbell Wiring


Device Kellems; HBL PP series service poles or comparable product by one of the following:

1. MonoSystems.
2. Wiremold.
3. <Insert manufacturer's name>.

B. Description:

1. Factory-assembled and -wired units to extend power and voice and data communication
from distribution wiring concealed in ceiling to devices or outlets in pole near floor.
2. Poles: Nominal 2.5-inch- (65-mm-) square cross section, with height adequate to extend
from floor to at least 6 inches (150 mm) above ceiling, and with separate channels for
power wiring and voice and data communication cabling.
3. Mounting: Ceiling trim flange with concealed bracing arranged for positive connection to
ceiling supports; with pole foot and carpet pad attachment.

Specify final finish in "Finishes" Subparagraph below if known.


4. Finishes: [Manufacturer's standard painted finish and trim combination] [Satin-
anodized aluminum].
5. Material and Finish: [Painted steel] [Extruded anodized aluminum].
6. Wiring: Sized for minimum of five No. 12 AWG power and ground conductors and a
minimum of four, four-pair, Category 3 or Category 5 voice and data communication
cables.
7. Power Receptacles: Two duplex, 20-A, straight-blade receptacles complying with
requirements in this Section.

WIRING DEVICES 262726 - 22


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

8. Voice and Data Communication Outlets: [Blank insert with bushed cable opening]
[Two RJ-45 jacks] [Four RJ-45 jacks] complying with requirements in Section 271500
"Communications Horizontal Cabling."

0.19 FINISHES

See Editing Instruction No. 2 in the Evaluations for a discussion of wiring-device colors. Coordinate with
Drawings.

A. Device Color:

Retain "Wiring Devices Connected to Normal Power System" Subparagraph below unless colors are
indicated or scheduled on Drawings. If retaining subparagraph, revise title if a separate emergency power
system serving wiring devices is not provided.

1. Wiring Devices Connected to Normal Power System: [Almond] [Black] [Brown]


[Gray] [Ivory] [White] [As selected by Architect] <Insert color> unless otherwise
indicated or required by NFPA 70 or device listing.

Retain "Wiring Devices Connected to Emergency Power System" Subparagraph below if a separate
emergency power system serving wiring devices is required.
2. Wiring Devices Connected to Emergency Power System: [Red] <Insert color>.
3. TVSS Devices: Blue.
4. Isolated-Ground Receptacles: [Orange] [As specified above, with orange triangle on
face].

B. Wall Plate Color: For plastic covers, match device color.

PART 3 - EXECUTION

0.1 INSTALLATION

NECA 1 referenced in first paragraph below includes device mounting-height requirements. See
"Mounting Heights and Locations" Article in the Evaluations for device mounting heights in that
standard.

A. Comply with NECA 1, including mounting heights listed in that standard, unless otherwise
indicated.

See Editing Instruction No. 4 in the Evaluations for timing and sequencing of construction to assist in
avoiding contamination of devices during construction.

B. Coordination with Other Trades:

1. Protect installed devices and their boxes. Do not place wall finish materials over device
boxes and do not cut holes for boxes with routers that are guided by riding against outside
of boxes.

WIRING DEVICES 262726 - 23


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

2. Keep outlet boxes free of plaster, drywall joint compound, mortar, cement, concrete, dust,
paint, and other material that may contaminate the raceway system, conductors, and
cables.
3. Install device boxes in brick or block walls so that the cover plate does not cross a joint
unless the joint is troweled flush with the face of the wall.
4. Install wiring devices after all wall preparation, including painting, is complete.

C. Conductors:

1. Do not strip insulation from conductors until right before they are spliced or terminated
on devices.
2. Strip insulation evenly around the conductor using tools designed for the purpose. Avoid
scoring or nicking of solid wire or cutting strands from stranded wire.
3. The length of free conductors at outlets for devices shall meet provisions of NFPA 70,
Article 300, without pigtails.
4. Existing Conductors:

a. Cut back and pigtail, or replace all damaged conductors.


b. Straighten conductors that remain and remove corrosion and foreign matter.
c. Pigtailing existing conductors is permitted, provided the outlet box is large enough.

D. Device Installation:

1. Replace devices that have been in temporary use during construction and that were
installed before building finishing operations were complete.
2. Keep each wiring device in its package or otherwise protected until it is time to connect
conductors.
3. Do not remove surface protection, such as plastic film and smudge covers, until the last
possible moment.
4. Connect devices to branch circuits using pigtails that are not less than 6 inches (152 mm)
in length.
5. When there is a choice, use side wiring with binding-head screw terminals. Wrap solid
conductor tightly clockwise, two-thirds to three-fourths of the way around terminal
screw.
6. Use a torque screwdriver when a torque is recommended or required by manufacturer.
7. When conductors larger than No. 12 AWG are installed on 15- or 20-A circuits, splice
No. 12 AWG pigtails for device connections.
8. Tighten unused terminal screws on the device.
9. When mounting into metal boxes, remove the fiber or plastic washers used to hold
device-mounting screws in yokes, allowing metal-to-metal contact.

E. Receptacle Orientation:

Retain first subparagraph below if the position of the ground pin is important for consistency. Trade and
professional literature is inconsistent in recommending benefits of either orientation.

1. Install ground pin of vertically mounted receptacles [up] [down], and on horizontally
mounted receptacles to the [right] [left].

Recommendation in subparagraph below is made in IEEE 602.

WIRING DEVICES 262726 - 24


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

2. Install hospital-grade receptacles in patient-care areas with the ground pin or neutral
blade at the top.

F. Device Plates: Do not use oversized or extra-deep plates. Repair wall finishes and remount
outlet boxes when standard device plates do not fit flush or do not cover rough wall opening.

G. Dimmers:

1. Install dimmers within terms of their listing.


2. Verify that dimmers used for fan speed control are listed for that application.
3. Install unshared neutral conductors on line and load side of dimmers according to
manufacturers' device listing conditions in the written instructions.

Coordinate both paragraphs below with Drawings.

H. Arrangement of Devices: Unless otherwise indicated, mount flush, with long dimension vertical
and with grounding terminal of receptacles on top. Group adjacent switches under single,
multigang wall plates.

I. Adjust locations of floor service outlets and service poles to suit arrangement of partitions and
furnishings.

0.2 GFCI RECEPTACLES

A. Install non-feed-through-type GFCI receptacles where protection of downstream receptacles is


not required.

0.3 IDENTIFICATION

A. Comply with Section 260553 "Identification for Electrical Systems."

B. Identify each receptacle with panelboard identification and circuit number. Use hot, stamped, or
engraved machine printing with [black] [white] [red]-filled lettering on face of plate, and
durable wire markers or tags inside outlet boxes.

0.4 FIELD QUALITY CONTROL

Retain "Perform the following tests and inspections" Paragraph below to require Contractor to perform
tests and inspections.

A. Perform the following tests and inspections[ with the assistance of a factory-authorized
service representative]:

1. In healthcare facilities, prepare reports that comply with recommendations in NFPA 99.
2. Test Instruments: Use instruments that comply with UL 1436.
3. Test Instrument for Convenience Receptacles: Digital wiring analyzer with digital
readout or illuminated digital-display indicators of measurement.

WIRING DEVICES 262726 - 25


Copyright 2013 AIA MasterSpec Premium 12/13
PRODUCT MASTERSPEC LICENSED BY ARCOM TO HUBBELL INCORPORATED WIRING
DEVICES - KELLEMS.

B. Tests for Convenience Receptacles:

1. Line Voltage: Acceptable range is 105 to 132 V.


2. Percent Voltage Drop under 15-A Load: A value of 6 percent or higher is unacceptable.
3. Ground Impedance: Values of up to 2 ohms are acceptable.
4. GFCI Trip: Test for tripping values specified in UL 1436 and UL 943.
5. Using the test plug, verify that the device and its outlet box are securely mounted.
6. Tests shall be diagnostic, indicating damaged conductors, high resistance at the circuit
breaker, poor connections, inadequate fault current path, defective devices, or similar
problems. Correct circuit conditions, remove malfunctioning units and replace with new
ones, and retest as specified above.

C. Test straight-blade [convenience outlets in patient-care areas] [hospital-grade convenience


outlets] for the retention force of the grounding blade according to NFPA 99. Retention force
shall be not less than 4 oz. (115 g).

See Section 014000 "Quality Requirements" for retesting and reinspecting requirements and
Section 017300 "Execution" for requirements for correcting the Work.

D. Wiring device will be considered defective if it does not pass tests and inspections.

E. Prepare test and inspection reports.

END OF SECTION 262726