100% GENERATOR STATOR
GROUND FAULT PROTECTION
WHAT WORKS, WHAT DOESNT AND WHY
Chuck Mozina
Consultant
Beckwith Electric
Stator Ground Fault Protection
BACKGROUND:
BACKGROUND:
PAPER ADDRESSES:
CONVENTIONAL (59G)
STATOR GROUND FAULT
PROTECTION
Stator Ground Fault Protection
1.0
Voltage at Neutral
pu
(60 Hz)
90-95%
0.5
pu
0
59G 0% 50% 100%
N Fault Position T
Stator Ground Fault Protection
CH-L
F2
59G
3RN C0 VHO
VR
Where:
VHO = High side zero sequence voltage for a transmission
system ground fault.
CH-L= Generator step-up transformer high-to-low winding
capacitance
C 0 = Generator system zero sequence capacitance per
phase
3RN = Equivalent primary resistance in generator neutral
Stator Ground Fault Protection
VT Connection to Avoid 59G Coordination
with VT Fuses
59G
Stator Ground Fault Protection
3 rd
HARMONIC
STATOR GROUND
FAULT DETECTION
SCHEMES
Stator Ground Fault Protection
3rd HARMONIC
NEUTRAL
UNDERVOLTAGE
SCHEME
Stator Ground Fault Protection
59G
59G
Stator Ground Fault Protection
Overlapping of 59G and 27TN to Provide 100%
Stator Ground Fault Coverage
59G
59G
Stator Ground Fault Protection
Advantages / Disadvantages:
3rd HARMONIC
RATIO SCHEME
Stator Ground Fault Protection
3V0
59D T h ir d H a r m o n ic
R a t io R e la y
C o n v e n t io n G r o u n d
O v e r v o lt a g e R e la y
59G
Stator Ground Fault Protection
Advantages / Disadvantages:
LIMITATIONS
OF
3rd HARMONIC
SCHEMES
Stator Ground Fault Protection
BUS
G1 GSU
59G
27TN
G2
59G
27TN
Stator Ground Fault Protection
GSU
W in d in g 2 W in d in g 1
W in d in g n o t c o v e re d b y
27TN
27TN
Stator Ground Fault Protection
SUBHARMONIC
VOLTAGE
INJECTION
SCHEME
Stator Ground Fault Protection
N a tu r a l C a p a c ita n c e
* V
C o u p lin g V o lt a g e R e la y
F ilt e r In je c t o r M e a s u re m e n ts
59G
N o te s :
S u b h a r m o n ic in je c tio n ty p ic a lly a t 1 5 - 2 0 H z
C o u p lin g filte r lo w p a s s o r n o tc h tu n e d fo r s u b h a r m o n ic fr e q u e n c y
M e a s u r e m e n t in p u ts tu n e d to r e s p o n d to s u b h a r m o n ic fr e q u e n c y
Stator Ground Fault Protection
Coupling Filter and Voltage Injector
Stator Ground Fault Protection
Advantages / Disadvantages:
CONCLUSIONS
Its Important to Upgrade to 100% Stator Ground Fault
Protection.
If 3rd Harmonic Schemes are to Being Considered-- It is
Important to First Determine 3rd Harmonic Signature
of the Generator.
Recognize that 3rd Harmonic Schemes Have
Limitations.
Subharmonic Injection Provides an Viable Alternative to
3rd Harmonic Schemes.
Injection Scheme Cost have Reduced with Digital
Technology Good Choice for Important Generators.
Injection Scheme can Detect Stator Grounds Over the
Entire Stator Winding and in an Off-line Generator.
Stator Ground Fault Protection
15 YEARS OF EXPERIENCE
WITH
100% GENERATOR STATOR
GROUND FAULT PROTECTION
WHAT WORKS, WHAT DOESNT AND WHY
THE END
Questions ?