(ZSCC, ZSCC/4)

ZSCC The Zeta addressable sounder circuit


controllers (ZSCC & ZSCC/4) are used to
connect any conventional alarm warning
devices (for instance sounders, flashers or
bells) to any Zeta addressable fire alarm
system. It needs external power to be supplied
from a suitable 24V power supply.
The unit has a built in loop short circuit isolator to help
ZSCC/4 keep the unit operational in the event of a problem on
the loop wiring.

It has 3 indication LEDs on the front of the unit, one for


alarm, one for local fault and one for addressable loop
fault (isolator active).

Model ZSCC ZSCC/4


Part No. 48-110 48-111
Number of Interface Unit
1 4
Sounder Circuits
Operating Voltage 17 33V DC
Quiescent Current 900uA (6.8 mA from ext PSU) Serial No

10.6mA (10mA + 42.4mA (10mA per ZIU Pt No: 48-100


ZIOU Pt No: 48-105
Alarm Current sounder load from circuit + sounder ZSCC Pt No: 48-110 Snd Supply

PSU) load from PSU)


Fault Current 2.8mA (10mA from PSU) Hundreds Tens Units
901 901 901
78

78

78
23

23

23

Isolating Current 7.3mA (6.8 mA from ext PSU)


456 456 456

Address

Sounder End of
47K
Line
Line Monitoring
Open & Short Circuit
Conditions Quad Sounder Unit
Sounder Output 1 Amp (If Ext PSU Allows) Snd 1 O/P Snd 2 O/P Snd 3 O/P Snd 4 O/P

Operating
0C to 50C
Temperature Line
Isolated
Loop In/Out

Snd Snd Snd Snd Snd Snd Snd Snd


Active Fault Active Fault Active Fault Active Fault

Maximum Humidity 95% RH Non Condensing


IP Rating IP 43
Size 127 x 88 x 59mm 195 x 143 x 79mm Serial No

Weight 220g 400g

Hundreds Tens Units Snd Supply


901 901 901
78

78

78
23

23

23

456 456 456

Address

Issue #1 Issue Date 05/07/2010 Revision #2