Você está na página 1de 28

Chapter

Seismic Design of Concrete


10
Shielding Block Assemblies

FOREWORD: The Facility Managers Perspective Donald G. Eagling

Massive concrete shielding blocks pose a very The simplest and most economical way of
special problem in earthquake safety. In 1975, avoiding this hazard is to locate shielding b16cks
full-sized shielding blocks were subjected to far enough away from building columns and
realistic earthquake motions for the first time occupied areas so that contact is not possible
utilizing the University of Californias 90-ton during an earthquake. If a building column must
shaking table at the Earthquake Engineering penetrate the shielding stack, the problem is
Research Center in Richmond, California. Until much more difficult. One possibility is to fill the
then, only theoretical studies were available for space between the shielding and the column with
reference, and these primarily concerned rocking nonrigid, frangible shielding materials that
action and overturning. In instances in which minimize the impact on the column in the event
earthquakes were actually taken into of differential motion. This expedient is not
consideration, design was usually predicated on recommended as a permanent solution, but it
the aspect ratio (height-to-width) of blocks. The could be used to temporarily reduce the risk in an
idea was to prevent toppling. Little consideration existing installation.
was given to sliding; thus, the proximity of heavy
shielding blocks to building columns, A permanent solution involves anchoring the
experimental equipment, or habitable shelters shielding blocks against movement and
was usually ignored. Experiments on the shaking designing the stack of blocks to incorporate a
table clearly demonstrated the sliding hazard. predictable lateral-force-resisting system. The
After static friction between the block and the important thing to recognize in this approach is
concrete surface of the shaking table was that almost all of the inertial energy induced by
overcome, the table moved almost freely beneath earthquake shaking must be resisted directly by
the block. Imagine what would happen if a huge the lateral-force-resisting-system. Buildings
stack of massive concrete shielding blocks generally have enumerable structural members
impacted a vital building column, located in close and joints that, along with nonstructural
proximity, with an acceleration of 0.7g. Nominal architectural appendages, flex and deform both
anchor bolts in the column base plate would elastically and inelastically to absorb large
provide little shear resistance against this amounts of dynamic energy and thus reduce the
enormous force. effective forces on the lateral-force-resisting
system. Unlike a building, little energy is
absorbed in deforming very rigid blocks, and

101
little molecular damping occurs within individual apparata are designed and fabricated with no
blocks. The redundancy available in most consideration for forces induced by earthquakes.
building framing systems is not available in the When it is necessary to protect the internals, it is
individual block. Consequently, for shielding usually feasible to design the equipment base to
blocks, the lateral-force-restraining system should dissipate some or most of the seismic motion at
be designed for a static lateral force coefficient the base so that the sensitive apparata are not
close to the effective peak ground acceleration. If subjected to the full ground motion, This can be
the stack is quite high with respect to its depth, accomplished by providing seismic isolation or
consideration should be given to amplification of shock absorbers between the shielding and the
the induced base motion with height. equipment so that the apparata experience less
acceleration than the shielding. It is essential,
It is important that designers analyze however, that there is adequate horizontal
shielding restraints as a complete lateral-force- clearance between the isolated equipment and the
resisting system, including the interaction among shielding to handle the differential movement
the ground, the foundation, and the shielding. A without pounding.
set of calculations covering the complete system,
including a narrative description of how the The chapter that follows deals primarily with
system is expected to function, should be made. the restraint of shielding block assemblies. The
The best way to ensure this happens is to require methods described have been utilized in the field
a design review by independent experienced without the benefit of a full-scale test by the
earthquake engineers. There is small likelihood master inspectorthe real earthquake. The 1989
that the persons responsible for designing the Loma Prieta, California earthquake produced
experimental apparatus per se can give realistic only 0.12g at the Lawrence Berkeley Laboratory
consideration to seismic restraints; therefore, it is and .26g at the Stanford Linear Accelerator
vital that responsibility for the analysis and Center in Palo Alto, California. However,
design is delegated to a structural engineer. emphasis is placed on design rather than analysis
with the objective that possible failure be limited
Auxiliary support equipment, important to inelastic behavior of the lateral-force-resisting
experimental apparata, and sensitive research system rather than collapse, even if the intensity
instrumentation may be attached to shielding of the earthquake greatly exceeds the design
assemblies. Often, state-of-the-art experimental motion.
.

10-2
Chapter

10a
Planning and Design
Methodologies for Blocks
Donald G. Eagling
John J. Earle
Daniel Shapiro

Introduction This chapter provides recommendations for


the design of shielding blocks for earthquake
When operating particle accelerators, it is resistance based on the referenced research and
necessary to shield personnel as well as the design applications at the Lawrence Berkeley
surrounding environment from ionizing Laboratory. These recommendations are
radiation. For this purpose, concrete blocks are discussed under the following headings:
often used as modular shielding elements.
Concrete blocks are massive and may slide, rock, Earthquake effects on shielding blocks
or topple in earthquakes. They must be
restrained to provide a safe seismic environment Basic configurations of shielding block
for people and prevent damage to adjacent assemblies
structures and experimental equipment. An
official code for designing concrete shielding Building code considerations
block assemblies does not exist at present.
Seismic design criteria for shielding blocks
Little is known from actual earthquakes
about how massive items similar to shielding Applications to individual blocks
blocks behave, particularly when restrained.
I
However, experiments with shielding blocks on Anchorage design
the 90-ton shaking table at the University of
California Berkeleys Earthquake Engineering Prevention of dislocation and overturning
Research Center have been carried out to
investigate both rocking and sliding motions. Design of shielding walls and tunnels for
This research has been documented in two earthquakes
references; Sliding Response of Rigid Bodies to
Earthquake Motions (Ref. 1) and Rocking and Design of shielding caves for earthquakes
Overturning Response of Rigid Bodies to Earthquake
Motion (Ref. 2). Summary of recommended earthquake
design for shielding blocks

10a-1
r

Earthquake Effects on Shielding Blocks

Because of the massive character of blocks,


resistance to earthquake shaking involves
different considerations than those that apply to
typical buildings. Earthquakes may induce
responses in blocks or block structures that can
cause the following hazardous conditions (Fig.
10a-1):

Sliding or lateral movement Block Stacks


Rocking, wobbling, or random movement

Overturning /0-
//~ \

0 4 I Block slides
Shifting and misalignment to new position
I
I I
Collapse of the block structure or roof blocks

Collision with adjacent internal equipment, ~ 4 ~brationcan


building elements, or other obstacles. induce sliding in
i each direction
1-

I
Sliding

/
Rocking motion orwobble

Block remains
upright
fy

n/
II
/-- -,

/0
4%9 // .
/
,/
0

Rocking Shifting-misalignment

r~<
I
I ;(,
Ii .
;/ \l
It
I
. \ 4 I

Slidina collision
Overturning

Fig. 10a-1. Concrete block response.

10a-2
Basic Configurations of Shielding
Block Assemblies

Thickness, density, and height requirements


for shielding vary. Individual block sizes are
usually limited by the capacity of handling
equipment available to move them, such as
overhead cranes and forklifts. It is necessary to
accommodate blocks to varying requirements by
stacking them or placing units side by side.
Thus, shielded spaces are formed by assembling
individual blocks in some required pattern. Individual biocks
Blocks may be arranged in many different
configurations, depending on the degree of
shielding required and the physical area
available.

Concrete blocks are durable, heavy, bulky,


and very expensive. This makes re-use attractive,
b%%.-
but storage costly. Thus, blocks constructed for
one project are usually adapted to subsequent
layouts not always compatible with their sizes or
configurations.

The most common block configurations are


(Fig. 10a-2):

. Individual blocks in line with or at right angles


to one another and without a ceiling cover

Tunnelswith two parallel lines of wall blocks


with or without roof blocks

. Caves, which form enclosures with a roof and Tunnels


four mutually perpendicular walls similar to
a box.
Roof
Usually blocks are supported on a reinforced
blocks
concrete slab on grade or a heavy foundation
structure. Such heavy loads should not be placed
directly on the ground or on unstable ground or
potential landslide areas. Whether loads are
supported by a slab or structure, the bearing
capacity of the underlying materials and/or
structure must be verified as well as the ability of
the slab to transmit shear into the ground.
\
Building Code Considerations

The seismic provisions of model building 1-


codes such as the 2.Ini@m Building Code (UBC)
Caves
(Ref. 3) have been developed primarily for
buildings that have seismic response
Fig. 10a-2. Block configurations.

10a-3
characteristics and structural properties not
generally applicable to massive shielding block
structures. The UBC includes seismic loading
requirements for nonbuilding structures,
including rigid structures, but these requirements
q+-,
are not intended for such massive and unyielding

L
2
objects as shielding blocks that, if restrained, are
generally fixed to a concrete slab-on-grade or
heavy foundation. Blocks are generally of low
profile and so stiff that they will respond as a
rigid body with constant acceleration, top to v
bottom. For all practical purposes, a block does X of Lateral
not bend or deflect, and very little internal V = Base shear=
loads F1 & F2
damping can occur. Consequently almost all of
the inertial energy induced in a massive block by
lateral ground motion manifests itself as a Fig. 10a-3. Static base shear.
dynamic base shear force on the connecting
system fastening the block to its foundation. natural period jf it is braced and as ductile
portions of the restraining system experience
Moderate earthquakes of magnitude 5 and inelastic behavior, the period of the cave will
above have been knopm to produce horizontal vary. A dynamic analysis would be very complex
and vertical peak gr@md accelerations over 0.5g and of questionable value. Consequently, it is far
near the epicep@ and along a causative fault. simpler and efficient to use a static lateral load
Effective ~eak ground accelerations greater than (or base shear, V) for analysis related to the
0.7g liave been experienced in major weight of the shielding and the effective peak
earthquakes. Generally steel-base clip angles ground acceleration estimated for a site.
that are used to bolt shielding blocks to a
concrete slab have too little steel volume to In the text that follows, seismic criteria are
absorb large amounts of energy through ductility those recommended by the authors. They were
(flexual inelastic bending). However, Steel is a not extracted from the UBC or any other model
predictable ductile material in contrast to the code or industry standard.
brittle concrete into which most bolts are
anchored, both in the block and the concrete Seismic Design Criteria for Shielding
floor slab. The ultimate failure of steel angle and Blocks
bolt connectors occurs only after considerable
plastic (inelastic) deformation, whereas the The UBC specifies stresses to be used for
concrete that encompasses and anchors the bolts design that are interdependent with its other
ultimately fails abruptly if it is not reinforced to provisions to work properly as an integrated
develop a ductile anchoring medium. system. It allows working stresses to be
increased one-third for earthquakes and wind
The seismic provisions of the UBC define loads because of their short duration. For mild
static lateral load as a base shear that is the steel, this means that the maximum allowable
summation of all horizontal inertial loads acting stress for earthquakes is close to the elastic yield
on a structure at any one time (Fig. 10a-3). The stress. However, for the purposes of designing
code also prescribes how tributary lateral loads lateral-force-resisting systems for shielding
are distributed through the height of a structure. blocks, it is more practical to deal directly with
yield and ultimate stresses.
Shaking-table experiments have shown that
various natural rocking periods can be induced These seismic criteria are based on the
into a single unrestrained block (Fig. 10a-4. following considerations:
However, anchoring a single block against
displacement causes the block to have a very . Potential risk or frequency of damaging
short fundamental period. Even a cave earthquakes and the estimated maximum
constructed of shielding blocks has a very short intensity of horizontal ground shaking at
the site

10a-4
/
Jpraio
Natural
period of

Period
~. / +
equals \ \I -;
time \ J
\ ,1\
Interval \ \ I\/ /t
for one \ I
\\ I jb
cycle \ I Period T (sac)
;\ /
\ /-, ~= ~

Free vibration

Restraints
shorten
I period of
vibration
of block

Period T (sac)

Period much shorter


than free vibration
response depending
on degree of
restraint

Restrained vibration

Fig. 10a-4. Dynamic vibration.

The type of failure, ductile or brittle, to be In strong earthquakes, designers must


expected from the restraining material being anticipate that heavy shaking may cause stress
designed excursions well beyond the elastic yield stress
resulting in plastic (inelastic) deformation (Fig.
The consequences of failure (monetary, 10a-5). Consequently, the extreme distortions
injury, life-safety, release of toxic materials, associated with yield or ultimate strength levels
loss of emergency services, etc.). (short of rupture) may make connections
unsuitable for future use,

10a-5
Local
cushing
}

T <-
I
d

I
Permanently
deformed
restraints
,Im Bent and
distorted
angle

----rJ--rJfJ
E=h Sacrificial
restraints
r ~,,,,,
,
// //////////

Fig.10a-5. Inelastic distortions.

Table 10a-1 summarizes the authors Category 1 (PC-1) taken from Tables C-5a and C-
recommendations for static lateral force criteria 5b from DOE-STD-1O2O.
for the seismic design of shielding block systems.
These recommendations are meant to provide a For shielding assemblies that house
level of safety equivalent to Standard-(lccupancy hazardous operations and/or essential
Structures and Essential Facilities as defined by the components that must remain operational in the
UBC which correspond to Performance aftermath of a damaging earthquake, the
Categories 1 (PC-1) and 2 (PC-2) facilities as importance factor (I) should be increased to 1.25 in
defined in DOE-STD-1O2O(Ref. 4). These criteria keeping with UBC Table 16-K, Occupancy Category
provide a basis for application in various for Essential Facilities. This increase produces ~
locations of the United States by utilizing the acceleration factors greater than the maximum
SeismicZone Factor (Z) from Table 16-1 of the 1994 horizontal ground surface accelerations listed for
UBC. A Seismic Zone Map of the United States DOE sites (Tables C-5a and C-5b from DOE-STD-
(Fig. 16-2 from the UBC) is reproduced here in 1020) for Performance Category 2 (PC-2).
Fig. 10a-6 for determination of the appropriate Z Although Essential Facilities should be designed
factor. Generally, the calculated accelerations for a base shear (V) with an importance factor (I)
(2.5 Z I CP) derived using Table lea-l of 1.25, nonstructural components of systems and
recommendations will be greater than the equipment (and their attachments) that must
maximum horizontal ground surface remain operational for life safety or other
accelerations at DOE sites for Performance emergency needs should be designed for a lateral
force using I equal to 1.50. I

10a-6
,

Table 10a-L

Seismic criteria for static analysis of shielding block assemblies.


V= 2.5 ZICPW
v= Static Base Shear
I = Importance Factor
z = Seismic Zone Factor
Cp = Lateral Force Factor
w= Total Seismic Dead Load

Material Cp Stress Limit

Steel(l) 0.5 Yield Strength


Steel Diagonal Bracing and
connections (Mild Steel)(z) 0.75 Yield Strength
Non-Ductile Concrete
Bending, Compression and Shear 0.7 0.85 Ultimate Strength
Bearing 0.7 0.60 Ultimate Strength

Anchor Bolts 0.7 0.75 Ultimate Load Value(3J

(1) For structuralsteel or other materialsthat exhibitnon-linearplasticbehavior(similarto steel)beyondyield


stress.
(2) Some higherstrengthsteek maynot exhibita usableyieldplateauand shouldbe designedmore conservatively
(3) Based on load tests.

Seismic Zone Factors(Z)


(fromUBC Table 16-1)

zone(l) 1 2A 2B 3 4
z 0.075 0.15 0.20 0.30 0.40

m Zoneto be determinedfromU8C SeismicZone Map of the UnitedStates,(see Fig. 10a-6).

Importance Factors (I)


i
Importance Catego@) Importance Factor, I
,
Standard Occupancy Structures 1.00
Essential Facilities 1.25Q)
Hazardous Facilities 1.50(3)

(1) For occupancywithinshielding,see UBC Table16-K,OccupuncyCategoy, for definitions.


(2) Nonstructuralcomponentsof systemsand equipment(andtheir attachments)that mustremainoperationalfor
life safetyor otheremergencyneeds shallhave an ImportanceFactorof 1.50.
(3) For shieldingthat housesdispersibletoxicmaterialsor equipmentthat mustremainoperationalfor life safety
systemsor containmentof toxicmaterials.

10a-7
u

,. . -.
Fig. 10a-6. UBC Seismic Zone Map of the United states (Figure 16-2 from the 1994 edition). For areas
outside of the United States, see UBC Appendix Chapter l;.

For design of shielding assemblies that height-to-width ratio greater than the static
contain highly toxic materials and related coefficient of friction will rock. Individual
equipment that must remain operational, the I blocks may be made to rock at different
factor should be increased to 1.5 instead of frequencies. In earthquakes, both horizontal
1.25. This produces acceleration factors that and vertical accelerations are erratic, inducing
are conservative in relation to the maximum chaotic movement. Consequently, blocks
horizontal ground surface accelerations listed should be anchored to resist these phenomena.
for DOE sites in Table C-5a and C-5b from
DOE-STD-1O2O for Performance Category 3 When anchoring individual concrete blocks
(PC-3). Tables C-5a and C-5b list maximum for lateral stability, use of a base shear
horizontal ground surface accelerations for calculated from Table 10a-1 results in static
Performance Categories PC-1 through PC-4, lateral loads that are conservative in relation to
but recommend site-specific seismic hazard inertial forces that result from effective peak
curves for PC-3 and higher. The seismic design ground accelerations. Because most blocks rest
criteria in Table 10a-1 have been formulated for on a slab-on-grade, some energy may be
PC-1 and 2 categories only. Refer to DOE-STD- dissipated in mobilizing the heavily loaded
1020 (Ref. 4) for specific requirements slab, resulting in some attenuation of the actual
concerning facilities in Performance Categories ground acceleration provided the slab is
PC-3 and higher. adequately reinforced. Conversely, when
blocks rest on structural framing that is integral
Applications to Individual Blocks with a building frame, rather than on a slab-on-
grade, there may be amplification of the ground
Shaking-table tests show that individual motion. Upper floor accelerations are usually
unanchored blocks with a height-to-width amplified above the ground motion. This
ratio less than the static coefficient of friction amplification can be calculated by dynamic
will usually slide when subjected to horizontal analysis of the base structure and applied to the
earthquake forces, whereas blocks with a block as a higher base shear factor.

10a-8
Of concern is the possibility of resonance Because some reserve capacity (short of brittle
between the forcing frequencies or ground failure) should be retained for concrete, a factor
vibrations and the fundamental period of the of 0.85 is recommended for application to the
anchored block. An anchored block has a very ultimate-stress values for bending, shear, and
short fundamental period, so an installation compressive-stress capacities and 0.6 for
supported on a geologic site having ii short bearing-stress capacity. Concrete is a brittle
natural period (rock) must be designed more material susceptible to sudden failure or
conservatively than one on a softer foundation. structural deterioration; therefore, it is best to
be conservative when relying on its post yield
An individual block does not benefit from strength properties. It is possible, however,
continuity or redundancy inherent in a unitized when designing new foundations for shielding-
building system; therefore, it is essential that the block assemblies to incorporate reinforcing
base c~nnections that transmit the ground around anchor bolts to impart necessary
motions to the block do not break or tear away toughness and ductility.
from the floor or the block.
Anchorage Design
Once the seismic input is determined, other
factors should be considered in selection of the Anchors may be expansion-type anchor bolts
restraining systems. If first cost economics drilled into existing concrete work or standard
dictate, restraint systems may be made anchor bolts embedded in new concrete (Fig. 10a-
expendable for the maximum seismic event so 9). Allowable working loads are usually given as a
that ductile materials will be stressed well into percentage of ultimate test loads, 25% being the
the plastic or ultimate strength region. However, most common. Considering that anchor failure
overturning or nonductile failure must be in concrete is abfipt, the ultimate values should
prevented. Bending, buckling, stretching and be multiplied by a capacity-reduction factor of
distorting of members and anchors are important 0.75 for use in ultimate-strength design. When
sources of energy dissipation. At the mild steel using manufacturers design values, one should
yield stress value, with a flat-yield plateau (Fig. ensure that they have been certified by the ICBO
10a-7), considerable reserve strain capacity is EzuluationServices, Inc. (See Chapter 13). Cast-in-
available before the steel strains reach the place anchor bolts may be designed using ACI-
ultimate value and rupture ensues. 349, Appendix B (Ref. 7).

Concrete (Fig. 10a-8) and higher strength When anchoring shielding blocks, the basic
steels do not exhibit the same type of yield idea is to provide enough restraint to prevent
plateau as mild steel; therefore, yield values dislocation and/or toppling of the block.
and reserve capacity are not as easy to define. Ductile components of the restraint system

II Upper yield
stress

tensile strength

0
UJ
g -_
yield stress
6

Strain, e

Fig. 10a-7. Structural steel stress-strain curve.


I

1 10a-9
I
-i- 1.0

0.85fc

Tq Standard rateT of loading

16.7 psiperssc

0.000 0.001 0.002 0.003 0.004


Unit strain inconcrete
Fig. 10a-8. Typical stress-stain curve for concrete cylinders.

Allowable ultimate tension equals 3/4 x


manufacturers recommended
ultimate load

a Provide adequate
0=
or reduce pull-

----
( :

+%

II
II \
II=
Potential failure plane
LI

Fig. 10a-9. Anchor bolts in concrete.

should be designed for stresses (or strain yielding. When the angle is reinforced with
conditions) approaching yield. For example, stiffeners, it should not be so heavily stiffened
the steel base-clip angle itself should be that it rigidly transmits the design shear
designed to yield before brittle failure of the directly into the anchor bolts without
concrete holding the anchor bolt can occur. deforming the clip angle.
This allows designers to build some energy
absorption into the restraining system. If the angle thickness is designed to achieve
the required ductility in the connection (for CP =
Clip angles used to anchor shielding blocks 0.5), its thickness will not be enough to eliminate
should be strong enough to provide enough prying action of the bolts. Therefore, an analysis
ductility to absorb energy in bending after should be made using the American Institute of

10a-10
Steel Construction (AISC) procedures to compute or casting keyways in existing construction is not
the additional load in the bolts and driIIed-in always feasibIe. Anchorage is still required in
(proprieta~) anchors caused by prying action. any case. Heavy pins can be placed in holes
drilled into existing slabs (Fig. 10a-11) so that
Alternatively, prying action on the bolts can they protrude up into holes formed in the bottom
be relieved by using full-depth stiffeners on the of the block when the block is set in position on
base clip angle. Smaller or fewer bolts can then the floor. Lateral loads are transferred by shear
be used however, the connection will have so and bending in the pin and bearing of the pin on
little ductility that it should be considered as a the concrete, and through shear and bearing at
nonductile connection with CP=0.7. the keyway edges. In lieu of pins at the base,
angle clips can be attached to the block and
It is also very important that the bolts that secured to the floor with pins or anchor bolts
anchor the angle to the concrete floor slab and to (Fig. 10a-12). Flat-steel plate inserts with
the concrete shielding block have proper substantial anchors into the concrete can be cast
embedment in each and adequate edge distance. in the face of the base of the block. Base angle
The distance from an anchor bolt to a free edge of clips can then be welded to these plates, or stud
the concrete is an important consideration in anchors can be welded perpendicular to the flat
anchorage design. If possible, anchor bolts face of the plate and block and used to bolt
should be located and embedded so that (clamp) the base angle to the face of the block.
reinforcing steel intercepts potential cracking The weldment may be the most brittle point in
planes. If sufficient embedment depth and edge the system. If in the designers judgement this is
distance to develop the strength of the anchor so, then a CP = 0.7 should be applied.
cannot be achieved, then the capacity values for
shear and pull-out of the anchor should be Other anchoring systems can be devised with
reduced appropriately. Shear and tension the function of keeping the concrete floor slab
interaction should be accounted for in the anchor from shearing away from the blocks as the
if they can occur simultaneously. If several bolts ground induces earthquake motion into the block
are parallel to a free edge, the effect of through the slab.
overlapping failure planes on the concrete design
strength also must be taken into account. If floor When new shielding can be tied into existing
clip angles are used on opposite sides of the anchored shielding block installations, the ability
block, consider using a through bolt. This of the existing shielding to resist movement of
eliminates pull out problems, and leaves shear as the new blocks or assemblies may be utilized.
a consideration. It is still important to have Intersecting blocks or block walls can also be
reinforcing bars between the bolt and the edge of placed to resist displacement. Designers should
the block. For these important considerations, consider the blocks as a system and provide base
readers are referred to the article, Guide to the anchors, keys, pins, and ties as necessary to
Design of Anchor Bolts and Other Steel Embedments maintain elements in place.
(Ref. 5). See also Anchors in Concrete, Design and
Behavior, (Ref. 6), and Code Requirements for Generally, building framing members,
Nuclear Safety, Related Concrete Structures (Ref.7). especially columns, should not be used to resist
lateral loads from massive shielding blocks.
Prevention of Dislocation and. Blocks and their restraints should be free and
adequately clear of building support members.
Overturning
The use of framing elements that are part of the
vertical-load-carrying building frame should
Oneof the easiest and least expensive ways
always be avoided.
to minimize block dislocation is to key blocks
together at coplanar surfaces and to the floor
Base anchors (Fig. 10a-13) are effective
(Fig. 10a-10). Where blocks in line abut each
against sliding and differential displacement, but
other, continuous tongue-and-groove keyways
are not always a positive safeguard against
along the contact surfaces are effective. Floor
overturning under severe or sustained rocking
keys can be cast in new construction where block
motion. Overturning restraint (Fig. 10a-14) can
locations have been predetermined, but chipping
be incorporated with base anchors in the form of

10a-11
(4 h
Continuous keyways
In edge of block

Plan

WJ4
Continuous
tongue and
groove
keyways

7
I
I
/// ////////
End elevation
Fig. 10a-10. Concrete keyways.

~ recess in block resists


L earthquake shears

Fig. 10a-11. Heavy shear pins.

10a-12
Base
clip Angie weidad
angie to piate insert
I in biock. Provide
I 1- adequate anchors
.-
--- I 1- and edge distance
.- J .- 1

Ilil
11,1 driiiad in
111 expansion-type
I:J
+ anchors
L-

Steei pin
grouted into
\ oversized hoie
driiied into concrete
siab on ground

Fig. 10a-12. Seciming angle clips with pins or anchor bolts.

10a-13
Intersecting waiis ~
tied together

Waii biocks ,7
keyed 4-7-A I .
Ogether/
/ / I A#a
// Iwlw d
intersecting
biock and waiis
used to mutuaiiy
brace each
other

each biock
L.

Fig. 10a-13. Base anchors.

tie-down rods or straps attached to block support Design of Shielding Walls and Tunnels
framing systems, foundations, or other ballast for Earthquakes
with sufficient resistance or mass to counteract
uplift loads. Often, shielding blocks are assembled in a
longitudinal tunnel configuration (without
Diagonal bracing struts perpendicular to the
transverse walls) with roof blocks supported
long face of blocks are a good method of
directly on longitudinal wall blocks. It is
maintaining block stability. Bracing struts imperative that a support and anchorage system
should rest or react against the top third of the for the component blocks be provided to prevent
block height. The principal drawback to the use misalignment or shifting of tunnel wall blocks
of struts is their encroachment on space adjacent that could cause the collapse of roof blocks.
to the blocks. To avoid this problem,
cantilevered steel columns can be connected to The premise that the base anchorage should
horizontal beams that engage the faces of the be designed to prevent brittle failure yet provide
blocks such that the beams span horizontally ductility in the angle is as valid for tunnel
between columns and deliver the (lateral) block configurations as for individual blocks.
load to the cantilever columns. Cantilever However, it is possible to take advantage of
action can be obtained by anchoring the bottom additional energy-dissipating phenomena at the
of the column in a caisson or shaft drilled into interface of wall and roof. Connections can be
the ground and filled with concrete (Fig. 10a-15). devised that allow for distortion and stress
Formulas are available in the UBC to define the reversal that, along with friction and damping,
drilled shafts depth and diameter. Soil-bearing will relieve the effects of dynamic loading. Non-
values can usually be interpolated from ductile base connections should be designed for
previously available information or seismic forces based on CP = 0.7, but the ductile
conservatively assumed from visual site
structural elements above the base can be
inspection, geologic maps, or code tables.
designed for seismic forces (see Table 10a-1)

10a-14
Angle
// cross arm
/L

Rod tie
down
1- [

Base anchors
or pins must Rod tie
be provided to down
resist sliding
k 1 anchor

ooa~
C.G
so

F m

r #-Max.

1
to resist
sliding
r
Fig. 10a-14. Overturning restraints.

based on CP = 0.5 and still meet energy demand ductile and more brittle features of the same
through inelastic deformation. It is necessary to connection. The ductile or steel portion can be
design the ductile lateral-force-resisting system designed for yield stress against seismic forces
and connections to yield and let the strain energy (see Table 10a-1) based on CP = 0.5 and the
of yielding absorb the load without rupture. concrete anchorage for the same connection
should be capable of withstanding stresses based
To prevent premature or brittle failure of a on 0.85 ultimate stress against seismic forces
connection, one should differentiate between the based on CP = 0.7. In most instances, the steel

10a-15
-rCantilever
Lcolumn

. __
__ __,
__,
.
)
Horizontal
--f- transfer beam

I
Base
anchors
#

m\
~ II

!-t
Cantilever column
L-.
anchored In concrete
/ caisson
____ -1

Fig. 10a-15. Cantilever restraints.

1
Supplemental
shelding
Power source
/

b
I I
I
v

II

-f L -1 L
Permanently fixed equipment and
supplemental sh[eldlng contribute
to total mass

Fig. 10a-16, Tunnel assembly cross section.

10a-16
parts (i.e., angles, plates, pins, and bolts) can be cycles of stress reversal to the flames created by
designed using the yield strength of the material. the connections. Moment can be resisted at the
However, where a steel member relies on the base by a couple provided by base clip angles on
strength of the concrete for effectiveness, such as both sides of wall blocks. Care should be taken
anchor bolts, pins, and drilled-in expansion in the analysis to account for the fact that the
anchors bearing against concrete, the individual blocks are extremely stiff in relation to the
part of the connection dependent on the concrete connections. Tiedowns to resist overturning and
should be sized using CP = 0.7 against maximum uplift should be utilized if the base clip angles
bending stresses at 0,85 times the ultimate cannot prevent the blocks from rocking severely.
strength of concrete and bearing stresses at 0.6
times the ultimate strength of the concrete. Thus, In tunnel construction, the plane of the
concrete anchorages should be tough enough to ceiling or underside of the roof is a convenient
allow the beneficial dissipation of energy through place to put horizontal diagonal bracing. This
the inelastic distortion of the ductile materials in location is preferred when the roof blocks must
the connection. be occasionally removed. A horizontal truss
system (Fig. 10a-18) can be utilized to receive
With block structures having roofs, the lateral loads from the blocks. Truss reactions
question arises as to what gravity loads to use to must be transferred to the foundation through
calculate the seismic design force. Normally, one frame action of the wall and roof blocks or via
need only consider the dead weight of the wall extra framing, i.e., diagonal bracing struts and/or
and roof blocks. However, heavy experimental frames at the ends of the tunnel or spaced
equipment, supplemental shielding, and power intermittently along the length of the tunnel. To
sources are frequently anchored permanently on compensate for potential buckling of diagonal
the roof (Fig. 10a-1 6). Unless these accessory bracing, the design force should be increased by a
weights are effectively isolated, they (or some factor of 1.5 for yield stress analysis. To maintain
proportion) must be included in the dead load the same concept of resistance for the truss
calculation. This effective dead load (W) used in system, one should apply the 1.5 load factor for
the equation V=2.5 Z I CP W, results in the base the yield stress analysis by modifying the
shear (V), which is the static lateral force to be earthquake coefficient CP to 1.5x0.5 or 0.75. This
applied to the tunnel assembly. Materials and provision has been included in the Seismic Criteria
equipment placed on the roof, but unsecured for Static Analysis of Shielding Blocks Assemblies
will move around during an earthquake, but summarized in Table 10a-1. First-yield stresses
only a portion of its weight needs to be should be utilized for the diagonal bracing with
considered. However, if it is unsecured, it could this modified coefficient.
walk off the roof. Consequently, it is best to
secure such items. If seismic truss reactions at the ends of the
tunnel or reaction points are transferred to the ,
As with individual blocks, a primary foundation by moment frame action of the wall
principle is isolation of the tunnel and its and roof block assembly, these seismic reactions
components from building supports or adjacent for the moment frame need not include the 1.5
structures. Wall blocks should be keyed to load-modification factor when designing the
adjacent blocks and roof blocks keyed or moment frame connections and base
mechanically interlocked to prevent relative anchorages. Design of truss member
movement (Fig. 10a-1 7). Base angle clips and connections to block assemblies (moment frame)
pins can be incorporated to prevent sliding. should use seismic reactions derived with the
Frame action can be utilized by incorporating 1.5 modifier. When diagonal braces in a vertical
angles and brackets to develop moment capacity plane are employed to hold the horizontal truss
at roof block and wall block interfaces. In this in the roof plane, the modified lateral force
situation, the clip angles transfer seismic energy factor, CP = 0.75, should continue to control sizes
directly into this interlocked frame for dissipation and details. Foundation bearing pressures can
rather than relying upon the clip angles alone to be evaluated on the basis of reactions calculated
dissipate energy. For this reason, clip angles without the 1.5 factor, which applies only to the
should be sufficiently stiffened to transfer several braces and their connections.

10a-17
Equivalent
,._--SeeDetailA
static load /
/

.= ,0 . ..
Jllllli
. .

HHHH
Overturning loads
must be investigated

A
Moment
clip Pin to resist shear
/

y II - ;1 1
----,1 I ,1
--- I I ,1
Il. ,1 4 7
.--JI I ,1
- II ,1
II ,1
I I J I
*
II w
JI [
m
-- I I
l_l
----- ___
--- ____ Moment resisting
clips must be
--- capable of taking
K --
~ J
several cycles
I of stress reversal
4-
I

Detail A

Fig. 10a-17. Frame action details.


Diagonal bracing can also be located in the Caves by definition usually have four walls
plane of the top of the roof blocks if the mutually perpendicular to each other; therefore,
exposure of the framing poses no hazard to these walls can be used to counteract loads
personnel and does not interfere with concentrated by collectors. Internal stresses
experimental equipment or occasional within the blocks are seldom critical, but
dismantling. Depending on design loads, connections of bracing elements or collectors to
connection of the truss diagonals to the blocks the blocks must be strong enough to prevent
(Fig. 10a-18, Section A-A) may be accomplished premature breaking away (Fig. 10a-21). Resisting
with anchor bolts, drilled-in-place concrete loads by members in tension and bolts in shear is
anchors, welded studs, or pins. Most support the preferred approach. Bolts should be high-
techniques used for individual blocks or blocks strength fasteners tightened in accordance with
in-line are equally adaptable to tunnel-like or recommended standard procedures. Values for
roofed-over configurations. Diagonal struts can slip-critical bolts should be used whenever high-
be used to brace each wall block, or a system of strength bolts are used in conjunction with
horizontal beams and cantilevered columns can welding. Drilled-in-place proprietary anchors
be integrated to support the walls. Because the may be used; however, cast-in-place anchors or
inertial loads to be resisted are large, the bolts epoxied into drilled holes are tougher and
problem of controlling deflection is enccmntered more reliable.
when using cantilevers. A check of deflections
is necessary, coupled with an evaluation of Other building design techniques are useful
potential effects of translations and rotations on for caves, the most expedient being the use of the
the stability of the cell unit. Elastic properties cave roof as a diaphragm. Shear plates can be
of the ground resistance against the caisson used to transfer seismic shears from block to
must be considered in determining deflections. block, and structural steel shapes can form
The modulus of subgrade reaction is a useful flanges (chords) for the diaphragm and load-
parameter for this purpose. transfer elements (Fig. 10a-22). Individual wall
blocks can be anchored together and to the floor
Design of Shielding Caves for to complete the path to the ground to transfer the
Earthquakes dynamically induced forces. Where walls can be
unitized, tiedowns at the ends to resist uplift are
seldom necessary. Interior cross walls, if
Because cave facilities resemble buildings
permanently located, are useful as additional
more than other shielding configurations
resisting elements, but they must be anchored to
(Fig. 10a-19), one might logically reassess the
the roof and floor for their proportionate load.
earthquake coefficient for such caves relying on
Maintaining integrity and alignment are
experience with similar massive building
necessary adjuncts to a satisfactory system.
structures. Generally, however, the authors
Previous emphasis on keys, pins, and mechanical
recommend the use of higher lateral load
interlocks applies.
coefficients and yield stress capacities that are
more in keeping with the primary response of a
Supplemental bracing schemes external to
massive and very rigid structure such as a cave of
the shielding blocks are sometimes a viable
shielding blocks.
alternative (Fig. 10a-23).
Designers must make sure that there is an
Diagonally braced or moment-resisting
uninterrupted path for transferring loads in the
frames may be used, but additional caution is
bracing members to the ground or bearing
necessary when relying on ductile moment-
medium. Collectors can be used to drag loads
resisting frames. Because blocks are unyielding
from areas tributary to the bracing elements (Fig.
and resist movement, they prevent the necessary
10a-20). Connections and splices must be strong
energy-absorbing distortions of the frame from
enough to prevent collected loads from breaking
taking place. This could lead to premature
the link to the bracing members and isolating
failure of the assembly or anchorages because the
part of the cave. This type of failure would leave
frame may not be able to absorb the required
the cave without lateral support and susceptible
energy through plastic yielding before failure of
to collapse.
the stiffer elements. A careful compatibility

10a-19
Horizontal steel truss
in plane of roof
([

Truss members
anchored to
roof blocks

ri
II
II
I
1
I
,----
L----
__
__

= - K

A
Y Wall blocks
must be tied
to roof blocks

Section A-A

Fig. 10a-18. Horizontal diagonal bracing.

10a-20
Wall top plates acting Roof diaphragm
as fianges (chords) A< /

at

Building

Waii biocks act


.<
as shear waii
L

Cave

Fig. 10a-19. Cave-building analogy.

Coiiector
~ Beam under
Cave h L
r ---
4
,- - -- - -- -1
I Roof and

T
\ I JI
I
r I waii isoiated
I A
I from cave
I
I I
I
I )
I
I
I
I
I Beam under
L-- -. -- --

Roof Plan

Fig. 10a-20. Load collectors.

10a-21
Collector 1 / Collector or drag strut

collector
~
Z&z 4
< - ~-
a

and /or Roof blocks


chord
Wail block
/

Fig. 10a-21. Cave assembly connections.

Diaphragm
shear transfer
plate (steel)
>J L

/
/& /
/,
//
Anchor
bolts

Steel section acts as


diaphragm
chord

b-
Chord bolted
to roof and
wall block
I I
II
\
Roof diaphragm

Wall block

Angle clip

///
Fig. 10a-22. Shear transfer plates and roof chords.

10a-22
~ Transverse bracing frame
I I
-- --- -
I
I
I
I
I
I
I
I --- --- --- ---
k

open end J
ROOF PLAN

\ 1

/k
1 I

XX steel bra
frame
,~ <
\
A \

ductile frame

. . . .0 0. ...0 . . . . . O.U. 0. . 0? .
(

I
Frame bolted
to blocks
k +

stiffness control

Fig. 10a-23. Supplemental bracing schemes.

10a-23
analysis is therefore necessary. Usually a stiffer requirements for steel structures resisting forces
frame is required than would be indicated from a induced by earthquake motions as related to braced
design for moments and shears only. frames, bracing connections, and bracing
configurations. Because these columns probably
A concentric diagonally-braced steel frame (Fig. wont carry gravity loads, the strong-column versus
10a-24), if properly designed and detailed, will also weak-beam requirement is not so important.
work. It must have sufficient strength to undergo
several sudden load reversals during any seismic The eccentric-braced frame is coming more
event; thus, members and connections must be into use in earthquake design. This system adds
tough enough to resist severe impulse loading. ductility absent in concentric-braced frames.
Strength can best be achieved by designing the Energy is absorbed in bending a link beam,
system to carry as much of the load as possible by lessening the potential for buckling of the
members in tension. Toughness can be attained by diagonal brace. Designers must follow published
making the comections of members stron& durable, design procedures and detailing
and capable of developing the full plastic strength of recommendations for the connections of the brace I
the connected steel members. Regardless of the and link beam. The eccentric-braced frame easily
direction of load (tension or compression) indicated adapts to yield and/or ultimate strength analysis.
by analysis, connections should be designed to
develop the most critical strength of the member Some newer developments in earthquake-
used, be it tension or compression, so that severe resistant design include energy-dissipating
stress reversals can be accommodated. Thus, the systems such as base isolation and passive
connections will be able to transfer member forces devices that absorb energy by slipping, flexing,
without failing before the member does. It must be and distorting. These systems will result in
assumed that a tension member will be stressed in larger lateral displacement of the isolated /
compression and vice versa; therefore, steel structure. Generally, large displacements should
connections should be designed for the actual be avoided in shielding block installations or
plastic strength of the member in either mode. accounted for with conservative clearances.
Designem should check the building code for special

r Members designed ,
for 1 1/2x
actual load

I
connected member
I
t
I /,

u Intersections to be concentric
Fig. 10a-24. Concentric brace connection.

10a-24
Summary of Recommended Earthquake recommended, utilizing ultimate-stress values
Design Criteria for Shielding Blocks reduced by an appropriate capacity reduction
factor. For normal reinforced concrete, it is
The earthquake design criteria for bracing recommended that a capacity-reduction factor of
0.85 be applied to the ultimate strength values of
concrete shielding blocks should take into
consideration site specific seismicity, the type of concrete for bending, shear, and compressive
system used to brace the shielding blocks against stresses and 0.6 for bearing stresses.
earthquake ground motions, and the
For the design of anchor bolts or proprietary
consequences of failure.
expansion anchors that depend on concrete for
In keeping with Table 10a-1, the formula, their ultimate-load capacity, use 0.75 times the
V=2.5 Z I CP W, is used to determine the base manufacturers ultimate-load values (based on
load tests), with proper consideration for edge
shear, V, to be applied for static lateral force
distance and embedment of the anchors. Anchor
analysis and design.
bolts and shear pins should be designed to be
tough enough to allow the beneficial dissipation
Site seismicity is incorporated by
of energy by the distortion of the steel elements
determinin g the seismic zone in which the site is
of the connection before failure of the anchorage.
located from the UBC (Ref. 3) Seismic Zone Map
(Fig. 10a-6), and selecting the Seismic Zone Factor,
References
Z, from Table 10a-1. Alternatively, the effective
peak ground acceleration from site-specific
1. Sliding Response of Rigid Bodies to Earthquake
hazard curves may be used for Z based upon
Motions, M. Aslam, W.G. Godden,
methodology specified in DOE-STD-1O2O(Ref. 4).
D.T. Scalise, LBL-3868, Lawrence Berkeley
The Importance Factor, 1, is obtained from the Laboratory, Berkeley California, 1975.
appropriate chart in Table 10a-1. This selection
2. Rocking and Overturning Response of Rigid
should be in keeping with the performance
Bodies to Earthquake Motion, M.Aslam, W.G.
categories described in Reference 4.
Godden, D.T. Scalise, LBL 7539, Lawrence
Berkeley Laboratory, Berkeley, California,
The lateral force factor, Cp varies with the type
1978.
of bracing system and within the system, by the
ductility (or lack of) of each component. For 3. Uniform Building Code, International
ductile bracing systems, connections, and/or Conference of Building Officials Whittier,
components that are constructed of materials (such California, 1994.
as structural steel) that exhibit ductile nonlinear
behavior at stresses at or beyond their yieki points, 4. Natural Phenomena Hazards Design and
a value of CP = 0.5 is recommended, using the Evaluation Criteria for DOE Facilities, DOE-
actual yield stresses of the ductile materials in the STD-102O-94, U.S. Department of Energy,
earthquake-resisting system. Diagonal bracing Washington, D.C., 1994.
members and their connections should be
designed to resist forms resulting from a base shear 5. Guide to the Design of Anchor Bolts and Other
increased by a load modification factor of 1.5 times Steel Embedments, R.W. Cannon, D.A.
0.50, or a CP = 0.75, to obtain a greater strength and Godfrey, and F.L. Moreadith, Concrete
safety factor against buckling. Ductile diagonal International, 1981.
bracing members and their comections should be
designed utilizing yield stresses. 6. Anchors in Concrete, Design and Behavior,
G.A. Senkin, H.B. Lancelot, III Editor, 1991.
For nonductile systems and connections
constructed of structural materials that do not 7. Code Requirements for Nuclear Safety, Related
exhibit reserve strain energy capacity resulting ConcreteStructures, ACI-349, Appendix B.
from nonlinear behavior, like non-ductile
reinforced concrete, a value of Cp = 0.7 is

10a-25

Você também pode gostar