with Switchgear
Unrestricted / Siemens AG 2017
Wind Turbine
Products of Siemens Wind Equipment (blue)
Main Power
Generator &
Power converter
Power Distribution
Contactor
Breaker
~
~
Converter 400 V
Auxiliaries:
Yaw, Pitch,
Heating,
Consulting
Frequency
Converter
MSS
PLC
Turbine Control
Infeed panel
Transformer
~ Synchronous
Gear SG
~ generator with full
inverter system
Contactor
Breaker
~
~
Converter 400 V
Circuit Converter
Breaker (sometimes several
(non-automatic) modules parallel)
Contactor Circuit
Breaker
Examples
3 Contactors 3RT14, each 690 A * 2,5 (Derating) = 1.700 A 1,2 MW per Converter module
3 Contactors 3TF69, each 910 A * 2,5 (Derating) = 2.300 A 1,6 MW per Converter module
If space requirements inside the If power loss inside the Sure connections also at Vibrations. Spring Loaded
control cabinet have to be reduced cabinet has to be reduced Mounting, wiring and testing reduced
45 mm
170 mm
Motor starter Overload Relay Solid State Soft Starter Motor Starter Compact Load Feeder Motor Starter
Contactor 3RT
protector 3RV 3RU, 3RB contactor 3RF 3RW 3RM1 Starter 3RA6 3RA2 ET200SP
Overload
Window
Profinet
ET200S
400
690 V
Rotating CW CCW
direction
Yaw Hydraulic Fan
...
How to get information
Motor Protection Standard-IO before
overload or damage
Contactor stops the machine ?
PROFINET
ET200S
400
690 V
Standard Monitoring Monitoring
SIRIUS Relay Motor Starter
Rotating CW CCW
IO-Link PROFINET
direction
Motor Protection
24V IO
Contactor
Overload Relay
3RR24
e.g.: up to 12
Yaw - Motors
PROFINET Monitoring of
ET200SP
400 current overshoot and undershoot
690 V
broken conductors
no-load operation and load shedding, e.g. in the event of a torn
Rotating CW CCW
V-belt or no-load operation of a pump
direction
Standard-IO
overload, e.g. due to an excessive load
the functionality of electrical loads such as heaters
wrong phase sequence on equipment such as cranes
high-impedance faults to ground, e.g. caused by
damaged insulation or moisture
Motor Protection
Overload
Contactor
24V IO
IO-Link Window
Monitoring Relay
3RR2
Monitoring
e.g.: up to 12
Yaw - Motors
L+ Standard-IO IO-Link
1 C/Q
2 4
3
3 simple wires (signal, plus, minus)
L- replace many single wires and
transfers extensive Data
Internet
IEC 61131-9
Electronic
Overload Relay
Switch on:
Manually or Automatic Automatic Automatic Automatic
Remote (PLC) Remote (PLC) Remote Remote
(Safety PLC) (Safety PLC)
Unrestricted Siemens AG 2017
Page 28 2017-11 Technical Concepts with Switchgear DF CP
Switchgear Combinations
400 V 690 V, Short Circuit Case
Breaker
400 V
Limiter
Breaker Breaker
Limiter Motor
Limiter Starter
Diesel ET200SP
Generator
Circuit
Breaker
1.Contactor
(Safety)
Generator Contactor
2.Contactor
(Safety)
enclosed pdf-File
Further Benefits
No 400 V- Transformer (only 230 V, PLC)
much smaller cabinet
Safe energy (e.g. 3% of all auxiliaries)
Safe costs
Unrestricted Siemens AG 2017
Page 31 2017-11 Technical Concepts with Switchgear DF CP
Auxiliaries
Maintenance
More
Parameters are in the PLC easy Configuration, also via TIA Portal
Wide Range up to 15 kW: 5 power variants only
Unrestricted Siemens AG 2017
Page 32 2017-11 Technical Concepts with Switchgear DF CP
Agenda
Power
Sensor
Controller
4 till 12 Motors
Controlling with SIRIUS & Compact Starters Small, reliable and easy to use
Regulated Frequency Converters SINAMICS for high dynamic systems
Requirements Highlights
Compact (in turbines there is less room) Compact
High reliability Up to 15 kW (32 A at 400 V AC)
Technical Concept Reliably
CPS in IEC 60947-6-2
(Control & Protective Switching Device)
45 mm
Even at a short circuit: No welding of contacts
Remote-Reset after a temporarily motor-overload possible
(e.g. by software)
170 mm
Connection with spring-loaded terminals
safe connection even at vibrations and extreme temperature
changings
Easy
Less cabling simple installation
A Compact Starter combines functional switching, overload and short-circuit current protection
Contactor, circuit breaker, overload relay
PROFINET
ET200S
400V ~
Optional:
Soft Starter
preserve mechanics
Load Control
current, voltage IO-Link IO-Link
Limiter more short-
circuit current prevention
Compact Starter
Yaw-
Motors
PROFINET
ET200S
Topics
~400V All operating data available
(Current, Voltage, Load, Energy, Earth fault)
Rotating IO-Link:
CW CCW Standard-IO
direction 3 simple wires (signal, plus, minus) replaces
many single wires and transfers extensive Data
Short Circuit
Motor Protection Cost-efficient availability of data
Contactor
for preventive maintenance
IO-Link
Monitoring Relay:
Overload, Energy
3RR24
e.g.: up to 12
Yaw - Motors
IO-Link
Only one 3-wire-cable is needed to monitor and transfer all data of the application
All data are available at the PLC e.g. controller SIMATIC S7
Diagnosis & preventive maintenance.
Compact Starter
Remote or auto reset possible.
Variants enormous reduced: UL and IEC. Wide spread. Overload Class 10 or 20
Vibrations are no danger: With Cage Clamp technology you get a firm connection
At each single motor the following parameters are monitored all the time:
Switching status, end of service life, overload, short circuit and more
Soft Starter
Preserve mechanics and avoiding electric current peaks while starting of motors.
Additional increasing of compact starters life-time (switching operations).
Extreme Requirements:
Vibrations & Centrifugal Force
Offshore & Salt-containig Air
Extreme Temperatures
Electronic
E.g. printed circuit boards can be protected against salt
The whole electronic component is available for extreme temperatures, vibrations
SIPLUS Extreme
Fastening surface
with maximum acceleration (up to 7*g)!
Contactor
enclosed File
Vibrations
The complete components are shock tested.
But many problems in the long run are caused by faults in the wiring.
Spring-Loaded connection technology helps very much
6 Safety
7 Security
8 Consulting for Panel Builders
Unrestricted Siemens AG 2017
Page 48 2017-11 Technical Concepts with Switchgear DF CP
Cold Climate
Process
IEC 61400
???
Ta Te
C
+50
Operation Temp. To
Energy Production Temp. Tp
IEC 61400 - Certification
Gearbox
Component Tc
Microbox
+40
SIPLUS S7-1200
SIRIUS for low Temp.
Energy Prod. Tp
+30
SIRIUS
Cabinet
+20
+10
0
Survival T. Ts
-10
Survival T. Ts
-20
CCV
-30
-40
-50
Ambient Temp. Ta
Enviromental Temp. Te
of the Wind Turbine
of the Components
Unrestricted Siemens AG 2017
Page 50 2017-11 Technical Concepts with Switchgear DF CP
Cold Climate
Start Phases
Heating of Cabinets
Main Cabinets
Oil in the gearbox
Start
Temperatures
Gearbox
Rotation speed
Torque
~
~
690 V~ 400 V~
20 kV~
Generator Nacelle
Wind Speed
Ambient Temp.
Main Cabinet
0C +60C
Basic Com.
Converter CPU Switch
Wind Farm
Management
3WL Heating Cabinet
Te > -40C
SIRIUS
400 /
230V~
690 V~
20 kV~
Switchgears
Inside of Cabinets SIRIUS
Standard down to -25 C
Low Temp. down to -40 / -50 C e. g. 3RV2011-1EA25-0BA0
Outside of Cabinets
The Pitch-Motor can be turned off at end-position by limit switches.
Low Temp. down to -40 C (3SE1AJ.) enclosed File
These proven product characteristics distinguish Siemens from other and facilitate the
industrial controls' safe application in wind turbines.
Cabinet
Nacelle in each Blade
690 V~
PROFINET ET 200SP
Nacelle
Cabinet
Breaker 3RV2
in each Blade
Short Circuit Protection
760 V~
142 A
AC1
Nacelle Fuses,
Breaker
Short Circuit
Cabinet up to 40 kA
760 V~
Heating
Wires 3 Branches (Abzweige).
One per Blade
Heating
Wires
7 Security
8 Consulting for Panel Builders
Unrestricted Siemens AG 2017
Page 61 2017-11 Technical Concepts with Switchgear DF CP
Safety
Process
Start End
Yes
Risk analysis
Pitch Yaw
Contactor
Frequency
Converter
MSS
PLC
Turbine Control
400 V ~
PL c / d CW CCW Rotating
Rotary
direction
Encoder
Short Circuit
PL d Protection
Contactor
Monitoring Relay:
Overload, Energy
Danger of
Cabel Yaw
Twisting Motors
Speed
Overspeed Tripping Device
3TK2810-1 Stop Wind Turbine:
Pitch Blades 90
Sensor Yaw Motors Stop
Brake on
PL c/d
Ball in Shock
Ring Sensor
Turbine Control
enclosed File
Rotor Speed 1 Rotor Speed 2
Parameterize
High flexibility and reliability of planning: Modular design Simple thanks to a clear product portfolio and
More space in the control cabinet and lower costs thanks universal functionality
to a highly modular quantity structure
Flexible thanks to a modular product concept
More functionality and time saving through a
parameterizable software system and versatile parameterization
Extensive diagnostics on site and project documentation Economical thanks to little variance and low
using the MSS ES software wiring costs
1 3
2
4 6
5
Rights
16
Turbine owner Cervice Centre
Each white ID Key has an individual Chipcode (like your credit card)
PLC in each Turbine allows actions, depending on the colour In each single Wind Turbine PLC the selected ID Keys with
Group Keys (no personal key) individual Rights are stored, and this PLC allows actions
Additional possible (in Preparation):
All ID Keys and Rights are stored in a central PLC in parallel
This PLC transfers the data to the PLC in eachTurbine
3SU1900-0FU60-0AA0 wt
3SU1400-1GD10-1AA0 ET 200SP
RFID Key Chipcode IO-Link
Software PCT = Port Configuration Tool
integrated in TIA Portal (free of charge)
>FAQ IO-Link Connection
Unrestricted Siemens AG 2017
Page 71 2017-11 Technical Concepts with Switchgear DF CP
Securitiy ID Key Switch
PCT - Tool - module parameters
Sales Support
Individual Consulting, also on customers site
3D models
CAE-Support
(Macros) Datasheets
Dimensional drawings
Configuration Support
Top highlights
Feature Benefit
Tools for selecting and configuring Process acceleration thanks to central
products (e.g. SIZER, TIA selection selection and interfaces to
tool, configurators) conventional engineering tools
Design and dimensioning using Optimum, standard-compliant product
efficient tools (e.g. SIMARIS planning and system design for a wide range of
tool) applications
Internet:
Planning
Efficiency
siemens.com