V1.0
I- Type of publication
II- Product
- Product range : - Product family :
TesysT LTMR
III- Introduction
This document will describe you how to configure TeSysT on a network Profibus with a PLC
Siemens S300 station. The CPU is a CPU 315 - 2 DP with Profibus port embedded.
We use Simatic S7, STEP 7 V5.4 SP3. Into Simatic you have two sub-softwares to configure the
Profibus Network : NetPro and HW Config.
NetPro: you define which kind of product you need on your Profibus network (TesysU, TesysT)
HW Config:
- PLC hardware configuration
- Configuration for each device Network (TesysT with or without expension module, which control
unit for TesysU and which information you want to exchange on the network)
Page 1/11
R036
V1.0
IV- Description
Page 2/11
R036
V1.0
We show this configuration without using Wizard tool of Simatic software because it is more difficult
to configure without Wizard tool.
a
Right click on
Project Name
Page 3/11
R036
V1.0
You access to
HWConfig
e
Insert PLC
f rack
Page 4/11
R036
V1.0
You can click on the CPU reference that you have (see above) to insert it into the rack. A
configuration window occurs (you add a Profibus connection because Profibus master is embedded into the
CPU):
Page 5/11
R036
V1.0
You need to define your power supply for the PLC. On our bench we have a PS 307 2A:
The hardware configuration for the PLC is finished so you can compile and save the step1:
Page 6/11
R036
V1.0
After you can import the GSD with Simatic on HWConfig interface:
Select the
module DP
a
b
c
d
Double click to add a
new TesysT on the
network.
Page 7/11
R036
V1.0
e
TesysT address = 1
TesysT baudrate is
f automatic
g
You can double click on
the icon to access to the
Software configuration of
the product, you will
define:
-The length of information
exchanged
-Which information you
want to read/write
-If you have expansion
module or not
Page 8/11
R036
V1.0
After double click on the device under NetPro automatically a window occurs to configure the
software configuration of the product:
For example:
MMC R: LTMR alone without expansion + Remote
configuration.
MMC L PKW EV40: LTMR + LTMEV + Local
configuration and we can read/write all information by
DPV0 service.
Page 9/11
R036
V1.0
Page 10/11
R036
V1.0
Compile the last information and after you can download the configuration into the PLC:
a
Click on Ok for all
windows occur
after pressing the
download icon
Page 11/11