STRUCTURE CONVEYOR GALLERY
0
DESN CHKD
TITLE GALLERY WIND LOAD CALCULATION
NVK JTP

Wind load calculation for gallary :


Details of wind load for gallary are described below:
The design wind loads shall be calculated in accordance with IS 875-1987(part -III)
as specified in this document. The evaluation of design velocity pressure shall be made on
the basis of following parameters.

Design wind speed (Vz) Vz = Vb*K1*K2*K3


Basic wind speed Vb = 50 m/s
Category = 2
Class = C For conveyor
Height of the structure from the ground level = 50.00 m

Probability factor(K1) = 1.00


Terrain,Height and struucture factor(k2) = 1.10
Topography factor(k3) = 1.0
Enhance factor(k) = 1.15
Design wind velocity or speed Vz = 63.25 m/s

Design wind pressure Pd= 0.6x(63.25x63.25 pz 0.6Vz 2


Pz (or) q (or) Pd = 2.40 kN/m2

The wind analysis shall be consider along the wind direction relative to the structure
and both external and internal pressures as applied to the windward and leeward sides of
the structure.

Length of the building = 24.00 m


Width of the building = 6.60 m
Height of the building = 3.00 m

H/W = 0.455 L/W = 3.636

[From IS 875 ( Part 3 ) :1987]


External pressure coefficients (Cpe) for h / w < 1/2 , 3/2 < l / w < 4

Wind load for wall:


External pressure coefficient for Wall (Cpe):
WIND ANGLE A B C D

0 degree 0.70 -0.25 -0.60 -0.60

90 degree -0.50 -0.50 0.70 -0.10


Wind load for Roof:

External pressure coefficient for Roof(Cpe) :


WIND ANGLE 0 degree 90 degree
ROOF ANGLE EF GH EG FH

17 DEGREE -0.64 -0.40 -0.73 -0.60


The internal pressure coefficient Cpi = +/- 0.5

Wind load acting in a direction normal to the structural element is


F = ( Cpe - Cpi ).q.A
Where, Cpe = external pressure coefficient
Cpi = internal pressure coefficient
A = surface area of structural element
q = design wind pressure
Net co-efficients ( Cpe - Cpi ) :
FOR WALL:
DIRECTION OF No. of Co-efficient Panel A B C D
WIND face / Pressure width 1 1 0 0
Co-efficient 1.20 0.25 -0.10 -0.10
0 Degree(suc) 1 2.5 m
Pressure 7.20 1.50 0.00 0.00
Co-efficient 0.20 -0.75 -1.10 -1.10
0 Degree(pres) 1 2.5 m
Pressure 1.20 -4.50 0.00 0.00
Co-efficient 0.00 0.00 1.20 0.40
0 2.5 m
90 Degree(suc) Pressure 0.00 0.00 0.00 0.00
90 Co-efficient -1.00 -1.00 0.20 -0.60
0 2.5 m
Degree(pres) Pressure 0.00 0.00 0.00 0.00

FOR ROOF:
Panel
DIRECTION OF Co-efficient width
EF GH
WIND / Pressure
Co-efficient -0.14 0.10
0 Degree(suc) 2.5 m
Pressure -0.84 0.60
Co-efficient -1.14 -0.90
0 Degree(pres) 2.5 m
Pressure -6.84 -5.40
EG FH
Co-efficient -0.23 -0.10
2.5 m
90 Degree(suc) Pressure -1.38 -0.60
90 Co-efficient -1.23 -1.10
2.5 m
Degree(pres) Pressure -7.38 -6.60

Drag force for gallary:


The friction focre for the structure shall be applied when structure size meeting the
following criteria:

d/h = 8.00 d/b = 3.6364


DRAG FORCE SHALL BE APPLIED FOR THIS STRUCTURE

d = 24.00 m
h = 3.00 m
b = 6.60 m

hb Hence use 1. Formula


for Cf ' value 1.Without corrugation or ribs = 0.01
2.With corrugation = 0.02
3.With ribs = 0.03
Enter type of Roof surface for Cf' value 2
The value of Cf ' = 0.02

The total drag force value = 7.26 kN

Take half of the loading from total drag force and applied first 1/3rd of the gallery
along wind direction and remaining half of the total drag force applied next 2/3 rd of the gallery.
DOCUMENT NO.
PROJECT TOSHIBA
JTP-XXX-S01
Rev. No Page
STRUCTURE JUNCTION TOWER
0
DESN CHKD
TITLE WIND LOAD CALCULATION
SVK JTP

3 WIND LOAD CALCULATION


DOCUMENT NO.
PROJECT TOSHIBA
JTP-XXX-S01
Rev. No Page
STRUCTURE JUNCTION TOWER
0
DESN CHKD
TITLE WIND LOAD CALCULATION
SVK JTP

Wind load calculation for Junction Tower :


Details of wind load for gallary are described below:
The design wind loads shall be calculated in accordance with IS 875-1987(part -III)
as specified in this document. The evaluation of design velocity pressure shall be made on
the basis of following parameters.

Design wind speed (Vz) Vz = Vb*K1*K2*K3


Basic wind speed Vb = 50 m/s
Category = 2
Class = A For conveyor
Height of the structure from the ground level = 50.00 m

Probability factor(K1) = 1.08


Terrain,Height and struucture factor(k2) = 1.10
Topography factor(k3) = 1.0
Enhance factor(k) = 1.00
Design wind velocity or speed Vz = 59.29 m/s

Design wind pressure Pd= 0.6x(59.292x59.292 pz 0.6Vz 2


Pz (or) q (or) Pd = 2.11 kN/m2

The wind analysis shall be consider along the wind direction relative to the structure
and both external and internal pressures as applied to the windward and leeward sides of
the structure.

Length of the building = 15.10 m


Width of the building = 10.50 m
Height of the building = 59.00 m

H/W = 5.619 L/W = 1.438

[From IS 875 ( Part 3 ) :1987]


External pressure coefficients (Cpe) for 3/2 < h/w < 6 , 1 < l/w < 3/2

Wind load for wall:


External pressure coefficient for Wall (Cpe):
WIND ANGLE A B C D

0 degree 0.80 -0.25 -0.80 -0.80

90 degree -0.80 -0.80 0.80 -0.25


Wind load for Roof:

External pressure coefficient for Roof(Cpe) :


WIND ANGLE 0 degree 90 degree
ROOF ANGLE EF GH EG FH

20 DEGREE -0.80 -0.60 -0.80 -0.80

The internal pressure coefficient Cpi = +/- 0.5


Wind load acting in a direction normal to the structural element is
F = ( Cpe - Cpi ).q.A
Where, Cpe = external pressure coefficient
Cpi = internal pressure coefficient
A = surface area of structural element
q = design wind pressure
Net co-efficients ( Cpe - Cpi ) :
FOR WALL:
DIRECTION OF No. of Co-efficient Panel A B C D
WIND face / Pressure width 1 1 1 1
Co-efficient 1.30 0.25 -0.30 -0.30
0 Degree(suc) 1 7.3 m
Pressure 19.88 3.82 -4.59 -4.59
Co-efficient 0.30 -0.75 -1.30 -1.30
0 Degree(pres) 1 7.3 m
Pressure 4.59 -11.47 -19.88 -19.88
Co-efficient -0.30 -0.30 1.30 0.25
1 5.3 m
90 Degree(suc) Pressure -3.32 -3.32 14.40 2.77
90 Co-efficient -1.30 -1.30 0.30 -0.75
1 5.3 m
Degree(pres) Pressure -14.40 -14.40 3.32 -8.31

FOR ROOF:
Panel
DIRECTION OF Co-efficient width
EF GH
WIND / Pressure
Co-efficient -0.30 -0.10
0 Degree(suc) 7.3 m
Pressure -4.62 -1.54
Co-efficient -1.30 -1.10
0 Degree(pres) 7.3 m
Pressure -20.02 -16.94
EG FH
Co-efficient -0.30 -0.30
5.3 m
90 Degree(suc) Pressure -3.35 -3.35
90 Co-efficient -1.30 -1.30
5.3 m
Degree(pres) Pressure -14.53 -14.53

Drag force for gallary:


The friction focre for the structure shall be applied when structure size meeting the
following criteria:

d/h = 0.26 d/b = 1.4381

DRAG FORCE SHALL NOT BE CONSIDERED FOR THIS STRUCTURE

d = 15.10 m
h = 59.00 m
b = 10.50 m
1

h>b Hence use 2.Formula


for Cf ' value 1.Without corrugation or ribs = 0.01
2.With corrugation = 0.02
3.With ribs = 0.03
Enter type of Roof surface for Cf' value 2
The value of Cf ' = 0.02

The total drag force value = -145.82 kN

Take half of the loading from total drag force and applied first 1/3rd of the gallery
along wind direction and remaining half of the total drag force applied next 2/3 rd of the gallery.
DOCUMENT NO.
PROJECT TOSHIBA
JTP-XXX-S01
Rev. No
STRUCTURE JUNCTION TOWER
0
DESN
TITLE WIND LOAD CALCULATION
SVK

CALCULATION OF WIND LOAD FOR Junction Tower


Basic wind speed Vb 50 m/s
Probability factor k1 1.08
Terrain, Height & structure size factor k2 1.1

Topography factor k3 1
Topography factor f 1.1
Design wind velocity or speed Vz = 65.34 m/s

Design wind pressure Pd= 0.6x(65.34x65.34)


pz 0.6Vz 2
Pz (or) q (or) Pd = 2.56 kN/m2
Longer direction of JT:
Wind along conveyor direction:
SOLIDITY RATIO :
Member Length(m) Member Specification Size Nos Area
Column 39.4 UC356X368X202 0.375 2 29.55
Tie beam 15.1 UB914X419X343 0.91 8 109.928
A bracing 9 TUBE220X220X12 0.22 16 31.68
Other Bracing 1 3.7 TUBE90X90X4.5 0.09 16 5.328
Other Bracing 2 4.4 TUBE90X90X4.5 0.09 16 6.336

SL.ratio cf
Total area of members 182.5 m^2 0.1 1.9
FRAME OCCUPATION AREA 595 m^2 0.2 1.8
Solidity ratio 0.31 0.3 1.7
0.4 1.7
Referring table 28 of IS 875-3 Solidity ratio 0.31 0.5 1.6
Force Coefficient 1.74 0.75 1.6
1 2
0.31 1.749463
Near Side
Wind force on member = 20.65 kN/m Per m length
= 10.32 kN/m Per column

Fare Side
Leg spacing = 15.10 m
Frame spacing ratio = 2.29 Greater than 0.5
Shielding factor = 1.00 From Table-29
Wind force on member = 20.65 kN/m Per m length
= 10.32 kN/m Per column

Total Wind Load on individual legs


Per m length = 20.65 kN/m
DOCUMENT NO.
JTP-XXX-S01
Page

CHKD
JTP
DOCUMENT NO.
PROJECT TOSHIBA
JTP-XXX-S01
Rev. No
STRUCTURE JUNCTION TOWER
0
DESN
TITLE WIND LOAD CALCULATION
SVK

CALCULATION OF WIND LOAD FOR Junction Tower


Basic wind speed Vb 50 m/s
Probability factor k1 1.08
Terrain, Height & structure size factor k2 1.1

Topography factor k3 1
Topography factor f 1
Design wind velocity or speed Vz = 59.40 m/s

Design wind pressure Pd= 0.6x(59.4x59.4)


pz 0.6Vz 2
Pz (or) q (or) Pd = 2.12 kN/m2
Longer direction of JT:
Wind along conveyor direction:
SOLIDITY RATIO :
Member Length(m) Member Specification Size Nos Area
Column 39.4 UC356X368X202 0.375 2 29.55
Tie beam 10.5 ISMC300FR 0.3 8 25.2
A bracing 7.2 TUBE220X220X12 0.22 16 25.344
Other Bracing 3.6 TUBE90X90X4.5 0.09 16 5.184
Other Bracing 2.6 TUBE90X90X4.5 0.09 16 3.744

SL.ratio cf
Total area of members 89 m^2 0.1 1.9
FRAME OCCUPATION AREA 413.7 m^2 0.2 1.8
Solidity ratio 0.22 0.3 1.7
0.4 1.7
Referring table 28 of IS 875-3 Solidity ratio 0.22 0.5 1.6
Force Coefficient 1.74 0.75 1.6
1 2
0.22 1.745047
Near Side
Wind force on member = 8.32 kN/m Per m length
= 4.16 kN/m Per column

Fare Side
Leg spacing = 10.50 m
Frame spacing ratio = 1.59 Less than 0.5
Shielding factor = 0.92 From Table-29 Linear interpolate
Wind force on member = 7.66 kN/m Per m length
= 3.83 kN/m Per column

Total Wind Load on individual legs


Per m length = 7.99 kN/m
Cant use.Because it is
assumed as a box
section (soild)

(ii)Wind along conveyor direction:


Force coefficient = 2 Refer from Table 26 of IS 875 part-3
Member width = 0.4

Wind force on member = 1.69 kN/m


DOCUMENT NO.