Transfer Switch Controls

TS1311
(Line to Neutral Sensing)

Description Features
The TS1311 control is a microprocessor-based Major features of the control include:
power transfer control system. The control provides
normal and generator source monitoring, generator Voltage Sensing Control directly senses utility
set starting, and power switch control functions. It is and generator set voltages from 75-600 VAC line to
suitable for use in emergency, standby, and optional line. The control senses all phases on the normal
standby applications. The integration of all functions source, and one phase on the generator set source.
into a single control system provides enhanced Frequency Sensing Selectable 50 Hz or 60 Hz
reliability and performance compared to conventional (generator set source)
transfer switch control systems.
Easy to Use Operator Panel Reliable color-coded
The operator panel of the TS1311 control is easy to LED indicating lamps and graphical labeling make it
use and understand, utilizing LED lamps for status easy for an operator to understand source condition
indications, and push-button controls for operator and switch position.
control functions.
Environmental Protections - The control enclosure
The TS1311 control is field programmable without the is protected from dust, moisture, and physical
use of a service tool. intrusion. The operator panel is provided with UV
The control source monitoring provisions include protection for long life in direct sunlight.
single or 3 phase monitoring for the normal source Environment The control is designed for proper
and single phase monitoring for the generator source. operation without recalibration in ambient
The control is configurable to provide commonly temperatures from -30 C to +70 C, and for storage
required features such as programmed transition, from -55 C to +80 C; and will operate at 95%
sync check, pre-transfer signals, generator exercisor, relative humidity, non-condensing.
and other functions. Warranty and Service All Cummins Power
Generation products are backed by a
Certifications comprehensive warranty and worldwide distributor
The TS1311 meets the requirements of the following service network to provide fast, local parts and
codes and standards. service support.
NFPA110 - Standard for Emergency and
Standby Power Systems
NFPA70 - US National Electrical Code
NFPA99 - Standard for Health Care Facilities
NEMA250 - Standard for electrical enclosures.
The control enclosure provides a NEMA-4 rating
(for indoor use, protection from moisture, dust
and object intrusions).
CSA C22.2, No. 14 M91 - Industrial Equipment.
Control System Operating Modes

Front Panel Test Pushbutton - The control will Open Transition with programmed transition
activate a generator set test or exercise when this (adjustable 0-10 seconds)
pushbutton is pressed and held for 2 seconds. This Open Transition with phase check monitor and
test or exercise can be configured to occur with and programmed transition backup
without load. A without load test will start the Exercise Mode
generator and run without transfer of loads. A test Test Mode
with load will cause loads to be transferred to the Phase Check - Configurable for initiation of transfer
genset for the duration of the test. The test is functions when sources are in phase, and including
terminated by pressing the Front Panel Test button ability to enable a programmed transition backup to the
again. function so that if sources are not in phase within 120
seconds, the system will activate the programmed
Override Pushbutton Pressing the Override transition backup.
pushbutton terminates active time delays for time
delay start, transfer, retransfer, and genset stop. Exerciser Clock - Integral exerciser configurable for
operation on 7, 14, 21, or 28 day cycle. Includes 12-hr
Set Exerciser Pushbutton - Pressing this button offset for more convenient setting of exercise time.
allows programming a generator set exercise period. Fixed 20 minute exercise duration.
Can be configured with or without load and with or
without a 12 hour offset. Time-Delay Functions - The control provides the
following time delay functions:
LED Indicating Lamps The control includes LED Engine Start - Prevents nuisance generator set
lamp indication for the following functions: starts due to momentary power system variation or
Normal Connected loss. Adjustable from 0-10 seconds; default to 3
Normal Available seconds.
Emergency Connected Transfer Normal to Emergency - Allows generator
Emergency Available set to stabilize before application of load. Prevents
Exercise power interruption if normal source variation or loss
Test is momentary. Allows staggered transfer of loads in
LED indicating lamps, in conjunction with push-button multiple transfer switch systems. Adjustable from 0-
switches on the face of the panel are used for system 300 seconds; default to 5 seconds.
configuration. Retransfer Emergency to Normal - Allows the
utility to stabilize before retransfer of load. Prevents
Control Configuration - A control configuration
needless power interruption if return of normal
switch is provided to allow a technician to adjust time
source is momentary. Allows staggered transfer of
delays and other system configuration details. The
loads in multiple transfer switch systems. Adjustable
control configuration switch is used in conjunction
from 0-30 minutes; default to 10 minutes.
with the 8 LED lamps on the front panel to indicate
control configuration. Generator Set Stop - Maintains availability of the
generator set for immediate reconnection in the
event that the normal source fails shortly after
Control Functions transfer. Allows gradual generator set cool down by
Nominal Voltage Setting - The control is running unloaded. Not included in utility to utility
configurable for use at the following voltage levels: systems. Adjustable from 0-30 minutes; default to
110, 115, 120, 127, 139, 220, 230, 240, 255, 277, 10 minutes.
and 347. Programmed Transition - Controls the speed of
operation of the transfer switch power contacts to
Elevator Pre-Transfer - The control is capable of allow load generated voltages and inductive devices
sending a steady state output to an elevator control to decay prior to connecting a live source. Transfer
system that there is an impending Transfer or Re- switch and control design prevents the device from
Transfer. being stuck in neutral position. Adjustable from 0-
Voltage Sensing - All phases on the Normal source 10 seconds; default to 0 seconds.
and single phase on the Generator source. The Elevator Signal - Provides an adjustable time delay
control senses line-to-neutral voltage. Normal to prevent interruption of power during elevator
Source Pickup: adjustable 90-95%, Dropout: operation or as a load disconnect signal. Adjustable
adjustable 70, 80, 85 or 90% of nominal voltage; from 0-300 seconds; defaulted to 0 seconds.
Generator Source pickup: 90%, Dropout: 75% of Configurable for pre-transfer only, or pre-transfer
nominal voltage. through post transfer. (Requires optional elevator
signal relay for use)
Frequency Sensing - Generator Source Pickup:
90% of nominal frequency; Dropout;75% of nominal
frequency (50Hz or 60 Hz).
Control Interface Transfer Switch Connected to Emergency - The
Generator Start Command The control provides a control accepts a ground signal to indicate that the
normally open contact that closes to command transfer switch loads are connected to the generator set.
generator set starting. Utility Source Voltage Sensing
The control accepts a 3-phase and neutral connection
Power Switching Mechanism Control (line-to-neutral) to monitor the normal service, rated at
Open Normal - The control provides a solid state up to 480 line to line.
output to open the Normal side of the transfer Generator Source Voltage Sensing
switch. The control accepts a single phase (line-to-neutral),
Close Normal - A solid state output is provided which is used to allow the control to monitor generator
to close the Normal side of the transfer switch. set source condition.
Open Emergency - The control provides a solid 12 and 24 VDC Battery Operation - The TS1311
state output to open the Emergency side of the operates normally with input control voltage from 8 to 35
transfer switch. VDC and can survive 0 VDC for 50ms without
Close Emergency - The control is capable of misoperation.
sending a solid state output to close the
Emergency side of the transfer switch. Options
Remote Override - Momentary input that is activated Elevator Signal Relay - Provides 2 N/O and 2 N/C
with a ground signal and functions in the same contacts for the elevator signal function. Contact rating
fashion as the operator panel override switch. is 10A @ 600 VAC.
Remote Test - Maintained input that is active with a Programmable Exerciser Clock - Provides a fully
ground. The test is configurable for with or without programmable 7 day clock to provide greater flexibility in
load; same as with the front panel test. scheduling exercise periods and duration, than the
Transfer Inhibit - Maintained input that is active with standard integral exerciser.
ground and is typically used by a supervisory control
system to control the load transfer to generator sets
in a controlled manner. Part Number Information
Re-transfer Inhibit - Maintained input that is active Kit Description Kit Part Numbers
with a ground and is typically used to prevent the TS1311 0541-1221
control from automatically re-transferring the load Elevator Pre-Transfer Signal
Relay (12V Relay Coil) 0179-3760-01
back to the Utility during power outages.
Transfer Switch Connected to Normal The Elevator Pre-Transfer Signal
control accepts a ground signal to indicate that the Relay (24V Relay Coil) 0179-3761-01
transfer switch loads are connected to the normal
External Exerciser Clock
service. (12V and 24V) 0541-1106
Dimensions mm (inches)
Electrical Connections

Cummins Power Generation Cummins Power Generation Cummins Power Generation


1400 73rd Avenue N.E. 8 Tanjong Penjuru Columbus Avenue, Manston
Minneapolis, MN 55432, USA Singapore 609019 Park Ramsgate, Kent CT12
Phone: 763.574.5000 Phone: (65) 62650155 5BF
Fax: 763.574.5298 Fax: (65) 62660432 Phone: (44) 1843255000
Fax: (44) 1843255900
Cummins Power Generation is a subsidiary of Cummins Inc.
PowerCommand is a registered trademark of Cummins Inc.

Você também pode gostar