Escolar Documentos
Profissional Documentos
Cultura Documentos
AIRFLOW
Model: BSQ-420-100
Belt Drive Centrifugal Inline Fan
AIRFLOW
TOP VIEW
Dimensional
Quantity 1
Weight w/o Acc's (lb) 845
Weight w/ Acc's (lb) 849 18.00 MAX
Performance
Requested Volume (CFM) 20,985
Actual Volume (CFM) 20,985
External SP (in. wg) 1
Total SP (in. wg) 1
Fan RPM 620
Operating Power (hp) 8.7
Elevation (ft) 180
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 3.6
Tip Speed (ft/min) 6,859
Static Eff. (%) 39
Motor
Motor Mounted Yes
Size (hp) 10
Voltage/Cycle/Phase 380/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 18
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2014. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 94 98 87 81 80 75 70 66 87 75 29 licensed by AMCA International
Radiated 97 99 83 75 72 60 52 50 85 73 25 Sones - calculated using AMCA 301 at 5 ft
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B:
Free inlet, Ducted outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The inlet sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in
a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet
hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies
to inlet sone ratings only. Radiated (casing) sound data is the sound generated through the fan housing when the fan is
ducted on both the inlet and outlet.
AIRFLOW
Model: BSQ-240-15
Belt Drive Centrifugal Inline Fan
AIRFLOW
TOP VIEW
Dimensional
Quantity 1
Weight w/o Acc's (lb) 268
16.00 MAX
Weight w/ Acc's (lb) 272
Max T Motor Frame Size 215 54.13
Performance
Requested Volume (CFM) 5,049
Actual Volume (CFM) 5,049
External SP (in. wg) 1
Total SP (in. wg) 1
Fan RPM 798
Operating Power (hp) 1.48
Elevation (ft) 180
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 5.3
Tip Speed (ft/min) 5,116
Static Eff. (%) 57
Motor
Motor Mounted Yes
Size (hp) 1 1/2
Voltage/Cycle/Phase 380/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 3.3
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2014. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 82 83 81 74 70 67 61 55 78 66 15.0 licensed by AMCA International
Radiated 85 84 77 68 62 52 43 39 73 62 11.7 Sones - calculated using AMCA 301 at 5 ft
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B:
Free inlet, Ducted outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The inlet sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in
a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet
hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies
to inlet sone ratings only. Radiated (casing) sound data is the sound generated through the fan housing when the fan is
ducted on both the inlet and outlet.
AIRFLOW
Model: BSQ-360-50
Belt Drive Centrifugal Inline Fan
AIRFLOW
TOP VIEW
Dimensional
Quantity 1
Weight w/o Acc's (lb) 639
18.00 MAX
Weight w/ Acc's (lb) 643
Max T Motor Frame Size 215
70.00
Performance
Requested Volume (CFM) 13,005
Actual Volume (CFM) 13,005
External SP (in. wg) 1
Total SP (in. wg) 1
Fan RPM 618
Operating Power (hp) 4.73
Elevation (ft) 180
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Drive Loss (%) 4.0
Tip Speed (ft/min) 5,823
Static Eff. (%) 45
Motor
Motor Mounted Yes
Size (hp) 5
Voltage/Cycle/Phase 380/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 9.7
Notes:
All dimensions shown are in units of in.
*NEC FLA - based on tables 430.248 or 430.250 of
National Electrical Code 2014. Actual motor FLA may vary,
Sound Power by Octave Band for sizing thermal overload, consult factory.
Sound LwA - A weighted sound power level, based on ANSI S1.4
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones dBA - A weighted sound pressure level, based on 11.5 dB
Data attenuation per Octave band at 5 ft - dBA levels are not
Inlet 90 92 86 78 77 75 69 64 84 72 23 licensed by AMCA International
Radiated 93 93 82 72 69 60 51 48 80 68 18.8 Sones - calculated using AMCA 301 at 5 ft
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B:
Free inlet, Ducted outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings do not include the
effects of appurtenances (accessories). The inlet sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in
a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: free inlet
hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies
to inlet sone ratings only. Radiated (casing) sound data is the sound generated through the fan housing when the fan is
ducted on both the inlet and outlet.
Fan Configuration
Construction Type PermaLock
Size 44
Arrangement 10
Rotation CW
Discharge Position UB
Spark Resistance None
Scroll Material Steel
Wheel Material Steel
Inlet Cone Material Steel
Pedestal Material Steel
Equipment Weights
Fan (LMD)(lb) 1,388
Motor/Drive (lb) 264
Accessories (lb) 139
Model: USF-444-10-AF-I-150
Centrifugal Utility Fan - Airfoil Wheel
38.77
34.98
24.75
CENTERLINE
0.90 3.45
HOUSING
SHAFT
CENTERLINE
24.75
50.69 46.9
6.00 TYP
0.81
461 lbs 379 lbs
4 Holes
18.86
46.5
INLET OD 3.45
0.90 3.49 52.49
3.49
6.00 TYP
INLET 0.44 DIA. 32 HOLES
OUTLET
89.58
83.02
34.98
48.28
21.59 (To Slip Fit Inlet)
32.32
56.50 74.23
88.23
END VIEW
SIDE VIEW
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
*DISCHARGE POSITION CAN NOT BE MODIFIED IN FIELD
*FANS ARE SUBJECT TO .125 INCH TOLERANCE
*DUE TO CONTINUAL IMPROVEMENTS DIMENSIONS MAY CHANGE
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free
inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). Power ratings
(BHP/kW) include transmission losses. The sound power level ratings shown are in decibels, referred to 10-12 watts
calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet Lwi, LwiA, and outlet Lwo, LwoA sound power levels for installation type B: Free
inlet, Ducted outlet. Outlet ratings include the effects of duct end correction. dBA levels are not licensed by AMCA
International. The AMCA Certified Ratings Seal for Sound applies to inlet LwiA and outlet LwoA ratings only.
Fan Configuration
Construction Type PermaLock
Size 24
Arrangement 10
Rotation CW
Discharge Position UB
Spark Resistance None
Scroll Material Steel
Wheel Material Steel
Inlet Cone Material Steel
Pedestal Material Steel
Equipment Weights
Fan (LMD)(lb) 375
Motor/Drive (lb) 73
Accessories (lb) 58
Model: USF-424-10-AF-0-50
Centrifugal Utility Fan - Airfoil Wheel
19.47 OD
15.17
CENTERLINE
HOUSING
SHAFT
CENTERLINE
15.17
26.03 OD
0.44
137 lbs 118 lbs
30.86 4 Holes 4.47 10.63
INLET OD
40.20
INLET OUTLET
45.26 57.55
19.26
25.72
12.88 (To Slip Fit Inlet)
19.59
33.04
56.30
END VIEW
SIDE VIEW
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free
inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). Power ratings
(BHP/kW) include transmission losses. The sound power level ratings shown are in decibels, referred to 10-12 watts
calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet Lwi, LwiA, and outlet Lwo, LwoA sound power levels for installation type B: Free
inlet, Ducted outlet. Outlet ratings include the effects of duct end correction. dBA levels are not licensed by AMCA
International. The AMCA Certified Ratings Seal for Sound applies to inlet LwiA and outlet LwoA ratings only.
Fan Configuration
Construction Type PermaLock
Size 36
Arrangement 10
Rotation CW
Discharge Position UB
Spark Resistance None
Scroll Material Steel
Wheel Material Steel
Inlet Cone Material Steel
Pedestal Material Steel
Equipment Weights
Fan (LMD)(lb) 972
Motor/Drive (lb) 173
Accessories (lb) 110
Model: USF-436-10-AF-I-100
Centrifugal Utility Fan - Airfoil Wheel
CENTERLINE
HOUSING
SHAFT
CENTERLINE
20.57
42.26 38.47 6.00 TYP
68.47 79.04
28.69
39.91
16.95 (To Slip Fit Inlet)
27.23
48.14 65.19
79.19
END VIEW
SIDE VIEW
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
*DISCHARGE POSITION CAN NOT BE MODIFIED IN FIELD
*FANS ARE SUBJECT TO .125 INCH TOLERANCE
*DUE TO CONTINUAL IMPROVEMENTS DIMENSIONS MAY CHANGE
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and
comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free
inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances (accessories). Power ratings
(BHP/kW) include transmission losses. The sound power level ratings shown are in decibels, referred to 10-12 watts
calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet Lwi, LwiA, and outlet Lwo, LwoA sound power levels for installation type B: Free
inlet, Ducted outlet. Outlet ratings include the effects of duct end correction. dBA levels are not licensed by AMCA