Revision A
CIVIL DEFENCE DEPARTMENT 06-May-2007
MINISTRY OF INTERIOR, QATAR
REVISION HISTORY
Maj Hassan
0 Issued for review --- ---
P Khoo FSE Yeo SK
Revisio Description Issued Date Checked By Date Approved by Date
n by
TABLE OF CONTENTS
Section Title Page No.
Material:
FSS
BASIC REQUIREMENTS No: 1.1
Preamble
Material:
FSS
BASIC REQUIREMENTS No: 1.1
Material:
FSS
BASIC REQUIREMENTS No: 1.1
6.0 Valves
Shall be UL Listed, VDS or FM approved or LPC certified.
7.0 Sprinklers
Shall be UL Listed, VDS or FM approved or LPC certified.
They shall be selected and installed in accordance with the NFPA13.
Sprinklers shall be installed in concealed spaces in excess of 400mm
deep. Where Concealed spaces can be shown to have no combustible
material and are less than 800mm deep, sprinklers may be omitted.
Material:
FSS
BASIC REQUIREMENTS No: 1.1
10.0 Fittings
Fittings shall be from material compatible with the pipe chosen.
Jointing methods shall be threaded, grooved, flanged or other suitable
method able to withstand the test pressures.
Grooved joints shall be LPC certified, UL Listed or VDS or FM approved.
Welded joints shall be qualified.
12.0 Mimic Panels with indicating LEDs shall be provided at each floor.
Material:
FSS
BASIC REQUIREMENTS No: 1.1
Smoke Control System Fan controls shall be located adjacent to the Main
Fire Alarm Panel.
16.0 All fire and life safety systems shall be properly maintained under a
documented preventative maintenance inspection and test plan.
The minimum guidelines in NFPA25 shall be applied.