Você está na página 1de 6

Professional Provider of Power Testing Instrument

PCT200 Series CT/PT Test System

PT
TP YCT Bushing type CT

Bushing Type CT M type CT

GIS CT

PT

PONOVO POWER CO., LTD.


No.139 Jinghai Third Road, BDA, Beijing, China. 100176
Tel : +86 (10) 95089666
Fax : +86 (10) 59089999
www.relaytest.com

PONOVO POWER CO., LTD


Principle

Excitation characteristics Ratio test based on voltage method


test based on DC method

<Conventional method> <Conventional method>


A
T1 T2 TAx
s A Current A
v
Features: source

Current source is at primary side


1 . Test CT according to IEC60044-1/6. IEC61896-2 and current measurement is at the secondary side
and ANSI/IEEE C57.13
2. Can test all types of CT <New method>

3. One test can get all CT parameters <New method>


4. Fast test for excitation check
V
ol
TAx ta
g
10kV knee point check time: 50s V V
A e
s
Variable- o
ur
1kV knee point check time: 15s Frequency v power
source
c
e

5. PT test Voltage source is at secondary side and


Ratio
Voltage measurement is at primary side
Polarity
Features of new method: Features of new method:
Excitation
Cancheck CT with high knee point value Ratiocheck up to 30000:1
Burden
Highefficiency, high accuracy, more safe Cancheck bushing CT
Cancheck GIS CT

Error check with


extrapolation method for M type CT Test special CT

P1 P2

S1 S2

Load

Current
source
L2 Standard CT L1 P1 CT under test P2

V V V
o
l
t
a
g

A
e

K2 K 1 S1 S2

s
o
ur
c
Load e

CT Tester

Bushing type CT requires large power output capacity which


Getthe ratio error and angle error based on conventional CT tester can not give. New test method can solve
extrapolation method, no need to use extra this problem
standard CT nor standard load. Theprimary side length is long for GIS type CT and this requir
e s l a r g e p o w e r o u t p u t c a p a c i t y w h i c h
conventional CT test can not supply. New test method can solve
this problem

01 02 www.relaytest.com
Test at field
Simple wiring Test Report

PCT200i Report PCT series report analyze software

P1
S1

Load

S2
P2

Standard Accessories

Soft bag Test leads

SoftwareInterface
Signal Cable(Double wired)
2.5mm2 3m2

PCT200i operation

Signal CableDouble wired


TransportationCase 0.75mm2 15m1

(AntiWater&vibration)

Earthing Lead with


Clap 4mm2 3m1

Excelformat test report


A4size
Testresult can be exported to key drive through USB port.
Cansave 10.000 results in non-volatile memory Claps with Jaws open 30mm4
Spike Test Pen2
Cable Connector2
Claps with Jaws open 10mm4

www.relaytest.com 03 04 www.relaytest.com
Comparison with traditional method Field Test Examples

Shan Xi CT/PT Research Institute Customer: Beijing High Transmission Company


Comparison of excitation tests between
conventional test method and PCT200i 500kV TPY(transient) type CT

Comparison with traditional test method Test data Report

Test results

Chongqing Power Plant


Generator Output CT

omparison test with traditional CT test method was made in Shan Xi

C CT & PT Research Institute. 0.2 class reference CT was used in the test. The
results show the maximum Ratio test difference is 0.08414% and the maximum
Phase deviation test difference is 0.34188.
Generator output 6000:1 Test Result

www.relaytest.com 05 06 www.relaytest.com
Szechwan Substation (500kV) Shen yang CT/PT factory

Tianjing Huapanshan Power Plant Shan Xi 500kV Substation

500kV Tranformer Bushing CT 220kV Transmission Line CT

500kV ClassCT TPY 4000:1 Test result Shen yang CT/PT factory

500kV Transformer TPY Class


220kV Transmission line GIS CT P
Casing CT TPY Class 1250:1test Datasheet
Class 1250:1 excitation characteristic curve

Generator Output TPY CT

200 kV transmission line


GIS CT Class P 1500:1 Test result

www.relaytest.com 07 08 www.relaytest.com
PCT200 Series CT/PT Test System
Specifications

PCT200i PCT200Ai
Application Test M/P/TP type CT and PT Test M/P/TP type CT and PT

Output voltage range 0~120V 0~120V

Specifications Output current range 0~5Arms(15A peak) 0~5Arms(15A peak)


Output power 0.0001~500VArms(1500VA peak) 0.0001~500VArms(1500VA peak)

Ratio test range 35000:1~45000:5 35000:1~45000:5


Ratio test accuracy 0.1% 0.05%
Max. knee point voltage 45000V 45000V
Burden test range 0.001-1000 0.001-1000
Burden test accuracy 0.05%1m Typ. 0.1%1m Gur. 0.05%1m Typ. 0.1%1m Gur.
Winding resistance test rang 0.001~1000 0.001~1000
Winding resistance test accuracy 0.05%1m Typ. 0.1%1m Gur. 0.05%1m Typ. 0.1%1m Gur.
CT
Accuracy limiting factor (ALF) Yes Yes
Instrument security factor (FS) Yes Yes
Remanence flux (Kr) Yes Yes
Secondary time constant (Ts) Yes Yes
Unsaturated inductance (Lu) Yes Yes
Saturated inductance (Ls) Yes Yes
Excitation characteristic curve Yes Yes
10%(5%)error curve Yes Yes
Rated symmetrical short
circuit current factor (Kssc) Yes Yes
Accuracy limiting voltage (Eal) Yes Yes
Transient dimensioning factor (Ktd) Yes Yes
Peak instantaneous error (^ ) Yes Yes
Composite error (c ) Yes Yes

Ratio error 0.05%Typ. 0.1%Gur. 0.02% Typ. 0.05% Gur.

Phase displacement 1min Typ. 3min Gur. 1min Typ. 2min Gur.
0.1min 0.01min

Ratio Yes Yes


PT
Polarity Yes Yes

Excitation characteristic Yes Yes

110-240Vac/50-60Hz (norminal) 110-240Vac/50-60Hz (norminal)


Others Main supply
90-260Vac/45-65Hz (permissible) 90-260Vac/45-65Hz (permissible)

Operation temperature -10~50 -10~50


Relative humidity 90%,non-condensing 90%,non-condensing
Dimensions 470 x200 x 245mm (WHL 470 x200 x 245mm (WHL
Weight 10Kg 14Kg
LCT display 8.4 inch, color display 8.4 inch, color display
Operating system windows windows

www.relaytest.com 09 10 www.relaytest.com

Você também pode gostar